Critical Control - GMR - Gexpro
Document Sample


Critical Control
GMR
GMR
GMR
Genius
The architecture is based on the strong Genius Concept
Enhanced Diagnostics
Rigid
Proven
Modular
Scalable
Flexible
Redundancy
Safety
Fail Safe
Fault Tolerant
Availability
October 2001 2
Introduction
Architectures
Input-group
CPU-group
Output-group
October 2001 3
Architecture
Input CPU Output
Simplex Simplex Simplex T-Pattern
Duplex Duplex Diagnostic H-Pattern
Triplex Triplex I-Pattern
I-Pattern = Fail Safe
T-Pattern = Fault Tolerant
H-Pattern = Fail Safe &
Fault Tolerant
October 2001 4
Architecture
October 2001 5
Architecture
GE Fanuc Model
October 2001 6
Architecture
PFD for GE Fanuc Safety System
INPUT GROUP
configuration PFD
Simplex 6.81 x 10-5
Duplex (1oo2D) 1.34 x 10-06
Duplex (1oo2) 1.35 x 10-06 me
Si pl x Dupl x ( 1oo2 D)
e e
Dupl x ( 1oo2 ) pe
Tri l x
Triplex 1.36 x 10-06
CPU GROUP
configuration PFD
Simplex (1oo1) 7.11 x 10-4
Simplex (1oo1D) 8.24 x 10-04
Duplex (1oo2D) 1.63 x 10-05
me
Si pl x ( 1oo1) me
Si pl x ( 1oo1D) Dupl x ( 1oo2 D)
e e
Dupl x ( 1oo2 ) pe
T r i l x ( 2 oo3 )
Duplex (1oo2) 1.71 x 10-05
Triplex (2oo3) 2.19 x 10-05
OUTPUT GROUP
configuration PFD
Simplex (1oo1) 7.11 x 10-4
Simplex (1oo1D) 8.24 x 10-04
Duplex (1oo2D) 1.63 x 10-05 1oo1 1oo1D 1oo2 D 1oo2 D 2 oo3
Duplex (1oo2) 1.71 x 10-05
October 2001 7
PFD
PFD for GE Fanuc Safety Configurations
INPUT GROUP CPU GROUP OUTPUT GROUP
configuration PFD configuration PFD configuration PFD
Simplex 6.81×10-05 Simplex 7.11×10-04 Simplex 6.81×10-05
Simplex 6.81×10-05 Duplex (1oo2) 1.63×10-05 Simplex 6.81×10-05
Simplex 6.81×10-05 Duplex (1oo2d) 1.71×10-05 Simplex 6.81×10-05
Simplex 6.81×10-05 Triplex (2oo3) 2.19×10-05 Simplex 6.81×10-05
Simplex 6.81×10-05 SimplexD 8.24×10-04 I-Block/1oo1d 1.34×10-06
Duplex (1oo2d) 1.34×10-06 SimplexD 8.24×10-04 I-Block/1oo1d 1.34×10-06
Duplex (1oo2d) 1.34×10-06 Duplex (1oo2d) 1.63×10-05 I-Block/1oo1d 1.34×10-06
Duplex (1oo2d) 1.34×10-06 Duplex (1oo2d) 1.63×10-05 H-block/1oo2d 1.35×10-06
Simplex 6.81×10-05 SimplexD 8.24×10-04 I-Block/1oo1d 1.34×10-06
Duplex (1oo2) 1.35×10-06 SimplexD 8.24×10-04 I-Block/1oo1d 1.34×10-06
Duplex (1oo2) 1.35×10-06 Duplex (1oo2) 1.71×10-05 I-Block/1oo1d 1.34×10-06
Duplex (1oo2) 1.35×10-06 Duplex (1oo2) 1.71×10-05 H-Block/1oo2d 1.35×10-06
Triplex (2oo3) 1.36×10-06 Triplex (2oo3) 2.19×10-05 I-Block/1oo1d 1.34×10-06
Triplex (2oo3) 1.36×10-06 Triplex (2oo3) 2.19×10-05 H-Block/1oo2d 1.35×10-06
October 2001 8
PFD
Approvals
APPROVALS
DIN NFPA IEC
V 19250/05.94 72/96 61508/12.97 (Draft
V VDE 0801/01.90 8501/97 part 1,3,4,5,6,7)
EN 50178/04.98 8502/99 61508-2 (Draft)
EN 55011/91 1131-2/92
EN 54-2/12.97 61000-4-2,3,4,5
VDE 0116/10.89 60068-2-
1,2,6,14,27,30
October 2001 9
Approvals
Certification
October 2001 10
Approvals
Applications
F&G (Fire and Gas) FPSO (Flow Production &
ESD (Emergency Shutdown Offloading Unit)
BMS (Burner Management SBM (Single Boy Mooring)
System) Semi Submersibles
BMS (Boiler Management Submarine Control
System) Pipeline
BOP (Blow Out Preventor) Wellhead control
Transport Furnace
Tunnel Oven / Autoclave
Crane High Pressure tanks
Turbine Bridge / Sluice / Gate
HSRG (Heat Steam Recovery Jail / Guarding
Generator)
Aeroplane / Ship Fuelling
October 2001 11
Applications
Why GE Fanuc ?
=
Best Practises
October 2001 12
6 Sigma
CGR
References
Our Customers
Maer
sk Diamond Offshore
China Railways
Our Experience (Click on Details)
October 2001 13
References
TECHNOLOGY AND MORE
October 2001 14
Get documents about "