All Power Battery DC systems are available with output

Document Sample
All Power Battery DC systems are available with output Powered By Docstoc
					All Power Battery DC systems are available with output circuit breakers for overload protection
or as DC disconnect. These thermal magnetic trip breakers are designed to meet
t o d a y ’s rigorous re q u i rements while offering safety for both the operator and the system.

                                                                            FEATURES AND BENEFITS
                                                              • U.L. Listed.
                                                              • Double insulation for total separation of the power and
                                                                auxiliary circuits.
                                                              • T h e rm   al-magnetic trips.
                                                              • E l e c t romagnetic compatibility - does not generate
                                                                interference with other electronic equipment.
                                                              • Installation position - can be installed upright and
                                                                horizontally with no variation of rated characteristics.
                                                              • Vibration resistant - unaffected by vibrations caused
                                                                mechanically or electromagnetically.
                                                              • B reaker accessories are field installable.



                                                                               BREAKER SELECTION
    2 POLE (500 VDC) CIRCUIT BREAKER
                                                              • Maximum amps: the kWb multiplied by 1000 and
 SELECTION CHART AND OUTPUT WIRE SIZE                           divided by the system cutoff voltage.
 CIRCUIT ALLOWED MAXIMUM
BREAKER AMPS FOR RUN TIMES      SUGGESTED OUTPUT WIRE SIZE
RATING, LESS THAN  THREE                NEC TABLE
 MODEL    THREE    HOURS                 310-16
NUMBER    HOURS   OR MORE
                                                                                BREAKER OPTIONS
 H30          29.7     23.7         10 Ga. - 1/0 Ga.
 H50          49.5     39.6            8 Ga. - 1/0 Ga.        • Auxiliary switch: (double pole, double throw) add
 H60          59.4     47.5            6 Ga. - 1/0 Ga.          “A/S”, ”A/D” to the breaker part number.
                                                              • Shunt trip: add “S” and the DC shunt voltage* to the
 H70          69.3     55.4            4 Ga. - 1/0 Ga.
                                                                breaker part number. Example: “S24”
 H100         99.0     79.2            2 Ga. - 1/0 Ga.
                                                              • Under voltage release: add “UV” and the DC under voltage
 H125         123.7    99.0            1 Ga. - 4/0 Ga.          release voltage* to the part number. Example: “UV24”
 H150         148.5    118.8       1/0 Ga. - 4/0 Ga.          • Hinge out breaker plate.
 H175         173.2    138.6       2/0 Ga. - 300 MCM          • Bell alarms: To order add BA to breaker part #.
 H200         198.0    158.4       3/0 Ga. - 300 MCM          • 3 pole (750 VDC) version also available.
 H225         222.7    178.2       4/0 Ga. - 300 MCM          * If a shunt trip or under voltage release for AC voltage is
 H300         297.0    237.6   2 X 1/0 Ga. - 2 X 250 MCM        required, add an "A" after the voltage. (Example a shunt
 H400         396.0    316.8   2 X 3/0 Ga. - 2 X 250 MCM        trip at 120 V.A.C. would be S120A)
 H600         594.0    475.2   3 X 3/0 Ga. - 3 X 400 MCM
 H800         792.0    633.6   3 X 300 MCM - 3 X 400 MCM

                                                                     SYSTEM PART NUMBER DESCRIPTION
  CIRCUIT BREAKER                        BREAKER
    ACCESSORIES                        ENCLOSURES             • To order a cabinet system with a circuit breaker simply
 ACCESSORY            PART #     PART#         WILL HOLD
                                                                add the appropriate circuit breaker part number to the
                                                                end of the cabinet system part number.
 Under voltage         UVR       E-1        H30, H60, H100,
                                                              • Example: Cabinet system part number 1CR4-40120S-480
                                              H125, H225
                                                                using an H400 circuit breaker with a 24 volt shunt trip.
 Auxillary switch       AD       E-2              H400
                                                                The complete part number will be: 1CR4-40120S-480-H400-S24
                                 E-3           H600, H800
 Shunt trip             S        E-4          H1000, H1200
                                                                                                                                                  }
                                                                                                                                                      Auxiliary
                                                                                                                                                      contacts
                                                                                                                                                      (A/S)


                                                                                                                                                  }   Undervoltage
                                                                                                                                                      release
                                                                                                                                                      (UV24)




    Typical cabinet system with breaker                                                      System connection points



                                                                                • Type 1 general purpose indoor
                                                                                  enclosure intended for use in
                                                                                  normal environments.
                                                                                • Sheet steel, surface mount.
                                                                                • Breaker is front operable and
                                                                                  can be padlocked via a front
                                                                                  hasp.
                                                                                • U.L. listed for use as service
                                                                                  entrance equipment (SUSE).
                                                                                • ANSI – 61 grey.



                                                                          WALL MOUNTED BREAKER ENCLOSURES
      1 CR3-20TC150C-240-7.0-H400
• 240 volt battery and charger system with a
                                                                        BREAKER         ENC.             DIMENSIONS IN/MM
  400 amp breaker on a hinged swing out panel,                           TYPE           NO.              H                  W     D
  for easy system maintenance.
                                                                      H30 to H225       EN-1 22.0/559                  12.0/305 4.5/114
                                                                      H300, H400        EN-2 30.0/762                  17.5/444 4.5/114
                                                                      H600, H800        EN-3 44.0/1117 22.0/559 6.0/152
                                                                      H1000, H1200 EN-4 51.8/1316 20.3/514                      7.75/197
U.S.A.                               CANADA                                         UK                                           ITALY
Power Battery Company, Inc.          Power Battery (Iberville) Ltd.                 Power Batteries Ltd.                         Power Battery Srl
25 McLean Blvd.                      770 Thomas Ave.                                Premier Way, Abbey Park Industrial Estate    Via Locatelli 105
Paterson, N.J. 07514-1507            Iberville, Québec, J2X 5E7                     Romsey, Hampshire, SO51 9AQ                  20046 Biassono MI - ITALY
Phone:      (973) 523-8630           Phone: (450) 346-3273                          Phone: +44 (0)1794 835900                    Phone: +(39) 039 2324571
Fax:        (973) 523-3023           Fax:        (450) 346-8003                     Fax:     +44 (0)1794 835910                  Fax:      +(39) 039 2499200
E-mail:     sales@powbat.com         E-mail: powerbat@sympatico.ca                  E-mail: sales@powbat.co.uk                   E-mail: calberti@powbat.it