									March 2009                                          CSS ES Rated Fire Damper




                                                       CSS Damper
                                        CSS Smoke ES Rated Fire Damper




Features


G Tested to EN 1366-2.


G Achieved 2 hour ES
  classification for both horizontal
  and vertical application.


G Suitable for standard or 50mm
  insulated circular ductwork.


G Available in standard duct sizes
  100mm to 355mm diameter.


G Easy installation.


G Ex stock availability.




                                        Dampers Controls Fancoils

                                       Ruskin Air Management Limited
                                            www.ruskinuk.co.uk
                                                                                                  CSS ES Rated Fire Damper


Introduction

The CSS circular smoke and fire damper
is the latest development to join the
Actionair’s innovative and tested range of
damper products.
The damper has been developed for
installing into standard circular spiral
duct systems where the duct passes
through, up to 2 hour rated walls. The
easy fit flange system makes the
installation quick and simple.
The CSS is available in a number of
circular sizes to suit 50mm thermal
insulated or non insulated ductwork, and
is supplied with a factory fitted control
mode, with Electrical Thermal Release
(ETR) as utilised on our Smoke, Vent /
Shield ranges.

Specification
Smoke/Fire (fail-safe closed) version           1 pair of 1.2mm galvanised steel hinged
The Actionair CSS Circular automatic            Installation flanges are provided with each
                                                                                                Control Options
Smoke ES rated Fire dampers with a              damper.                                         A choice of two motorised compact
single galvanised steel blade incorporating     The Actionair Factory fitted Compact            Control Modes 5 (24 volt) and 6 (230 volt)
patented seal to provide both ambient           electrical control mode with fail-safe open     are available, these are optimised motor /
and fire rated low leakage.                     operation upon removal of electrical power.     spring return type with remote reset-
Damper conforms to EN1366-2.                    Electrical actuators are fitted with halogen    release facilities, with volt free contacts for
Classification E120 and ES120 and               free low smoke and fume cables. They            provision of external indication, monitoring
damper casings conform to BSEN1506              have 60 second reset time and a 20              and control by means of Actionpac
for both horizontal and vertical application.   second release time.                            damper control system, or by suitable
1 pair of 1.2mm galvanised steel hinged         End switches are provided with each             alternative proprietary control format.
Installation flanges are provided with each     mode for reset and release monitoring.          Factory fitted and fully tested Control
damper. The Actionair Factory fitted            The CSS Damper and selected Vent                Modes are located outside of the
Compact electrical control mode with            Compact Control Mode (Mode 5 –24v, or           ductwork for easy access and installation.
thermal sensing to provide Fail-Safe-           Mode 6 – 230v) as supplied by Actionair.
Closed operation.
Electrical actuators are fitted with halogen
free low smoke and fume cables. They
                                                The Range                                       Application
have 60 second reset time and a 20
second release time. Each actuator has a
                                                The CSS circular range of Quality
                                                Engineered Dampers are suitable for air
                                                                                                Parameters
72°C rated electrical thermal release           conditioning and ventilation systems            CSS circular smoke and fire dampers can
(ETR). The ETR incorporates a safety            requiring up to 2 hour fire protection.         be incorporated in Smoke/Shield systems
electrical interlock that only permits                                                          or within exclusive circular ventilation
actuator operation when correctly fitted.       These circular bladed dampers are fail –        systems as a competitively priced
A green ‘Healthy’ indication lamp is built      safe spring close with factory fitted           alternative to the circular Smoke/Shield
into the ETR to give a simple and clear         electrical reset control modes.                 601 dampers.
visual check that the actuator is receiving                                                     The CSS dampers can be used where
power, the ETR is correctly fitted and the
thermal fuse is intact.
                                                Blade and Casing                                the operating total system pressure is up
                                                                                                to 1500 Pascals and duct velocities to
A manual test switch allowing periodic
operation of the damper for testing
                                                Features                                        15m/second.
                                                                                                The CSS round damper blade is normally
purposes simulates actuator fail-safe           The circular fire damper incorporates a         open and fail-safe to the closed position.
release under fire/smoke conditions.            unique and patented seal that provide ES        This product is ES rated.
End switches are provided with each             leakage performance at both ambient and         Actionair CSS dampers are designed for
mode for reset and release monitoring.          fire conditions. It is housed in a galvanised   application in normal dry filtered air
The CSS Damper and selected Compact             case complete with two installation             systems. If exposed to fresh air intakes
Control Mode (Mode 5 –24v, or Mode 6 –          flanges for easy fitting into stud and solid    and / or inclement conditions, the
230v) as supplied by Actionair.                 wall applications.                              dampers should be subject to a planned
Vent (fail-safe open) version                                                                   inspection programme.
The Actionair CSS Circular Vent automatic
smoke release dampers with a single             Sizes Available
galvanised steel blade incorporating            100, 125, 150, 160, 200, 250, 300, 315,
patented seal to provide ambient low leakage.   350 and 355. Manufactured to
Damper casings conform to BSEN1506.             BS EN 1506.


