Review of Phase I Oilheat Chimney Venting Project Summary of Key
Document Sample


Review of Phase I Oilheat
Chimney Venting Project
Summary of Key Technical Issues
Prepared by:
Oilheat Manufacturers Association
John E. Batey, PE
Technical Director
Acknowledgements
Oilheat Manufacturers Association (OMA)
members supported this draft vent study.
We also thank Jamie Pye and the Maine
Oil Dealers Association for their valuable
input and funding for this Phase I study.
In additional, we recognize the important
contributions made by Brookhaven
National Laboratory for many years of
oilheat venting research.
Introduction
Technical concerns with chimney venting of
higher efficiency oilheat equipment have
existed for the past 20 years.
Many of these remain unresolved. They need
to be resolved so that consensus guidelines
can be developed to assist oilheat equipment
manufacturers, installers, and code officials.
This initial report summarizes key concerns
and areas where additional research is
needed.
Overview
Chimneys were required for early natural draft oilheat
equipment to draw in the combustion air and to vent
exhaust gases.
In the 1970s the average flue gas temperature was
~ 650F to 700F.
After the 1970s, equipment efficiencies increased
rapidly and flue gas temps dropped.
This increases the possibility of chimney damage from
flue gas condensation especially in older and larger
chimneys.
Existing oilheat chimneys are both lined and unlined
and code groups have begun to look into re-lining.
The concerns are increasing as the efficiency of new
heating equipment continues to rise.
KEY QUESTIONS:
How high can new oilheat equipment
combustion efficiencies go without
incurring chimney damage?
What is the current inventory of
chimneys serving oilheat equipment?
Existing Technical Concerns and Past Research
Past research on chimney venting of gas
appliances identified a number of concerns
related to flue gas condensation and chimney
damage in mid- to high efficiency equipment.
Chimney liners were recommended to increase
flue gas temperatures and lower condensation
rates. (Ref 1,2)
Older gas chimneys are oversized and can
experience flue gas spillage and moisture
condensation within the chimney leading to
chimney damage and potential safety concerns
Technical Concerns and Past Research
Key points include:
Chimney inspection is essential
Sizing tables are needed for the new liners
Periodic vent inspections are recommended
Causes of chimney damage must be understood
before relining
Appliance must be sized to the actual heating demand
Masonry chimneys showing damage should be relined
Vent table should be used to size the reliner when
mid-efficiency gas appliances are installed in an older
masonry chimneys
For oil to gas conversions, careful cleaning of the
chimney liner and debris removal is essential
Technical Concerns and Past Research
Vent II computer model identifies when existing masonry
chimneys are acceptable and when relining is needed.
Unlined masonry chimneys deteriorated more rapidly than lined
chimneys
Chimney crown damage due to freeze-thaw cycling was the most
common damage – the outdoor chimney crown was a good
indicator of chimney condition
Tall chimneys and cold climates contribute to increased
condensation
For gas appliances, water vapor can condense in chimneys lined
with clay tile when exposed at outdoor air temperatures of 32F to
35F – (Note: oil is expected to condense at lower temperatures.)
Dilution air is expected to reduce condensation rates in chimneys
(Note: the difference in dilution rates between gas draft diverters
and oil barometric dampers needs to be examined.)
Vent “wet time” was examined as a measure of vent condensation
Dilution air decreases vent gas temperature, however, and the
benefit of higher vent gas temperature needs to be compared the
reduction in dew point from dilution air.
Technical Concerns and Past Research
The Vent II model’s ability to predict condensation rates
was verified by field tests and was the basis for
developing vent relining tables to guide installation of
gas heating equipment.
Most clay tile lined chimneys that experiences problems
had excessively long vent connectors, were high
chimneys, or did not have dilution air.
Clay tile pieces, mortar, or other debris in the chimney
clean-out are signs of chimney damage
Single gas-fired fan-assisted appliances should not be
vented with unlined or clay tile lined masonry chimneys.
Variability in chimney construction makes it difficult to
determine dilution air rates
Many existing masonry chimneys were not built to
code.
Technical Concerns and Past Research
In 1994 local code officials in Oregon interpreted
national fire codes in a way that prohibited the use of
unlined chimneys for new oil heaters, even though many
had been operating without incident for decades. This
prevented the installation of new oil heating equipment
unless the chimney was lined or rebuilt. (Ref 3)
This incident underscores the need for chimney
venting research and guidelines for oil heating
equipment.
Technical Concerns and Past Research
This initiated an OMA project with the
collaboration of state oil heat associations to
supply input at the National Fire Protection
Association technical committee meetings for
installation of oil burning equipment.
