UTILIZING VENTILATION EFFICIENCY FACTORS TO PREDICT INDOOR CARBON

W
Document Sample
scope of work template
							  UTILIZING VENTILATION EFFICIENCY FACTORS TO PREDICT
     INDOOR CARBON DIOXIDE CONCENTRATION IN FIELD
       MEASUREMENTS OF TAIWAN’S OFFICE BUILDINGS

                Yen-Yi Li, Che-Ming Chiang, Po-Chen Chou, Chi-Ming Lai, Yu-Feng Tu

                      Department of Architecture, ArchiLife Environ-Control Research Center,
                         National Cheng-Kung University, Tainan, 70101 Taiwan, R.O.C.




ABSTRACT

The ventilation criteria of Building Code in Taiwan stipulate only the least air exchange volume per square
meter, an index of air exchange efficiency. However, the indoor air pollutants from many investigated
buildings are found to be with concentrations higher than several exposure criteria. We consider that the lack
of including “effective ventilation factors” in current Building Code can be in part explained as contributing to
the above phenomenon. Therefore, a more comprehensive index to reflect the air exchange efficiency should
be considered for inclusion in the Building Code.

A trace-gas technique was used to measure the ventilation efficiency in field studies. The ACH (air change
per hour) value, mean age of air, air exchange efficiency, and CO2 concentrations were measured
simultaneously. We also utilize the ACH values, air exchange efficiency, and CO2 concentrations to construct
the theory calculation.

A simplified, predictive equation is established after the field data is compared with the values calculated
from the above theoretical equation. The air exchange efficiency is shown to be the critical factor to build the
EACH (Effective ACH) from ACH. The simplified predictive formulae enables us to calculate what the
acceptable number of people are for the room based on HVAC ventilation efficiency even before the
building is occupied.

KEYWORDS

ACH value, Tracer-Gas Technique, Air Exchange Efficiency, Field Measurements, Office Building

INTRODUCTION

Taiwan is an island located in subtropical region with high temperature and humidity year-round according to
the data of National Central Weather Bureau. The average temperature is 34.5 ¢J in summer, and even in
spring and fall the temperature is 28 ¢J . Therefore, the application of HVAC system becomes essential to
control the thermal comfort in most building.

According to the investigation experience in Office Building survey, the indoor air pollutants from many
investigated buildings are found to be with concentrations higher than several exposure criteria. We
considered it could be lack of fresh air exchanging, so we improved the air exchange rate to get good indoor
air quality (IAQ). However, it seems that only increase the intake fresh air volume couldn’t improve the IAQ
of all the area. We consider that the lack of including “effective ventilation factors” in current Building Code
in Taiwan can be in part explained as contributing to the above phenomenon. Therefore, a more
comprehensive index to reflect the air exchange efficiency should be considered for inclusion in the Building
Code.

METHODS

   The IAQ and Ventilation Efficiency field measurements in this study can be divided into three main
categories: the building selection include the performance of HVAC system, the IAQ survey include
concentration levels, population distribution density levels and thermal comfort and the ventilation efficiency
measurements. Methods for each are described briefly below.

Test building Selection

   To realize different HVAC system and different building construction types affected the IAQ and
ventilation situations, six different buildings were chosen to be the test objectives. Table 1 is the brief overview
of the buildings. The performance of HVAC system can be evaluated via current operational situations, air
exchange rate, air distribution, and thermal comfort conditions:

                                                    Table 1.
                                         The details of six test buildings
            ID No.           Bldg. A      Bldg. B        Bldg. C        Bldg. D     Bldg. E       Bldg. E
           Location         Kaohsiung Kaohsiung          Tainan        Tainan        Taipei        Taipei
         Construction          RC            RC            RC         SRC         RC         SRC
          Age, years           18            16            14           15         19         10
                               FCU          AHU                      FCU +
         HVAC type                         (Air Handling    FCU                  FCU        AHU
                           (Fan Coil Unit)     Unit)                 Natural
                                           Peripheral               Peripheral Peripheral
        Room location       Inner zone                   Inner zone                       Inner zone
                                              zone                    zone       zone
           Test date        Oct. 1997 April 1998 April 1998 May. 1998 Dec. 1997 Mar. 1998
            Layout          Open plan Cellular Open plan Cellular               Cellular Open plan

Indoor Air Quality Survey

  To assess the IAQ situation and evaluate the ventilation efficiency, it is necessary to take a Standard
Operation Procedure in field survey. It can be briefly illustrated as follows.