 2     www.actionair.co.uk
CSS ES Rated Fire Damper


Control Modes
                                                                                                                SUPPLY
Mode 5 CSS (24V System)
                                                                                   BLACK               1    –   24V A.C. or D.C.
                                                  A.C./D.C.24V                M
                                                                                                            +   TYPICALLY 5W (MOTORING)
Power On       – Damper motors open.               50 / 60 Hz                      WHITE               2
                                                                                                                2.5W (RESET)
Power Off      – Spring closure.
Electrical Thermal Release.
External mechanical position indicator                                                                 1
                                                                                                             CONTACT MADE BETWEEN
with pointer.                                                                                          2     1 AND 2 WHEN DAMPER
Release Time ≈ 20 secs.                                                                                      FULLY RELEASED
Reset Time ≈ 60 secs.                                                                                  3

(Connect 24V via a safety isolating                  7VA              A.C.                             4
                                                   5 / 2.5 W          250V                                   CONTACT MADE BETWEEN
transformer.)
                                                                      6(3)A                            5     4 AND 6 WHEN DAMPER
                                                                                                             FULLY RESET
*   Not fitted to Vent versions.                     Imax
                                                                                                       6
                                                  5.8A @ 5ms

                                                                                                             ELECTRICAL THERMAL RELEASE
                                                                                            TF 72 °C         (MUST BE FITTED TO DUCTING
                                                                                                             FOR DAMPER OPERATION).
                                                                                                             NOT AVAILABLE VENT VERSION
                                                  –30...+50 °C         *
                                                 CONTINUOUS
                                                                                                             (SPRING BIASED TEST SWITCH)

                                                                      DIAGRAM SHOWS ACTUATOR IN FULLY RELEASED STATE



Mode 6 CSS (230V System)                                                           BLUE                N     SUPPLY
                                                   A.C. 230V                  M                              230V A.C.50/60 Hz
Power On       – Damper motors open.               50 / 60 Hz                     BROWN                L1    TYPICALLY 5W (MOTORING)
Power Off      – Spring closure.                                                                             3W (RESET
Electrical Thermal Release.
External mechanical position indicator                                                                 1
with pointer.                                                                                                CONTACT MADE BETWEEN
                                                                                                       2     1 AND 2 WHEN DAMPER
Release Time ≈ 20 secs.
                                                                                                             FULLY RELEASED
Reset Time ≈ 60 secs.                                                                                  3
(To isolate from main power supply, the             7VA                                                4
system must incorporate a device which              5/3W                                                     CONTACT MADE BETWEEN
                                                                      A.C.
disconnects the phase conductors, with a                              250V
                                                                                                       5     4 AND 6 WHEN DAMPER
least 3mm contact gap.)                                                                                      FULLY RESET
                                                                      6(3)A
                                                                                                       6
*   Not fitted to Vent versions.
                                                                                                             ELECTRICAL THERMAL RELEASE
                                                                                            TF 72 °C         (MUST BE FITTED TO
                                                 –30...+50 °C
                                                                                                             DUCTING FOR DAMPER
                                                CONTINUOUS
                                                                                                             OPERATION).
                                                                       *                                     NOT AVAILABLE VENT VERSION
                                                                                                             (SPRING BIASED TEST SWITCH)

