PRIVATIZATION ARMY LODGING

					                                         SECTION 230500

                           COMMON WORK RESULTS FOR HVAC


PART 1 - GENERAL


1.1     RELATED DOCUMENTS

  A.    Drawings and general provisions of the Contract, including General and
        Supplementary Conditions and Division 01 Specification Sections, apply to this
        Section.


1.2     SUMMARY

  A.    This Section includes the following:

        1.    Piping materials and installation instructions common to most piping systems.
        2.    Escutcheons.
        3.    HVAC demolition.
        4.    Equipment installation requirements common to equipment sections.
        5.    Painting and finishing.
        6.    Supports and anchorages.


1.3     DEFINITIONS

  A.    Finished Spaces: Spaces other than mechanical and electrical equipment rooms,
        furred spaces, pipe and duct chases, unheated spaces immediately below roof, spaces
        above ceilings, unexcavated spaces, crawlspaces, and tunnels.

  B.    Exposed, Interior Installations: Exposed to view indoors. Examples include finished
        occupied spaces and mechanical equipment rooms.

  C.    Exposed, Exterior Installations: Exposed to view outdoors or subject to outdoor
        ambient temperatures and weather conditions. Examples include rooftop locations.

  D.    Concealed, Interior Installations: Concealed from view and protected from physical
        contact by building occupants. Examples include above ceilings and chases.

  E.    Concealed, Exterior Installations: Concealed from view and protected from weather
        conditions and physical contact by building occupants but subject to outdoor ambient
        temperatures. Examples include installations within unheated shelters.

  F.    The following are industry abbreviations for plastic materials:

        1.    CPVC: Chlorinated polyvinyl chloride plastic.
        2.    PE: Polyethylene plastic.
        3.    PVC: Polyvinyl chloride plastic.
Privatized Army Lodging                    230500 - 1                           Lend Lease
Alterations for HIE Branding                            Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                         October 20, 2011
  G.    The following are industry abbreviations for rubber materials:

        1.    EPDM: Ethylene-propylene-diene terpolymer rubber.
        2.    NBR: Acrylonitrile-butadiene rubber.


1.4     SUBMITTALS

  A.    Product Data: For the following:

        1.    Escutcheons.

  B.    Welding certificates.


1.5     QUALITY ASSURANCE

  A.    Steel Support Welding: Qualify processes and operators according to AWS D1.1,
        "Structural Welding Code--Steel."

  B.    Steel Pipe Welding: Qualify processes and operators according to ASME Boiler and
        Pressure Vessel Code: Section IX, "Welding and Brazing Qualifications."

        1.    Comply with provisions in ASME B31 Series, "Code for Pressure Piping."
        2.    Certify that each welder has passed AWS qualification tests for welding
              processes involved and that certification is current.

  C.    Electrical Characteristics for HVAC Equipment: Equipment of higher electrical
        characteristics may be furnished provided such proposed equipment is approved in
        writing and connecting electrical services, circuit breakers, and conduit sizes are
        appropriately modified. If minimum energy ratings or efficiencies are specified,
        equipment shall comply with requirements.


1.6     DELIVERY, STORAGE, AND HANDLING

  A.    Deliver pipes and tubes with factory-applied end caps. Maintain end caps through
        shipping, storage, and handling to prevent pipe end damage and to prevent entrance of
        dirt, debris, and moisture.

  B.    Store plastic pipes protected from direct sunlight. Support to prevent sagging and
        bending.


1.7     COORDINATION

  A.    Arrange for pipe spaces, chases, slots, and openings in building structure during
        progress of construction, to allow for HVAC installations.

  B.    Coordinate installation of required supporting devices and set sleeves in poured-in-
        place concrete and other structural components as they are constructed.

Privatized Army Lodging                    230500 - 2                           Lend Lease
Alterations for HIE Branding                            Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                         October 20, 2011
  C.    Coordinate requirements for access panels and doors for HVAC items requiring access
        that are concealed behind finished surfaces. Access panels and doors are specified in
        Division 08 Section "Access Doors and Frames."


PART 2 - PRODUCTS


2.1     ESCUTCHEONS

  A.    Description: Manufactured wall and ceiling escutcheons and floor plates, with an ID to
        closely fit around pipe, tube, and insulation of insulated piping and an OD that
        completely covers opening.

  B.    One-Piece, Deep-Pattern Type: Deep-drawn, box-shaped brass with polished chrome-
        plated finish.

  C.    Split-Casting, Cast-Brass Type: With concealed hinge and set screw.

        1.    Finish: Polished chrome-plated.

  D.    Split-Plate, Stamped-Steel Type: With concealed hinge, set screw, and chrome-plated
        finish.

  E.    One-Piece, Floor-Plate Type: Cast-iron floor plate.

  F.    Split-Casting, Floor-Plate Type: Cast brass with concealed hinge and set screw.


PART 3 - EXECUTION


3.1     HVAC DEMOLITION

  A.    Refer to Division 01 Section "Cutting and Patching" and Division 02 Section "Selective
        Structure Demolition" for general demolition requirements and procedures.

  B.    Disconnect, demolish, and remove HVAC systems, equipment, and components
        indicated to be removed.

        1.    Piping to Be Removed: Remove portion of piping indicated to be removed and
              cap or plug remaining piping with same or compatible piping material.
        2.    Piping to Be Abandoned in Place: Drain piping and cap or plug piping with same
              or compatible piping material.
        3.    Ducts to Be Removed: Remove portion of ducts indicated to be removed and
              plug remaining ducts with same or compatible ductwork material.
        4.    Ducts to Be Abandoned in Place: Cap or plug ducts with same or compatible
              ductwork material.
        5.    Equipment to Be Removed:           Disconnect and cap services and remove
              equipment.


Privatized Army Lodging                  230500 - 3                           Lend Lease
Alterations for HIE Branding                          Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                       October 20, 2011
        6.    Equipment to Be Removed and Reinstalled: Disconnect and cap services and
              remove, clean, and store equipment; when appropriate, reinstall, reconnect, and
              make equipment operational.
        7.    Equipment to Be Removed and Salvaged: Disconnect and cap services and
              remove equipment and deliver to Owner.

  C.    If pipe, insulation, or equipment to remain is damaged in appearance or is
        unserviceable, remove damaged or unserviceable portions and replace with new
        products of equal capacity and quality.


3.2     PIPING SYSTEMS - COMMON REQUIREMENTS

  A.    Install piping according to the following requirements and Division 23 Sections
        specifying piping systems.

  B.    Drawing plans, schematics, and diagrams indicate general location and arrangement of
        piping systems. Indicated locations and arrangements were used to size pipe and
        calculate friction loss, expansion, pump sizing, and other design considerations. Install
        piping as indicated unless deviations to layout are approved on Coordination Drawings.

  C.    Install piping in concealed locations, unless otherwise indicated and except in
        equipment rooms and service areas.

  D.    Install piping indicated to be exposed and piping in equipment rooms and service areas
        at right angles or parallel to building walls. Diagonal runs are prohibited unless
        specifically indicated otherwise.

  E.    Install piping above accessible ceilings to allow sufficient space for ceiling panel
        removal.

  F.    Install piping to permit valve servicing.

  G.    Install piping at indicated slopes.

  H.    Install piping free of sags and bends.

  I.    Install fittings for changes in direction and branch connections.

  J.    Install piping to allow application of insulation.

  K.    Select system components with pressure rating equal to or greater than system
        operating pressure.

  L.    Install escutcheons for penetrations of walls, ceilings, and floors according to the
        following:

        1.    New Piping:

              a.    Piping with Fitting or Sleeve Protruding from Wall:         One-piece, deep-
                    pattern type.

Privatized Army Lodging                       230500 - 4                             Lend Lease
Alterations for HIE Branding                                 Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                              October 20, 2011
              b.    Chrome-Plated Piping: One-piece, cast-brass type with polished chrome-
                    plated finish.
              c.    Insulated Piping: One-piece, stamped-steel type with spring clips.
              d.    Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-piece,
                    cast-brass type with polished chrome-plated finish.
              e.    Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-piece,
                    stamped-steel type.
              f.    Bare Piping at Ceiling Penetrations in Finished Spaces: Split-casting, cast-
                    brass type with polished chrome-plated finish.
              g.    Bare Piping at Ceiling Penetrations in Finished Spaces: Split-plate,
                    stamped-steel type with concealed hinge and set screw.
              h.    Bare Piping in Unfinished Service Spaces: One-piece, cast-brass type with
                    polished chrome-plated finish.
              i.    Bare Piping in Unfinished Service Spaces: One-piece, stamped-steel type
                    with concealed hinge and.
              j.    Bare Piping in Equipment Rooms: One-piece, cast-brass type.
              k.    Bare Piping in Equipment Rooms: One-piece, stamped-steel type with set
                    screw.
              l.    Bare Piping at Floor Penetrations in Equipment Rooms: One-piece, floor-
                    plate type.

        2.    Existing Piping: Use the following:

              a.    Chrome-Plated Piping: Split-casting, cast-brass type with chrome-plated
                    finish.
              b.    Insulated Piping: Split-plate, stamped-steel type with concealed hinge and
                    spring clips.
              c.    Bare Piping at Wall and Floor Penetrations in Finished Spaces: Split-
                    casting, cast-brass type with chrome-plated finish.
              d.    Bare Piping at Wall and Floor Penetrations in Finished Spaces: Split-plate,
                    stamped-steel type with concealed hinge and spring clips.
              e.    Bare Piping at Ceiling Penetrations in Finished Spaces: Split-casting, cast-
                    brass type with chrome-plated finish.
              f.    Bare Piping at Ceiling Penetrations in Finished Spaces: Split-plate,
                    stamped-steel type with concealed hinge and set screw.
              g.    Bare Piping in Unfinished Service Spaces: Split-casting, cast-brass type
                    with polished chrome-plated finish.
              h.    Bare Piping in Unfinished Service Spaces: Split-plate, stamped-steel type
                    with concealed hinge and set screw or spring clips.
              i.    Bare Piping in Equipment Rooms: Split-casting, cast-brass type.
              j.    Bare Piping in Equipment Rooms: Split-plate, stamped-steel type with set
                    screw or spring clips.
              k.    Bare Piping at Floor Penetrations in Equipment Rooms: Split-casting,
                    floor-plate type.

  M.    Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings,
        and floors at pipe penetrations. Seal pipe penetrations with firestop materials. Refer to
        Division 07 Section "Penetration Firestopping" for materials.

  N.    Verify final equipment locations for roughing-in.


Privatized Army Lodging                    230500 - 5                           Lend Lease
Alterations for HIE Branding                            Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                         October 20, 2011
   O.    Refer to equipment specifications in other Sections of these Specifications for
         roughing-in requirements.


3.3      PIPING JOINT CONSTRUCTION

   A.    Join pipe and fittings according to the following requirements and Division 23 Sections
         specifying piping systems.

   B.    Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.

   C.    Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before
         assembly.

   D.    Soldered Joints: Apply ASTM B 813, water-flushable flux, unless otherwise indicated,
         to tube end. Construct joints according to ASTM B 828 or CDA's "Copper Tube
         Handbook," using lead-free solder alloy complying with ASTM B 32.

   E.    Brazed Joints: Construct joints according to AWS's "Brazing Handbook," "Pipe and
         Tube" Chapter, using copper-phosphorus brazing filler metal complying with
         AWS A5.8.

   F.    Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1.
         Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs
         and restore full ID. Join pipe fittings and valves as follows:

         1.    Apply appropriate tape or thread compound to external pipe threads unless dry
               seal threading is specified.
         2.    Damaged Threads: Do not use pipe or pipe fittings with threads that are
               corroded or damaged. Do not use pipe sections that have cracked or open
               welds.

   G.    Welded Joints: Construct joints according to AWS D10.12, using qualified processes
         and welding operators according to Part 1 "Quality Assurance" Article.

   H.    Flanged Joints: Select appropriate gasket material, size, type, and thickness for
         service application. Install gasket concentrically positioned. Use suitable lubricants on
         bolt threads.


3.4      PIPING CONNECTIONS

   A.    Make connections according to the following, unless otherwise indicated:

         1.     Install unions, in piping NPS 2 and smaller, adjacent to each valve and at final
                connection to each piece of equipment.
         2.     Install flanges, in piping NPS 2-1/2 and larger, adjacent to flanged valves and at
                final connection to each piece of equipment.
         3.     Dry Piping Systems: Install dielectric unions and flanges to connect piping
                materials of dissimilar metals.
         4.     Wet Piping Systems: Install dielectric coupling and nipple fittings to connect
                piping materials of dissimilar metals.
Privatized Army Lodging                      230500 - 6                                Lend Lease
Alterations for HIE Branding                             Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                October 20, 2011
3.5     EQUIPMENT INSTALLATION - COMMON REQUIREMENTS

  A.    Install equipment to allow maximum possible headroom unless specific mounting
        heights are not indicated.

  B.    Install equipment level and plumb, parallel and perpendicular to other building systems
        and components in exposed interior spaces, unless otherwise indicated.

  C.    Install HVAC equipment to facilitate service, maintenance, and repair or replacement of
        components. Connect equipment for ease of disconnecting, with minimum interference
        to other installations. Extend grease fittings to accessible locations.

  D.    Install equipment to allow right of way for piping installed at required slope.


3.6     PAINTING

  A.    Painting of HVAC systems, equipment, and components is specified in Division 09
        Sections "Interior Painting" and "Exterior Painting."

  B.    Damage and Touchup: Repair marred and damaged factory-painted finishes with
        materials and procedures to match original factory finish.


3.7     ERECTION OF METAL SUPPORTS AND ANCHORAGES

  A.    Refer to Division 05 Section "Metal Fabrications" for structural steel.

  B.    Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and
        elevation to support and anchor HVAC materials and equipment.

  C.    Field Welding: Comply with AWS D1.1.


END OF SECTION 230500




Privatized Army Lodging                    230500 - 7                            Lend Lease
Alterations for HIE Branding                             Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                          October 20, 2011
                                      SECTION 230513

               COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT


PART 1 - GENERAL


1.1     SUMMARY

  A.    Section includes general requirements for single-phase and polyphase, general-
        purpose, horizontal, small and medium, squirrel-cage induction motors for use on ac
        power systems up to 600 V and installed at equipment manufacturer's factory or
        shipped separately by equipment manufacturer for field installation.


1.2     COORDINATION

  A.    Coordinate features of motors, installed units, and accessory devices to be compatible
        with the following:

        1.    Motor controllers.
        2.    Torque, speed, and horsepower requirements of the load.
        3.    Ratings and characteristics of supply circuit and required control sequence.
        4.    Ambient and environmental conditions of installation location.


PART 2 - PRODUCTS


2.1     GENERAL MOTOR REQUIREMENTS

  A.    Comply with NEMA MG 1 unless otherwise indicated.


2.2     MOTOR CHARACTERISTICS

  A.    Duty: Continuous duty at ambient temperature of 40 deg C and at altitude of 3300 feet
        above sea level.

  B.    Capacity and Torque Characteristics: Sufficient to start, accelerate, and operate
        connected loads at designated speeds, at installed altitude and environment, with
        indicated operating sequence, and without exceeding nameplate ratings or considering
        service factor.


2.3     POLYPHASE MOTORS

  A.    Description: NEMA MG 1, Design B, medium induction motor.


Privatized Army Lodging                   230513 - 1                           Lend Lease
Alterations for HIE Branding                           Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                        October 20, 2011
  B.    Efficiency: Energy efficient, as defined in NEMA MG 1.

  C.    Service Factor: 1.15.

  D.    Multispeed Motors: Variable torque.

        1.    For motors with 2:1 speed ratio, consequent pole, single winding.
        2.    For motors with other than 2:1 speed ratio, separate winding for each speed.

  E.    Rotor: Random-wound, squirrel cage.

  F.    Bearings: Regreasable, shielded, antifriction ball bearings suitable for radial and thrust
        loading.

  G.    Temperature Rise: Match insulation rating.

  H.    Insulation: Class F.

  I.    Code Letter Designation:

        1.    Motors: Manufacturer's standard starting characteristic.

  J.    Enclosure Material: Cast iron for motor frame sizes 324T and larger; rolled steel for
        motor frame sizes smaller than 324T.


2.4     POLYPHASE MOTORS WITH ADDITIONAL REQUIREMENTS

  A.    Motors Used with Reduced-Voltage and Multispeed Controllers:            Match wiring
        connection requirements for controller with required motor leads. Provide terminals in
        motor terminal box, suited to control method.


2.5     SINGLE-PHASE MOTORS

  A.    Motors larger than 1/20 hp shall be one of the following, to suit starting torque and
        requirements of specific motor application:

        1.    Permanent-split capacitor.
        2.    Split phase.
        3.    Capacitor start, inductor run.
        4.    Capacitor start, capacitor run.

  B.    Multispeed Motors: Variable-torque, permanent-split-capacitor type.

  C.    Bearings: Prelubricated, antifriction ball bearings or sleeve bearings suitable for radial
        and thrust loading.

  D.    Motors 1/20 HP and Smaller: Shaded-pole type.



Privatized Army Lodging                    230513 - 2                           Lend Lease
Alterations for HIE Branding                            Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                         October 20, 2011
  E.    Thermal Protection: Internal protection to automatically open power supply circuit to
        motor when winding temperature exceeds a safe value calibrated to temperature rating
        of motor insulation. Thermal-protection device shall automatically reset when motor
        temperature returns to normal range.


PART 3 - EXECUTION (Not Applicable)


END OF SECTION 230513




Privatized Army Lodging                 230513 - 3                           Lend Lease
Alterations for HIE Branding                         Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                      October 20, 2011
                                           SECTION 230523

                             GENERAL-DUTY VALVES FOR HVAC PIPING


PART 1 - GENERAL


1.01     SUMMARY

   A.    Section Includes:

         1.    Bronze ball valves.

   B.    Related Sections:

         1.    Division 23 HVAC piping Sections for specialty valves applicable to those Sections only.
         2.    Division 23 Section "Identification for HVAC Piping and Equipment" for valve tags and
               schedules.


1.02     SUBMITTALS

   A.    Product Data: For each type of valve indicated.


1.03     QUALITY ASSURANCE

   A.    Source Limitations for Valves:    Obtain each type of valve from single source from single
         manufacturer.

   B.    ASME Compliance: ASME B16.10 and ASME B16.34 for ferrous valve dimensions and design
         criteria.


PART 2 - PRODUCTS


2.01     GENERAL REQUIREMENTS FOR VALVES

   A.    Refer to HVAC valve schedule articles for applications of valves.

   B.    Valve Pressure and Temperature Ratings: Not less than indicated and as required for system
         pressures and temperatures.

   C.    Valve Sizes: Same as upstream piping unless otherwise indicated.

   D.    Valve Actuator Types:

         1.    Handlever: For quarter-turn valves NPS 6 and smaller.

   E.    Valves in Insulated Piping: With 2-inch stem extensions and the following features:



Privatized Army Lodging                        230523 - 1                               Lend Lease
Alterations for HIE Branding                                    Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                 October 20, 2011
         1.     Ball Valves: With extended operating handle of non-thermal-conductive material, and
                protective sleeve that allows operation of valve without breaking the vapor seal or
                disturbing insulation.

   F.    Valve-End Connections:

         1.     Solder Joint: With sockets according to ASME B16.18.
         2.     Threaded: With threads according to ASME B1.20.1.