 1.Walk-through Inspection

   This task is to understand the building/HAVC system and its surroundings. Efforts should be made to look
for the inherent characteristics that can result in IAQ problems, for example, outdoor-air intake, frequency of
duct cleaning etc. Factors, which can adversely affect the performance, should also be noted. For example,
combustion devices, copy machines, office cleaning frequencies, cleaning agents, interior decoration
materials… etc. Results should be recorded in the checklists or via photographs.
2.Chemical Pollutants Measurements

    Carbon monoxide (CO), Carbon dioxide (CO2), and Suspended Particles (PM10, counted by those are
smaller than 10 mm in aerodynamic particle size) were monitored continuously for a 24-hour period. Their
detection principles are illustrated in Table 3 respectively.

   Formaldehyde (HCHO) and Total Volatile Organic Compounds (TVOC) samples from investigated
locations were collected continuously and sent to the Multi-Gas Monitor, which is based on the photo-
acoustics detection principle.
                                                     Table 2.
                       Performance of apparatus for monitoring chemical contaminants
       Item                 Method for analyzing                           Range         Precision
       CO                   Electrochemical oxidation                    0~150 ppm      < ±1 ppm
       CO2                  Non-dispersion infrared absorption          0~5000 ppm      < ±50 ppm
                                                                                      3
       PM10                 Light scatter at a fixed angle            0.001~10mg/m        < 10 %
       Formaldehyde         Photo-acoustics infrared spectroscopy        ~0.04 ppm      < ±1.55 %
       TVOC                 Photo-acoustics infrared spectroscopy       ~0.02 mg/m  3
                                                                                        < ±1.55 %

3.Thermal Comfort

   On-situation measurements of air temperature, relative humidity, and velocity were accomplished to
evaluate the indoor thermal conditions for a 24-hour period. Performances of the apparatus are listed in Table
3.
                                                  Table 3.
                          Performance of apparatus for thermal comfort evaluation
          Item                        Method for analyzing                Range               Precision
          Temperature                 Resistance                       -40~115¢J              <±0.3¢J
          Relative humidity           Capacitance                      0~100%RH               <±0.1%
          Velocity                    Hot-wire                          0~30m/s                 <±2%


Ventilation Efficiency Measurements

 1.Air Exchange Rate Measurement

    Air exchange rate was measured with the tracer gas decay method. An adequate amount of Sulphur
Hexafluoride (SF6) gas is injected directly into the air supply main duct. After injection, about 1.5 hours is
allowed for mixing of the tracer gas. Samples from investigated locations and the return duct are collected
continuously and sent one after another into the Multi-Gas monitor that is based on the photoacoustic
detection principle. The Air exchange rate is then obtained by plotting the measured concentrations in
logarithm scales against time in hours. Those data are fitted with a straight line and the slope of the line is the
Air exchange rate (ACH). [Shaw, 1991]

 2.Air Exchange Efficiency

  The Air Exchange Efficiency (AEE) can present the air-flow-pattern of the ventilation room. To decide the
AEE depended on the major two factors in the office building with HVAC system:
   -     Relative location of the supply and extract devices
   -     Momentum of the jet
                                                     Table 4.
             Performance of Room ventilation situation and the Air Exchange Efficiency representation
          Situation                Air-Exchange Efficiency         The Evaluation with the Age-of-air
        Unidirectional                                              Local mean age-of-air in Exhaust
                                            100¢M
                                       50¢M¡ã
            Flow                                                    ¡×Room average age-of-air¡Ñ 2
                                                                    Local mean age-of-air in Exhaust
        Perfect Mixing                      50¢M
                                                                      ¡×Room average age-of-air
                                                                    Local mean age-of-air in Exhaust
       Short- Circuiting                     50¢M
                                         0¢M¡ã
                                                                      ¡ÕRoom average age-of-air

   For ventilation measurement, the Concentration Decay Method is chosen for the standard operation
procedure. The Air Exchange Rate (ACH), Room average age-of-air and Local mean age-of-air were
measured at the same time. The AEE value was also calculated with the age-of-air indicators.

