									     EXHIBIT 14 20 00-2, ELEVATOR DESIGN CHECK-OFF SHEET




                    AE Drawing and Written Specification Development Process & Check-off Sheet
     All below items must be noted as to "Do not install until placement is coordinated with Elevator contractor's equipment"
                                         regardless of locations shown on AE drawings
                                 Written      Location of
                              specification    Detail on
                              designation      drawings
                                shall be        shall be
                               provided in     provided
                             space - below       below
                             Item Location      Item
                                 within       Location
          PITS                Documents:        show                 Comments
                              page & spec     Drawing's
                                number         sheet #

     All below items must be noted as to "Do not install until placement is coordinated with Elevator contractor's equipment"
                                         regardless of locations shown on AE drawings
                                                                                                        See Drawing 14 20 00-3,
         Ladder
                                                                                                        Elevator Pit Ladder Detail.
                                                                                                         See Section 22 13 29 –
   Sump pump hole
                                                                                                            Sewerage Pumps.
                                                                                                         See Section 22 13 29 –
  Sump pump & cover
                                                                                                            Sewerage Pumps.
                                                                                                      See Section 26 80 00 - Elevator
Sump pump elec. outlet
                                                                                                         Electrical Requirements
Sump pump discharge                                                                                       See Section 22 13 29 –
       detail                                                                                               Sewerage Pumps.
                                                                                                      See Section 26 80 00 - Elevator
      Light switch
                                                                                                         Electrical Requirements

                                                                                                      See Section 26 80 00 - Elevator
      Light fixture
                                                                                                         Electrical Requirements

                                                                                                      See Section 26 80 00 - Elevator
       GFI outlet
                                                                                                         Electrical Requirements
                                                                                                      See Section 21 10 00 – Water-
        Sprinkler                                                                                        Based Fire Suppression
                                                                                                                 Systems.
                                                                                                       There should never be a heat
  NO heat nor smoke
                                                                                                      detector nor a smoke detector
detector installed in pit.
                                                                                                        installed in an elevator pit.


                             Item Location      Item
                                 within       Location
       Hoistway               Documents:        show
                              page & spec     Drawing's
                                number         sheet #

     All below items must be noted as to "Do not install until placement is coordinated with Elevator contractor's equipment"
                                         regardless of locations shown on AE drawings
                                                                                                      Nothing else allowed to exist in
                                                                                                      the elevator hoistway - unless -
    Other equipment
                                                                                                        "directly" associated with the
                                                                                                                   elevator.
Sprinklers in overhead -                                                                              See Section 21 10 00 – Water-
only in existing buildings                                                                                Based Fire Suppression
           - IF -                                                                                                  Systems.
  Smoke detectors in
overhead - typically not                                                                              See Section 28 30 00 – Fire and
         required                                                                                       Smoke Detection System.
    Heat detectors in
overhead - typically not                                                                              See Section 28 30 00 – Fire and
         required                                                                                       Smoke Detection System.




                                                                                                                     EXHIBIT 14 20 00-2
     U OF I FACILITIES STANDARDS                                Page 1 of 3                                  LAST UPDATED JULY 1, 2010
     EXHIBIT 14 20 00-2, ELEVATOR DESIGN CHECK-OFF SHEET




                                                                                                        Check drawings for ledges in
                                                                                                        hoistway and if they exist they
        Ledges                                                                                        must be chamfered 75 degrees -
                                                                                                      show on drawings and assign in
                                                                                                         specification to a contractor.
                                                                                                           Special requirements but
                                                                                                      typically not an issue - check for
        Sub pit                                                                                        requirements if sub pit exists -
                                                                                                          discuss requirements with
                                                                                                              elevator consultant.
                                                                                                       Must have adequate overhead
                                                                                                       working clearances on elevator
      Overhead                                                                                         car top as per elevator code --
                                                                                                             Confirm with Elevator
                                                                                                                  Consultant.
                                                                                                        Only required when overnight
        Venting                                                                                           sleeping involved with new
                                                                                                                   buildings.
Hoistway Sill Support                                                                                   Show detail on drawings - as
Details for C3 & heavy                                                                                   applicable - coordinate with
  loading elevators                                                                                           elevator consultant.
                           Item Location     Item
                               within      Location
    Machine room            Documents:       show
                            page & spec    Drawing's
                              number        sheet #