2.02     BRONZE BALL VALVES

   A.    Two-Piece, Full-Port, Bronze Ball Valves with Stainless-Steel Trim:

         1.     Manufacturers: Subject to compliance with requirements, provide products by one of the
                following:

                a.     Conbraco Industries, Inc.; Apollo Valves.
                b.     Crane Co.; Crane Valve Group; Crane Valves.
                c.     Hammond Valve.
                d.     Lance Valves; a division of Advanced Thermal Systems, Inc.
                e.     Milwaukee Valve Company.
                f.     NIBCO INC.
                g.     Watts Regulator Co.; a division of Watts Water Technologies, Inc.

         2.     Description:

                a.     Standard: MSS SP-110.
                b.     SWP Rating: 150 psig.
                c.     CWP Rating: 600 psig.
                d.     Body Design: Two piece.
                e.     Body Material: Bronze.
                f.     Ends: Threaded.
                g.     Seats: PTFE or TFE.
                h.     Stem: Stainless steel.
                i.     Ball: Stainless steel, vented.
                j.     Port: Full.


PART 3 - EXECUTION


3.01     EXAMINATION

   A.    Examine valve interior for cleanliness, freedom from foreign matter, and corrosion. Remove
         special packing materials, such as blocks, used to prevent disc movement during shipping and
         handling.

   B.    Operate valves in positions from fully open to fully closed. Examine guides and seats made
         accessible by such operations.

   C.    Examine threads on valve and mating pipe for form and cleanliness.

   D.     Examine mating flange faces for conditions that might cause leakage. Check bolting for proper
          size, length, and material. Verify that gasket is of proper size, that its material composition is
          suitable for service, and that it is free from defects and damage.
Privatized Army Lodging                             230523 - 2                                  Lend Lease
Alterations for HIE Branding                                         Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                        October 20, 2011
   E.    Do not attempt to repair defective valves; replace with new valves.


3.02     VALVE INSTALLATION

   A.    Install valves with unions or flanges at each piece of equipment arranged to allow service,
         maintenance, and equipment removal without system shutdown.

   B.    Locate valves for easy access and provide separate support where necessary.

   C.    Install valves in horizontal piping with stem at or above center of pipe.

   D.    Install valves in position to allow full stem movement.


3.03     ADJUSTING

   A.    Adjust or replace valve packing after piping systems have been tested and put into service but
         before final adjusting and balancing. Replace valves if persistent leaking occurs.


3.04     GENERAL REQUIREMENTS FOR VALVE APPLICATIONS

   A.    If valve applications are not indicated, use the following:

         1.    Shutoff Service: Ball valves.

   B.    If valves with specified SWP classes or CWP ratings are not available, the same types of valves
         with higher SWP classes or CWP ratings may be substituted.

   C.    Select valves, except wafer types, with the following end connections:

         1.    For Copper Tubing, NPS 2 and Smaller: Threaded ends except where solder-joint valve-
               end option is indicated in valve schedules below.


3.05     CONDENSER-WATER VALVE SCHEDULE

   A.    Pipe NPS 2 and Smaller:

         1.    Bronze Valves: May be provided with solder-joint ends instead of threaded ends.
         2.    Ball Valves: Two piece, full port, bronze with stainless-steel trim.


                                            END OF SECTION




Privatized Army Lodging                         230523 - 3                                 Lend Lease
Alterations for HIE Branding                                       Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                    October 20, 2011
                                           SECTION 230529

                 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT


PART 1 - GENERAL


1.01     SUMMARY

   A.    Section Includes:

         1.    Metal pipe hangers and supports.
         2.    Thermal-hanger shield inserts.
         3.    Fastener systems.
         4.    Equipment supports.


1.02     PERFORMANCE REQUIREMENTS

   A.    Structural Performance: Hangers and supports for HVAC piping and equipment shall withstand
         the effects of gravity loads and stresses within limits and under conditions indicated according
         to ASCE/SEI 7.

         1.    Design supports for multiple pipes capable of supporting combined weight of supported
               systems, system contents, and test water.
         2.    Design equipment supports capable of supporting combined operating weight of
               supported equipment and connected systems and components.


1.03     SUBMITTALS

   A.    Product Data: For each type of product indicated.

   B.    Welding certificates.


1.04     QUALITY ASSURANCE

   A.    Structural Steel Welding Qualifications: Qualify procedures and personnel according to
         AWS D1.1/D1.1M, "Structural Welding Code - Steel."

   B.    Pipe Welding Qualifications: Qualify procedures and operators according to ASME Boiler and
         Pressure Vessel Code.


PART 2 - PRODUCTS


2.01     METAL PIPE HANGERS AND SUPPORTS

   A.    Carbon-Steel Pipe Hangers and Supports:

         1.    Description: MSS SP-58, Types 1 through 58, factory-fabricated components.

Privatized Army Lodging                       230529 - 1                               Lend Lease
Alterations for HIE Branding                                   Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                October 20, 2011
         2.    Galvanized Metallic Coatings: Pregalvanized or hot dipped.
         3.    Nonmetallic Coatings: Plastic coating, jacket, or liner.
         4.    Padded Hangers: Hanger with fiberglass or other pipe insulation pad or cushion to
               support bearing surface of piping.
         5.    Hanger Rods: Continuous-thread rod, nuts, and washer made of carbon steel.

   B.    Stainless-Steel Pipe Hangers and Supports:

         1.    Description: MSS SP-58, Types 1 through 58, factory-fabricated components.
         2.    Padded Hangers: Hanger with fiberglass or other pipe insulation pad or cushion to
               support bearing surface of piping.
         3.    Hanger Rods: Continuous-thread rod, nuts, and washer made of stainless steel.

   C.    Copper Pipe Hangers:

         1.    Description: MSS SP-58, Types 1 through 58, copper-coated-steel, factory-fabricated
               components.
         2.    Hanger Rods: Continuous-thread rod, nuts, and washer made of copper-coated steel or
               stainless steel.


2.02     THERMAL-HANGER SHIELD INSERTS

   A.    For Clevis or Band Hangers: Insert and shield shall cover lower 180 degrees of pipe.

   B.    Insert Length: Extend 2 inches beyond sheet metal shield for piping operating below ambient
         air temperature.


2.03     EQUIPMENT SUPPORTS

   A.    Description: Welded, shop- or field-fabricated equipment support made from structural carbon-
         steel shapes.


2.04     MISCELLANEOUS MATERIALS

   A.    Structural Steel:   ASTM A 36/A 36M, carbon-steel plates, shapes, and bars; black and
         galvanized.

   B.    Grout: ASTM C 1107, factory-mixed and -packaged, dry, hydraulic-cement, nonshrink and
         nonmetallic grout; suitable for interior and exterior applications.

         1.    Properties: Nonstaining, noncorrosive, and nongaseous.
         2.    Design Mix: 5000-psi, 28-day compressive strength.


PART 3 - EXECUTION


3.01     HANGER AND SUPPORT INSTALLATION

   A.    Metal Pipe-Hanger Installation: Comply with MSS SP-69 and MSS SP-89. Install hangers,
         supports, clamps, and attachments as required to properly support piping from the building
         structure.

Privatized Army Lodging                       230529 - 2                               Lend Lease
Alterations for HIE Branding                                   Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                October 20, 2011
   B.    Thermal-Hanger Shield Installation: Install in pipe hanger or shield for insulated piping.

   C.    Install hangers and supports complete with necessary attachments, inserts, bolts, rods, nuts,
         washers, and other accessories.

   D.    Equipment Support Installation: Fabricate from welded-structural-steel shapes.

   E.    Install hangers and supports to allow controlled thermal and seismic movement of piping
         systems, to permit freedom of movement between pipe anchors, and to facilitate action of
         expansion joints, expansion loops, expansion bends, and similar units.

   F.    Install lateral bracing with pipe hangers and supports to prevent swaying.

   G.    Install building attachments within concrete slabs or attach to structural steel. Install additional
         attachments at concentrated loads, including valves, flanges, and strainers, NPS 2-1/2 and
         larger and at changes in direction of piping. Install concrete inserts before concrete is placed;
         fasten inserts to forms and install reinforcing bars through openings at top of inserts.

   H.    Load Distribution: Install hangers and supports so that piping live and dead loads and stresses
         from movement will not be transmitted to connected equipment.

   I.    Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and to not exceed
         maximum pipe deflections allowed by ASME B31.9 for building services piping.

   J.    Insulated Piping:

         1.    Attach clamps and spacers to piping.

               a.     Piping Operating above Ambient Air Temperature: Clamp may project through
                      insulation.
               b.     Piping Operating below Ambient Air Temperature: Use thermal-hanger shield
                      insert with clamp sized to match OD of insert.
               c.     Do not exceed pipe stress limits allowed by ASME B31.9 for building services
                      piping.

         2.    Install MSS SP-58, Type 39, protection saddles if insulation without vapor barrier is
               indicated. Fill interior voids with insulation that matches adjoining insulation.

               a.     Option: Thermal-hanger shield inserts may be used. Include steel weight-
                      distribution plate for pipe NPS 4 and larger if pipe is installed on rollers.

         3.    Install MSS SP-58, Type 40, protective shields on cold piping with vapor barrier. Shields
               shall span an arc of 180 degrees.

               a.     Option: Thermal-hanger shield inserts may be used. Include steel weight-
                      distribution plate for pipe NPS 4 and larger if pipe is installed on rollers.

         4.    Shield Dimensions for Pipe: Not less than the following:

               a.     NPS 1/4 to NPS 3-1/2: 12 inches long and 0.048 inch thick.
               b.     NPS 4: 12 inches long and 0.06 inch thick.

         5.    Thermal-Hanger Shields: Install with insulation same thickness as piping insulation.



Privatized Army Lodging                         230529 - 3                                Lend Lease
Alterations for HIE Branding                                      Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                   October 20, 2011
3.02     EQUIPMENT SUPPORTS

   A.    Fabricate structural-steel stands to suspend equipment from structure overhead or to support
         equipment above floor.

   B.    Grouting: Place grout under supports for equipment and make bearing surface smooth.

   C.    Provide lateral bracing, to prevent swaying, for equipment supports.


3.03     METAL FABRICATIONS

   A.    Cut, drill, and fit miscellaneous metal fabrications for equipment supports.

   B.    Fit exposed connections together to form hairline joints. Field weld connections that cannot be
         shop welded because of shipping size limitations.

   C.    Field Welding: Comply with AWS D1.1/D1.1M procedures for shielded, metal arc welding;
         appearance and quality of welds; and methods used in correcting welding work; and with the
         following:

         1.    Use materials and methods that minimize distortion and develop strength and corrosion
               resistance of base metals.
         2.    Obtain fusion without undercut or overlap.
         3.    Remove welding flux immediately.
         4.    Finish welds at exposed connections so no roughness shows after finishing and so
               contours of welded surfaces match adjacent contours.


3.04     ADJUSTING

   A.    Hanger Adjustments: Adjust hangers to distribute loads equally on attachments and to achieve
         indicated slope of pipe.

   B.    Trim excess length of continuous-thread hanger and support rods to 1-1/2 inches.


3.05     PAINTING

   A.    Touchup: Clean field welds and abraded areas of shop paint. Paint exposed areas
         immediately after erecting hangers and supports. Use same materials as used for shop
         painting. Comply with SSPC-PA 1 requirements for touching up field-painted surfaces.

         1.    Apply paint by brush or spray to provide a minimum dry film thickness of 2.0 mils.

   B.    Touchup: Cleaning and touchup painting of field welds, bolted connections, and abraded areas
         of shop paint on miscellaneous metal are specified in Division 09 painting Sections.

   C.    Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply
         galvanizing-repair paint to comply with ASTM A 780.


3.06     HANGER AND SUPPORT SCHEDULE

   A.     Specific hanger and support requirements are in Sections specifying piping systems and
          equipment.
Privatized Army Lodging                     230529 - 4                                 Lend Lease
Alterations for HIE Branding                               Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                October 20, 2011
   B.    Comply with MSS SP-69 for pipe-hanger selections and applications that are not specified in
         piping system Sections.

   C.    Use hangers and supports with galvanized metallic coatings for piping and equipment that will
         not have field-applied finish.

   D.    Use nonmetallic coatings on attachments for electrolytic protection where attachments are in
         direct contact with copper tubing.

   E.    Use carbon-steel pipe hangers and supports and attachments for general service applications.

   F.    Use copper-plated pipe hangers and copper or stainless-steel attachments for copper piping
         and tubing.

   G.    Use padded hangers for piping that is subject to scratching.

   H.    Use thermal-hanger shield inserts for insulated piping and tubing.

   I.    Horizontal-Piping Hangers and Supports: Unless otherwise indicated and except as specified in
         piping system Sections, install the following types:

         1.    Adjustable, Steel Clevis Hangers (MSS Type 1): For suspension of noninsulated or
               insulated, stationary pipes NPS 1/2 to NPS 30.
         2.    Yoke-Type Pipe Clamps (MSS Type 2): For suspension of up to 1050 deg F, pipes
               NPS 4 to NPS 24, requiring up to 4 inches of insulation.
         3.    Carbon- or Alloy-Steel, Double-Bolt Pipe Clamps (MSS Type 3): For suspension of pipes
               NPS 3/4 to NPS 36, requiring clamp flexibility and up to 4 inches of insulation.
         4.    Adjustable, Steel Band Hangers (MSS Type 7): For suspension of noninsulated,
               stationary pipes NPS 1/2 to NPS 8.
         5.    U-Bolts (MSS Type 24): For support of heavy pipes NPS 1/2 to NPS 30.
         6.    Pipe Saddle Supports (MSS Type 36): For support of pipes NPS 4 to NPS 36, with steel-
               pipe base stanchion support and cast-iron floor flange or carbon-steel plate.
         7.    Pipe Stanchion Saddles (MSS Type 37): For support of pipes NPS 4 to NPS 36, with
               steel-pipe base stanchion support and cast-iron floor flange or carbon-steel plate, and
               with U-bolt to retain pipe.
         8.    Single-Pipe Rolls (MSS Type 41): For suspension of pipes NPS 1 to NPS 30, from two
               rods if longitudinal movement caused by expansion and contraction might occur.
         9.    Complete Pipe Rolls (MSS Type 44): For support of pipes NPS 2 to NPS 42 if
               longitudinal movement caused by expansion and contraction might occur but vertical
               adjustment is not necessary.

   J.    Vertical-Piping Clamps: Unless otherwise indicated and except as specified in piping system
         Sections, install the following types:

         1.    Extension Pipe or Riser Clamps (MSS Type 8): For support of pipe risers NPS 3/4 to
               NPS 24.
         2.    Carbon- or Alloy-Steel Riser Clamps (MSS Type 42): For support of pipe risers NPS 3/4
               to NPS 24 if longer ends are required for riser clamps.

   K.    Hanger-Rod Attachments: Unless otherwise indicated and except as specified in piping system
         Sections, install the following types:

         1.    Steel Turnbuckles (MSS Type 13): For adjustment up to 6 inches for heavy loads.
         2.    Steel Clevises (MSS Type 14): For 120 to 450 deg F piping installations.



Privatized Army Lodging                        230529 - 5                               Lend Lease
Alterations for HIE Branding                                    Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                 October 20, 2011
   L.    Building Attachments: Unless otherwise indicated and except as specified in piping system
         Sections, install the following types:

         1.    Steel or Malleable Concrete Inserts (MSS Type 18): For upper attachment to suspend
               pipe hangers from concrete ceiling.
         2.    Top-Beam C-Clamps (MSS Type 19): For use under roof installations with bar-joist
               construction, to attach to top flange of structural shape.
         3.    Side-Beam or Channel Clamps (MSS Type 20): For attaching to bottom flange of beams,
               channels, or angles.
         4.    Center-Beam Clamps (MSS Type 21): For attaching to center of bottom flange of beams.
         5.    Welded Beam Attachments (MSS Type 22): For attaching to bottom of beams if loads
               are considerable and rod sizes are large.
         6.    C-Clamps (MSS Type 23): For structural shapes.
         7.    Welded-Steel Brackets: For support of pipes from below, or for suspending from above
               by using clip and rod. Use one of the following for indicated loads:

               a.     Light (MSS Type 31): 750 lb.
               b.     Medium (MSS Type 32): 1500 lb.
               c.     Heavy (MSS Type 33): 3000 lb.

         8.    Side-Beam Brackets (MSS Type 34): For sides of steel or wooden beams.
         9.    Plate Lugs (MSS Type 57): For attaching to steel beams if flexibility at beam is required.

   M.    Saddles and Shields: Unless otherwise indicated and except as specified in piping system
         Sections, install the following types:

         1.    Steel-Pipe-Covering Protection Saddles (MSS Type 39): To fill interior voids with
               insulation that matches adjoining insulation.
         2.    Protection Shields (MSS Type 40): Of length recommended in writing by manufacturer to
               prevent crushing insulation.
         3.    Thermal-Hanger Shield Inserts: For supporting insulated pipe.

   N.    Spring Hangers and Supports: Unless otherwise indicated and except as specified in piping
         system Sections, install the following types:

         1.    Spring Cushions (MSS Type 48): For light loads if vertical movement does not exceed 1-
               1/4 inches.
         2.    Spring-Cushion Roll Hangers (MSS Type 49): For equipping Type 41, roll hanger with
               springs.
         3.    Variable-Spring Base Supports (MSS Type 52): Preset to indicated load and limit
               variability factor to 25 percent to allow expansion and contraction of piping system from
               base support.


                                          END OF SECTION




Privatized Army Lodging                       230529 - 6                                Lend Lease
Alterations for HIE Branding                                    Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                 October 20, 2011
                                           SECTION 230553

                       IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT


PART 1 - GENERAL


1.01     SUMMARY

   A.    Section Includes:

         1.    Equipment labels.
         2.    Pipe labels.


1.02     SUBMITTAL

   A.    Product Data: For each type of product indicated.


PART 2 - PRODUCTS


2.01     EQUIPMENT LABELS

   A.    Plastic Labels for Equipment:

         1.    Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving,
               1/8 inch thick, and having predrilled holes for attachment hardware.
         2.    Letter Color: White.
         3.    Background Color: Black.
         4.    Maximum Temperature: Able to withstand temperatures up to 160 deg F.
         5.    Minimum Label Size: Length and width vary for required label content, but not less than
               2-1/2 by 3/4 inch.
         6.    Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24
               inches, 1/2 inch for viewing distances up to 72 inches, and proportionately larger lettering
               for greater viewing distances. Include secondary lettering two-thirds to three-fourths the
               size of principal lettering.
         7.    Fasteners: Stainless-steel rivets or self-tapping screws.
         8.    Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.

   B.    Label Content: Include equipment's Drawing designation or unique equipment number,
         Drawing numbers where equipment is indicated (plans, details, and schedules), plus the
         Specification Section number and title where equipment is specified.

   C.    Equipment Label Schedule: For each item of equipment to be labeled, on 8-1/2-by-11-inch
         bond paper. Tabulate equipment identification number and identify Drawing numbers where
         equipment is indicated (plans, details, and schedules), plus the Specification Section number
         and title where equipment is specified. Equipment schedule shall be included in operation and
         maintenance data.




Privatized Army Lodging                        230553 - 1                               Lend Lease
Alterations for HIE Branding                                    Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                 October 20, 2011
2.02     PIPE LABELS

   A.    General Requirements for Manufactured Pipe Labels: Preprinted, color-coded, with lettering
         indicating service, and showing flow direction.

   B.    Pretensioned Pipe Labels: Precoiled, semirigid plastic formed to partially cover circumference
         of pipe and to attach to pipe without fasteners or adhesive.