RESULTS

   All the results of the field survey in different six buildings are as Table 5 shows. The ACH (air change per
hour) value, mean age of air, air exchange efficiency, and CO2 concentrations were measured simultaneously.
As figure 1 shows, when the HVAC system introducing outdoor air the EACH (Effective ACH, EACH =
ACH ¡Ñ AEE) value is higher than the no outdoor-air intake situation. To compare with the ACH and added
CO2 concentration (Figure 2), the EACH value has more representation than only ACH in describing the
ventilation efficiency. We also utilize the ACH values, air exchange efficiency, and CO2 concentrations to
construct the theory calculation. The result equations are as follows:

       Cadd = 1000 ⋅ EACH −2 (open outdoor air inlet)                                                       (1)
                           −1 .5
       Cadd = 500 ⋅ EACH           (close outdoor air inlet)                                                (2)

   Where Cadd is the added CO2 concentration by the occupies.

   A simplified, predictive equation is established after the field data is compared with the values calculated
from the above theoretical equation. The air exchange efficiency is shown to be the critical factor to build the
EACH (Effective ACH) from ACH.
Added CO 2 Conc. per meter per person




                                                                                             Added CO 2 Conc. per meter per person
                                        16000                                                                                        14000
                                        14000                                     -2                                                 12000
                                                                     y = 1000x                                                                                        y = 500x-1.7
                                        12000
                                                                                                                                     10000
                                        10000                        R 2 = 0.6987                                                                                     R 2 = 0.5252
                                                                                                                                      8000
                                        8000
                                                                                                                                      6000
                                        6000
                                                                                                                                      4000
                                        4000
                                        2000                                                                                          2000

                                           0                                                                                             0
                                                0.0    0.5     1.0      1.5      2.0   2.5                                                   0.0   0.2   0.4    0.6     0.8   1.0    1.2

                                                             EACH Value (open)                                                                           EACH Value (close)

                                                      Figure 1: The added CO2 conc. per meter per person and the EACH relationship
  Added CO2 Conc. per meter per person




                                                                                               Added CO2 Conc. per meter per person
                                         12000                                                                                        12000

                                         10000                                                                                        10000

                                           8000                                                                                       8000

                                           6000                                                                                       6000

                                           4000                                                                                       4000

                                           2000                                                                                       2000

                                              0                                                                                          0
                                                  0.0     1.0     2.0     3.0      4.0   5.0                                                  0.0   0.5     1.0      1.5      2.0   2.5
                                                                ACH Value (open)                                                                          ACH Value (close)

                                                        Figure 2: The added CO2 conc. per meter per person and the ACH relationship

DISCUSSION

   The furniture location and HVAC system type are the critical factors for the air exchange efficiency. The
ACH and AEE value constructed EACH value could be the effective design criteria In the architecture design
procedure. The simplified predictive formulae enables us to calculate what the acceptable number of people
are for the room based on HVAC ventilation efficiency even before the building is occupied.

ACKNOWLEDGEMENT

   We are especially grateful to ARCHILIFE Research Foundation for support of Numerical and
experimental facilities.

