					V8 SERIES ELECTRIC VALVE

V8 series electric valve
特点
            Low power consumption Position feedback by signal Direct/reverse acting 4-20mA/0-10V/2-10V choice Maintenance free Quick and easy installation No separate linkage required Accurate valve positioning Indicator Continuous Position Indicator Manual Override Non-clutch design Gear Permanently lubricated and self locking Stall Protection Built-in thermal protection

Aplication
The QM/QF series of electric valve actuators are used in heating, ventilation, and air-conditioning (HVAC) applications. The QM series of electric valve actuators are modulating control actuators used with controls that provide an analog output of 0 to 10Vdc, 2 to 10Vdc or 4-20mA. The internal selector plug can be used to reverse the direction of action. The QF series of electric valve actuators are controlled by an on/off output.

Ordering :
Valve type V8224 V8225 V8231 V8232 V8239 V8240 V8249 V8250 V8263 V8265 V8279 V8280 V8299 V82100
V1.0

DN mm 25 25 32 32 40 40 50 50 65 65 80 80 100 100

KVs 16 26 16 32 25 32 40 49 95 110 110 145 145 180

Close bar 8 8 8 8 8 8 8 8 8 8 8 8 8 8

Actuator type A8105 A8005 A8110 A8010 A8110 A8010 A8110 A8010 A8116 A8016 A8116 A8016 A8125 A8025

power AC 24V AC 24V AC 24V AC 24V AC 24V AC 24V AC 24V AC 24V AC 24V AC 24V AC 24V AC 24V AC 24V AC 24V

Control signal DC 0(2) -10V On/off or 3 point DC 0(2) -10V On/off or 3 point DC 0(2) -10V On/off or 3 point DC 0(2) -10V On/off or 3 point DC 0(2) -10V On/off or 3 point DC 0(2) -10V On/off or 3 point DC 0(2) -10V On/off or 3 point

Running time 120s 120s 120s 120s 120s 120s 120s 120s 120s 120s 120s 120s 120s 120s

Torque N.m 5 5 10 10 10 10 10 10 16 16 16 16 25 25
Page 1/4

Australia Controls Hysine

V8 SERIES ELECTRIC VALVE

Technical data:
Actuator
Actuator 扭矩 电源 运行时间 运行时功率 输出角度 控制信号 反馈信号 保护等级 工作环境 净重 材质 A81X 05, 10, 16, 25N.m AC 24V 大约 120S 5VA 90°± 3° 4-20mA/0(2)-10V DC 0-10V IP54 温度-10℃~55℃;湿度小于 90% 1 公斤 阻燃 ABS 开关/浮点 位置开关 A80X

Valve
煤质 煤质温度 阀体承压 渗漏率 关断压力 口径 材质 安装位置 冷冻水,热水,最大 50% 乙二醇 -10° +100° C.. C 16 或 27 公斤 密封(气密性为 DIN 3230) 10 公斤 DN25-DN100 阀体为不锈钢或铸铜,阀杆为不锈钢 垂直,或水平安装(禁止倒装)

Asemble
Opening/closing the valve can be judged by the line on the valve stem. When the valve opened, the line is parallel with flow direction.
Operate the valve manually to fully open or fully closedposition before the actuator is mounted. Operate the actuator and valve stem to fully open or fully closed position. Check that the actuator and valve stem are in correct position. Please note, valve and actuator must be in the same mode (fully open/fully closed) prior to the assembly. Mount the actuator on the valve and check that the actuator and valve stems are centered and aligned.

Motor protection
The internal force sensor will turn off the actuator when the valve is locked accidentally during running, so the motor of the actuator will never overload. Manual operation The QM/QF are equipped with a manual operator knob to open or close valves in the events of power failure. Push down the manual operator knob and turn the knob: A: counterclockwise to drive the valve close B: clockwise to drive the valve open

V1.0

Australia Controls Hysine

Page 2/4

V8 SERIES ELECTRIC VALVE Direction of action Repositioning the selector plug S3 can change the direction of action. S3 ON 10V / 20 mA OFF 0V

Control signal
The control signal Vdc/mA can be changed by selector plug S1. The control signal 0-10V/2-10V can be changed by selector plug S2
S1 S2 ON ON ON 0-20mA / OFF 0-10V 2-10V / OFF 0-10V 4-20mA /OFF 0-20 mA

Terminal connections

A81X

Proportional

A80X on/off

A80X 3-point

WARNING
1.Only for professional installation. To avoid injury and electric shock, do not perform any servicing other than that contained in this manual. 2. All actuators have been installed before shipped from the factory; no electrical adjustments are required before placing them in operation. 3.Check the connections before energizing the power supply because wrong connections can damage the equipment. 4.The actuator should be stored in a clean and dry shipping carton.

V1.0

Australia Controls Hysine

Page 3/4

V8 SERIES ELECTRIC VALVE

Dimension :

Diameter
mm 65 80 100

Dimension (mm) L 185 200 215 H 185 200 215

R 120 135 150

N On / off

Kvs Proportional

4 8 8

119
140 175

95
110 140

Diameter
mm 25 32 40 50
V1.0

Dimension (mm) Lmp. 1 1-1/4 1-1/2 2 L 80 100 110 120 H 70 70 85 90

thread R 1 1-1/4 1-1/2 2 On / off

Kvs Proportional

25
32 40 50

16
18 25 40
Page 4/4