   C.    Pipe Label Contents: Include identification of piping service using same designations or
         abbreviations as used on Drawings, pipe size, and an arrow indicating flow direction.

         1.    Flow-Direction Arrows: Integral with piping system service lettering to accommodate both
               directions, or as separate unit on each pipe label to indicate flow direction.
         2.    Lettering Size: At least 1-1/2 inches high.


PART 3 - EXECUTION


3.01     PREPARATION

   A.    Clean piping and equipment surfaces of substances that could impair bond of identification
         devices, including dirt, oil, grease, release agents, and incompatible primers, paints, and
         encapsulants.


3.02     EQUIPMENT LABEL INSTALLATION

   A.    Install or permanently fasten labels on each major item of mechanical equipment.

   B.    Locate equipment labels where accessible and visible.


3.03     PIPE LABEL INSTALLATION

   A.    Locate pipe labels where piping is exposed or above accessible ceilings in finished spaces;
         machine rooms; accessible maintenance spaces such as shafts, tunnels, and plenums; and
         exterior exposed locations as follows:

         1.    Near each valve and control device.
         2.    Near each branch connection, excluding short takeoffs for fixtures and terminal units.
               Where flow pattern is not obvious, mark each pipe at branch.
         3.    Near penetrations through walls, floors, ceilings, and inaccessible enclosures.
         4.    At access doors, manholes, and similar access points that permit view of concealed
               piping.
         5.    Near major equipment items and other points of origination and termination.
         6.    Spaced at maximum intervals of 50 feet along each run. Reduce intervals to 25 feet in
               areas of congested piping and equipment.
         7.    On piping above removable acoustical ceilings. Omit intermediately spaced labels.

   B.    Pipe Label Color Schedule:

         1.    Condenser-Water Piping:

                 a.    Background Color: Black.
                 b.    Letter Color: White.
Privatized Army Lodging                      230553 - 2                                  Lend Lease
Alterations for HIE Branding                                     Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                  October 20, 2011
                                     END OF SECTION




Privatized Army Lodging                 230553 - 3                            Lend Lease
Alterations for HIE Branding                          Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                       October 20, 2011
                                           SECTION 230593

                        TESTING, ADJUSTING, AND BALANCING FOR HVAC


PART 1 - GENERAL


1.01     SUMMARY

   A.    Section Includes:

         1.    Balancing Air Systems:

               a.     Constant-volume air systems.

         2.    Balancing Hydronic Piping Systems:

               a.     Constant-flow hydronic systems.

   B.    AABC: Associated Air Balance Council.

   C.    NEBB: National Environmental Balancing Bureau.

   D.    TAB: Testing, adjusting, and balancing.

   E.    TABB: Testing, Adjusting, and Balancing Bureau.

   F.    TAB Specialist: An entity engaged to perform TAB Work.


1.02     SUBMITTALS

   A.    LEED Submittal:

         1.    Air-Balance Report for LEED Prerequisite EQ 1: Documentation of work performed for
               ASHRAE 62.1-2004, Section 7.2.2, "Air Balancing."

   B.    Strategies and Procedures Plan: Within 60 days of Contractor's Notice to Proceed, submit TAB
         strategies and step-by-step procedures as specified in "Preparation" Article.

   C.    Certified TAB reports.


1.03     QUALITY ASSURANCE

   A.    TAB Contractor Qualifications: Engage a TAB entity certified by AABC or NEBB.

         1.    TAB Field Supervisor: Employee of the TAB contractor and certified by AABC or NEBB.
         2.    TAB Technician: Employee of the TAB contractor and who is certified by AABC or NEBB
               as a TAB technician.

   B.    Certify TAB field data reports and perform the following:


Privatized Army Lodging                        230593 - 1                                Lend Lease
Alterations for HIE Branding                                     Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                  October 20, 2011
         1.    Review field data reports to validate accuracy of data and to prepare certified TAB
               reports.
         2.    Certify that the TAB team complied with the approved TAB plan and the procedures
               specified and referenced in this Specification.

   C.    TAB Report Forms: Use standard TAB contractor's forms approved by Architect.

   D.    Instrumentation Type, Quantity, Accuracy, and Calibration:     As described in ASHRAE 111,
         Section 5, "Instrumentation."


PART 2 - PRODUCTS (Not Applicable)


PART 3 - EXECUTION


3.01     EXAMINATION

   A.    Examine the Contract Documents to become familiar with Project requirements and to discover
         conditions in systems' designs that may preclude proper TAB of systems and equipment.

   B.    Examine systems for installed balancing devices, such as test ports, gage cocks, thermometer
         wells, flow-control devices, balancing valves and fittings, and manual volume dampers. Verify
         that locations of these balancing devices are accessible.

   C.    Examine the approved submittals for HVAC systems and equipment.

   D.    Examine design data including HVAC system descriptions, statements of design assumptions
         for environmental conditions and systems' output, and statements of philosophies and
         assumptions about HVAC system and equipment controls.

   E.    Examine ceiling plenums and underfloor air plenums used for supply, return, or relief air to
         verify that they meet the leakage class of connected ducts as specified in Division 23 Section
         "Metal Ducts" and are properly separated from adjacent areas. Verify that penetrations in
         plenum walls are sealed and fire-stopped if required.

   F.    Examine equipment performance data including fan and pump curves.

         1.    Relate performance data to Project conditions and requirements, including system effects
               that can create undesired or unpredicted conditions that cause reduced capacities in all
               or part of a system.
         2.    Calculate system-effect factors to reduce performance ratings of HVAC equipment when
               installed under conditions different from the conditions used to rate equipment
               performance. To calculate system effects for air systems, use tables and charts found in
               AMCA 201, "Fans and Systems," or in SMACNA's "HVAC Systems - Duct Design."
               Compare results with the design data and installed conditions.

   G.    Examine system and equipment installations and verify that field quality-control testing,
         cleaning, and adjusting specified in individual Sections have been performed.

   H.    Examine test reports specified in individual system and equipment Sections.

   I.    Examine HVAC equipment and filters and verify that bearings are greased, belts are aligned
         and tight, and equipment with functioning controls is ready for operation.

Privatized Army Lodging                       230593 - 2                               Lend Lease
Alterations for HIE Branding                                   Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                October 20, 2011
   J.    Examine terminal units, such as variable-air-volume boxes, and verify that they are accessible
         and their controls are connected and functioning.

   K.    Examine strainers. Verify that startup screens are replaced by permanent screens with
         indicated perforations.

   L.    Examine three-way valves for proper installation for their intended function of diverting or mixing
         fluid flows.

   M.    Examine heat-transfer coils for correct piping connections and for clean and straight fins.

   N.    Examine system pumps to ensure absence of entrained air in the suction piping.

   O.    Examine operating safety interlocks and controls on HVAC equipment.

   P.    Report deficiencies discovered before and during performance of TAB procedures. Observe
         and record system reactions to changes in conditions. Record default set points if different from
         indicated values.


3.02     PREPARATION

   A.    Prepare a TAB plan that includes strategies and step-by-step procedures.

   B.    Complete system-readiness checks and prepare reports. Verify the following:

         1.    Permanent electrical-power wiring is complete.
         2.    Hydronic systems are filled, clean, and free of air.
         3.    Automatic temperature-control systems are operational.
         4.    Equipment and duct access doors are securely closed.
         5.    Balance, smoke, and fire dampers are open.
         6.    Isolating and balancing valves are open and control valves are operational.
         7.    Ceilings are installed in critical areas where air-pattern adjustments are required and
               access to balancing devices is provided.
         8.    Windows and doors can be closed so indicated conditions for system operations can be
               met.


3.03     GENERAL PROCEDURES FOR TESTING AND BALANCING

   A.    Perform testing and balancing procedures on each system according to the procedures
         contained in AABC's "National Standards for Total System Balance" or NEBB's "Procedural
         Standards for Testing, Adjusting, and Balancing of Environmental Systems" and in this Section.

         1.    Comply with requirements in ASHRAE 62.1-2004, Section 7.2.2, "Air Balancing."

   B.    Cut insulation, ducts, pipes, and equipment cabinets for installation of test probes to the
         minimum extent necessary for TAB procedures.

         1.    After testing and balancing, patch probe holes in ducts with same material and thickness
               as used to construct ducts.
         2.    Install and join new insulation that matches removed materials. Restore insulation,
               coverings, vapor barrier, and finish according to Division 23 Section "HVAC Insulation."



Privatized Army Lodging                        230593 - 3                                Lend Lease
Alterations for HIE Branding                                     Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                  October 20, 2011
   C.     Mark equipment and balancing devices, including damper-control positions, valve position
          indicators, fan-speed-control levers, and similar controls and devices, with paint or other
          suitable, permanent identification material to show final settings.

   D.     Take and report testing and balancing measurements in inch-pound (IP) units.


3.04      GENERAL PROCEDURES FOR BALANCING AIR SYSTEMS

   A.     Prepare test reports for both fans and outlets. Obtain manufacturer's outlet factors and
          recommended testing procedures. Crosscheck the summation of required outlet volumes with
          required fan volumes.

   B.     Prepare schematic diagrams of systems' "as-built" duct layouts.

   C.     For variable-air-volume systems, develop a plan to simulate diversity.

   D.     Determine the best locations in main and branch ducts for accurate duct-airflow measurements.

   E.     Check airflow patterns from the outdoor-air louvers and dampers and the return- and exhaust-
          air dampers through the supply-fan discharge and mixing dampers.

   F.     Locate start-stop and disconnect switches, electrical interlocks, and motor starters.

   G.     Verify that motor starters are equipped with properly sized thermal protection.

   H.     Check dampers for proper position to achieve desired airflow path.

   I.     Check for airflow blockages.

   J.     Check condensate drains for proper connections and functioning.

   K.     Check for proper sealing of air-handling-unit components.

   L.     Verify that air duct system is sealed as specified in Division 23 Section "Metal Ducts."


3.05      PROCEDURES FOR CONSTANT-VOLUME AIR SYSTEMS

   A.     Adjust fans to deliver total indicated airflows within the maximum allowable fan speed listed by
          fan manufacturer.

          1.    Measure total airflow.

                a.     Where sufficient space in ducts is unavailable for Pitot-tube traverse
                       measurements, measure airflow at terminal outlets and inlets and calculate the
                       total airflow.

          2.    Measure fan static pressures as follows to determine actual static pressure:

                a.     Measure outlet static pressure as far downstream from the fan as practical and
                       upstream from restrictions in ducts such as elbows and transitions.
                 b.    Measure static pressure directly at the fan outlet or through the flexible connection.
                 c.    Measure inlet static pressure of single-inlet fans in the inlet duct as near the fan as
                       possible, upstream from the flexible connection, and downstream from duct
                       restrictions.
Privatized Army Lodging                         230593 - 4                                        Lend Lease
Alterations for HIE Branding                                       Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                           October 20, 2011
               d.     Measure inlet static pressure of double-inlet fans through the wall of the plenum
                      that houses the fan.

         3.    Measure static pressure across each component that makes up an air-handling unit,
               rooftop unit, and other air-handling and -treating equipment.

               a.     Report the cleanliness status of filters and the time static pressures are measured.

         4.    Measure static pressures entering and leaving other devices, such as sound traps, heat-
               recovery equipment, and air washers, under final balanced conditions.
         5.    Review Record Documents to determine variations in design static pressures versus
               actual static pressures. Calculate actual system-effect factors. Recommend adjustments
               to accommodate actual conditions.
         6.    Obtain approval from Architect for adjustment of fan speed higher or lower than indicated
               speed. Comply with requirements in Division 23 Sections for air-handling units for
               adjustment of fans, belts, and pulley sizes to achieve indicated air-handling-unit
               performance.
         7.    Do not make fan-speed adjustments that result in motor overload. Consult equipment
               manufacturers about fan-speed safety factors. Modulate dampers and measure fan-
               motor amperage to ensure that no overload will occur. Measure amperage in full-cooling,
               full-heating, economizer, and any other operating mode to determine the maximum
               required brake horsepower.

   B.    Adjust volume dampers for main duct, submain ducts, and major branch ducts to indicated
         airflows within specified tolerances.

         1.    Measure airflow of submain and branch ducts.

               a.     Where sufficient space in submain and branch ducts is unavailable for Pitot-tube
                      traverse measurements, measure airflow at terminal outlets and inlets and
                      calculate the total airflow for that zone.

         2.    Measure static pressure at a point downstream from the balancing damper, and adjust
               volume dampers until the proper static pressure is achieved.
         3.    Remeasure each submain and branch duct after all have been adjusted. Continue to
               adjust submain and branch ducts to indicated airflows within specified tolerances.

   C.    Measure air outlets and inlets without making adjustments.

         1.    Measure terminal outlets using a direct-reading hood or outlet manufacturer's written
               instructions and calculating factors.

   D.    Adjust air outlets and inlets for each space to indicated airflows within specified tolerances of
         indicated values. Make adjustments using branch volume dampers rather than extractors and
         the dampers at air terminals.

         1.    Adjust each outlet in same room or space to within specified tolerances of indicated
               quantities without generating noise levels above the limitations prescribed by the
               Contract Documents.
         2.    Adjust patterns of adjustable outlets for proper distribution without drafts.




Privatized Army Lodging                        230593 - 5                               Lend Lease
Alterations for HIE Branding                                    Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                 October 20, 2011
3.06     GENERAL PROCEDURES FOR HYDRONIC SYSTEMS

   A.    Prepare test reports with pertinent design data, and number in sequence starting at pump to
         end of system. Check the sum of branch-circuit flows against the approved pump flow rate.
         Correct variations that exceed plus or minus 5 percent.

   B.    Prepare schematic diagrams of systems' "as-built" piping layouts.

   C.    Prepare hydronic systems for testing and balancing according to the following, in addition to the
         general preparation procedures specified above:

         1.    Open all manual valves for maximum flow.
         2.    Check liquid level in expansion tank.
         3.    Check makeup water-station pressure gage for adequate pressure for highest vent.
         4.    Check flow-control valves for specified sequence of operation, and set at indicated flow.
         5.    Set differential-pressure control valves at the specified differential pressure. Do not set at
               fully closed position when pump is positive-displacement type unless several terminal
               valves are kept open.
         6.    Set system controls so automatic valves are wide open to heat exchangers.
         7.    Check pump-motor load. If motor is overloaded, throttle main flow-balancing device so
               motor nameplate rating is not exceeded.
         8.    Check air vents for a forceful liquid flow exiting from vents when manually operated.


3.07     PROCEDURES FOR CONSTANT-FLOW HYDRONIC SYSTEMS

   A.    Measure water flow at pumps. Use the following procedures except for positive-displacement
         pumps:

         1.    Verify impeller size by operating the pump with the discharge valve closed. Read
               pressure differential across the pump. Convert pressure to head and correct for
               differences in gage heights. Note the point on manufacturer's pump curve at zero flow
               and verify that the pump has the intended impeller size.

               a.     If impeller sizes must be adjusted to achieve pump performance, obtain approval
                      from Architect and comply with requirements in Division 23 Section "Hydronic
                      Pumps."

         2.    Check system resistance. With all valves open, read pressure differential across the
               pump and mark pump manufacturer's head-capacity curve. Adjust pump discharge valve
               until indicated water flow is achieved.

               a.     Monitor motor performance during procedures and do not operate motors in
                      overload conditions.

         3.    Verify pump-motor brake horsepower. Calculate the intended brake horsepower for the
               system based on pump manufacturer's performance data. Compare calculated brake
               horsepower with nameplate data on the pump motor. Report conditions where actual
               amperage exceeds motor nameplate amperage.
         4.    Report flow rates that are not within plus or minus 10 percent of design.

   B.    Measure flow at all automatic flow control valves to verify that valves are functioning as
         designed.

   C.    Measure flow at all pressure-independent characterized control valves, with valves in fully open
         position, to verify that valves are functioning as designed.
Privatized Army Lodging                        230593 - 6                                Lend Lease
Alterations for HIE Branding                                     Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                  October 20, 2011
   D.    Set calibrated balancing valves, if installed, at calculated presettings.

   E.    Measure flow at all stations and adjust, where necessary, to obtain first balance.

         1.     System components that have Cv rating or an accurately cataloged flow-pressure-drop
                relationship may be used as a flow-indicating device.

   F.    Measure flow at main balancing station and set main balancing device to achieve flow that is 5
         percent greater than indicated flow.

   G.    Adjust balancing stations to within specified tolerances of indicated flow rate as follows:

         1.     Determine the balancing station with the highest percentage over indicated flow.
         2.     Adjust each station in turn, beginning with the station with the highest percentage over
                indicated flow and proceeding to the station with the lowest percentage over indicated
                flow.
         3.     Record settings and mark balancing devices.

   H.    Measure pump flow rate and make final measurements of pump amperage, voltage, rpm, pump
         heads, and systems' pressures and temperatures including outdoor-air temperature.

   I.    Measure the differential-pressure-control-valve settings existing at the conclusion of balancing.

   J.    Check settings and operation of each safety valve. Record settings.


3.08     PROCEDURES FOR MOTORS

   A.    Motors, 1/2 HP and Larger: Test at final balanced conditions and record the following data:

         1.     Manufacturer's name, model number, and serial number.
         2.     Motor horsepower rating.
         3.     Motor rpm.
         4.     Efficiency rating.
         5.     Nameplate and measured voltage, each phase.
         6.     Nameplate and measured amperage, each phase.
         7.     Starter thermal-protection-element rating.


3.09     TOLERANCES

   A.    Set HVAC system's air flow rates and water flow rates within the following tolerances:

         1.     Supply, Return, and Exhaust Fans and Equipment with Fans: Plus or minus 10 percent.
         2.     Air Outlets and Inlets: Plus or minus 10 percent.
         3.     Condenser-Water Flow Rate: Plus or minus 10 percent.


3.10     FINAL REPORT

   A.    General: Prepare a certified written report; tabulate and divide the report into separate sections
         for tested systems and balanced systems.

         1.      Include a certification sheet at the front of the report's binder, signed and sealed by the
                 certified testing and balancing engineer.
          2.     Include a list of instruments used for procedures, along with proof of calibration.
Privatized Army Lodging                           230593 - 7                                      Lend Lease
Alterations for HIE Branding                                        Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                          October 20, 2011
   B.    Final Report Contents: In addition to certified field-report data, include the following:

         1.    Pump curves.
         2.    Fan curves.
         3.    Manufacturers' test data.
         4.    Field test reports prepared by system and equipment installers.
         5.    Other information relative to equipment performance; do not include Shop Drawings and
               product data.

   C.    General Report Data: In addition to form titles and entries, include the following data:

         1.    Title page.
         2.    Name and address of the TAB contractor.
         3.    Project name.
         4.    Project location.
         5.    Architect's name and address.
         6.    Engineer's name and address.
         7.    Contractor's name and address.
         8.    Report date.
         9.    Signature of TAB supervisor who certifies the report.
         10.   Table of Contents with the total number of pages defined for each section of the report.
               Number each page in the report.
         11.   Summary of contents including the following:

               a.     Indicated versus final performance.
               b.     Notable characteristics of systems.
               c.     Description of system operation sequence if it varies from the Contract
                      Documents.

         12.   Nomenclature sheets for each item of equipment.
         13.   Data for terminal units, including manufacturer's name, type, size, and fittings.
         14.   Notes to explain why certain final data in the body of reports vary from indicated values.
         15.   Test conditions for fans and pump performance forms including the following:

               a.     Settings for outdoor-, return-, and exhaust-air dampers.
               b.     Conditions of filters.
               c.     Cooling coil, wet- and dry-bulb conditions.
               d.     Settings for supply-air, static-pressure controller.
               e.     Other system operating conditions that affect performance.