REFERENCE

                                         ASHRAE, (1989), ASHRAE Handbook ¡AFundamental Volume¡AAmerican Society of Heating,
                                         Refrigerating and Air-conditioning Engineering Inc., Atlanta, GA.
                                         ASHRAE, (1989). ASHRAE Standard 62,Ventilation for Acceptable Air Quality¡AAmerican
                                         Society of Heating, Refrigerating and Air-conditioning Engineering Inc., Atlanta, GA.
                                         Shaw, C. Y., Magee, R. J., Shirtliffe, C. J. and Unligil, H., 1991, Indoor Air Quality Assessment in an
                                         Office-Library Building: Part 1-Test Methods, ASHRAE Transactions. Vol. 97, No. 2, 129-135.
                                         A.I.V.C. Guide to Ventilation. (1996). A Guide to Energy Efficient Ventilation. Martin W Liddament
                                         Che-Ming Chiang, Yen-Yi Li, Po-Cheng Chou, Chi-Ming Lai, (1999). CFD Simulation to Predict
                                         Natural Ventilation Efficiency in a Dwelling Bedroom with the Central Horizontal Pivot Window,
                                         INDOOR AIR 99, Vol. 4.
                                         Che-Ming Chiang, Chi-Ming Lai, Po-Cheng Chou, Yen-Yi Li, (1999). The Influence of An
                                         Architectural Design Alternative (Transoms) on Indoor Air Environment in Conventional Kitchens
                                         in Taiwan. BUILDING AND ENVIRONMENT.
                                         C.M Chiang, R.P. Lai, (1998). The diagnostic methods of relationship between indoor air quality
                                         and HVAC facilities in office buildings. The Research Report of the Architecture and Building
                                         Research Institute, Taiwan.
Table 5 The detail results of six test buildings
                                    Kaohsiung              Kaohsiung              Tainan   Tainan        Taipei               Taipei
                                    Building A             Building B            Bldg. C  Bldg. D      Building E           Building F
             Factors
                                       Fall                 Summer               Summer   Summer         winter              Spring
                                   2F        3F      5F        2F       1F          2F       2F        7F      10F       3F      5F         6F
                                                                                           FCU +
        HVAC System               FCU        FCU     AHU      AHU       AHU       FCU                 FCU      FCU       AHU      AHU      AHU
                                                                                           Ducts
    Construction Type                   RC                   RC                    RC       SRC             RC                   SRC
                 Ages                  1982                 1984                  1986      1985           1981                  1990
                 Area                70       104      525     341        525        735       853    722      722         176      377      129
     Population Number               4~5     9~10       11      13         28         13        52     92       62          36       40        1
                Density            0.06      0.09     0.02    0.04       0.05       0.02      0.06    0.13     0.09       0.20     0.11     0.01
                 High               966       658      628     642        932        776       809      600 1222         1512     1374       732
         CO 2   Average             562       545      467     452        760        579       598      420      607       524      437      456
        (ppm)     SD                166        32      105     122        118        129       145        50     324       405      224       76
                 High              0.10      0.24     0.07    0.07       0.07       0.12      0.07      0.03     0.02     0.02     0.01     0.03
         PM 10  Average            0.06      0.08     0.05    0.05       0.05       0.06      0.05      0.02     0.02     0.01     0.01     0.02
      (mg/m3)     SD               0.02      0.06     0.02    0.01       0.01       0.02      0.01      0.01         0    0.01     0.00     0.01
         ACH     open              3.92      2.42     1.50    1.30       1.74       0.78      2.32     2.10     1.89      2.78     2.80     2.98
         (h-1)   close             1.45      1.05     1.25    1.10       1.49       0.41      2.15     1.65     1.32      1.65     1.45     1.90
                 open             20.6%     36.0%    36.7% 89.0%        22.6%      31.8%     24.0%    81.9% 39.6%        26.9%    32.4%    15.3%
         AEE
                 close            24.5%     34.3%    35.6% 67.8%        15.4%      29.3%     13.0%    65.5% 37.1%        45.2%    55.4%    17.5%
                 open             0.808     0.872    0.551   1.157      0.393      0.248     0.557    1.720 0.749        0.749    0.906    0.457
        EACH
                 close            0.355     0.360    0.445   0.746      0.229      0.120     0.280    1.080 0.490        0.746    0.804    0.333
                 High              26.5      27.2     27.1    26.1       27.2       25.1      25.2      20.6    19.5      27.9     26.4     26.6
        Temp    Average            25.9      26.6     26.0    24.9       26.2       24.3      23.4      19.1    18.5      27.3     25.5     24.8
         ( ¢J )   SD                 0.8       0.5      1.1     1.4        0.9        0.8       1.1      0.4      0.6     30.6       0.6    33.6
                 High              67.2      70.8     66.1    70.0       64.3       46.0      59.1      53.8    55.7      78.0     65.5     84.5
          RH    Average            56.9      64.9     55.3    62.8       55.9       45.3      53.4      49.5    51.7      64.9     50.4     64.7
       ¡]¢M¡^     SD               10.6        2.3      7.4     6.6        6.5        0.5       4.0      2.9      2.7     21.8       9.7    24.8
                 High              0.03      0.51     0.08    0.05       0.05       0.06      0.08      0.08    0.21      0.07     2.07     0.17
           V    Average            0.03      0.03     0.01    0.03       0.02       0.03      0.05      0.07    0.10      0.02     0.31     0.05
       (m/sec)    SD               0.01      0.10     0.01    0.01       0.02       0.02      0.02      0.01    0.03      0.02     0.43     0.04

						
Related docs