                                                                      DIAGRAM SHOWS ACTUATOR IN FULLY RELEASED STATE



Electrical Thermal Release (ETR)
Smoke/Fire version only
Compact Control Modes 5 and 6 fail-safe        For safety reasons the ETR is designed to
by means of a unique and patented              operate once only when the activation
electrical thermal release which operates at   temperature is reached. (It will then need
72°C or if the power supply is interrupted,    replacing with a new replacement ETR72,
complying with BS 5588 Part 9: 1999.           Part Number. DNNN00359)
The ETR incorporates triple safety
features, including an ingenious device
that ensures the fail-safe status of the
damper if the ETR is not correctly fitted
on to the damper case. CSS Dampers
                                               As standard, a green LED lamp is built
ETR is factory fitted.
                                               into the ETR housing. This gives the user
A manual test switch allows periodic           a simple and clear visual check that the
operation of the damper for testing            Actuator is receiving power, the ETR is
purposes simulating actual fail-safe           correctly fitted and the thermal fuse is
release under smoke/fire conditions.           intact.


                                                                                                            www.actionair.co.uk        3
                                                                                                CSS ES Rated Fire Damper



Vertical Mounting in a Rigid Construction Wall

General                                       Actuator                                        Maintenance
This method of installation is effectively    1. The control mode/actuator is supplied        (Refer to BS 5588-12)
suitable for most wall types of rigid         fitted. This should be checked for
construction, where they are of an equal      damage and the manual operation of the          1. Carefully inspect the units and clean
or greater density to the lightweight board   damper checked.                                 and remove any dust and debris.
partition tested. Details shown are
essentially for an existing dry wall          2. Check that the Electrical Thermal            2. Lubricate the units with a light oil spray,
partition. However this installation method   Release (ETR) is still firmly connected         wiping over all the surfaces.
may be used for masonry or blockwork          through the damper case. If it is not, the
                                              actuator/control mode may not work              3. Operate the mode to ensure that it is
walls as long as they have a greater
                                              electrically.                                   moving the blade from open to closed
density than the partition shown. Also a
                                                                                              and the reverse.
drywall partition may be built around the
                                              3. A special feature of the Actionair CSS
damper, as long as the clearances are                                                         4. If the microswitches (volt free contacts)
                                              modes is that they may be adjusted from
followed.                                                                                     within the mode are being used, they
                                              pointing straight out along the duct
                                              (standard configuration) through 90° to         should be checked to ensure they are
                                              point either up or down if required.            actually indicating that the blades are
                                                                                              open and closed. This is done by running
Health and Safety                             4. The mode should be wired into the            a cycle and checking both the blade open
This process must be undertaken by            system using the site wiring detail, plus       and closed position and the feedback
competent persons. More than one              the details shown on the label.                 indication from the microswitches is
person may be required to ensure the                                                          correct.
safe handling of large dampers and other
materials.                                    Commissioning
Use must be made of access equipment          1. The units should be carefully inspected
to ensure unsafe practices are not used       and checked to ensure that they have
to approach walls or difficult access         been built in, in accordance with
areas. Standard site PPE should be used       manufacturers’ recommendations and fire
(minimum steel toe cap boots, hard hat);      authority and building control
together with any protective eyewear,         requirements.
gloves and masks, when drilling or cutting
is being undertaken. The latter should        2. The mode should be operated to
also be used when handing the wall            ensure that it is moving the blade from
construction materials, as defined by the     open to closed and the reverse.
material suppliers. If loud equipment is
                                              3. If the microswitches (volt free contacts)
being used, hearing protection should be
                                              within the mode are being used, they
used. All waste materials should be
                                              should be checked to ensure they are
collected and disposed of as defined by
                                              actually indicating that the blades are
the relevant supplier.
                                              open and closed. This is done by running
                                              a cycle and checking both the blade open
                                              and closed position and the feedback
                                              indication from the microswitches is
                                              correct.