   D.    System Diagrams: Include schematic layouts of air and hydronic distribution systems. Present
         each system with single-line diagram and include the following:

         1.    Quantities of supply, return, and exhaust airflows.
         2.    Water flow rates.
         3.    Duct, outlet, and inlet sizes.
         4.    Pipe and valve sizes and locations.
         5.    Balancing stations.
         6.    Position of balancing devices.


3.11     ADDITIONAL TESTS

   A.    Within 90 days of completing TAB, perform additional TAB to verify that balanced conditions are
         being maintained throughout and to correct unusual conditions.

Privatized Army Lodging                         230593 - 8                                 Lend Lease
Alterations for HIE Branding                                       Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                    October 20, 2011
   B.    Seasonal Periods: If initial TAB procedures were not performed during near-peak summer and
         winter conditions, perform additional TAB during near-peak summer and winter conditions.


                                        END OF SECTION




Privatized Army Lodging                     230593 - 9                              Lend Lease
Alterations for HIE Branding                                Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                             October 20, 2011
                                           SECTION 230700

                                          HVAC INSULATION


PART 1 - GENERAL


1.01     RELATED DOCUMENTS

   A.    Drawings and general provisions of the Contract, including General and Supplementary
         Conditions and Division 1 Specification Sections, apply to this Section.


1.02     SUMMARY

   A.    This Section includes semirigid and flexible duct, plenum, and breeching insulation; insulating
         cements; field-applied jackets; accessories and attachments; and sealing compounds.

   B.    Related Sections include the following:

         1.     Division 2 Section "Hydronic Distribution" for loose-fill pipe insulation in underground
                piping outside the building.
         2.     Division 7 Section "Penetration Firestopping" for firestopping materials and requirements
                for penetrations through fire and smoke barriers.
         3.     Division 23 Section "Hangers and Supports" for pipe insulation shields and protection
                saddles.
         4.     Division 23 Section "Metal Ducts" for duct liner.


1.03     SUBMITTALS

   A.    Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field
         applied, if any), for each type of product indicated.

   B.    Material Test Reports: From a qualified testing agency acceptable to authorities having
         jurisdiction indicating, interpreting, and certifying test results for compliance of insulation
         materials, sealers, attachments, cements, and jackets with requirements indicated. Include
         dates of tests.

   C.    Installer Certificates:   Signed by the Contractor certifying that installers comply with
         requirements.


1.04     QUALITY ASSURANCE

   A.    Installer Qualifications: Skilled mechanics who have successfully completed an apprenticeship
         program or another craft training program certified by the U.S. Department of Labor, Bureau of
         Apprenticeship and Training.

   B.     Fire-Test-Response Characteristics: As determined by testing materials identical to those
          specified in this Section according to ASTM E 84, by a testing and inspecting agency
          acceptable to authorities having jurisdiction. Factory label insulation and jacket materials and
          sealer and cement material containers with appropriate markings of applicable testing and
          inspecting agency.
Privatized Army Lodging                         230700 - 1                                    Lend Lease
Alterations for HIE Branding                                     Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                       October 20, 2011
         1.    Insulation Installed Indoors: Flame-spread rating of 25 or less, and smoke-developed
               rating of 50 or less.
         2.    Insulation Installed Outdoors: Flame-spread rating of 75 or less, and smoke-developed
               rating of 150 or less.


1.05     DELIVERY, STORAGE, AND HANDLING

   A.    Packaging: Ship insulation materials in containers marked by manufacturer with appropriate
         ASTM specification designation, type and grade, and maximum use temperature.


1.06     COORDINATION

   A.    Coordinate clearance requirements with duct Installer for insulation application.


1.07     SCHEDULING

   A.    Schedule insulation application after testing duct systems. Insulation application may begin on
         segments of ducts that have satisfactory test results.


PART 2 - PRODUCTS


2.01     MANUFACTURERS

   A.    Manufacturers:    Subject to compliance with requirements, provide products by one of the
         following:

         1.    Mineral-Fiber Insulation:

               a.     CertainTeed Manson.
               b.     Knauf FiberGlass GmbH.
               c.     Owens-Corning Fiberglas Corp.
               d.     Schuller International, Inc.


2.02     INSULATION MATERIALS

   A.    Mineral-Fiber Board Thermal Insulation: Maximum “K” factor of .25 @ 70° F. Glass fibers
         bonded with a thermosetting resin 1.5#/ft3 density for use to 400° F. Comply with ASTM C 612,
         Type IB, without facing and with all-service jacket manufactured from kraft paper, reinforcing
         scrim, aluminum foil, and vinyl film. Basis of design: Ultra Duct Fiberglass duct system by
         Certain-Teed.

   B.    Mineral-Fiber Blanket Thermal Insulation: Maximum “K” factor of .25 @ 70° F. Glass fibers
         bonded with a thermosetting resin 1.5#/ft3 density for use to 250° F. Comply with ASTM C 553,
         Type II, without facing and with all-service jacket manufactured from kraft paper, reinforcing
         scrim, aluminum foil, and vinyl film. Basis of design: Duct wrap by Certain-Teed.


2.03     ACCESSORIES AND ATTACHMENTS


Privatized Army Lodging                        230700 - 2                                Lend Lease
Alterations for HIE Branding                                     Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                  October 20, 2011
   A.    Glass Cloth and Tape: Comply with MIL-C-20079H, Type I for cloth and Type II for tape.
         Woven glass-fiber fabrics, plain weave, presized a minimum of 8 oz./sq. yd..

         1.    Tape Width: 4 inches.

   B.    Weld-Attached Anchor Pins and Washers: Copper-coated steel pin for capacitor-discharge
         welding and galvanized speed washer. Pin length sufficient for insulation thickness indicated.

         1.    Welded Pin Holding Capacity: 100 lb for direct pull perpendicular to the attached surface.

   C.    Adhesive-Attached Anchor Pins and Speed Washers: Galvanized steel plate, pin, and washer
         manufactured for attachment to duct and plenum with adhesive. Pin length sufficient for
         insulation thickness indicated.

         1.    Adhesive: Recommended by the anchor pin manufacturer as appropriate for surface
               temperatures of ducts, plenums, and breechings; and to achieve a holding capacity of
               100 lb for direct pull perpendicular to the adhered surface.

   D.    Self-Adhesive Anchor Pins and Speed Washers: Galvanized steel plate, pin, and washer
         manufactured for attachment to duct and plenum with adhesive. Pin length sufficient for
         insulation thickness indicated.


2.04     VAPOR RETARDERS

   A.    Moisture Barrier: 3-mil Dupont Surlyn

   B.    Mastics: Materials recommended by insulation material manufacturer that are compatible with
         insulation materials, jackets, and substrates.
         1.    Exterior Insulation (Metal Jacket): Flexible elastomeric based, vapor barrier sealant
               designed to seal metal joints, .02 perm max, -50 to 250 ° F, aluminum color.
         2.    Interior Insulation: Water based fire resistive composition with a water permeance of .08
               max. and temperature range of -20 to 180° F.


PART 3 - EXECUTION


3.01     EXAMINATION

   A.    Examine substrates and conditions for compliance with requirements for installation and other
         conditions affecting performance of insulation application.

   B.    Proceed with installation only after unsatisfactory conditions have been corrected.


3.02     PREPARATION

   A.    Surface Preparation: Clean and dry surfaces to receive insulation. Remove materials that will
         adversely affect insulation application.


3.03     GENERAL APPLICATION REQUIREMENTS


Privatized Army Lodging                          230700 - 3                             Lend Lease
Alterations for HIE Branding                                    Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                 October 20, 2011
   A.    Apply insulation materials, accessories, and finishes according to the manufacturer's written
         instructions; with smooth, straight, and even surfaces; and free of voids throughout the length of
         ducts and fittings.

   B.    Refer to schedules at the end of this Section for materials, forms, jackets, and thicknesses
         required for each duct system.

   C.    Use accessories compatible with insulation materials and suitable for the service. Use
         accessories that do not corrode, soften, or otherwise attack insulation or jacket in either wet or
         dry state.

   D.    Apply multiple layers of insulation with longitudinal and end seams staggered.

   E.    Seal joints and seams with vapor-retarder mastic on insulation indicated to receive a vapor
         retarder.

   F.    Keep insulation materials dry during application and finishing.

   G.    Apply insulation with tight longitudinal seams and end joints. Bond seams and joints with
         adhesive recommended by the insulation material manufacturer.

   H.    Apply insulation with the least number of joints practical.

   I.    Apply insulation over fittings and specialties, with continuous thermal and vapor-retarder
         integrity, unless otherwise indicated.

   J.    Hangers and Anchors: Where vapor retarder is indicated, seal penetrations in insulation at
         hangers, supports, anchors, and other projections with vapor-retarder mastic. Apply insulation
         continuously through hangers and around anchor attachments.

   K.    Insulation Terminations: For insulation application where vapor retarders are indicated, seal
         ends with a compound recommended by the insulation material manufacturer to maintain vapor
         retarder.

   L.    Apply insulation with integral jackets as follows:

         1.    Pull jacket tight and smooth.
         2.    Joints and Seams: Cover with tape and vapor retarder as recommended by insulation
               material manufacturer to maintain vapor seal.
         3.    Vapor-Retarder Mastics: Where vapor retarders are indicated, apply mastic on seams
               and joints and at ends adjacent to duct flanges and fittings.

   M.    Cut insulation according to manufacturer's written instructions to prevent compressing insulation
         to less than 75 percent of its nominal thickness.

   N.    Install vapor-retarder mastic on insulation scheduled to receive vapor retarders.

         1.    Insulation Vapor Retarders: Overlap insulation facing at seams and seal with vapor-
               retarder mastic and pressure-sensitive tape having same facing as insulation. Repair
               punctures, tears, and penetrations with tape or mastic to maintain vapor-retarder seal.
         2.    Insulation without Vapor Retarders: Overlap insulation facing at seams and secure with
               outward clinching staples and pressure-sensitive tape having same facing as insulation.

   O.    Interior Wall and Partition Penetrations: Apply insulation continuously through walls and
         partitions, except fire-rated walls and partitions.

Privatized Army Lodging                         230700 - 4                                Lend Lease
Alterations for HIE Branding                                      Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                   October 20, 2011
   P.    Fire-Rated Wall and Partition Penetrations: Terminate insulation at fire/smoke damper sleeves
         for fire-rated wall and partition penetrations.

   Q.    Floor Penetrations: Terminate insulation at underside of floor assembly and at floor support at
         top of floor.

         1.    For insulation indicated to have vapor retarders, taper termination and seal insulation
               ends with vapor-retarder mastic.


3.04     MINERAL-FIBER INSULATION APPLICATION

   A.    Blanket Applications for Ducts and Plenums: Secure blanket insulation with adhesive and
         anchor pins and speed washers with wrap facing out.

         1.    Apply adhesives according to manufacturer's recommended coverage rates per square
               foot, for 100 percent coverage of duct and plenum surfaces.
         2.    Apply adhesive to entire circumference of ducts and pipes and to all surfaces of fittings
               and transitions.
         3.    Install anchor pins and speed washers on sides and bottom of horizontal ducts and sides
               of vertical ducts as follows:

               a.     On duct sides with dimensions 18 inches and smaller, along longitudinal centerline
                      of duct. Space 3 inches maximum from insulation end joints, and 16 inches o.c.
               b.     On duct sides with dimensions larger than 18 inches. Space 16 inches o.c. each
                      way, and 3 inches maximum from insulation joints. Apply additional pins and clips
                      to hold insulation tightly against surface at cross bracing.
               c.     Anchor pins may be omitted from top surface of horizontal, rectangular ducts and
                      plenums.
               d.     Do not over compress insulation during installation.
               e.     On rectangular ducts, 24” and greater, insulation shall be secured to bottom of the
                      duct with fasteners spaced 18” o.c. to prevent sagging.

         4.    Impale insulation over anchors and attach speed washers.
         5.    Cut excess portion of pins extending beyond speed washers or bend parallel with
               insulation surface. Cover exposed pins and washers with tape matching insulation
               facing.
         6.    Create a facing lap for longitudinal seams and end joints with insulation by removing 2
               inches from one edge and one end of insulation segment. Secure laps to adjacent
               insulation segment with 1/2-inch staples, 1 inch o.c., and cover with pressure-sensitive
               tape having same facing as insulation.
         7.    Overlap unfaced blankets a minimum of 2 inches on longitudinal seams and end joints.
               Secure with steel band at end joints and spaced a maximum of 18 inches o.c.
         8.    Apply insulation on rectangular duct elbows and transitions with a full insulation segment
               for each surface. Apply insulation on round and flat-oval duct elbows with individually
               mitered gores cut to fit the elbow.
         9.    Insulate duct stiffeners, hangers, and flanges that protrude beyond the insulation surface
               with 6-inch- wide strips of the same material used to insulate duct. Secure on alternating
               sides of stiffener, hanger, and flange with anchor pins spaced 6 inches o.c.
         10.   Apply vapor-retarder mastic or tape matching the insulation facing, to open joints, breaks,
               and punctures for insulation indicated to receive vapor retarder.
         11.   Cover piping with standard PVC jacket on all vertical piping within 8’-0” of floor when
               exposed to view.
         12.   Cut insulation to “stretch out” dimensions as indicated by manufacturer.



Privatized Army Lodging                       230700 - 5                                Lend Lease
Alterations for HIE Branding                                    Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                 October 20, 2011
   B.    Board Applications for Ducts and Plenums: Secure board insulation with adhesive and anchor
         pins and speed washers.

         1.    Apply adhesives according to manufacturer's recommended coverage rates per square
               foot, for 100 percent coverage of duct and plenum surfaces.
         2.    Apply adhesive to entire circumference of ducts and to all surfaces of fittings and
               transitions.
         3.    Space anchor pins as follows:

               a.     On duct sides with dimensions 18 inches and smaller, along longitudinal centerline
                      of duct. Space 3 inches maximum from insulation end joints, and 16 inches o.c.
               b.     On duct sides with dimensions larger than 18 inches. Space 16 inches o.c. each
                      way, and 3 inches maximum from insulation joints. Apply additional pins and clips
                      to hold insulation tightly against surface at cross bracing.
               c.     Anchor pins may be omitted from top surface of horizontal, rectangular ducts and
                      plenums.
               d.     Do not over compress insulation during installation.

         4.    Cut excess portion of pins extending beyond speed washers or bend parallel with
               insulation surface. Cover exposed pins and washers with tape matching insulation
               facing.
         5.    Create a facing lap for longitudinal seams and end joints with insulation by removing 2
               inches from one edge and one end of insulation segment. Secure laps to adjacent
               insulation segment with 1/2-inch staples, 1 inch o.c., and cover with pressure-sensitive
               tape having same facing as insulation.
         6.    Apply insulation on rectangular duct elbows and transitions with a full insulation segment
               for each surface. Groove and score insulation to fit as closely as possible to outside and
               inside radius of elbows. Apply insulation on round and flat-oval duct elbows with
               individually mitered gores cut to fit the elbow.
         7.    Insulate duct stiffeners, hangers, and flanges that protrude beyond the insulation surface
               with 6-inch- wide strips of the same material used to insulate duct. Secure on alternating
               sides of stiffener, hanger, and flange with anchor pins spaced 6 inches o.c.
         8.    Apply vapor-retarder mastic or tape matching the insulation facing, to open joints, breaks,
               and punctures for insulation indicated to receive vapor retarder.

   C.    Apply insulation to valves and specialties as follows:

         1.    Apply premolded insulation sections of the same material as straight segments of pipe
               insulation when available. Secure according to manufacturer's written instructions.
         2.    When premolded insulation sections are not available, apply glass-fiber blanket insulation
               to valve body. Arrange insulation to permit access to packing and to allow valve
               operation without disturbing insulation. For check valves, arrange insulation for access to
               stainer basket without disturbing insulation.
         3.    Apply insulation to flanges as specified for flange insulation application.
         4.    Use preformed standard PVC fitting covers for valve sizes where available. Secure fitting
               covers with manufacturer's attachments and accessories. Seal seams with tape and
               vapor-retarder mastic.
         5.    For larger sizes where PVC fitting covers are not available, seal insulation with canvas
               jacket and sealing compound recommended by the insulation material manufacturer.


3.05     FINISHES

   A.    Flexible Elastomeric Thermal Insulation: After adhesive has fully cured, apply two coats of
         insulation manufacturer's recommended protective coating.


Privatized Army Lodging                         230700 - 6                                Lend Lease
Alterations for HIE Branding                                      Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                   October 20, 2011
3.06     FIELD QUALITY CONTROL

   A.    Insulation applications will be considered defective if on site observation reveals noncompliance
         with requirements. Remove defective Work and replace with new materials according to these
         Specifications.


3.07     DUCT SYSTEM APPLICATIONS

   A.    Materials and thicknesses for systems listed below are specified in schedules at the end of this
         Section.

   B.    Insulate the following plenums and duct systems:

         1.     Indoor concealed supply-, return-, and outside-air ductwork.
         2.     Outdoor exposed supply and return ductwork.

   C.    Items Not Insulated: Unless otherwise indicated, do not apply insulation to the following
         systems, materials, and equipment:

         1.     Fibrous-glass ducts.
         2.     Metal ducts with duct liner.
         3.     Factory-insulated flexible ducts.
         4.     Factory-insulated plenums, casings, terminal boxes, and filter boxes and sections.
         5.     Flexible connectors.
         6.     Vibration-control devices.
         7.     Nameplates and data plates.
         8.     Access panels and doors in air-distribution systems.
         9.     Exposed ductwork unless noted otherwise.


3.08     INDOOR DUCT AND PLENUM APPLICATION SCHEDULE – Ductwork shall be as shown in
         the following table unless otherwise indicated.

   A.    Low velocity supply air ducts – downstream of air handler.

         1.     Material: Fiberglass blanket wrap.
         2.     Thickness: 1-1/2”.
         3.     Vapor Retarder: Yes.

   B.    Low velocity supply air ducts – downstream of ERV.

         1.     Material: Fiberglass blanket wrap.
         2.     Thickness: 1-1/2”.
         3.     Vapor Retarder: Yes.

   C.    Low velocity supply air ductwork to diffuser runouts.

         1.     Material: Fiberglass blanket wrap.
         2.     Thickness: 2”.
         3.     Vapor Retarder: Yes.

   D.    Outside air ductwork upstream of ERV.

          1.     Material: Fiberglass blanket wrap.
          2.     Thickness: 2”.
Privatized Army Lodging                         230700 - 7                               Lend Lease
Alterations for HIE Branding                                     Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                  October 20, 2011
   E.    Exhaust air ductwork downstream of ERV.

         1.    Material: Fiberglass blanket wrap.
         2.    Thickness: 2”.


                                         END OF SECTION




Privatized Army Lodging                      230700 - 8                           Lend Lease
Alterations for HIE Branding                              Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                           October 20, 2011
                                               SECTION 232113

                                               HYDRONIC PIPING


PART 1 - GENERAL


1.01     SUMMARY

   A.    This Section includes pipe and fitting materials, joining methods, special-duty valves, and
         specialties for the following:
         1.    Condenser-water piping.
         2.    Condensate-drain piping.
         3.    Air-vent piping.


