									Comparison of IEEE 62 IEEE Guide for Diagnostic Field Testing of Electric Power Apparatus Part 1: Oil Filled Power Transformers, Regulators, and Reactors to PC57.93 Draft D 10 Guide for Installation and Maintenance of LiquidImmersed Power Transformers
Prepared by: John Mathews, Lewis Powell, Paulette Payne Powell, and Kipp Yule Sheet 1 -- Section 4 Diagnostics & Annex C Sheet 2 -- Section 5 Personnel - Safety Sheet 3 -- Section 6 Tests & Annex A & B

Comparison of IEEE 62 to ANSI/IEEE C57.93 IEEE Guide for Diagnostic Field Testing of Electric Power Apparatus Part 1: Oil Filled Power Transformers, Regulators, and Reactors Prepared by John Mathews (BGE) Clause in IEEE 62
Clause 4 Diagnosti c Test Chart

Subject Issue

Requirements / Recommendations

Other Document and clause
PC57.93 - Draft 10 Guide for Installation and Maintenance of Liquid-Immersed Power Transformers

Requirements / Recommendations

Reference Conflict? each other? (Y/N) (Y/N)

Winding Short Circuit Impedance Induced Voltage/Partial Discharge/RIV

Cls 4

Not mentioned.

Should be included to establish base measurement.

N

N

"

Not mentioned.

Not required. Should be included to establish base measurement. Not required.

N

N

Oil Particle Count Oil Oxidation Stability

" "

Not mentioned. Not mentioned.

N N

N N

Frequency Response Analysis Liquid-To-Water Heat Exchanger Pressure Test CT Ratio, Polarity, and Resistance Tests Tank Vacuum Test Oil Furan Test Paper Insulation DP Test

"

Not listed. Should be added.

3.2, 4.3.1, 4.11

Swept Frequency Response Analysis is recommended. This should be revised to generic Frequency Response Analysis.

N

N

"

Not listed. Should be added.

4.7.3

N

N

" " " "

Not listed. Should be added. Not listed. Should be added. Not listed. Should be added. Not listed. Should be added. Not listed. Should consider addition.

4.7.4, 4.11 4.8.1 4.13.1.5 4.13.1.5

N N N N

N N N N

Dewpoint Test

"

Annex C

N

N

Additional Note: The Clause 4 Diagnostic Test Chart does not list Load Tap Changer Tests to be performed on regulators. This addition should be considered during revision.

Comparison of IEEE 62 to ANSI/IEEE C57.93 IEEE Guide for Diagnostic Field Testing of Electric Power Apparatus Part 1: Oil Filled Power Transformers, Regulators, and Reactors Prepared by Kipp Yule Section 5 Safety Note IEEE 62-1995 provides a section specific to safety, while there is not a dedicated section for safety in PC57.93 D10. Consideration should be given to adding a section on safety to C57.93 for topics that include: (CSE) Confined Space Entry , Spill Containment Kits, Material Safety Data Sheets (MSDS), Lock Out -Tag Out Procedures (LOTO), Protection from Voltage Hazard, and Protection from Arc FlashHazard.

IEEE 62
5.2.1

C57.93

Topic

Discussion
More detailed guidance could be provide regarding disconneted, isolated & grounded with respect to what conditions need to be coincident to constitute a safe working environment. (Possible suggest may include LOTO, references to NESC, and IEEE 1584) Possible suggestion to include LOTO

No directly Safety / Personnel / Hazards corresponding section

5.2.3

5.2.5

5.3.1

No directly corresponding section No directly corresponding section No directly corresponding section

Safety / Personnel / Precautions

Safety / Personnel / Atomsphere Possible suggest may elaborate on Confined Space Entry Inside Tank procerdures, including personnel recovery, tool inventory / control. Safety / Apparatus / The consequence of fire is lightly addressed. Further best Conequences of failure practices could be enhanced for fire prevention as well as fire mitigation. The intensity of the arc hazard should be quantified and appropriate personnel protective equipment used based in incident energy levels in use or possible. This should include gas generation or even tank rupture in the event of a catastrpohic event.

5.3.2

N/A N/A N/A N/A

No directly Safety / Apparatus / Overvoltage corresponding section 3.1 General 2nd paragraph "For outdoor …." 3.2 Inspection and receipt 3.3.1 General practices for Inspection and receipt 3.6 Storage

Possible suggestion to request / review MSDS Available of oil spill kits may be appropriate. Possible suggestion to include LOTO ….. Drums stored outside must be protected from the possibility of water contamination….. (add in spill prevention dyke enclosure with MSDS accompaning shipments). Add provision for spill prevention dyke enclosure and MSDS accompaning liquid delivery.

N/A

4.8.4

Processing dielectric liquid

Comparison of IEEE 62 to ANSI/IEEE C57.93 IEEE Guide for Diagnostic Field Testing of Electric Power Apparatus Part 1: Oil Filled Power Transformers, Regulators, and Reactors Prepared by Lewis Powell and Paulette Payne Powell Section 6.0 and the Annexes A& B. Note IEEE 62 provides detail not given in C57.93. Item for potential revision is 6.1.3.2.

IEEE 62
6.1.1

C57.93
4.11e

Topic
Winding Resistance

Discussion
C57.93 only states comparison to factor data, whereas IEEE 62 also includes comparison to winding phases or terminal pairs depending on winding connection. C57.93 only states Kelvin Bridge, whereas IEEE 62 also includes micro-ohmmeter for <1ohm and Wheatstone bridge >1ohm. C57.93 states ratio on each tap (DETC); if LTC - on all load tap positions - it is unclear but could be construed as all combinations of DETC and LTC; IEEE 62 is clearer - it states it load taps present - with DETC in one position such as nominal or maximum turns position on all LTC tap positions, and on other DETC positions with LTC at neutral. C57.93 states at reduced test voltage, whereas IEEE 62 states at the highest possible test voltage without exceeding the voltage rating of the excited winding. The test voltage should be similar what is stated in 6.1.6.5 - i.e. as in the field the test is usually performed at 10kV or lower voltage. No overlaps or conflicting information No overlaps or conflicting information power factor for new transformers/reactors <0.5% consistent with both documents measurement of C1 and C2 consistent with C57.93

6.1.1.1

4.11.e

Measurement Techniques

6.1.2.3

4.11d

Turns Ratio Test

6.1.3.2

4.11.j

Exciting Current - Test Methods

6.1.5 6.1.6 6.1.6.8

4.11a 4.11b 4.1

Insulation Resistance Capacitance, power factor and dissipation factor Capacitance, power factor and dissipation factor - Test procedure Bushings - Capacitance, power factor and dissipation factor

6.2.4 and Annex B

4.11c and

6.3 6.4 6.5.2 6.6 Annex A Annex B

4.7.2 4.11g 4.11.i 6.1.6 4.11.f and 4.11.i

Insulating Fluids Tap Changers Core insulation resistance and inadvertent ground test Tanks and associated devices

IEEE 62 includes all criteria listed in C57.93 plus additional criteria; there are no conflicts. No overlaps or conflicting information No overlaps or conflicting information No overlaps or conflicting information no conflicts no conflicts

Any section in 6.0 of IEEE 62 not listed above has no corresponding reference to C57.93


								