					PowerLogic
ION7550/ION7650
Energy and power quality meters
Purpose

● Improve power quality measurements and enhance functionality.
  (Certified ION7650 according to the IEC 61000-4-30 Class A)
       ● Anti-Aliasing
       ● Flicker
       ● Trending & Forecasting
       ● Disturbance direction detection
       ● Alarm Setpoint Learning
● Support new Ethernet Card for faster connections
● 100BASE-T/100BASE-FX
● SNMP traps
● Multilingual HMI



Schneider Electric - Division - Name – Date                       2
Markets. Supply Side. Cont…

● Reasons to buy
       ● Multipoint, multi-protocol communications
       ● PQ compliance monitoring
       ● Transient detection
       ● Waveform recording sampling rate
       ● High accuracy revenue metering
       ● ITC (Instrument Transformer Compensation). Eliminates need to replace
         Instrument transformers where accuracy is required
       ● Transformer losses compensation when the meter is in a different location
         than the billing point.




Schneider Electric - Division - Name – Date                                          5
Positioning

● Customers with Medium and Large Energy Consumption
       ● Reduce energy costs
       ● Making energy a variable cost


● Customers with Process Sensitive to PQ or Power Reliability
       ● Improve reliability
       ● Improve PQ


● The ION75/7650 together with the ION-E software provides a powerful
  tool that offers many other features to the above customers.




Schneider Electric - Division - Name – Date                             6
                 IEC 61000-4-7 (2002) :Aliasing
  What is Aliasing?
  ● Aliasing is an effect that causes different continuous signals to become
    indistinguishable (or aliases of one another) when sampled. When this
    happens, the original signal cannot be uniquely reconstructed from the
    sampled signal.

  ● Aliasing is a major concern in power quality analysis because improper
    sampling of the analog signal will cause high-frequency components to be
    aliased with genuine low-frequency ones, and be incorrectly reconstructed.




Schneider Electric - Division - Name – Date                                      9
Aliasing Effect
Wagon Wheel Example

● Optical illusion that occurs in older
  movies when wagon wheels appear to
  be turning backwards.
● Caused by slower frame speed of
  camera relative to the high speed of the
  wagon wheels.




Schneider Electric - Division - Name – Date   10
What Causes Aliasing?
   ● Aliasing (or folding) occurs when a signal is sampled at a rate that is insufficient to
     capture the changes in the signal.
   ● Sampling at a lower rates results not only in missing data, but also incorrect re-creation of
     the waveform, leading to faulty analysis.




    Sampled Source
    Sampling Point
    Re-created Signal

                                        Sampled Source   Re-created Signal

Schneider Electric - Division - Name – Date                                                    11
                                      Aliasing Effect Example
                           Sampled Source                                           100              Actual
                                                                                     90
                                                                                     80




                                                                  Amplitude (%)
                                                                                     70
                                                                                     60
                                                                                     50
                                                                                     40
                                                                                     30
                                                                                     20
                                                                                     10
                                                                                      0
                                                                                          1   3       5        7       9   11
                                                                                                  Harmonic Component




                          Re-created Signal                                                       Reported
                                                                                    100
                                                                                     90
                                                                                     80


                                                                    Amplitude (%)
                                                                                     70
                                                                                     60
                                                                                     50
                                                                                     40
                                                                                     30
                                                                                     20
                                                                                     10
                                                                                      0
                                                                                          1   3       5        7       9   11
                                                                                                  Harmonic Component


 Sampled Source                               Re-created Signal
Schneider Electric - Division - Name – Date                                                                                     12
How do you avoid Aliasing?
   ● The Nyquist Sampling Theorem states that in order to avoid aliasing, the
     sample rate should be at least twice the highest frequency contained in the
     sample




    Sampled Source
    Sampling Point
    Re-created Signal

                                         Sampled Source   Re-created Signal

Schneider Electric - Division - Name – Date                                        13
  Sampling Rate

  ● Sample rates are important in adequately representing the original
    signal.
  ● Oversampling the original signal:
        ● Increases the meter’s bandwidth
        ● Reduces metering error
        ● Provides a closer approximation to the original signal




PQA 2004 - Division - Name – Date
  Schneider Electric                                                     14
What is new with firmware 350?

● Trending and forecasting

● Disturbance direction detection

● Setpoint learning

● Gateway Functionality with Modbus TCP protocol

● Simple Network Management protocol (SNMP)

● 100 Base TX/FX




Schneider Electric - Division - Name – Date        16
Trending and forecasting

                       ● Trends and Forecast up to 10 different user configurable
                         channels
                               ● Hourly – Displays last 24 hrs plus current.
                               ● Daily– Displays last 30-31 days plus current.
                               .


                       ● Viewable through ION75/7650 Web-pages by using Ethernet
                         port and IE




Schneider Electric - Division - Name – Date                                         17
Schneider Electric - Division - Name – Date   18
Disturbance direction detection
Confidence Scores
                                              ● Requires a trigger (Sag, Swell or a
                                                Transient) to run the algorithm

                                              ● Then the ION 75/7650 determines the
                                                direction of a disturbance

                                              ● Provides a confidence score and the
                                                direction of the disturbance. All recorded in
                                               the Event Log.

                                              ● While the algorithm for a transient is
                                                running, any further pulses are ignored.