1.02     PERFORMANCE REQUIREMENTS

   A.    Hydronic piping components and installation shall be capable of withstanding the following
         minimum working pressure and temperature:

         1.     Condenser-Water Piping: 150 psig at 150 deg F.
         2.     Condensate-Drain Piping: 150 deg F.
         3.     Air-Vent Piping: 200 deg F.


1.03     SUBMITTALS

   A.    Product Data: For each type of the following:

         1.     Valves. Include flow and pressure drop curves based on manufacturer's testing for
                calibrated-orifice balancing valves and automatic flow-control valves.
         2.     Air control devices.
         3.     Chemical treatment.
         4.     Hydronic specialties.

   B.    Field quality-control test reports.

   C.    Operation and maintenance data.


PART 2 - PRODUCTS


2.01     COPPER TUBE AND FITTINGS

   A.    Drawn-Temper Copper Tubing: ASTM B 88, Type L.

   B.    Annealed-Temper Copper Tubing: ASTM B 88, Type K.

   C.    Wrought-Copper Fittings: ASME B16.22.



Privatized Army Lodging                           232113 - 1                             Lend Lease
Alterations for HIE Branding                                     Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                  October 20, 2011
         1.    Manufacturers: Subject to compliance with requirements, provide products by one of the
               following:

               a.     Anvil International, Inc.
               b.     S. P. Fittings; a division of Star Pipe Products.
               c.     Victaulic Company.

   D.    Wrought-Copper Unions: ASME B16.22.


2.02     JOINING MATERIALS

   A.    Solder Filler Metals: ASTM B 32, lead-free alloys. Include water-flushable flux according to
         ASTM B 813.


2.03     DIELECTRIC FITTINGS

   A.    General Requirements: Assembly of copper alloy and ferrous materials with separating
         nonconductive insulating material. Include end connections compatible with pipes to be joined.

   B.    Dielectric Unions:

         1.    Manufacturers: Subject to compliance with requirements, provide products by one of the
               following:

               a.     Capitol Manufacturing Company.
               b.     Central Plastics Company.
               c.     Hart Industries International, Inc.
               d.     Jomar International Ltd.
               e.     Matco-Norca, Inc.
               f.     McDonald, A. Y. Mfg. Co.
               g.     Watts Regulator Co.; a division of Watts Water Technologies, Inc.
               h.     Wilkins; a Zurn company.

         2.    Description:

               a.     Standard: ASSE 1079.
               b.     Pressure Rating: 125 psig minimum at 180 deg F.
               c.     End Connections: Solder-joint copper alloy and threaded ferrous.


2.04     VALVES

   A.    Ball Valves: Comply with requirements specified in Division 23 Section "General-Duty Valves
         for HVAC Piping."

   B.    Bronze, Calibrated-Orifice, Balancing Valves:
         1.   Manufacturers: Subject to compliance with requirements, provide products by one of the
              following:

                 a.    Armstrong Pumps, Inc.
                 b.    Bell & Gossett Domestic Pump; a division of ITT Industries.
                 c.    Flow Design Inc.
                 d.    Gerand Engineering Co.
                 e.    Griswold Controls.
Privatized Army Lodging                        232113 - 2                               Lend Lease
Alterations for HIE Branding                                    Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                 October 20, 2011
               f.     Taco.
               g.     Tour & Andersson; available through Victaulic Company.

         2.    Body: Bronze, ball or plug type with calibrated orifice or venturi.
         3.    Ball: Brass or stainless steel.
         4.    Plug: Resin.
         5.    Seat: PTFE.
         6.    End Connections: Threaded or socket.
         7.    Pressure Gage Connections: Integral seals for portable differential pressure meter.
         8.    Handle Style: Lever, with memory stop to retain set position.
         9.    CWP Rating: Minimum 125 psig.
         10.   Maximum Operating Temperature: 250 deg F.


2.05     AIR CONTROL DEVICES

   A.    Manufacturers:   Subject to compliance with requirements, provide products by one of the
         following:

         1.    Amtrol, Inc.
         2.    Armstrong Pumps, Inc.
         3.    Bell & Gossett Domestic Pump; a division of ITT Industries.
         4.    Taco.

   B.    Manual Air Vents:

         1.    Body: Bronze.
         2.    Internal Parts: Nonferrous.
         3.    Operator: Screwdriver or thumbscrew.
         4.    Inlet Connection: NPS 1/2.
         5.    Discharge Connection: NPS 1/8.
         6.    CWP Rating: 150 psig.
         7.    Maximum Operating Temperature: 225 deg F.


2.06     HYDRONIC PIPING SPECIALTIES

   A.    Y-Pattern Strainers:

         1.    Body: ASTM A 126, Class B, cast iron with bolted cover and bottom drain connection.
         2.    End Connections: Threaded ends for NPS 2 and smaller; flanged ends for NPS 2-1/2
               and larger.
         3.    Strainer Screen: 40-mesh startup strainer, and perforated stainless-steel basket with 50
               percent free area.
         4.    CWP Rating: 125 psig.

   B.    Stainless-Steel Bellow, Flexible Connectors:

         1.    Body: Stainless-steel bellows with woven, flexible, bronze, wire-reinforcing protective
               jacket.
         2.    End Connections: Threaded or flanged to match equipment connected.
         3.    Performance: Capable of 3/4-inch misalignment.
         4.    CWP Rating: 150 psig.
         5.    Maximum Operating Temperature: 250 deg F.


Privatized Army Lodging                       232113 - 3                               Lend Lease
Alterations for HIE Branding                                   Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                October 20, 2011
PART 3 - EXECUTION


3.01     PIPING APPLICATIONS

   A.    Condenser-water piping, aboveground, NPS 2 and smaller, shall be the following:

         1.     Type L, drawn-temper copper tubing, wrought-copper fittings, and soldered joints.

   B.    Condensate-Drain Piping: Type M, drawn-temper copper tubing, wrought-copper fittings, and
         soldered joints.


3.02     VALVE APPLICATIONS

   A.    Install shutoff-duty valves at each branch connection to supply mains, and at supply connection
         to each piece of equipment.

   B.    Install calibrated-orifice, balancing valves in the return pipe of each heat pump.

   C.    Install check valves at each pump discharge and elsewhere as required to control flow direction.

   D.    Install pressure-reducing valves at makeup-water connection to regulate system fill pressure.


3.03     PIPING INSTALLATIONS

   A.    Drawing plans, schematics, and diagrams indicate general location and arrangement of piping
         systems. Indicate piping locations and arrangements if such were used to size pipe and
         calculate friction loss, expansion, pump sizing, and other design considerations. Install piping
         as indicated unless deviations to layout are approved on Coordination Drawings.

   B.    Install piping in concealed locations, unless otherwise indicated and except in equipment rooms
         and service areas.

   C.    Install piping indicated to be exposed and piping in equipment rooms and service areas at right
         angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated
         otherwise.

   D.    Install piping above accessible ceilings to allow sufficient space for ceiling panel removal.

   E.    Install piping to permit valve servicing.

   F.    Install piping at indicated slopes.

   G.    Install piping free of sags and bends.

   H.    Install fittings for changes in direction and branch connections.

   I.    Install piping to allow application of insulation.

   J.    Select system components with pressure rating equal to or greater than system operating
         pressure.

   K.     Install groups of pipes parallel to each other, spaced to permit applying insulation and servicing
          of valves.
Privatized Army Lodging                          232113 - 4                                     Lend Lease
Alterations for HIE Branding                                       Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                        October 20, 2011
   L.    Install drains, consisting of a tee fitting, NPS 3/4 ball valve, and short NPS 3/4 threaded nipple
         with cap, at low points in piping system mains and elsewhere as required for system drainage.

   M.    Install piping at a uniform grade of 0.2 percent upward in direction of flow.

   N.    Reduce pipe sizes using eccentric reducer fitting installed with level side up.

   O.    Install branch connections to mains using tee fittings in main pipe, with the branch connected to
         the bottom of the main pipe. For up-feed risers, connect the branch to the top of the main pipe.

   P.    Install valves according to Division 23 Section "General-Duty Valves for HVAC Piping."

   Q.    Install unions in piping, NPS 2 and smaller, adjacent to valves, at final connections of
         equipment, and elsewhere as indicated.

   R.    Install strainers as indicated. Match size of strainer blowoff connection for strainers smaller
         than NPS 2.

   S.    Identify piping as specified in Division 23 Section "Identification for HVAC Piping and
         Equipment."

   T.    Install sleeves for piping penetrations of walls, ceilings, and floors. Comply with requirements
         for sleeves specified in Division 23 Section "Sleeves and Sleeve Seals for HVAC Piping."

   U.    Install sleeve seals for piping penetrations of concrete walls and slabs. Comply with
         requirements for sleeve seals specified in Division 23 Section "Sleeves and Sleeve Seals for
         HVAC Piping."

   V.    Install escutcheons for piping penetrations of walls, ceilings, and floors. Comply with
         requirements for escutcheons specified in Division 23 Section "Escutcheons for HVAC Piping."


3.04     HANGERS AND SUPPORTS

   A.    Hanger, support, and anchor devices are specified in Division 23 Section "Hangers and
         Supports for HVAC Piping and Equipment." Comply with the following requirements for
         maximum spacing of supports.

   B.    Install the following pipe attachments:

         1.    Adjustable steel clevis hangers for individual horizontal piping less than 20 feet long.
         2.    Spring hangers to support vertical runs.
         3.    Provide copper-clad hangers and supports for hangers and supports in direct contact with
               copper pipe.

   C.    Install hangers for drawn-temper copper piping with the following maximum spacing and
         minimum rod sizes:

         1.    NPS 3/4: Maximum span, 5 feet; minimum rod size, 1/4 inch.
         2.    NPS 1: Maximum span, 6 feet; minimum rod size, 1/4 inch.
         3.    NPS 1-1/2: Maximum span, 8 feet; minimum rod size, 3/8 inch.
         4.    NPS 2: Maximum span, 8 feet; minimum rod size, 3/8 inch.

   D.    Support vertical runs at roof, at each floor, and at 10-foot intervals between floors.


Privatized Army Lodging                            232113 - 5                             Lend Lease
Alterations for HIE Branding                                      Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                   October 20, 2011
3.05     PIPE JOINT CONSTRUCTION

   A.    Join pipe and fittings according to the following requirements and Division 23 Sections
         specifying piping systems.

   B.    Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.

   C.    Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before
         assembly.

   D.    Soldered Joints: Apply ASTM B 813, water-flushable flux, unless otherwise indicated, to tube
         end. Construct joints according to ASTM B 828 or CDA's "Copper Tube Handbook," using lead-
         free solder alloy complying with ASTM B 32.

   E.    Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut
         threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore
         full ID. Join pipe fittings and valves as follows:

         1.    Apply appropriate tape or thread compound to external pipe threads unless dry seal
               threading is specified.
         2.    Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or
               damaged. Do not use pipe sections that have cracked or open welds.


3.06     HYDRONIC SPECIALTIES INSTALLATION

   A.    Install manual air vents at high points in piping, at heat-transfer coils, and elsewhere as required
         for system air venting.


3.07     TERMINAL EQUIPMENT CONNECTIONS

   A.    Sizes for supply and return piping connections shall be the same as or larger than equipment
         connections.


3.08     FIELD QUALITY CONTROL

   A.    Prepare hydronic piping according to ASME B31.9 and as follows:

         1.    Leave joints, including welds, uninsulated and exposed for examination during test.
         2.    Flush hydronic piping systems with clean water; then remove and clean or replace
               strainer screens.
         3.    Isolate equipment from piping. If a valve is used to isolate equipment, its closure shall be
               capable of sealing against test pressure without damage to valve. Install blinds in
               flanged joints to isolate equipment.

   B.    Perform the following tests on hydronic piping:

         1.      Use ambient temperature water as a testing medium unless there is risk of damage due
                 to freezing. Another liquid that is safe for workers and compatible with piping may be
                 used.
          2.     While filling system, use vents installed at high points of system to release air. Use
                 drains installed at low points for complete draining of test liquid.
          3.     Subject piping system to hydrostatic test pressure that is not less than 1.5 times the
                 system's working pressure. Test pressure shall not exceed maximum pressure for any
Privatized Army Lodging                            232113 - 6                                Lend Lease
Alterations for HIE Branding                                        Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                     October 20, 2011
               vessel, pump, valve, or other component in system under test. Verify that stress due to
               pressure at bottom of vertical runs does not exceed 90 percent of specified minimum
               yield strength or 1.7 times "SE" value in Appendix A in ASME B31.9, "Building Services
               Piping."
         4.    After hydrostatic test pressure has been applied for at least 10 minutes, examine piping,
               joints, and connections for leakage. Eliminate leaks by tightening, repairing, or replacing
               components, and repeat hydrostatic test until there are no leaks.
         5.    Prepare written report of testing.

   C.    Perform the following before operating the system:

         1.    Open manual valves fully.
         2.    Set makeup pressure-reducing valves for required system pressure.
         3.    Inspect air vents at high points of system and determine if all are installed and operating
               freely (automatic type), or bleed air completely (manual type).


                                          END OF SECTION




Privatized Army Lodging                       232113 - 7                                Lend Lease
Alterations for HIE Branding                                    Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                 October 20, 2011
                                            SECTION 233113

                                             METAL DUCTS


PART 1 - GENERAL


1.01     SUMMARY

   A.    Section Includes:

         1.     Rectangular ducts and fittings.
         2.     Round ducts and fittings.
         3.     Sheet metal materials.
         4.     Sealants and gaskets.
         5.     Hangers and supports.

   B.    Related Sections:

         1.    Division 23 Section "Testing, Adjusting, and Balancing for HVAC" for testing, adjusting,
               and balancing requirements for metal ducts.
         2.    Division 23 Section "Nonmetal Ducts" for fibrous-glass ducts, thermoset fiber-reinforced
               plastic ducts, thermoplastic ducts, PVC ducts, and concrete ducts.
         3.    Division 23 Section "HVAC Casings" for factory- and field-fabricated casings for
               mechanical equipment.
         4.    Division 23 Section "Air Duct Accessories" for dampers, sound-control devices, duct-
               mounting access doors and panels, turning vanes, and flexible ducts.


1.02     PERFORMANCE REQUIREMENTS

   A.    Delegated Duct Design: Duct construction, including sheet metal thicknesses, seam and joint
         construction, reinforcements, and hangers and supports, shall comply with SMACNA's "HVAC
         Duct Construction Standards - Metal and Flexible" and performance requirements and design
         criteria indicated in "Duct Schedule" Article.

   B.    Structural Performance: Duct hangers and supports shall withstand the effects of gravity loads
         and stresses within limits and under conditions described in SMACNA's "HVAC Duct
         Construction Standards - Metal and Flexible" and ASCE/SEI 7.

   C.    Airstream Surfaces: Surfaces in contact with the airstream shall comply with requirements in
         ASHRAE 62.1.


1.03     SUBMITTALS

   A.    Product Data: For each type of product indicated.

   B.    Delegated-Design Submittal:

          1.     Sheet metal thicknesses.
          2.     Joint and seam construction and sealing.
          3.     Reinforcement details and spacing.
          4.     Materials, fabrication, assembly, and spacing of hangers and supports.
Privatized Army Lodging                          233113 - 1                                  Lend Lease
Alterations for HIE Branding                                      Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                      October 20, 2011
   C.    Welding certificates.


1.04     QUALITY ASSURANCE

   A.    Welding Qualifications: Qualify procedures and personnel according to the following:

         1.    AWS D1.1/D1.1M, "Structural Welding Code - Steel," for hangers and supports.
         2.    AWS D9.1M/D9.1, "Sheet Metal Welding Code," for duct joint and seam welding.

   B.    ASHRAE Compliance: Applicable requirements in ASHRAE 62.1, Section 5 - "Systems and
         Equipment" and Section 7 - "Construction and System Start-Up."

   C.    ASHRAE/IESNA Compliance: Applicable requirements in ASHRAE/IESNA 90.1, Section 6.4.4 -
         "HVAC System Construction and Insulation."


PART 2 - PRODUCTS


2.01     RECTANGULAR DUCTS AND FITTINGS

   A.    General Fabrication Requirements: Comply with SMACNA's "HVAC Duct Construction
         Standards - Metal and Flexible" based on indicated static-pressure class unless otherwise
         indicated.

   B.    Transverse Joints: Select joint types and fabricate according to SMACNA's "HVAC Duct
         Construction Standards - Metal and Flexible," Figure 2-1, "Rectangular Duct/Transverse Joints,"
         for static-pressure class, applicable sealing requirements, materials involved, duct-support
         intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and
         Flexible."

   C.    Longitudinal Seams: Select seam types and fabricate according to SMACNA's "HVAC Duct
         Construction Standards - Metal and Flexible," Figure 2-2, "Rectangular Duct/Longitudinal
         Seams," for static-pressure class, applicable sealing requirements, materials involved, duct-
         support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards -
         Metal and Flexible."

   D.    Elbows, Transitions, Offsets, Branch Connections, and Other Duct Construction: Select types
         and fabricate according to SMACNA's "HVAC Duct Construction Standards - Metal and
         Flexible," Chapter 4, "Fittings and Other Construction," for static-pressure class, applicable
         sealing requirements, materials involved, duct-support intervals, and other provisions in
         SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."


2.02     ROUND DUCTS AND FITTINGS

   A.    General Fabrication Requirements: Comply with SMACNA's "HVAC Duct Construction
         Standards - Metal and Flexible," Chapter 3, "Round, Oval, and Flexible Duct," based on
         indicated static-pressure class unless otherwise indicated.

   B.     Transverse Joints: Select joint types and fabricate according to SMACNA's "HVAC Duct
          Construction Standards - Metal and Flexible," Figure 3-1, "Round Duct Transverse Joints," for
          static-pressure class, applicable sealing requirements, materials involved, duct-support
          intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and
          Flexible."
Privatized Army Lodging                        233113 - 2                                 Lend Lease
Alterations for HIE Branding                                   Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                   October 20, 2011
   C.    Longitudinal Seams: Select seam types and fabricate according to SMACNA's "HVAC Duct
         Construction Standards - Metal and Flexible," Figure 3-2, "Round Duct Longitudinal Seams," for
         static-pressure class, applicable sealing requirements, materials involved, duct-support
         intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and
         Flexible."

   D.    Tees and Laterals: Select types and fabricate according to SMACNA's "HVAC Duct
         Construction Standards - Metal and Flexible," Figure 3-5, "90 Degree Tees and Laterals," and
         Figure 3-6, "Conical Tees," for static-pressure class, applicable sealing requirements, materials
         involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction
         Standards - Metal and Flexible."


2.03     SHEET METAL MATERIALS

   A.    General Material Requirements: Comply with SMACNA's "HVAC Duct Construction Standards
         - Metal and Flexible" for acceptable materials, material thicknesses, and duct construction
         methods unless otherwise indicated. Sheet metal materials shall be free of pitting, seam marks,
         roller marks, stains, discolorations, and other imperfections.

   B.    Galvanized Sheet Steel: Comply with ASTM A 653/A 653M.

         1.    Galvanized Coating Designation: [G60] [G90].
         2.    Finishes for Surfaces Exposed to View: Mill phosphatized.

   C.    Carbon-Steel Sheets: Comply with ASTM A 1008/A 1008M, with oiled, matte finish for exposed
         ducts.

   D.    Reinforcement Shapes and Plates: ASTM A 36/A 36M, steel plates, shapes, and bars; black
         and galvanized.

         1.    Where black- and galvanized-steel shapes and plates are used to reinforce aluminum
               ducts, isolate the different metals with butyl rubber, neoprene, or EPDM gasket materials.

