					Technical Description   FBP FieldBusPlug


V6

                        FBP System Accessories
                      FieldBusPlug
                      System Accessories
V6                    Technical Description

                      FieldBusPlug System Accessories


                      Contents



                      Technical data                                                                                       Page



                      Phase busbars and feed-in blocks
                      for MSD11-FBP and MSR22-FBP ........................................................................... 4


                      CAL11-FBP.0               Address label for FieldBusPlug ............................................. 5


                      CP-24/5.0                 Power supply 24 V DC / 5 A, output voltage adjustable ...... 6


                      ACS100-PAN                Control panel for UMC22-FBP ............................................... 8


                      ACS100-CAB                Extension cable and mounting set for ACS100-PAN ........... 9




                      Technical changes reserved




FieldBusPlug / Issued: 11.2003                                                                                          FBP System Accessories   3
                   FieldBusPlug
                   System Accessories
                   Technical Description                                                                              V6

                   Accessories for the motor starters MSD11-FBP and MSR22-FBP
                   Phase busbars and feed-in blocks


                   Phase busbars for MSD11-FBP and MSR22-FBP
                   for the crosswiring

                   Current carrying capacity max. 63 A, wire range 25/16 mm2, flexible/stranded conductors




                   Order numbers

                   PS1-2-0
                   for 2 devices          1SAM 201 906 R1002

                   PS1-3-0                                                           PS1-5-0
                   for 3 devices          1SAM 201 906 R1003

                   PS1-4-0
                   for 4 devices          1SAM 201 906 R1004

                   PS1-5-0
                   for 5 devices          1SAM 201 906 R1005




                   Feed-in blocks for phase busbars at MSD11-FBP and MSR22-FBP

                   Current carrying capacity max. 63 A, wire range 25/16 mm2, flexible/stranded conductors




                        S1-M1

                                                                                      S1-M2



                   Order numbers

                   S1-M1
                   flat style             1SAM 201 907 R1001

                   S1-M2
                   high style             1SAM 201 907 R1002



4   FBP System Accessories                                                                    FieldBusPlug / Issued: 11.2003
                      FieldBusPlug
                      System Accessories
V6                    Technical Description

                      Accessories for FieldBusPlugs
                      CAL11-FBP.0


                      CAL11-FBP.0
                      Address labels for FieldBusPlugs



                      Knockout labels in the frame

                      Recommended ink for plotter: INK 2000
                      and Clean 2000, Fa. Weidmüller

                      Dimensions of the labels: 8 x 17 mm

                      40 labels per frame

                      Colour: white




                      Order number

                      CAL11-FBP.0            1SAJ 929 005 R0001




FieldBusPlug / Issued: 11.2003                                    FBP System Accessories   5
                   FieldBusPlug
                   System Accessories
                   Technical Description                                                                                   V6

                   CP-24/5.0
                   Power supply 24 V DC / 5 A, output voltage adjustable

                   The switched-mode power supplies systron® PS offer
                   many advantages compared with conventional power
                   supplies:

                     Compact module for DIN rail mounting
                     Low weight
                     High effiency
                     Low temperature rise (low power dissipation)
                     High input voltage range
                     Constant (stabilized) output voltage
                     UL, CSA listed, EN 50178 (VDE 0160)
                     Short-circuit and overload protected
                     Input protected by internal fuse
                     Adjustable output voltage
                   Input
                   Input voltage range                         90...260 V AC
                                                               127...260 V DC
                   Frequency, if AC supply                     47... 63 Hz
                   Mains buffering                             min. 10 ms, 100% load
                   Current consumption with rated load         max. 1.8 A (90 V AC),
                                                               typ. 1.3 A (115 V AC) and 0.63 A (230 V AC)
                   Inrush current with 25° C (≤ 2 ms)          40 A (260 V)
                   Internal input fuse                         2 A, slow


                   Output
                   Output voltage                              24 V DC ± 3 % (23...28 V DC adjustable with pot. (max. 120 W))
                   Output current / power                      T ≤ 40°C               T > 40°C            T = 55°C
                   Derating for Uin > 45°C                     5 A (24 V)/120 W      -1.33W/°C        4.2 A (24 V)/100 W
                   Derating for Uin < 90 V DC or < 140 V AC    5 A (24 V)/120 W      -1.33W/°C        4.2 A (24 V)/100 W
                   Ripple                                      max. 200 mVpp
                   Input voltage regulation                    max. ± 0.05 %
                   Static load regulation                      max. ± 0.5 %
                   Dynamic load regulation 10-90 %             max. 5 %
                   Short-circuit protection                    switching-off with automatic restart
                   Overload protection                         switching-off by overtemperature and overload
                   Reset after switching-off
                   by overtemperature                          by switching off the input voltage for min. 30 s