Damper Installation Method
A photo storyboard for this method            2. Mark out the hole on the partition and       5. Fill the 4 triangular voids between the
follows on page 6.                            cut it out, cutting the top and bottom          damper and the edges of the hole with
                                              edges first to maintain stability.              fire rated stone wool
1. Measure the overall damper casing
size. Calculate the finished square hole      3. For drywall partitions, frame out the        6. Fit the remaining Installation Flange
size by adding 10mm ± 5mm to both             hole with stud and track and cover this
width and height (For drywall partitions,     with board. Finish edges with joint filler.
calculate the hole to cut size by adding
two board thicknesses to the finished         4. Install the damper and fasten one
hole width and height).                       Installation Flange so that the blade in it’s
                                              closed position is in the centre of the wall


 4    www.actionair.co.uk
CSS ES Rated Fire Damper




          STUD WALL - INSTALLATION DETAIL
                                                 IF YOUR PROPOSED
                                                INSTALLATION DETAIL
                                                 DIFFERS FROM THAT
                                                   SHOWN, PLEASE
                                               DISCUSS THIS WITH THE
                                                 BUILDING CONTROL
                                               AUTHORITY (BCA) USING
                                                THIS DOCUMENT AND
                                                THE ASSOCIATED FIRE
                                                TESTS ASSESSMENTS
                                                      AND OTHER
                                                DOCUMENTS SHOWN.
                                               THEIR APPROVAL MUST
                                               BE OBTAINED PRIOR TO
                                                    INSTALLATION.




                                                PHOTO STORYBOARD
                                                  CSS CATALOGUE
                                                 www.actionair.co.uk



                                                  APPLICABLE TEST
                                                 REPORTS EN1366-2

                                                   BRE 238072

          BRICK WALL - INSTALLATION DETAIL
                                                    BSEN13501-3
                                                   CLASSIFICATION


                                               E120    ES120   E120S


                                                VERTICAL APPLICATION
                                                      CIRCULAR
                                                   SMOKE/SHIELD
                                                    DAMPER SIZE:
                                                     355MM DIA.




                                             www.actionair.co.uk       5
                                                                                                CSS ES Rated Fire Damper


Vertical Mounting in a Rigid Construction Wall - Story board
Drill the four corners to project the         Tidy up all the edges of the hole               the sides. The board should be cut to a
rectangle onto the far side of the            Tidy up all the edges of the hole to leave      width to suit the wall thickness. After
wall                                          in as flat and clean a state as possible,       installation any rough edges should be
Drill through the wall at the four corners.   so that it can be easily lined with fresh       smoothed back. The board must be held
The four resulting holes should then be       board material                                  in place with additional grabber
connected to mark out the hole on the                                                         plasterboard screws
opposite side of the wall. The diagonals      For dry wall partitions, frame out top
should be checked to confirm                  and bottom edges of the hole
squareness.                                   Cut some track of the same type and
                                              dimension as that which was used in
Cut the top and bottom edges of the           the wall construction. This should be
hole                                          slightly longer than the hole top and
It is important to cut the horizontal (top    bottom edge dimension (up to 25mm
and bottom) edges of the hole first, as       longer). One piece is required for the
this keeps the verticals rigid, whilst any    bottom and one for the top of the hole.
studs are cut through. Do one side of         This track should be carefully be pushed
the wall and then the other. Use a fine       in to gap to face of the cavity. It may be
jigsaw blade when cutting through any         necessary to V-notch the ends of the            Finish the hole
studs, to prevent “snagging”.                 track to be able to force it in at the          Finish the edges with plasterboard joint
                                              ends.                                           filler.
Cut the vertical (side) edges of the
hole                                                                                          Install the damper
The vertical sides of the hole may now                                                        Fit one installation flange around the
be cut.                                                                                       damper such that when it is pushed
                                                                                              against the wall, the damper blade will be
                                                                                              at the centre of the wall. Place the
                                                                                              damper in the hole in the wall. Screw the
                                                                                              flange to the wall through the holes
                                                                                              provided.
                                                                                              Fill the gaps with fire rated stone wool
                                                                                              and then fit the remaining flange in a
                                                                                              similar way on the other side of the wall.