Schneider Electric - Division - Name – Date                                                     19
Alarm Setpoint Learning
                                  ● Setpoint Module (65).- Monitors a source with respect to an
                                    absolute threshold and it can evaluate either an over or an under
                                    condition

                                  ● Sag/Swell Module (1).- The Sag/Swell Module learns two
                                    values: a sag limit and a swell limit

                                  ● Disturbance Analyzer (6).- Learns an over-alarm If the pickup
                                    value is greater than 100% of the nominal value at the moment
                                    when learning period is initiated; also, an under-alarm will be
                                    learned if the pickup values is less than 100% of the nominal
                                    value.

                                  ● And Transient Module (6).- Evaluates when transients occur in
                                    the system.

                                  ● All four modules Include the following characteristics:
                                          ● Learn now input
                                          ● Learn install mode
                                          ● Learn duration


Schneider Electric - Division - Name – Date                                                           20
Gateway Functionality with Modbus TCP
protocol

● Provides gateway functionality when the Ethernet port and/or modem options
  are present
● Modbus Master allows front panel display of real-time parameters from any
  downstream Modbus devices.
                                                         EtherGate                                      ModemGate

                                              Ethernet                        Telephone line
                                                                     Serial                                         Serial




           ● EtherGate: access via Ethernet port and                          ● ModemGate: access from
             ModbusTCP to daisy-chained Modbus                                  telephone network to devices
             devices connected to the meter’s serial                            connected to the meter’s serial ports
             ports


Schneider Electric - Division - Name – Date                                                                                  22
Simple Network Management protocol
(SNMP)

● Some applications as Data Centers and Critical Power require SNMP protocol
  to map (convert) registers or data from the meter in to usable information for the
  different systems.

● This implementation of the ION7650 and 7550 supports read only mode, except
  for the following SNMP related text strings:
       ● System Contact
       ● System Name
       ● System Location


● You can also customize the text on the meter’s MIB (Management Information
  Base) file: ion7x50schneiderMIB.asn.




Schneider Electric - Division - Name – Date                                        23
100 Base TX/FX Connectivity

● New communications cards support 100 Base TX and 100 Base FX
  connections
● This will support more network infrastructures




Schneider Electric - Division - Name – Date                      26
New communications card. (Field
installations)

● Firmware v350 or higher is required

● The 7550/7650 communications card is not supported on legacy
  meters ION7500 and ION7600.

● The difference is only that the D7 and F1 provide faster Ethernet
  connections (100Base-TX and 100Base-FX rather than 10Base-T and
  10Base-FL).




Schneider Electric - Division - Name – Date                           34
New communications card. (Field
installations)
                                                       Speci
                       Comm
                                       Type             al
                        Card
                                                       Order

                     P765
                     C

                      ION7550 /
                      7650 Comm               Order Code       Description
                      Card*
                      Comm Card                 P765C          ION7550 / ION7650 Communications card for field retrofit installations

                      Type                        A0           Standard communications (1 RS-232/RS-485 port, 1 RS-485 port).
                                                               Front optical port support for meters with integrated display.

                                                  C1           Standard communications plus 10/100BASE-T Ethernet (RJ-45), 56k universal internal
                                                               modem (RJ-11; the modem port is shared with the front optical port). Ethernet and modem
                                                               gateway functions each use a serial communications port.

                                                  D7           Standard communications plus 10/100BASE-T Ethernet, 100BASE-FX Ethernet Fiber, 56k
                                                               universal internal modem (RJ-11; the modem port is shared with the front optical port).
                                                               Ethernet and modem gateway functions each use a serial communications port.

                                                  E0           Standard communications plus 10/100BASE-T Ethernet. Ethernet gateway function uses a
                                                               serial communications port.

                                                  F1           Standard communications plus 10/100BASE-T Ethernet, 100BASE-FX Ethernet Fiber (SC
                                                               fiber optic connection). Ethernet gateway function uses a serial communications port.

                                                  M1           Standard communications plus 56k universal internal modem (RJ-11; the modem port is
                                                               shared with the front optical port). Modem gateway function uses a serial communications
                                                               port.
                      Special Order               A            None

                                                  C            Tropicalization treatment applied




Schneider Electric - Division - Name – Date                                                                                                               35
New communications options and part
numbers

● Example of New Part Number with one of the new communications options:
                          M7650B1C0B6F1A0E
                Communications                ■ A0.- Standard Comms: 1 RS232/RS485 port (COM1), 1
                                                RS485 (COM2), Integrated display models also include a Type
                                                2 ANSI optical port (COM4)

                                              ■ E0.- Standard Comms. plus Ethernet 10/100 BaseT Ethernet
                                                (RJ-45). Ethernet gateway function uses a serial
                                                communications port.
                                              ■ D7..- Standard communications plus 10/100Base-T Ethernet
                                                (RJ-45) and 100BASE-FX Ethernet Fiber, 56k universal
                                                internal modem (RJ-11). Ethernet and modem gateway
                                                functions each use a serial communications port.

                                              ■ F1.- Standard communications plus 10/100Base-T Ethernet
                                                (RJ-45) and 100BASE-FX (SC fiber optic connection).
                                                Ethernet gateway function uses a serial communications port.

Schneider Electric - Division - Name – Date                                                                36
Integration with ION-Enterprise

● Version 5.6 SP1 supports all new features of the ION75/7650 firmware
  version 350




Schneider Electric - Division - Name – Date                              38

				