							                                THE CITY OF REDMOND
                       FIRE DEPARTMENT - PREVENTION DIVISION
                                   Uniform Fire Code
                    Administrative Ruling / Interpretation

Code Section: UFC 1006.2.2 and 1006.2.7                              Code Edition: 1997
Date: September 12, 2000
Statement of Need:
Two changes in commercial food preparation techniques have had a significant impact on fire
protection in recent years:
   •   Vegetable oils burn at a higher temperature (685 plus deg. F) than animal fats
       (550-600 deg. F).

   •   Energy efficient cooking appliances are now used extensively in restaurants.
       Highly insulated fryers keep cooking oils and metal appliances hot longer.
These two changes have created conditions that create fires that are more difficult to extinguish
and prone to re-ignite. There are documented fires in cooking equipment that were not
controlled by the existing pre U.L. 300 extinguishing systems. Extinguishment was affected only
after application of 1-3/4” hand lines.

On November 21, 1994, Underwriters Laboratories adopted a new standard, UL 300-Fire
Testing of Fire Extinguishing Systems for Protection of Restaurant Cooking Areas, which test for
these specific hazards. The U.L 300 standard provides for much greater cooling of the cooking
surfaces (requires up to five times additional agent for wet chemical systems). Note: There are
currently no dry chemical agent extinguishing systems that meet the U.L. 300 standard due to
the susceptibility for re-ignition of the fire.

Ruling/Interpretation:

UFC 1006.2.2, “Protection of Commercial Cooking Operations - Type of system”:

   o   U.L. 300 compliant systems shall be required for all new installations of fire extinguishing
       systems that protect cooking equipment that have the potential to release grease laden
       vapors.
   o   Existing extinguishing systems protecting cooking equipment that do not comply with
       U.L. 300 shall be brought into compliance with that standard within 6 months of written
       notification by Fire Prevention personnel.

UFC 1006.2.7, “Protection of Commercial Cooking Operations – Portable fire
extinguishers”:

New and existing cooking appliances using combustible cooking media (vegetable or animal oils
and fats) shall have a “K-type” portable fire extinguisher installed within 30 feet in lieu of a 40-
B:C dry chemical-type in accordance with NFPA 10 – 1998, “Standard for Portable Fire
Extinguishers”, Section 3-7, “Fire Extinguisher Size and Placement for Class K Fires”.




__________________________
Robert Lovett
Fire Marshal

          ~ 15670 NE 85 TH STREET ~ P.O. BOX 97010 ~ REDMOND, WASHINGTON 98073-9710 ~
                ~ FAX (425) 556-2250 ~ PHONE (425) 556-2255 –OR- (425) 556-2246 ~

						
Related docs
Other docs by niusheng
collateralfinal
Views: 0  |  Downloads: 0
armored sheath_ single loose tube
Views: 5  |  Downloads: 0
cosmetic - PDF
Views: 289  |  Downloads: 3
dgp227
Views: 2  |  Downloads: 0
BC-CHSI-ONLINEInternet
Views: 40  |  Downloads: 0
10 Autumn A4 edition 2007
Views: 5  |  Downloads: 0
Toyoda Shihan Memorial 2009
Views: 5  |  Downloads: 0
directions+for+intermedia+06-07+alumni+survey
Views: 2  |  Downloads: 0
Phytoextraction of polluted soils
Views: 44  |  Downloads: 0
Health Care Reform 2010 Seek a
Views: 6  |  Downloads: 0