Remove the cut material to leave the
hole
The waste wall material should now be
removed. Trying to remove some of the
board layers first, rather than trying to
remove the slug as a whole may ease this.

                                              Frame out the sides of the hole
                                              Cut some stud of the same type and
                                              dimension as that which was used in the
                                              wall construction. This should be the
                                              same as the hole side edge dimension.
                                              One piece is required for each side. This
                                              stud should be carefully pushed into the
                                              gap around the opening.

                                              Finish the installation of the track and
                                              stud
                                              Finish the installation of the track and stud
                                              by fastening at 300mm centres with
                                              grabber plasterboard screws of length to
                                              suit the board thicknesses used.

                                              Line the hole with board
                                              Cut pieces of board to line all four sides
                                              of the hole.
                                              These should be of a length to suit the
                                              width and then slightly reduced to fill in


 6    www.actionair.co.uk
CSS ES Rated Fire Damper




             HORIZONTAL CONCRETE SLAB
                                            IF YOUR PROPOSED
                - INSTALLATION DETAIL      INSTALLATION DETAIL
                                            DIFFERS FROM THAT
                                              SHOWN, PLEASE
                                          DISCUSS THIS WITH THE
                                            BUILDING CONTROL
                                          AUTHORITY (BCA) USING
                                           THIS DOCUMENT AND
                                           THE ASSOCIATED FIRE
                                           TESTS ASSESSMENTS
                                                AND OTHER
                                           DOCUMENTS SHOWN.
                                          THEIR APPROVAL MUST
                                          BE OBTAINED PRIOR TO
                                               INSTALLATION.




                                           INSTALLATION DETAILS
                                                   FOR

                                          246994 FIRE TEST
                                             25 SEPT 08


                                               HORIZONTAL
                                               APPLICATION
                                                 CIRCULAR
                                              SMOKE/SHIELD
                                              DAMPER SIZE:
                                                355MM DIA.




                                        www.actionair.co.uk       7
                                                                                              CSS ES Rated Fire Damper



    Dimensional Data




                   Standard Case Version

                                                                     Control can be mounted in one of three positions
                                                                     vertically down, horizontally or vertically up.
                                                                     Position 1,2 and 3 are as shown. Factory fitted is
                                                                     position 2.

                                                                     Short case version only be available for NDD
                                                                     <=250mm.

                                                                     *NDD: Nominal duct diameter.

                                                                     **ADD: Actual duct diameter. All sizes are
                                                                     accorded with BS EN 1506:1998.

                                                                     Actual duct diameter is approximately 1mm
                                                                     below nominal duct diameter.

                                                                     ****Inc.flanges and M6 actuator.

                 Short Case Version

     Model Ref   * Nominal Duct      *** Open Blade        Casing Leakage
                                                                                          ****
                                                                                                 Weight (Kg)
                     Diameter        Protrusion (mm)            Class
                                                                                  Standard Case Version           Short Case Version
        CSS           100                  –                     C                               4.5                       4.2
        CSS           125                  –                     C                               5.0                       4.6
        CSS           150                  –                     C                               5.4                       5.0
        CSS           160                  –                     C                               5.6                       5.2
        CSS           200                  –                     C                               6.5                       5.9
        CSS           250                  –                     C                               7.6                       6.9
        CSS           300                  –                     C                               8.8
        CSS           315                  –                     C                               9.2
        CSS           350                  6.5                   C                            10.1
        CSS           355                  9                     C                            10.2


    Ordering Information
    Examples
      Quantity    Product         Case              Type         Fail-Safe             Size             Control             Thermal
                                  Depth                          Position                                Mode               Release
         5         CSS             360           Smoke / Fire     Closed             150 Dia            Mode 6            Yes (ETR 72)
         7         CSS             495             Vent           Open               125 Dia            Mode 5            No (Non ETR)