   E.    Tie Rods: Galvanized steel, 1/4-inch minimum diameter for lengths 36 inches or less; 3/8-inch
         minimum diameter for lengths longer than 36 inches.


2.04     SEALANT AND GASKETS

   A.    General Sealant and Gasket Requirements: Surface-burning characteristics for sealants and
         gaskets shall be a maximum flame-spread index of 25 and a maximum smoke-developed index
         of 50 when tested according to UL 723; certified by an NRTL.

   B.    Two-Part Tape Sealing System:

         1.    Tape: Woven cotton fiber impregnated with mineral gypsum and modified acrylic/silicone
               activator to react exothermically with tape to form hard, durable, airtight seal.
         2.    Tape Width:3 inches.
         3.    Sealant: Modified styrene acrylic.
         4.    Water resistant.
         5.    Mold and mildew resistant.
         6.    Maximum Static-Pressure Class: 10-inch wg, positive and negative.
         7.    Service: Indoor and outdoor.
         8.    Service Temperature: Minus 40 to plus 200 deg F.

Privatized Army Lodging                        233113 - 3                               Lend Lease
Alterations for HIE Branding                                    Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                 October 20, 2011
         9.    Substrate: Compatible with galvanized sheet steel (both PVC coated and bare), stainless
               steel, or aluminum.

   C.    Water-Based Joint and Seam Sealant:

         1.    Application Method: Brush on.
         2.    Solids Content: Minimum 65 percent.
         3.    Shore A Hardness: Minimum 20.
         4.    Water resistant.
         5.    Mold and mildew resistant.
         6.    VOC: Maximum 75 g/L (less water).
         7.    Maximum Static-Pressure Class: 10-inch wg, positive and negative.
         8.    Service: Indoor or outdoor.
         9.    Substrate: Compatible with galvanized sheet steel (both PVC coated and bare), stainless
               steel, or aluminum sheets.

   D.    Flanged Joint Sealant: Comply with ASTM C 920.

         1.    General: Single-component, acid-curing, silicone, elastomeric.
         2.    Type: S.
         3.    Grade: NS.
         4.    Class: 25.
         5.    Use: O.
         6.    For indoor applications, use sealant that has a VOC content of 250 g/L or less when
               calculated according to 40 CFR 59, Subpart D (EPA Method 24).


2.05     HANGERS AND SUPPORTS

   A.    Hanger Rods for Noncorrosive Environments: Cadmium-plated steel rods and nuts.

   B.    Hanger Rods for Corrosive Environments: Electrogalvanized, all-thread rods or galvanized rods
         with threads painted with zinc-chromate primer after installation.

   C.    Strap and Rod Sizes: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and
         Flexible," Table 5-1, "Rectangular Duct Hangers Minimum Size," and Table 5-2, "Minimum
         Hanger Sizes for Round Duct."

   D.    Steel Cables for Galvanized-Steel Ducts: Galvanized steel complying with ASTM A 603.

   E.    Steel Cable End Connections: Cadmium-plated steel assemblies with brackets, swivel, and
         bolts designed for duct hanger service; with an automatic-locking and clamping device.

   F.    Duct Attachments: Sheet metal screws, blind rivets, or self-tapping metal screws; compatible
         with duct materials.

   G.    Trapeze and Riser Supports:

         1.    Supports for Galvanized-Steel Ducts: Galvanized-steel shapes and plates.
         2.    Supports for Stainless-Steel Ducts: Stainless-steel shapes and plates.
         3.    Supports for Aluminum Ducts: Aluminum or galvanized steel coated with zinc chromate.




Privatized Army Lodging                      233113 - 4                               Lend Lease
Alterations for HIE Branding                                  Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                               October 20, 2011
PART 3 - EXECUTION


3.01     DUCT INSTALLATION

   A.    Drawing plans, schematics, and diagrams indicate general location and arrangement of duct
         system. Indicated duct locations, configurations, and arrangements were used to size ducts
         and calculate friction loss for air-handling equipment sizing and for other design considerations.
         Install duct systems as indicated unless deviations to layout are approved on Shop Drawings
         and Coordination Drawings.

   B.    Install ducts according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible"
         unless otherwise indicated.

   C.    Install round ducts in maximum practical lengths.

   D.    Install ducts with fewest possible joints.

   E.    Install factory- or shop-fabricated fittings for changes in direction, size, and shape and for
         branch connections.

   F.    Unless otherwise indicated, install ducts vertically and horizontally, and parallel and
         perpendicular to building lines.

   G.    Install ducts close to walls, overhead construction, columns, and other structural and permanent
         enclosure elements of building.

   H.    Install ducts with a clearance of 1 inch, plus allowance for insulation thickness.

   I.    Route ducts to avoid passing through transformer vaults and electrical equipment rooms and
         enclosures.

   J.    Where ducts pass through non-fire-rated interior partitions and exterior walls and are exposed
         to view, cover the opening between the partition and duct or duct insulation with sheet metal
         flanges of same metal thickness as the duct. Overlap openings on four sides by at least 1-1/2
         inches.

   K.    Where ducts pass through fire-rated interior partitions and exterior walls, install fire dampers.
         Comply with requirements in Division 23 Section "Air Duct Accessories" for fire and smoke
         dampers.


3.02     DUCT SEALING

   A.    Seal ducts for duct static-pressure, seal classes, and leakage classes specified in "Duct
         Schedule" Article according to SMACNA's "HVAC Duct Construction Standards - Metal and
         Flexible."

   B.    Seal ducts to the following seal classes according to SMACNA's "HVAC Duct Construction
         Standards - Metal and Flexible":

         1.    Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."
         2.    Outdoor, Supply-Air Ducts: Seal Class A.
         3.    Outdoor, Exhaust Ducts: Seal Class C.
         4.    Outdoor, Return-Air Ducts: Seal Class C.

Privatized Army Lodging                          233113 - 5                               Lend Lease
Alterations for HIE Branding                                      Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                   October 20, 2011
         5.    Unconditioned Space, Supply-Air Ducts in Pressure Classes 2-Inch wg and Lower: Seal
               Class B.
         6.    Unconditioned Space, Supply-Air Ducts in Pressure Classes Higher Than 2-Inch wg:
               Seal Class A.
         7.    Unconditioned Space, Exhaust Ducts: Seal Class C.
         8.    Unconditioned Space, Return-Air Ducts: Seal Class B.
         9.    Conditioned Space, Supply-Air Ducts in Pressure Classes 2-Inch wg and Lower: Seal
               Class C.
         10.   Conditioned Space, Supply-Air Ducts in Pressure Classes Higher Than 2-Inch wg: Seal
               Class B.
         11.   Conditioned Space, Exhaust Ducts: Seal Class B.
         12.   Conditioned Space, Return-Air Ducts: Seal Class C.


3.03     HANGER AND SUPPORT INSTALLATION

   A.    Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Chapter 5,
         "Hangers and Supports."

   B.    Building Attachments:      Concrete inserts, powder-actuated fasteners, or structural-steel
         fasteners appropriate for construction materials to which hangers are being attached.

         1.    Where practical, install concrete inserts before placing concrete.
         2.    Install powder-actuated concrete fasteners after concrete is placed and completely cured.
         3.    Use powder-actuated concrete fasteners for standard-weight aggregate concretes or for
               slabs more than 4 inches thick.
         4.    Do not use powder-actuated concrete fasteners for lightweight-aggregate concretes or for
               slabs less than 4 inches thick.
         5.    Do not use powder-actuated concrete fasteners for seismic restraints.

   C.    Hanger Spacing: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and
         Flexible," Table 5-1, "Rectangular Duct Hangers Minimum Size," and Table 5-2, "Minimum
         Hanger Sizes for Round Duct," for maximum hanger spacing; install hangers and supports
         within 24 inches of each elbow and within 48 inches of each branch intersection.

   D.    Hangers Exposed to View: Threaded rod and angle or channel supports.

   E.    Support vertical ducts with steel angles or channel secured to the sides of the duct with welds,
         bolts, sheet metal screws, or blind rivets; support at each floor and at a maximum intervals of 16
         feet.

   F.    Install upper attachments to structures. Select and size upper attachments with pull-out,
         tension, and shear capacities appropriate for supported loads and building materials where
         used.


3.04     CONNECTIONS

   A.    Make connections to equipment with flexible connectors complying with Division 23 Section "Air
         Duct Accessories."

   B.    Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for branch,
         outlet and inlet, and terminal unit connections.




Privatized Army Lodging                        233113 - 6                                Lend Lease
Alterations for HIE Branding                                     Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                  October 20, 2011
3.05     DUCT CLEANING

   A.    Clean new duct system(s) before testing, adjusting, and balancing.

   B.    Use service openings for entry and inspection.

         1.    Create new openings and install access panels appropriate for duct static-pressure class
               if required for cleaning access. Provide insulated panels for insulated or lined duct.
               Patch insulation and liner as recommended by duct liner manufacturer. Comply with
               Division 23 Section "Air Duct Accessories" for access panels and doors.
         2.    Disconnect and reconnect flexible ducts as needed for cleaning and inspection.
         3.    Remove and reinstall ceiling to gain access during the cleaning process.

   C.    Particulate Collection and Odor Control:

         1.    When venting vacuuming system inside the building, use HEPA filtration with 99.97
               percent collection efficiency for 0.3-micron-size (or larger) particles.
         2.    When venting vacuuming system to outdoors, use filter to collect debris removed from
               HVAC system, and locate exhaust downwind and away from air intakes and other points
               of entry into building.

   D.    Clean the following components by removing surface contaminants and deposits:

         1.    Air outlets and inlets (registers, grilles, and diffusers).
         2.    Supply, return, and exhaust fans including fan housings, plenums (except ceiling supply
               and return plenums), scrolls, blades or vanes, shafts, baffles, dampers, and drive
               assemblies.
         3.    Air-handling unit internal surfaces and components including mixing box, coil section, air
               wash systems, spray eliminators, condensate drain pans, humidifiers and dehumidifiers,
               filters and filter sections, and condensate collectors and drains.
         4.    Coils and related components.
         5.    Return-air ducts, dampers, actuators, and turning vanes except in ceiling plenums and
               mechanical equipment rooms.
         6.    Supply-air ducts, dampers, actuators, and turning vanes.
         7.    Dedicated exhaust and ventilation components and makeup air systems.

   E.    Mechanical Cleaning Methodology:

         1.    Clean metal duct systems using mechanical cleaning methods that extract contaminants
               from within duct systems and remove contaminants from building.
         2.    Use vacuum-collection devices that are operated continuously during cleaning. Connect
               vacuum device to downstream end of duct sections so areas being cleaned are under
               negative pressure.
         3.    Use mechanical agitation to dislodge debris adhered to interior duct surfaces without
               damaging integrity of metal ducts, duct liner, or duct accessories.
         4.    Clean fibrous-glass duct liner with HEPA vacuuming equipment; do not permit duct liner
               to get wet. Replace fibrous-glass duct liner that is damaged, deteriorated, or delaminated
               or that has friable material, mold, or fungus growth.
         5.    Clean coils and coil drain pans according to NADCA 1992. Keep drain pan operational.
               Rinse coils with clean water to remove latent residues and cleaning materials; comb and
               straighten fins.
         6.    Provide drainage and cleanup for wash-down procedures.
         7.    Antimicrobial Agents and Coatings: Apply EPA-registered antimicrobial agents if fungus
               is present. Apply antimicrobial agents according to manufacturer's written instructions
               after removal of surface deposits and debris.


Privatized Army Lodging                       233113 - 7                               Lend Lease
Alterations for HIE Branding                                   Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                October 20, 2011
3.06     START UP

   A.    Air Balance: Comply with requirements in Division 23 Section "Testing, Adjusting, and
         Balancing for HVAC."


3.07     DUCT SCHEDULE

   A.    Fabricate ducts with galvanized sheet steel as follows:

   B.    Supply Ducts:

         1.    Ducts:

               a.       Pressure Class: Positive or negative 2-inch wg.
               b.       Minimum SMACNA Seal Class: B.
               c.       SMACNA Leakage Class for Rectangular: 12.
               d.       SMACNA Leakage Class for Round and Flat Oval: 6.

   C.    Return Ducts:

         1.    Ducts:

               a.       Pressure Class: Positive or negative 2-inch wg.
               b.       Minimum SMACNA Seal Class: B.
               c.       SMACNA Leakage Class for Rectangular: 12.
               d.       SMACNA Leakage Class for Round and Flat Oval: 6.

   D.    Exhaust Ducts:

         1.    Ducts:

               a.       Pressure Class: Positive or negative 2-inch wg.
               b.       Minimum SMACNA Seal Class: B.
               c.       SMACNA Leakage Class for Rectangular: 12.
               d.       SMACNA Leakage Class for Round and Flat Oval: 6.

   E.    Outdoor-Air Ducts:

         1.    Ducts:

               a.       Pressure Class: Positive or negative 2-inch wg.
               b.       Minimum SMACNA Seal Class: B.
               c.       SMACNA Leakage Class for Rectangular: 12.
               d.       SMACNA Leakage Class for Round and Flat Oval: 6.

   F.    Intermediate Reinforcement:

         1.    Galvanized-Steel Ducts: Galvanized steel or carbon steel coated with zinc-chromate
               primer.

   G.    Elbow Configuration:

         1.    Rectangular Duct: Comply with SMACNA's "HVAC Duct Construction Standards - Metal
               and Flexible," Figure 4-2, "Rectangular Elbows."

Privatized Army Lodging                        233113 - 8                                  Lend Lease
Alterations for HIE Branding                                       Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                    October 20, 2011
               a.     Velocity 1000 fpm or Lower:

                      1)    Radius Type RE 1 with minimum 0.5 radius-to-diameter ratio.
                      2)    Mitered Type RE 4 without vanes.

               b.     Velocity 1000 to 1500 fpm:

                      1)    Radius Type RE 1 with minimum 1.0 radius-to-diameter ratio.
                      2)    Radius Type RE 3 with minimum 0.5 radius-to-diameter ratio and two vanes.
                      3)    Mitered Type RE 2 with vanes complying with SMACNA's "HVAC Duct
                            Construction Standards - Metal and Flexible," Figure 4-3, "Vanes and Vane
                            Runners," and Figure 4-4, "Vane Support in Elbows."

               c.     Velocity 1500 fpm or Higher:

                      1)    Radius Type RE 1 with minimum 1.5 radius-to-diameter ratio.
                      2)    Radius Type RE 3 with minimum 1.0 radius-to-diameter ratio and two vanes.
                      3)    Mitered Type RE 2 with vanes complying with SMACNA's "HVAC Duct
                            Construction Standards - Metal and Flexible," Figure 4-3, "Vanes and Vane
                            Runners," and Figure 4-4, "Vane Support in Elbows."

         2.    Rectangular Duct: Comply with SMACNA's "HVAC Duct Construction Standards - Metal
               and Flexible," Figure 4-2, "Rectangular Elbows."

               a.     Radius Type RE 1 with minimum 1.5 radius-to-diameter ratio.
               b.     Radius Type RE 3 with minimum 1.0 radius-to-diameter ratio and two vanes.
               c.     Mitered Type RE 2 with vanes complying with SMACNA's "HVAC Duct
                      Construction Standards - Metal and Flexible," Figure 4-3, "Vanes and Vane
                      Runners," and Figure 4-4, "Vane Support in Elbows."

         3.    Round Duct: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and
               Flexible," Figure 3-4, "Round Duct Elbows."

               a.     Minimum Radius-to-Diameter Ratio and Elbow Segments:          Comply with
                      SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Table 3-1,
                      "Mitered Elbows." Elbows with less than 90-degree change of direction have
                      proportionately fewer segments.

                      1)    Radius-to Diameter Ratio: 1.5.

               b.     Round Elbows, 12 Inches and Smaller in Diameter: Stamped or pleated.
               c.     Round Elbows, 14 Inches and Larger in Diameter: Standing seam.

   H.    Branch Configuration:

         1.    Rectangular Duct: Comply with SMACNA's "HVAC Duct Construction Standards - Metal
               and Flexible," Figure 4-6, "Branch Connection."

               a.     Rectangular Main to Rectangular Branch: 45-degree entry.
               b.     Rectangular Main to Round Branch: Spin in.

         2.    Round: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and
               Flexible," Figure 3-5, "90 Degree Tees and Laterals," and Figure 3-6, "Conical Tees."
               Saddle taps are permitted in existing duct.

               a.     Velocity 1000 fpm or Lower: 90-degree tap.
Privatized Army Lodging                       233113 - 9                              Lend Lease
Alterations for HIE Branding                                  Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                               October 20, 2011
               b.     Velocity 1000 to 1500 fpm: Conical tap.
               c.     Velocity 1500 fpm or Higher: 45-degree lateral.


                                          END OF SECTION




Privatized Army Lodging                      233113 - 10                               Lend Lease
Alterations for HIE Branding                                   Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                October 20, 2011
                                           SECTION 233300

                                     AIR DUCT ACCESSORIES


PART 1 - GENERAL


1.01     SUMMARY

   A.    Section Includes:

         1.    Manual volume dampers.
         2.    Control dampers.
         3.    Flange connectors.
         4.    Turning vanes.
         5.    Duct-mounted access doors.
         6.    Flexible connectors.
         7.    Flexible ducts.
         8.    Duct accessory hardware.


1.02     SUBMITTALS

   A.    Product Data: For each type of product indicated.

   B.    Operation and maintenance data.


1.03     QUALITY ASSURANCE

   A.    Comply with NFPA 90A, "Installation of Air Conditioning and Ventilating Systems," and with
         NFPA 90B, "Installation of Warm Air Heating and Air Conditioning Systems."

   B.    Comply with AMCA 500-D testing for damper rating.


PART 2 - PRODUCTS


2.01     MATERIALS

   A.    Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for
         acceptable materials, material thicknesses, and duct construction methods unless otherwise
         indicated. Sheet metal materials shall be free of pitting, seam marks, roller marks, stains,
         discolorations, and other imperfections.

   B.    Galvanized Sheet Steel: Comply with ASTM A 653/A 653M.

         1.    Galvanized Coating Designation: G60.
         2.    Exposed-Surface Finish: Mill phosphatized.

   C.    Reinforcement Shapes and Plates:        Galvanized-steel reinforcement where installed on
         galvanized sheet metal ducts; compatible materials for aluminum and stainless-steel ducts.

Privatized Army Lodging                       233300 - 1                             Lend Lease
Alterations for HIE Branding                                 Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                              October 20, 2011
   D.    Tie Rods: Galvanized steel, 1/4-inch minimum diameter for lengths 36 inches or less; 3/8-inch
         minimum diameter for lengths longer than 36 inches.


2.02     MANUAL VOLUME DAMPERS

   A.    Standard, Steel, Manual Volume Dampers:

         1.    Manufacturers: Subject to compliance with requirements, provide products by one of the
               following:

               a.     Air Balance Inc.; a division of Mestek, Inc.
               b.     American Warming and Ventilating; a division of Mestek, Inc.
               c.     Flexmaster U.S.A., Inc.
               d.     McGill AirFlow LLC.
               e.     METALAIRE, Inc.
               f.     Nailor Industries Inc.
               g.     Pottorff; a division of PCI Industries, Inc.
               h.     Ruskin Company.
               i.     Trox USA Inc.
               j.     Vent Products Company, Inc.