                   General data
                   Efficiency with rated load                  77...85 % (90...260 V AC)
                   Indication of operation                     green LED indicates that the output voltage is o. k.
                   Operating temperature                       0° ... 55°C
                   Storage temperature                         -25° ... +75°C


6   FBP System Accessories                                                                       FieldBusPlug / Issued: 11.2003
                      FieldBusPlug
                      System Accessories
V6                    Technical Description

                      CP-24/5.0
                      Power supply 24 V DC / 5 A, output voltage adjustable

                      General data (continued)
                      Terminals                                   screw-type terminals, 2 x 14 AWG (2.5 mm2)
                      Weight                                      ca. 0.58 kg (1.3 Ib)
                      Dimensions (W x H x D)                      90 mm x 78 mm x 120 mm
                      Mounting hint                               Normal position: horizontal on DIN rail
                                                                  distance to other devices: left 1 cm, vertical 5 cm
                      Standards, approvals
                      Electrical safety                           EN 50178 (VDE 0160)/UL 508/CSA 22.2* (*pending)
                      Electrical isolation                        safe isolation according to IEC 664-1, DIN VDE 0106-101
                      Insulation test voltage                     1.5 kV AC piece by piece, 3 kV AC type test
                      Creepages and clearences                    overvoltage category 3, pollution severity 2
                      Electromagnetic immunity
                      according to EN 50082-2:                    ESD:                                       EN       61000-4-2   step 3 6/8 kV
                                                                  HF interference:                           EN       61000-4-3   step 3 10 V/m
                                                                  Burst:                                     EN       61000-4-4   step 3 2 kV
                                                                  Surge:                                     EN       61000-4-5           2 kV
                                                                  HF coupling input:                         EN       61000-4-6   step 3 10 V
                      Emitted interference
                            according to EN 50081-2               radio interference level according to EN 55011, class A
                      Input current of harmonic waves             limitation according to EN 61000-3-2, class A
                      Degree of protection
                       terminals                                  IP 20
                       housing                                    IP 20
                      Class of protection                         1

                                                                                                               Output L-
                                                                                                               Output L+
                     Connection of                                                                        Protected Earth
                     power supply CP-24/5.0




                                                                                                                                      green LED = ON:
                                                                                                                                      output voltage OK




                                                                                                       Label fields
                                                                                   Neutral N
                                                                        Phase L



                                                                                               Earth




                                                                                  Input
                                                                      Note: output voltage is adjustable from 23 to 28 V DC


                                                                      Approvals:
                      Order number
                      CP-24/5.0                 1SVR423416R0100



FieldBusPlug / Issued: 11.2003                                                                                              FBP System Accessories        7
                   FieldBusPlug
                   System Accessories
                   Technical Description                                            V6

                   Accessories for UMC22-FBP
                   ACS100-PAN




                   ACS100-PAN
                   Control panel for UMC22




                   For detailed description
                   see Technical Description
                   of UMC22-FBP




                   Order number

                   ACS100-PAN             1SAJ510001R0001




8   FBP System Accessories                                  FieldBusPlug / Issued: 11.2003
                     FieldBusPlug
                     System Accessories
                     Technical Description                                                                                   V6

                     Accessories ACS100-PAN (control panel for UMC22-FBP)

                     ACS100-CAB
                     Extension cable and mounting set for the control panel ACS100-PAN

                     The mounting set ACS100-CAB consists of an extension cable (3 m), a seal and the necessary
                     fixing material.

                     Remark: The second (smaller) sael is intended for mounting of an other device.




                                           Mounting base




                        Seal                                 Fixing screws

                                           Cable hole




                                                                 Plastic clip with
                                                                 adhesive tape

        Control panel
                                Extension cable
                                                        Connection to
                                                        UMC22-FBP
        Mounting overview                                                              Dimensions of the seal for
                                                                                       ACS100-CAB



        ACS100-CAB Extension cable




                                                           Outer sheath removed



               Section A-A                                                                                     Section B-B
                             Polar key
                                                                                                      no pin
             blue       black                                                                                           blue
               red      green                                                                             green         red
           yellow       white                                                                             white         yellow




                     Order number

                     ACS100-CAB               1SAJ510001R0001



10   FBP System Accessories                                                                    FieldBusPlug / Issued: 11.2003
                   FieldBusPlug
                   System Accessories
                   Technical Description                           V6




10   FBP System Accessories                FieldBusPlug / Issued: 11.2003
                                              Manual No. 2CDC 190 011 D0202




ABB STOTZ-KONTAKT       GmbH
Eppelheimer Straße 82   Postfach 101680
69123 Heidelberg        69006 Heidelberg
Germany                 Germany

Telephone   +49 6221 701-0
Telefax     +49 6221 701-240
E-Mail      desst.helpline@de.abb.com
Internet    http://www.abb.de/stotz-kontakt

				
DOCUMENT INFO
Shared By:
Categories:
Stats:
views:8
posted:2/8/2010
language:English
pages:12