8     www.actionair.co.uk
CSS ES Rated Fire Damper



Actionpac Damper Control Systems

Electro Mechanical Systems                       Actionpac LNS3 Intelligent Damper
                                                                                               • Optional automatic scheduled Damper
                                                 Control and Monitoring System                   testing
Actionpac EMS - Standard Control
                                                 The Actionpac LNS3 system represents a
and Monitoring System
                                                 new generation of smoke/fire damper
                                                                                               • Multiple wiring configurations to include
Control and monitoring of Mode 5 or                                                              Radial or Loop Topology
                                                 control. The system has been designed
Mode 6 damper actuators in groups of             with the user in mind, providing an           • Damper operational count provided
12, 24 or 36.                                    advanced tool that simplifies installation
                                                 and commissioning of smoke/fire
                                                                                               • Flexibility to accommodate any last
                                                                                                 minute changes to strategy, zones,
Actionpac EMB - Bespoke Control                  dampers and peripheral devices. The             damper quantities, references and
and Monitoring System Control Panel              Panel PC operates on a Windows™                 descriptions etc.
                                                 platform making it universally accepted
The EMB Control Panels typically consists
of the appropriate number of switches to
                                                 and utilises solid state technology for       • Powerful and flexible functionality
                                                 optimum reliability.                            enables standardisation of software (no
provide individual or group control, LED                                                         bespoke site specific versions required)
indication for status monitoring and all         It’s server architecture delivers new
necessary relays and timers to comply            benefits such as reduced commissioning        • Cause and effect scenarios easily
with the customer needs for fully or semi        time, simplified operation and scope for        accommodated
automatic damper operation. The EMB              future growth.
panels are purposely manufactured for
                                                                                               • Multiple options for monitoring
                                                 The Actionpac LNS3 system is designed           dampers, individually or by group or
any particular project to suit specific client                                                   zone - output contacts can be
                                                 to protect life and property from damage
requirements.                                                                                    triggered when a predefined
                                                 caused by smoke and fire, by providing
                                                 the means to:–                                  percentage within a group or zone
                                                                                                 change position
                                                 • Compartmentalise fire zones.
                                                 • Reduce the spread of smoke and fire.
                                                                                               • System designed to cater for
                                                                                                 environmental occupancy as well as
                                                 • Keep escape routes and fire-fighting          the building’s smoke / fire strategy.
Addressable Systems                                  access open.                                RS232 BMS link provided enabling a
                                                                                                 BMS to link directly to the system to
Actionpac 60 / 120 ( LNS Standard)               • Allow pressurisation and smoke extract        read damper positions etc.
Intelligent Damper Control and                       by combined operation of dampers
Monitoring System                                    and fans.                                 • Optional remote access available
Actionpac 60 for the control / monitoring        Benefits
                                                                                               • Graphical User Interface displays live
of up to 60 off CSS dampers.                                                                     damper status and details as well as
Actionpac 120 for the control /monitoring        •   Completely flexible to meet practically     cause and effect strategies
of up to 120 off CSS dampers.                        any building’s damper requirements
                                                                                               • Text fields facilitate clear description of
                                                 •   Three levels of alarm priority              device references and locations

                                                 • Panel PC driven system with real-time       • System wide activity logged and
                                                     graphic displays                            viewable for diagnostics and
                                                                                                 maintenance
                                                 • Panel PC utilises solid state technology
                                                     for optimum reliability                   • Allows for phased commissioning and
                                                                                                 future expansion
                                                 • Full configuration and diagnostics from
                                                     Panel PC                                  • CE marked, LVD and EMC compliant




Actionpac LNS3 Intelligent Damper                Fully comprehensive brochures are available on all Actionpac products. Visit the
Control and Monitoring System                    Actionair website w.w.w.actionair.co.uk and download the relevant pdf.