OMA led a group of oil heat associations that
recommended revisions to NFPA-31 to allow new
oil heat equipment to be installed. The revised
standard included provisions for a preliminary
chimney inspection and draft tests when the new
appliance was installed. (See Attachment A -
Action Plan and OMA Tech Update)
Technical Concerns and Past Research
NFPA-31 was also revised to include oil heating
equipment Venting Tables with relining
recommendations developed by Brookhaven
National Laboratory as Appendix E.
These tables are based on a vent model
developed by BNL for oil heat equipment. The
tables present recommendations for chimney
liners but are not requirements as they are
contained in the appendix of the standard.
Technical Concerns and Past Research
Technical Concerns and Past Research
It is noted that for a steady state efficiency of
88%, a chimney height of 10 feet, and a flue
connector 10 feet long, that the highest firing
rate recommended is 0.75 gallons per hour.
Four and five inch liners are not
recommended.
Technical Concerns and Past Research
Ref 4 was developed by engineers at Brookhaven
National Laboratory and focuses on relining
recommendations for masonry chimneys. It is
recommended for existing masonry chimneys to
improve draft and reduce flue gas condensation
when new higher efficiency heating equipment is
installed.
Inspection of the existing chimney liner is
recommended before installing a new appliance.
Many existing chimneys are oversized for the new
more efficient boilers and furnaces that operate
with much lower exhaust gas temperatures than
older equipment.
Technical Concerns and Past Research
One of the key criteria implicit in the BNL
recommendations is the need to maintain a
minimum exhaust gas temperature (95F to 120F)
at the top of the chimney to reduce condensation
and chimney damage.
Laboratory and field testing to verify these
minimum temperatures and validate the OHVAP
model was never conducted. Laboratory and
field testing is needed to validate the findings of
the OHVAP model before it can be used with
confidence.
Technical Concerns and Past Research
30 to 40 years ago flue gas temperatures of oil-
powered boilers and furnaces ranged from 650F
to 700 F.
Typical fuel oil firing rates were 1.25 to 1.50
gallon per hour range.
Modern oil heating equipment has much lower
flue gas temperatures (400 F to 450 F) and lower
firing rates (0.75 to 0.85 gallons per hour) as
equipment efficiencies rose and house heat loads
reduced.
Technical Concerns and Past Research
Exhaust temperatures decrease as efficiency
rises. Chimney draft decreases as the flue gas
temperature drops. Also, the flue gas
temperature at the top of the chimney decreases
as the inlet gas temperature drops. In this way,
installing higher efficiency heating equipment
increases the probability of flue gas condensation
and related chimney concerns.
No specific guidelines now exist that are
commonly acceptable for existing
installations or for the installation of new
higher efficiency oil heating equipment.
Technical Concerns and Past Research
The chimney has a fixed heat loss rate. If the
firing rate is reduced, less heat flow enters the
chimney, and therefore, (for the same chimney
heat losses) the exit gas temperature is lower.
This can contribute to condensation and chimney
damage by using appliances with lower fuel firing
rates.
Technical Concerns and Past Research
A venting report by Brookhaven National
Laboratory presented at the 1995 Oilheat
Technology Conference report contains chimney
venting tables for oil-fired appliances in Appendix
A.
It is noted that as the efficiency increases from
84% to 86% to 88%, the number of Not
Recommended (NR) cases increases indicating that
exhaust gas temperatures at the top of chimney
are considered to be too low. This occurs both for
the lower firing rates and for the taller chimneys.
(Ref 5)
Technical Concerns and Past Research
Field testing and validation of the BNL OHVAP
model is needed before it can be
recommended for use.
However, the vent tables supply valuable
insight into potential chimney venting
concerns for high efficiency oil heating
equipment in conventional masonry
chimneys. Research is needed to fully
evaluate chimney performance at lower flue
temperatures and at lower firing rates.
Technical Concerns and Past Research
Smoke and Odors
Reduction in smoke and combustion odors during
oil burner start-up and shut-down is very
important to enable side wall venting systems.
Research by Brookhaven has shown that
approximately two-thirds of the smoke produced
during cyclic operation is during burner starts and
stops.
Also, recent research with low sulfur and
biodiesel fuel blends suggests that these fuels
produce a significant reduction in PM and fuel and
combustion odors that could favor expanded use
of sidewall vent applications.
Technical Concerns and Past Research
Technical Concerns and Past Research
The Advance Oil Heat – “A Guide to Efficiency
Improvement” that was written by Brookhaven
National Laboratory and the Energy Research
Center about ten years ago includes discussions
on chimney venting.
A basic chimney inspection check list is
presented. Some of this information may be
useful in establishing initial chimney venting
guidelines.
Technical Concerns and Past Research
An article entitled “Backdrafting Woes” in
Progressive Builder provides a means for
quantifying house depressurization and
backdrafting concerns to multiple exhaust fans to
with oil and gas powered heating equipment.
In a tight house the exhaust fans compete with
the chimney-vented appliance for air supply. In
some cases the heating appliance can
backdraft, if the negative pressure in the house is
excessive.