     All below items must be noted as to "Do not install until placement is coordinated with Elevator contractor's equipment"
                                         regardless of locations shown on AE drawings
  Proper sizing for
                                                                                                         frequently sized too small
working on equipment
                                                                                                      See Section 26 80 00 - Elevator
      GFI outlet
                                                                                                         Electrical Requirements
                                                                                                       Confirm that a *note* exists on
   Machine room on
                                                                                                          all drawings in every elev
drawings - diagonals &
                                                                                                       machine room - on every sheet
     or notation on
                                                                                                      "Nothing may be installed or run
mechanical drawings so
                                                                                                          through this space unless
other equipment is not
                                                                                                           directly associated with
   run through space
                                                                                                                   elevator."
                                                                                                       Review drawings ensuring NO
                                                                                                        other equipment exists in the
  Other equipment -
                                                                                                         elevator hoistway - unless -
   review drawings
                                                                                                        "directly" associated with the
                                                                                                                   elevator.
                                                                                                      See Section 26 80 00 - Elevator
 Main line disconnect
                                                                                                         Electrical Requirements
 Main line Shunt Trip
                                                                                                      See Section 26 80 00 - Elevator
  breaker located in
                                                                                                         Electrical Requirements
    machine room
 Main line disconnect
                                                                                                      Ensure this Contact is written in
   Aux Contact for
                                                                                                         the electrical contractor
hydraulic elevators with
                                                                                                        specification - if applicable
   battery lowering
                                                                                                      See Section 26 80 00 - Elevator
Car lighting disconnect
                                                                                                         Electrical Requirements

  Emerg power to car                                                                                  See Section 26 80 00 - Elevator
    lighting circuit                                                                                     Electrical Requirements

  Emerg power to                                                                                      See Section 26 80 00 - Elevator
machine room lighting                                                                                    Electrical Requirements

Verify whether Program
  requires elevator to
have emergency power.




                                                                                                                     EXHIBIT 14 20 00-2
     U OF I FACILITIES STANDARDS                                Page 2 of 3                                  LAST UPDATED JULY 1, 2010
     EXHIBIT 14 20 00-2, ELEVATOR DESIGN CHECK-OFF SHEET




    Emerg power to
machine room cooling if                                                  See Section 26 80 00 - Elevator
  elevator on emerg                                                         Electrical Requirements
         power
Verify adequate power
ia provided to elevator
      equipment.

   Smoke detectors                                                       See Section 28 30 00 – Fire and
                                                                           Smoke Detection System.

    Heat detectors                                                       See Section 28 30 00 – Fire and
                                                                           Smoke Detection System.
   Telephone line &                                                          See Section 27 00 00 -
       conduit                                                                 Communications.
                                                                             See Section 27 00 00 -
  Ethernet & conduit
                                                                               Communications.
                                                                         See Section 26 80 00 - Elevator
      Light fixture
                                                                            Electrical Requirements

                                                                         See Section 26 80 00 - Elevator
      Light switch
                                                                            Electrical Requirements
                                                                            See Equipment Rooms,
       ventilation
                                                                                  Mechanical
                                                                         See Section 08 11 13 – Hollow
  42" door opens out
                                                                           Metal Doors and Frames
door hardware -- keying -                                                See Section 08 11 13 – Hollow
    closer - lockset                                                       Metal Doors and Frames
                                                                          ABC required in elev machine
   Fire extinguisher
                                                                                     room
   Removable code
   compliant Barrier                                                        See U of I Facilities and
 between hoistway and                                                      Standards elevator-related
    machine room                                                           documents; coordinate with
    (Basement Set                                                             elevator consultant.
      Machines )

                                                                            See U of I Facilities and
  Traction Elevators:       Item Location     Item                         Standards elevator-related
 Overhead Machinery             within      Location                        documents for overhead
 Space Requirements          Documents:       show                       machinery space requirements.
  (for non-overhead          page & spec    Drawing's                      Elevator consultant should
   machine rooms)              number        sheet #                      provide requirements as per
                                                                          building standards and code.




                                                                                        EXHIBIT 14 20 00-2