         2.    Standard leakage rating.
         3.    Suitable for horizontal or vertical applications.
         4.    Frames:

               a.     Hat-shaped, galvanized-steel channels, 0.064-inch minimum thickness.
               b.     Mitered and welded corners.
               c.     Flanges for attaching to walls and flangeless frames for installing in ducts.

         5.    Blades:

               a.     Multiple or single blade.
               b.     Parallel- or opposed-blade design.
               c.     Stiffen damper blades for stability.
               d.     Galvanized-steel, 0.064 inch thick.

         6.    Blade Axles: Galvanized steel.
         7.    Bearings:

               a.     Oil-impregnated bronze.
               b.     Dampers in ducts with pressure classes of 3-inch wg or less shall have axles full
                      length of damper blades and bearings at both ends of operating shaft.

         8.    Tie Bars and Brackets: Galvanized steel.

   B.    Jackshaft:

         1.    Size: 1-inch diameter.
         2.    Material: Galvanized-steel pipe rotating within pipe-bearing assembly mounted on
               supports at each mullion and at each end of multiple-damper assemblies.
         3.    Length and Number of Mountings: As required to connect linkage of each damper in
               multiple-damper assembly.

   C.    Damper Hardware:

Privatized Army Lodging                         233300 - 2                                 Lend Lease
Alterations for HIE Branding                                       Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                    October 20, 2011
         1.    Zinc-plated, die-cast core with dial and handle made of 3/32-inch- thick zinc-plated steel,
               and a 3/4-inch hexagon locking nut.
         2.    Include center hole to suit damper operating-rod size.
         3.    Include elevated platform for insulated duct mounting.


2.03     CONTROL DAMPERS

   A.    Manufacturers:   Subject to compliance with requirements, provide products by one of the
         following:

         1.    American Warming and Ventilating; a division of Mestek, Inc.
         2.    Arrow United Industries; a division of Mestek, Inc.
         3.    Cesco Products; a division of Mestek, Inc.
         4.    Duro Dyne Inc.
         5.    Flexmaster U.S.A., Inc.
         6.    Greenheck Fan Corporation.
         7.    Lloyd Industries, Inc.
         8.    M&I Air Systems Engineering; Division of M&I Heat Transfer Products Ltd.
         9.    McGill AirFlow LLC.
         10.   METALAIRE, Inc.
         11.   Metal Form Manufacturing, Inc.
         12.   Nailor Industries Inc.
         13.   NCA Manufacturing, Inc.
         14.   Ruskin Company.
         15.   Vent Products Company, Inc.
         16.   Young Regulator Company.

   B.    Frames:

         1.    Hat shaped.
         2.    Galvanized-steel channels, 0.064 inch thick.
         3.    Mitered and welded corners.

   C.    Blades:

         1.    Multiple blade with maximum blade width of 8 inches.
         2.    Opposed-blade design.
         3.    Galvanized steel.
         4.    0.064 inch thick.
         5.    Blade Edging: Closed-cell neoprene edging.
         6.    Blade Edging: Inflatable seal blade edging, or replaceable rubber seals.

   D.    Blade Axles: 1/2-inch- diameter; galvanized steel; blade-linkage hardware of zinc-plated steel
         and brass; ends sealed against blade bearings.

         1.    Operating Temperature Range: From minus 40 to plus 200 deg F.

   E.    Bearings:

         1.    Oil-impregnated bronze.
         2.    Dampers in ducts with pressure classes of 3-inch wg or less shall have axles full length of
               damper blades and bearings at both ends of operating shaft.
         3.    Thrust bearings at each end of every blade.



Privatized Army Lodging                       233300 - 3                                Lend Lease
Alterations for HIE Branding                                    Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                 October 20, 2011
2.04     FLANGE CONNECTORS

   A.    Manufacturers: Subject to compliance with requirements, available manufacturers offering
         products that may be incorporated into the Work include, but are not limited to, the following:

         1.    Ductmate Industries, Inc.
         2.    Nexus PDQ; Division of Shilco Holdings Inc.
         3.    Ward Industries, Inc.; a division of Hart & Cooley, Inc.

   B.    Description: Add-on or roll-formed, factory-fabricated, slide-on transverse flange connectors,
         gaskets, and components.

   C.    Material: Galvanized steel.

   D.    Gage and Shape: Match connecting ductwork.


2.05     TURNING VANES

   A.    Manufacturers:   Subject to compliance with requirements, provide products by one of the
         following:

         1.    Ductmate Industries, Inc.
         2.    Duro Dyne Inc.
         3.    METALAIRE, Inc.
         4.    SEMCO Incorporated.
         5.    Ward Industries, Inc.; a division of Hart & Cooley, Inc.

   B.    Manufactured Turning Vanes for Metal Ducts: Curved blades of galvanized sheet steel; support
         with bars perpendicular to blades set; set into vane runners suitable for duct mounting.

         1.    Acoustic Turning Vanes: Fabricate airfoil-shaped aluminum extrusions with perforated
               faces and fibrous-glass fill.

   C.    Manufactured Turning Vanes for Nonmetal Ducts: Fabricate curved blades of resin-bonded
         fiberglass with acrylic polymer coating; support with bars perpendicular to blades set; set into
         vane runners suitable for duct mounting.

   D.    General Requirements: Comply with SMACNA's "HVAC Duct Construction Standards - Metal
         and Flexible"; Figures 4-3, "Vanes and Vane Runners," and 4-4, "Vane Support in Elbows."

   E.    Vane Construction: Single wall.

   F.    Vane Construction:    Single wall for ducts up to 48 inches wide and double wall for larger
         dimensions.


2.06     DUCT-MOUNTED ACCESS DOORS

   A.    Manufacturers:   Subject to compliance with requirements, provide products by one of the
         following:

         1.    American Warming and Ventilating; a division of Mestek, Inc.
         2.    Cesco Products; a division of Mestek, Inc.
         3.    Ductmate Industries, Inc.

Privatized Army Lodging                        233300 - 4                                Lend Lease
Alterations for HIE Branding                                     Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                  October 20, 2011
         4.    Flexmaster U.S.A., Inc.
         5.    Greenheck Fan Corporation.
         6.    McGill AirFlow LLC.
         7.    Nailor Industries Inc.
         8.    Pottorff; a division of PCI Industries, Inc.
         9.    Ventfabrics, Inc.
         10.   Ward Industries, Inc.; a division of Hart & Cooley, Inc.

   B.    Duct-Mounted Access Doors: Fabricate access panels according to SMACNA's "HVAC Duct
         Construction Standards - Metal and Flexible"; Figures 7-2, "Duct Access Doors and Panels,"
         and 7-3, "Access Doors - Round Duct."

         1.    Door:

               a.      Double wall, rectangular.
               b.      Galvanized sheet metal with insulation fill and thickness as indicated for duct
                       pressure class.
               c.      Vision panel.
               d.      Hinges and Latches: 1-by-1-inch butt or piano hinge and cam latches.
               e.      Fabricate doors airtight and suitable for duct pressure class.

         2.    Frame: Galvanized sheet steel, with bend-over tabs and foam gaskets.
         3.    Number of Hinges and Locks:

               a.      Access Doors Less Than 12 Inches Square: No hinges and two sash locks.
               b.      Access Doors up to 18 Inches Square: Two hinges and two sash locks.
               c.      Access Doors up to 24 by 48 Inches: Three hinges and two compression latches.
               d.      Access Doors Larger Than 24 by 48 Inches: Four hinges and two compression
                       latches with outside and inside handles.


2.07     FLEXIBLE CONNECTORS

   A.    Manufacturers: Subject to compliance with requirements, available manufacturers offering
         products that may be incorporated into the Work include, but are not limited to, the following:

         1.    Ductmate Industries, Inc.
         2.    Duro Dyne Inc.
         3.    Ventfabrics, Inc.
         4.    Ward Industries, Inc.; a division of Hart & Cooley, Inc.

   B.    Materials: Flame-retardant or noncombustible fabrics.

   C.    Coatings and Adhesives: Comply with UL 181, Class 1.

   D.    Metal-Edged Connectors: Factory fabricated with a fabric strip 3-1/2 inches wide attached to 2
         strips of 2-3/4-inch- wide, 0.028-inch- thick, galvanized sheet steel or 0.032-inch- thick
         aluminum sheets. Provide metal compatible with connected ducts.

   E.    Indoor System, Flexible Connector Fabric: Glass fabric double coated with neoprene.

         1.    Minimum Weight: 26 oz./sq. yd..
         2.    Tensile Strength: 480 lbf/inch in the warp and 360 lbf/inch in the filling.
         3.    Service Temperature: Minus 40 to plus 200 deg F.


Privatized Army Lodging                         233300 - 5                                Lend Lease
Alterations for HIE Branding                                      Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                   October 20, 2011
   F.    Thrust Limits: Combination coil spring and elastomeric insert with spring and insert in
         compression, and with a load stop. Include rod and angle-iron brackets for attaching to fan
         discharge and duct.

         1.    Frame: Steel, fabricated for connection to threaded rods and to allow for a maximum of
               30 degrees of angular rod misalignment without binding or reducing isolation efficiency.
         2.    Outdoor Spring Diameter: Not less than 80 percent of the compressed height of the
               spring at rated load.
         3.    Minimum Additional Travel: 50 percent of the required deflection at rated load.
         4.    Lateral Stiffness: More than 80 percent of rated vertical stiffness.
         5.    Overload Capacity: Support 200 percent of rated load, fully compressed, without
               deformation or failure.
         6.    Elastomeric Element: Molded, oil-resistant rubber or neoprene.
         7.    Coil Spring: Factory set and field adjustable for a maximum of 1/4-inch movement at
               start and stop.


2.08     FLEXIBLE DUCTS

   A.    Manufacturers: Subject to compliance with requirements, available manufacturers offering
         products that may be incorporated into the Work include, but are not limited to, the following:

         1.    Flexmaster U.S.A., Inc.
         2.    McGill AirFlow LLC.
         3.    Ward Industries, Inc.; a division of Hart & Cooley, Inc.

   B.    Insulated, Flexible Duct: UL 181, Class 1, multiple layers of aluminum laminate supported by
         helically wound, spring-steel wire; fibrous-glass insulation; polyethylene vapor-barrier film.

         1.    Pressure Rating: 10-inch wg positive and 1.0-inch wg negative.
         2.    Maximum Air Velocity: 4000 fpm.
         3.    Temperature Range: Minus 20 to plus 210 deg F.
         4.    Insulation R-value: 4.2.

   C.    Flexible Duct Connectors:

         1.    Clamps: Nylon strap in sizes 3 through 18 inches, to suit duct size.


2.09     DUCT ACCESSORY HARDWARE

   A.    Instrument Test Holes: Cast iron or cast aluminum to suit duct material, including screw cap
         and gasket. Size to allow insertion of pitot tube and other testing instruments and of length to
         suit duct-insulation thickness.

   B.    Adhesives: High strength, quick setting, neoprene based, waterproof, and resistant to gasoline
         and grease.




Privatized Army Lodging                        233300 - 6                                Lend Lease
Alterations for HIE Branding                                     Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                  October 20, 2011
PART 3 - EXECUTION


3.01     INSTALLATION

   A.    Install duct accessories according to applicable details in SMACNA's "HVAC Duct Construction
         Standards - Metal and Flexible."

   B.    Install duct accessories of materials suited to duct materials; use galvanized-steel accessories
         in galvanized-steel, stainless-steel accessories in stainless-steel ducts, and aluminum
         accessories in aluminum ducts.

   C.    Install backdraft dampers at inlet of exhaust fans or exhaust ducts as close as possible to
         exhaust fan unless otherwise indicated.

   D.    Install volume dampers at points on supply, return, and exhaust systems where branches
         extend from larger ducts. Where dampers are installed in ducts having duct liner, install
         dampers with hat channels of same depth as liner, and terminate liner with nosing at hat
         channel.

         1.    Install steel volume dampers in steel ducts.
         2.    Install aluminum volume dampers in aluminum ducts.

   E.    Set dampers to fully open position before testing, adjusting, and balancing.

   F.    Install test holes at fan inlets and outlets and elsewhere as indicated.

   G.    Install duct access doors on sides of ducts to allow for inspecting, adjusting, and maintaining
         accessories and equipment at the following locations:

         1.    On both sides of duct coils.
         2.    At outdoor-air intakes and mixed-air plenums.
         3.    At drain pans and seals.
         4.    Downstream from manual volume dampers, control dampers, backdraft dampers, and
               equipment.
         5.    Adjacent to and close enough to fire or smoke dampers, to reset or reinstall fusible links.
               Access doors for access to fire or smoke dampers having fusible links shall be pressure
               relief access doors; and shall be outward operation for access doors installed upstream
               from dampers and inward operation for access doors installed downstream from
               dampers.
         6.    At each change in direction and at maximum 50-foot spacing.
         7.    Upstream from turning vanes.
         8.    Control devices requiring inspection.
         9.    Elsewhere as indicated.

   H.    Install access doors with swing against duct static pressure.

   I.    Access Door Sizes:

         1.    One-Hand or Inspection Access: 8 by 5 inches.
         2.    Two-Hand Access: 12 by 6 inches.
         3.    Head and Hand Access: 18 by 10 inches.
         4.    Head and Shoulders Access: 21 by 14 inches.
         5.    Body Access: 25 by 14 inches.
         6.    Body plus Ladder Access: 25 by 17 inches.

Privatized Army Lodging                         233300 - 7                                Lend Lease
Alterations for HIE Branding                                      Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                   October 20, 2011
   J.    Label access doors according to Division 23 Section "Identification for HVAC Piping and
         Equipment" to indicate the purpose of access door.

   K.    Install flexible connectors to connect ducts to equipment.

   L.    For fans developing static pressures of 5-inch wg and more, cover flexible connectors with
         loaded vinyl sheet held in place with metal straps.

   M.    Connect flexible ducts to metal ducts with draw bands.

   N.    Install duct test holes where required for testing and balancing purposes.

   O.    Install thrust limits at centerline of thrust, symmetrical on both sides of equipment. Attach thrust
         limits at centerline of thrust and adjust to a maximum of 1/4-inch movement during start and
         stop of fans.


3.02     FIELD QUALITY CONTROL

   A.    Tests and Inspections:

         1.    Operate dampers to verify full range of movement.
         2.    Inspect locations of access doors and verify that purpose of access door can be
               performed.
         3.    Operate fire and smoke dampers to verify full range of movement and verify that proper
               heat-response device is installed.
         4.    Inspect turning vanes for proper and secure installation.


                                           END OF SECTION




Privatized Army Lodging                         233300 - 8                                Lend Lease
Alterations for HIE Branding                                      Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                   October 20, 2011
                                           SECTION 233423

                                     HVAC POWER VENTILATORS


PART 1 - GENERAL


1.01     SUMMARY

   A.    Section Includes:

         1.    Ceiling-mounted ventilators.
         2.    Energy recovery ventilators.


1.02     SUBMITTALS

   A.    Product Data: For each type of product indicated.

   B.    Operation and maintenance data.


1.03     QUALITY ASSURANCE

   A.    Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
         by a qualified testing agency, and marked for intended location and application.

   B.    AMCA Compliance: Fans shall have AMCA-Certified performance ratings and shall bear the
         AMCA-Certified Ratings Seal.


PART 2 - PRODUCTS


2.01     CEILING-MOUNTED VENTILATORS

   A.    Manufacturers:      Subject to compliance with requirements, provide products by one of the
         following:

         1.    American Coolair Corporation.
         2.    Ammerman; Millennium Equipment.
         3.    Breidert Air Products.
         4.    Broan-NuTone LLC.
         5.    Broan-NuTone LLC; NuTone Inc.
         6.    Carnes Company.
         7.    FloAire.
         8.    Greenheck Fan Corporation.
         9.    JencoFan.
         10.   Loren Cook Company.
         11.   PennBarry.
         12.   W.W. Grainger, Inc.; Dayton Products.

   B.    Performance: Refer to schedules.

Privatized Army Lodging                        233423 - 1                             Lend Lease
Alterations for HIE Branding                                  Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                               October 20, 2011
   C.    Accessories:

         1.    Variable-Speed Controller: Solid-state control to reduce speed from 100 to less than 50
               percent mounted inside unit for balancing.
         2.    Isolation: Rubber-in-shear vibration isolators.
         3.    Manufacturer's standard roof jack or wall cap, and transition fittings where scheduled.


2.02     ENERGY RECOVERY VENTILATORS

   A.    Manufacturers:   Subject to compliance with requirements, provide products by one of the
         following:

         1.    American Coolair Corporation.
         2.    Ammerman; Millennium Equipment.
         3.    Breidert Air Products.
         4.    Broan-NuTone LLC.
         5.    Broan-NuTone LLC; NuTone Inc.
         6.    Carnes Company.
         7.    FloAire.
         8.    Greenheck Fan Corporation.
         9.    JencoFan.
         10.   Loren Cook Company.
         11.   PennBarry.
         12.   W.W. Grainger, Inc.; Dayton Products.

   B.    Performance: Refer to schedules.

   C.    Accessories:

         1.    Unit Mounted Variable-Speed Controller for both fans: Solid-state control to reduce
               speed from 100 to less than 50 percent mounted inside unit for balancing.
         2.    Carbon dioxide sensor: Carbon dioxide sensor shall display the CO2 concentration in
               ppm and the setpoint shall be field adjustable.
         3.    Isolation: Rubber-in-shear vibration isolators.
         4.    Filter: Two sets per airstream. Filters shall be 1” deep, 30% effective disposable filters.


PART 3 - EXECUTION


3.01     INSTALLATION

   A.    Support suspended units from structure using threaded steel rods and elastomeric hangers
         having a static deflection of 1 inch.

   B.    Install units with clearances for service and maintenance.


3.02     CONNECTIONS

   A.    Duct installation and connection requirements are specified in other Division 23 Sections.
         Drawings indicate general arrangement of ducts and duct accessories. Make final duct
         connections with flexible connectors. Flexible connectors are specified in Division 23 Section
         "Air Duct Accessories."

Privatized Army Lodging                        233423 - 2                               Lend Lease
Alterations for HIE Branding                                    Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                 October 20, 2011
   B.    Install ducts adjacent to power ventilators to allow service and maintenance.

   C.    Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical
         Systems."

   D.    Connect wiring according to Division 26 Section "Low-Voltage Electrical Power Conductors and
         Cables."


3.03     FIELD QUALITY CONTROL

   A.    Tests and Inspections:

         1.    Verify that shipping, blocking, and bracing are removed.
         2.    Verify that unit is secure on mountings and supporting devices and that connections to
               ducts and electrical components are complete. Verify that proper thermal-overload
               protection is installed in motors, starters, and disconnect switches.
         3.    Verify that cleaning and adjusting are complete.
         4.    Disconnect fan drive from motor, verify proper motor rotation direction, and verify fan
               wheel free rotation and smooth bearing operation. Reconnect fan drive system, align and
               adjust belts, and install belt guards.
         5.    Adjust damper linkages for proper damper operation.
         6.    Verify lubrication for bearings and other moving parts.
         7.    Disable automatic temperature-control operators, energize motor and adjust fan to
               indicated rpm, and measure and record motor voltage and amperage.
         8.    Shut unit down and reconnect automatic temperature-control operators.
         9.    Remove and replace malfunctioning units and retest as specified above.

   B.    Test and adjust controls and safeties.     Replace damaged and malfunctioning controls and
         equipment.

   C.    Prepare test and inspection reports.


3.04     ADJUSTING

   A.    Comply with requirements in Division 23 Section "Testing, Adjusting, and Balancing for HVAC"
         for testing, adjusting, and balancing procedures.