This work is based on many years of research in
Canada on house depressurization. This paper
begins to quantify house “air-tightness” and
exhaust fan air flow rates to house
depressurization.
Technical Concerns and Past Research
The chart that follows shows allowable exhaust
flow rates for a range of house air-tightness
ratings that produce safe and reliable chimney
venting.
A “house depressurization limit is calculated.
When the total exhaust air flow is below this line
the house is safe.
When it is above this line the house may not be
safe as chimney backdrafting may occur.
House depressurization limits vary from house to
house so this is not a general solution.
However, it does illustrate the importance of
treating the house and vent as a “system”, and
can help to diagnose venting problems if the
approach can be applied in a general way.
Technical Concerns and Past Research
Technical Concerns and Past Research
This work is important because it shows
the interaction between the house and the
venting system that directly impacts the
operation of chimney and venting system.
Technical Concerns and Past Research
A Brookhaven National Laboratory report in May 1991
summarizes the current state of chimney venting research:
“The occurrence of low vent-system temperatures, acid
corrosion and the potential for corrosion in the vent system
is an issue of major importance for oil-fired heating
equipment. The areas of immediate concern include the
corrosion of metal vent connectors and chimneys in the
field operation of mid- to high-efficiency equipment…
Based on this work and validation efforts on vent design
programs, recommendations for oil-fired residential
equipment categorization will be provided to the industry.”
This work has not been completed as US Department
of Energy funding was re-directed away from vent
research to other projects.
Preliminary Conclusions
a. Masonry chimneys that are unlined or lined with
clay tile may degrade over time if excessive flue
gas condensation occurs after installing new oil
heating equipment with lower exhaust gas
temperatures and reduced fuel firing rates.
b. Chimneys serving natural gas fired heaters
began to experience condensation concerns as
Annual Fuel Utilization Efficiencies reached 82
percent. Oil equipment operates with about 4
percent less heat loss due to water vapor in the
flue gas (latent heat). Therefore, as oil
appliances approach AFUE efficiencies in the
upper 80 percent range, then increased chimney
degradation through excess flue gas
condensation is more likely to occur.
Preliminary Conclusions
c. Oil heating equipment efficiencies have
increased substantially over the past three
decades increasing concerns related to the
suitability of existing chimneys. Average
AFUEs have increased from 78 percent twenty
years ago to the mid-80 percent range today.
The US Department of Energy is considering
increasing minimum efficiency levels even
further which increases these concerns.
d. Many variables impact the rate of condensation
in individual chimneys as discussed in this
report. There are no industry accepted
guidelines for prescribing the maximum
efficiency for heating equipment in chimneys of
varying designs and sizes.
Preliminary Conclusions
e. Fire protection and building standards and
codes require lined chimneys for new
installations. Code inspectors and authorities
having jurisdiction are free to interpret and
enforce the provisions of fire and building
codes. This has limited the installation of new
oil heat equipment in the past.
Recommended Actions
1. Draft initial guidelines for oilheat equipment
manufacturers and identify the need for additional
research to address areas of uncertainty or concern.
The information contained in this report and
references are a starting point for this effort. OMA
can play a key role in drafting these initial guidelines.
2. Revise initial oil heat chimney guidelines based on
review comments submitted by equipment
manufacturers and installers, and other interested
parties. Identify areas where additional information
is needed so that research efforts can be planned
and conducted.
3. Develop a Project Plan with the goal of producing
final guidelines for oil heat equipment and initiating
and supporting new research.
STATEMENT OF NEED
The absence of industry consensus
standards for the venting of oil-fired
heating appliances leads to confusion in
the market which is an impediment to oil
use generally and to the upgrade of
existing systems with new, high efficiency
equipment specifically.
1. Field measurements of surface temperatures on
inner walls of selected chimney systems
• Logged over 1 week time periods
• Correlated with weather conditions
• 12 sites targeted – lined masonry, steel, one- and two-
story, “good” and “problem” sites
• 8 or more measurement points along length of vent, local
data loggers
Purpose:
• To begin to establish criteria for what is acceptable with oil
• To develop and demonstrate simple temperature
measurement method
• Identify need-for and scope-of a more comprehensive field
test
2. CFD Simulation of Model Chimney
Systems
• Commercial Fluent Code, 3-D, transient
• Model and run several of field test sites
Purpose:
• Evaluate low-cost modeling method
• Validation against field results
3. Initial Draft of Preliminary Guidelines
• Develop initial guidelines based on Draft Phase I Report
• Prepare “strawman” guidelines for industry review
• Collect, review , and incorporate industry comments
• Identify specific areas where additional research is needed
Purpose:
• Develop preliminary venting guidelines
• Identify the need for addition research for formulating
final guidelines
Related docs
Get documents about "