                                                                                                           www.actionair.co.uk            9
                                                                                                  CSS ES Rated Fire Damper



General Schematic of Actionpac LNS3 Damper Control System




                To additional                                                                       To additional
                devices as required                                                                 devices as required




 24/230 volt    SFDI                                                                                           SFDI          24/230 volt
 (local power                                                                                                                (local power
 by others)                                                                                                                  by others)

                                                  SFDI
                                                                 Smoke Fire Damper Interface
                                                                 One per Control Mode


                                                                 Damper Control Mode*


                                                                 Network Digital Input / Output
                                                 NDI404          Device - provides four
                                                                 inputs and four outputs
 24/230 volt    SFDI                                                                                           SFDI          24/230 volt
 (local power                                                                                                                (local power
 by others)                                   One SFDI required per Damper/Section.                                          by others)
                                              Supply to each Damper Interface from
                                              nearest local distribution board.




 24/230 volt    SFDI                                                                                           SFDI          24/230 volt
 (local power                                                                                                                (local power
 by others)                                                                                                                  by others)




                                         SFDI               24/230 volt                           NDI404      24/230 volt
                                                            (local power                                      (local power
                                                            by others)                                        by others)




                                                      Data Network


                                                                   Panel PC

                                                                                                      Fire Alarm Inputs
                                                  OUTPUTS




                                                                                      INPUTS




                 Vent Panel
                                                                                                      BMS Inputs
                       B.M.S.
                                                                                                      Fireman’s Switch Inputs




                For further application, technical and pricing information, please refer to Actionair Sales Office.



10   www.actionair.co.uk
CSS ES Rated Fire Damper



Accessories

A range of indicator panels, push button switches and damper test units are also available. The housing for these units are
manufactured in rigid ABS plastic. The Damper Connection Box is in galvanised steel.




                                                                     DTU24             24V AC/DC                   XNNN00010


                             Damper Test Unit
                             Reset and release indication.
                                                                     DTU120            120V AC                     XNNN00305
                             Spring bias (power OFF) test
                             switch. Power normally ON.


                                                                     DTU230            230V AC                     DNNN00029




                                                                     DSI24             24V AC/DC                   DPNN00412



                             Damper Status Indicator
                             Reset and release indication.           DSI120            120V AC                     XNNN00308




                                                                     DSI230            230V AC                     DPNN00413




                                                                     DCU24             24V AC/DC                   XNNN00309



                             Damper Control Unit
                             Switch ON/OFF function.                 DCU120            120V AC                     XNNN00310
                             Reset and release indication.



                                                                     DCU230            230V AC                     XNNN00311




                              Damper Release and                     DRIM              24V – 230V AC/DC            XNNN00589
                              Indication Module (DRIM)
                              Control and monitoring of the
                              electrically operated
                              Smoke/Shield PTC™ Fire and
                              Smoke dampers.




                                                                     DCB               24V – 230V AC/DC            XNNN00312

                             Damper Connection Box
                             (All Voltages).




                                                                                                          www.actionair.co.uk   11
CSS ES Rated Fire Damper



Ruskin Air Management Limited
is a ISO 9001 and 14001 registered
company.
The statements made in this brochure or by our
representatives in consequence of any enquiries
arising out of this document are given for information
purposes only. They are not intended to have any
legal effect and the company is not to be regarded
as bound thereby. The company will only accept
obligations which are expressly negotiated for and
agreed and incorporated into a written agreement
made with its customers.

Due to a policy of continuous product development
the specification and details contained herein are
subject to alteration without prior notice.



 Comprehensive and detailed information
 is available for all Actionair products.
 Visit our website at www.actionair.co.uk




                                                                                          BROCHURE PRODUCTION www.geoffstrange.co.uk




                        Ruskin Air Management Limited
                                                         South Street, Whitstable, Kent
                                                         CT5 3DU England.
                                                         Tel: 01227 276100
                                                         Fax: 01227 264262
                                                         Email: sales@actionair.co.uk
                                                         Website: www.actionair.co.uk

								
To top