                                          END OF SECTION




Privatized Army Lodging                         233423 - 3                              Lend Lease
Alterations for HIE Branding                                    Rev 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                 October 20, 2011
                                           SECTION 233713

                                DIFFUSERS, REGISTERS, AND GRILLES


PART 1 - GENERAL


1.01     SUMMARY

   A.    Section Includes:

         1.    Air terminals.

   B.    Related Sections:

         1.    Division 08 Section "Louvers and Vents" for fixed and adjustable louvers and wall vents,
               whether or not they are connected to ducts.
         2.    Division 23 Section "Air Duct Accessories" for fire and smoke dampers and volume-
               control dampers not integral to diffusers, registers, and grilles.


1.02     SUBMITTALS

   A.    Product Data: For each type of product indicated, include the following:

         1.    Data Sheet: Indicate materials of construction, finish, and mounting details; and
               performance data including throw and drop, static-pressure drop, and noise ratings.
         2.    Diffuser, Register, and Grille Schedule: Indicate drawing designation, room location,
               quantity, model number, size, and accessories furnished.


PART 2 - PRODUCTS


2.01     AIR TERMINALS

   A.    Supply, return, transfer and exhaust:

         1.    Manufacturers: Subject to compliance with requirements, available manufacturers
               offering products that may be incorporated into the Work include, but are not limited to,
               the following:

               a.     A-J Manufacturing Co., Inc.
               b.     Anemostat Products; a Mestek company.
               c.     Carnes.
               d.     Hart & Cooley Inc.
               e.     Krueger.
               f.     METALAIRE, Inc.
               g.     Nailor Industries Inc.
               h.     Price Industries.
               i.     Titus.
               j.     Tuttle & Bailey.

         2.    Refer to schedule on the plans for Basis of design.

Privatized Army Lodging                          233713 - 1                                 Lend Lease
Alterations for HIE Branding                                         REV 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                    October 20, 2011
PART 3 - EXECUTION


3.01     INSTALLATION

   A.    Install diffusers, registers, and grilles level and plumb.

   B.    Ceiling-Mounted Outlets and Inlets: Drawings indicate general arrangement of ducts, fittings,
         and accessories. Air outlet and inlet locations have been indicated to achieve design
         requirements for air volume, noise criteria, airflow pattern, throw, and pressure drop. Make final
         locations where indicated, as much as practical. For units installed in lay-in ceiling panels,
         locate units in the center of panel. Where architectural features or other items conflict with
         installation, notify Architect for a determination of final location.

   C.    Install diffusers, registers, and grilles with airtight connections to ducts and to allow service and
         maintenance of dampers, and air extractors.


3.02     ADJUSTING

   A.    After installation, adjust diffusers, registers, and grilles to air patterns indicated, or as directed,
         before starting air balancing.


                                             END OF SECTION




Privatized Army Lodging                          233713 - 2                                        Lend Lease
Alterations for HIE Branding                                           REV 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                           October 20, 2011
                                             SECTION 238146

                              WATER-SOURCE UNITARY HEAT PUMPS


PART 1 - GENERAL


1.01     RELATED DOCUMENTS

   A.    Drawings and general provisions of the Contract, including General and Supplementary
         Conditions and Division 01 Specification Sections, apply to this Section.


1.02     SUMMARY

   A.    This Section includes the following types of water-source heat pumps:

         1.    Exposed, floor-mounted console units.
         2.    Horizontal concealed units.


1.03     ACTION SUBMITTALS

   A.    Product Data: Include rated capacities, furnished specialties, and accessories for each model.
         Color for console units.

   B.    Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads,
         required clearances, method of field assembly, components, and location and size of each field
         connection.

         1.    Wiring Diagrams: Power, signal, and control wiring.


1.04     INFORMATIONAL SUBMITTALS

   A.    Product Certificates:     For each type of water-source heat pump, signed by product
         manufacturer.

   B.    Warranty: Special warranty specified in this Section.


1.05     CLOSEOUT SUBMITTALS

   A.    Operation and Maintenance Data: For water-source heat pumps to include in emergency,
         operation, and maintenance manuals.


1.06     MAINTENANCE MATERIAL SUBMITTALS

   A.    Furnish extra materials described below that match products installed and that are packaged
         with protective covering for storage and identified with labels describing contents.

         1.    One set(s) of filters for each unit.


Privatized Army Lodging                          238146 - 1                                Lend Lease
Alterations for HIE Branding                                         REV 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                   October 20, 2011
1.07     QUALITY ASSURANCE

   A.    Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
         Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
         intended use.

   B.    Comply with NFPA 70.

   C.    Comply with safety requirements in UL 484 for assembly of free-delivery water-source heat
         pumps.

   D.    Comply with safety requirements in UL 1995 for duct-system connections.


1.08     COORDINATION

   A.    Coordinate layout and installation of water-source heat pumps and suspension components
         with other construction that penetrates ceilings or is supported by them, including light fixtures,
         HVAC equipment, fire-suppression system components, and partition assemblies.


1.09     WARRANTY

   A.    Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or
         replace components of water-source heat pumps that fail in materials or workmanship within
         specified warranty period.

         1.    Failures include, but are not limited to, refrigeration components.
         2.    Warranty Period: Five years from date of Substantial Completion.


PART 2 - PRODUCTS


2.01     MANUFACTURERS

   A.    In other Part 2 articles where titles below introduce lists, the following requirements apply to
         product selection:

         1.    Manufacturers: Subject to compliance with requirements, provide products by one of the
               manufacturers specified.


2.02     EXPOSED, CONSOLE WATER-SOURCE HEAT PUMPS

   A.    Available Manufacturers:

         1.    ClimateMaster, Inc.
         2.    Carrier.

   B.    Description: Packaged water-source heat pump with temperature controls; factory assembled,
         tested, and rated according to ARI-ISO-13256-1.

   C.    Cabinet and Chassis: Manufacturer's standard-height, extended galvanized-steel casing with
         the following features:


Privatized Army Lodging                        238146 - 2                                      Lend Lease
Alterations for HIE Branding                                         REV 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                       October 20, 2011
         1.    Access panel for access and maintenance of internal components.
         2.    Knockouts for electrical and piping connections.
         3.    Cabinet Insulation: Glass-fiber liner, 1/2 inch thick, complying with UL 181.
         4.    Condensate Drainage: Plastic or stainless-steel drain pan with condensate drain piping
               projecting to unit exterior and complying with ASHRAE 62.1.
         5.    Discharge Grille: Steel, aluminum, or plastic grille for adjustable discharge air pattern.
         6.    Color: Selected by Architect from manufacturer's standard color selection.
         7.    Airstream Surfaces:        Surfaces in contact with the airstream shall comply with
               requirements in ASHRAE 62.1.
         8.    Sound Attenuation Package: Provide one or more of the following.

               a.     Minimum 0.598-inch- thick compressor enclosure and front panel. Minimum
                      0.0937-inch thick foam gasket around the compressor and perimeter of end panel.

   D.    Fan: Direct driven, centrifugal, with multispeed motor mounted on a removable fan-motor
         board.

         1.    Motor: Multispeed, permanently lubricated, permanent split capacitor.

   E.    Water Circuit:

         1.    Refrigerant-to-Water Heat Exchanger: Coaxial heat exchanger with copper water tube
               with enhanced heat-transfer surfaces inside a steel shell; both shell and tube leak tested
               to 450 psig for refrigerant side and 400 psig for water side. Mount heat exchanger in unit
               on resilient rubber vibration isolators.

   F.    Refrigerant-to-Air Coils: Copper tubes with aluminum fins, leak tested to 450 psig.

   G.    Refrigerant Circuit Components:

         1.    Sealed Refrigerant Circuit: Charge with R-407C or R-410A refrigerant.
         2.    Charging Connections: Service fittings on suction and liquid for charging and testing.
         3.    Reversing Valve: Pilot-operated sliding-type valve designed to be fail-safe in heating
               position with replaceable magnetic coil.
         4.    Compressor: Hermetic rotary compressor installed on vibration isolators housed in an
               acoustically treated enclosure with factory-installed safeties as follows:

               a.     Antirecycle timer.
               b.     High-pressure cutout.
               c.     Low-pressure cutout or loss of charge switch.
               d.     Internal thermal-overload protection.
               e.     Freezestat to stop compressor if water-loop temperature in refrigerant-to-water
                      heat exchanger falls below 35 deg F.
               f.     Condensate overflow switch to stop compressor with high condensate level in
                      condensate drain pan.

         5.    Refrigerant Piping Materials: ASTM B 743 copper tube with wrought-copper fittings and
               brazed joints.
         6.    Pipe Insulation: Refrigerant minimum 3/8-inch- thick, flexible elastomeric insulation on
               piping exposed to airflow through the unit. Maximum 25/50 flame-spread/smoke-
               development indexes per ASTM E 84.
         7.    Refrigerant Metering Device:

               a.     Capillary tube.




Privatized Army Lodging                        238146 - 3                                      Lend Lease
Alterations for HIE Branding                                        REV 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                      October 20, 2011
  H.    Filters: Disposable, glass-fiber, flat type, 1 inch thick, treated with adhesive, and having a
        minimum of 80 percent arrestance according to ASHRAE 52.1 and a minimum efficiency
        reporting value of 5 according to ASHRAE 52.2.

  I.    Controls for HP-1 thru HP-6:

        1.    Thermostat shall be ClimateMaster ATA11U01.

  J.    Controls for HP-8 thru HP-27:

        1.    Thermostat shall be Honeywell YTH5320R1000.

  K.    Electrical Connection: Single electrical connection with fused disconnect.


2.03    CONCEALED WATER-SOURCE HEAT PUMPS

  A.    Available manufacturers:

        1.    ClimateMaster, Inc.
        2.    Carrier.

  B.    Description: Packaged water-source heat pump with temperature controls; factory assembled,
        tested, and rated according to ASHRAE/ARI/ISO-13256-1.

        1.    Electrical Components, Devices, and Accessories: Listed and labeled as defined in
              NFPA 70, by a testing agency acceptable to authorities having jurisdiction, and marked
              for intended location and application.

  C.    Cabinet and Chassis: Galvanized-steel casing with the following features:

        1.    Access panel for access and maintenance of internal components.
        2.    Knockouts for electrical and piping connections.
        3.    Flanged duct connections.
        4.    Cabinet Insulation: Glass-fiber liner, minimum 1/2 inch thick, complying with UL 181,
              ASTM C 1071, and ASTM G 21.
        5.    Units field convertible for various discharge configurations.
        6.    Condensate Drainage: High-density polyethylene plastic or stainless-steel drain pan with
              condensate drain piping projecting through unit cabinet.

              a.     Condensate Overflow Protection Switch: Solid state electronic; mechanical float
                     switch not permitted.

        7.    Airstream Surfaces:   Surfaces in contact with the airstream shall comply with
              requirements in ASHRAE 62.1.
        8.    Sound Attenuation Package: Provide one or more of the following:

              a.     Minimum 0.598-inch- thick compressor enclosure and front panel. Minimum
                     0.0937-inch- thick foam gasket around the compressor and perimeter of end panel.
              b.     Sound attenuating blanket over compressor.
              c.     Hot-gas muffler.

  D.    Fan: Direct driven, centrifugal, with multispeed motor resiliently mounted in fan inlet and with
        inlet rings to allow wheel removal from one side without removing housing.

        1.       General requirements for motors are specified in Section 230513 "Common Motor
                 Requirements for HVAC Equipment."
Privatized Army Lodging                     238146 - 4                                Lend Lease
Alterations for HIE Branding                                   REV 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                               October 20, 2011
         2.    Motor: Multispeed, permanently lubricated, permanent split capacitor motor.

   E.    Water Circuit:

         1.    Refrigerant-to-Water Heat Exchangers:

               a.     Coaxial heat exchangers with copper water tube with enhanced heat-transfer
                      surfaces inside a steel shell; both shell and tube are leak tested to 450 psig on
                      refrigerant side and 400 psig on water side. Factory mount heat exchanger in unit
                      on resilient rubber vibration isolators.

   F.    Refrigerant-to-Air Coils: Copper tubes with aluminum fins, leak tested to 450 psig.

   G.    Refrigerant Circuit Components:

         1.    Sealed Refrigerant Circuit: Charge with R-410A refrigerant.
         2.    Charging Connections: Service fittings on suction and liquid for charging and testing on
               each circuit.
         3.    Reversing Valve: Four-way, solenoid-activated valve designed to be fail-safe in heating
               position with replaceable magnetic coil.
         4.    Compressor: Hermetic, single-stage compressor installed on vibration isolators and
               housed in an acoustically treated enclosure with factory-installed safeties as follows:

               a.     Antirecycle timer.
               b.     High-pressure cutout.
               c.     Low-pressure cutout or loss of charge switch.
               d.     Internal thermal-overload protection.
               e.     Freezestat to stop compressor if water-loop temperature in refrigerant-to-water
                      heat exchanger falls below 35 deg F.
               f.     Condensate overflow switch to stop compressor with high condensate level in
                      condensate drain pan.

         5.    Refrigerant Piping Materials: ASTM B 743 copper tube with wrought-copper fittings and
               brazed joints.
         6.    Pipe Insulation: Refrigerant minimum 3/8-inch- thick, flexible elastomeric insulation on
               piping exposed to airflow through the unit. Maximum 25/50 flame-spread/smoke-
               developed indexes according to ASTM E 84.
         7.    Refrigerant Metering Device: Thermal-expansion valve.

   H.    Filters: Disposable, glass-fiber, flat type, 1 inch thick, treated with adhesive, and having a
         minimum efficiency reporting value of 5 according to ASHRAE 52.2.

   I.    Controls for HP-7:

         1.    Thermostat shall be ClimateMaster ATA11U01.

   J.    Electrical Connection: Single electrical connection.


2.04     HOSE KITS

   A.    General: Hose kits shall be designed for minimum 400 psig working pressure, and operating
         temperatures from 33 to 211 deg F. Tag hose kits to equipment designations.

   B.    Hose: Length 24 inches. Minimum diameter, equal to water-source heat-pump connection
         size.

Privatized Army Lodging                        238146 - 5                                      Lend Lease
Alterations for HIE Branding                                        REV 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                      October 20, 2011
   C.    Isolation Valves: Two-piece bronze-body ball valves with stainless-steel ball and stem and
         galvanized-steel lever handle. Provide valve for supply and return. If balancing device is
         combination shutoff type with memory stop, the isolation valve may be omitted on the return.

   D.    Strainer: Y-type with blowdown valve in supply connection.

   E.    Balancing Device: Mount in return connection. Include meter ports to allow flow measurement
         with differential pressure gage.

         1.    Manual, venturi-type balancing valve.


2.05     THERMOSTATS FOR HEAT PUMPS IN GUEST ROOMS

   A.    Controls for existing heat pumps in guestroom suites:

         1.    Thermostat shall be Honeywell YTH5320R1000.


PART 3 - EXECUTION


3.01     EXAMINATION

   A.    Examine areas and conditions for compliance with requirements for installation tolerances and
         other conditions affecting performance of water-source heat pumps.

   B.    Examine roughing-in for piping and electric installations for water-source heat pumps to verify
         actual locations of piping connections and electrical conduit before installation.

   C.    Proceed with installation only after unsatisfactory conditions have been corrected.


3.02     INSTALLATION

   A.    Equipment Mounting: Install console type water-source heat pumps using elastomeric pads.

         1.    Minimum Deflection: 1/4 inch.

   B.    Equipment Mounting: Install water-source heat pumps with continuous-thread hanger rods and
         spring hangers of size required to support weight of water-source heat pump unit.

         1.    Comply with requirements for hangers and supports specified in Section 230529
               "Hangers and Supports for HVAC Piping and Equipment."


3.03     CONNECTIONS

   A.    Drawings indicate general arrangement of piping, fittings, and specialties. Specific connection
         requirements are as follows:

         1.    Connect supply and return hydronic piping to heat pump with hose kits.
         2.    Connect heat-pump condensate drain pan to indirect waste connection with condensate
               trap of adequate depth to seal against the pressure of fan. Install cleanouts in piping at
               changes of direction.


Privatized Army Lodging                        238146 - 6                                      Lend Lease
Alterations for HIE Branding                                        REV 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                      October 20, 2011
   B.    Duct installation requirements are specified in other Sections. Drawings indicate general
         arrangement of ducts. Specific connection requirements are as follows:

         1.    Connect supply and return ducts to water-source heat pumps with flexible duct
               connectors specified in Section 233300 "Air Duct Accessories."

   C.    Install electrical devices furnished by manufacturer but not specified to be factory mounted.

   D.    Install piping adjacent to machine to allow service and maintenance.

   E.    Ground equipment according to Section 260526 "Grounding and Bonding for Electrical
         Systems."

   F.    Connect wiring according to Section 260519 "Low-Voltage Electrical Power Conductors and
         Cables."


3.04     FIELD QUALITY CONTROL

   A.    Perform the following field tests and inspections and prepare test reports:

         1.    After installing water-source heat pumps and after electrical circuitry has been energized,
               test units for compliance with requirements.
         2.    Inspect for and remove shipping bolts, blocks, and tie-down straps.
         3.    Operational Test: After electrical circuitry has been energized, start units to confirm
               proper motor rotation and unit operation.
         4.    Test and adjust controls and safeties. Replace damaged and malfunctioning controls
               and equipment.

   B.    Remove and replace malfunctioning units and retest as specified above.


3.05     STARTUP SERVICE

   A.    Complete installation and startup checks according to manufacturer's written instructions and do
         the following:

         1.    Inspect for visible damage to unit casing.
         2.    Inspect for visible damage to compressor, coils, and fans.
         3.    Inspect internal insulation.
         4.    Verify that labels are clearly visible.
         5.    Verify that clearances have been provided for servicing.
         6.    Verify that controls are connected and operable.
         7.    Verify that filters are installed.
         8.    Adjust vibration isolators.
         9.    Inspect operation of barometric dampers.
         10.   Verify bearing lubrication on fan.
         11.   Inspect fan-wheel rotation for movement in correct direction without vibration and binding.
         12.   Start unit according to manufacturer's written instructions.
         13.   Complete startup sheets and attach copy with Contractor's startup report.
         14.   Inspect and record performance of interlocks and protective devices; verify sequences.
         15.   Operate unit for an initial period as recommended or required by manufacturer.
         16.   Verify thermostat calibration.
         17.   Inspect controls for correct sequencing of heating, mixing dampers, refrigeration, and
               normal and emergency shutdown.


Privatized Army Lodging                        238146 - 7                                      Lend Lease
Alterations for HIE Branding                                        REV 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                       October 20, 2011
3.06     ADJUSTING

   A.    Adjust initial temperature set points.

   B.    Set field-adjustable switches and circuit-breaker trip ranges as indicated.


3.07     CLEANING

   A.    Replace filters used during construction prior to air balance or substantial completion.

   B.    After completing installation of exposed, factory-finished water-source heat pumps, inspect
         exposed finishes and repair damaged finishes.


3.08     DEMONSTRATION

   A.    Engage a factory-authorized service representative to train Owner's maintenance personnel to
         adjust, operate, and maintain water-source heat pumps.             Refer to Section 017900
         "Demonstration and Training."


                                            END OF SECTION




Privatized Army Lodging                           238146 - 8                                   Lend Lease
Alterations for HIE Branding                                         REV 0 – ISSUED FOR CONSTRUCTION
Ft. Leavenworth, KS - Building 695                                                        October 20, 2011

				