Docstoc

chiller modeled 10b tcu

Document Sample
chiller modeled 10b tcu Powered By Docstoc
					                                                               THERMAX




                               SUBMITTALS

                                    FOR

              EXHAUST FIRED ABSORPTION CHILLERS
                       (TRiGENiE Series)




    PROJECT: NEW LOOP ENERGY – C 200

   CHILLER MODEL: ED 10B TCU

    Offer no.:      T.Inc/PP/202/NT/0612



THERMAX INC.                               THERMAX LIMITED
 21800, Haggerty Road                      Cooling & Heating Division
 Suite 112,                                D-13, R. D. Aga Road,
 Northville, MI 48167                      Chinchwad, Pune 411 019
 USA                                       INDIA

Visit us at      : www.thermax-usa.com or www.thermaxindia.com


         Improving your business is our business




                                                                         1
                                              THERMAX



EXHAUST FIRED ABSORPTION CHILLERS
THE LATEST ENERGY EFFICIENT TRiGENiE SERIES




THE ECO-FRIENDLY SOLUTION –

FOR AIR CONDITIONING AND INDUSTRIAL COOLING


                                                        2
                                                                                                                            THERMAX



Table of Contents

I. SPECIFICATION FOR VAPOR ABSORPTION CHILLER .................................................................... 3
II. SCOPE OF SUPPLY DOUBLE EFFECT EXHAUST FIRED VAPOR ABSORPTION CHILLER....... 6
III. THERMAX BATTERY LIMITS ............................................................................................................. 8
IV. SCOPE OF SUPPLY OF THE PURCHASER ........................................................................................ 8
V. STANDARD INSTRUMENTS & COMPONENTS MAKES ...............................................................10
VI. PERFORMANCE CRITERIA AT SITE ................................................................................................11
VII. SITE TEST AND STANDARD WATER QUALITY...........................................................................12
VIII. MATERIALS OF CONSTRUCTION..................................................................................................13
IX. QUANTITIES OF LIQUIDS ........................................... ERROR! BOOKMARK NOT DEFINED.15
X. COMMERCIAL OFFER ..........................................................................................................................15
XI. TERMS & CONDITIONS ......................................................................................................................16




I. Specification for Vapor Absorption Chiller
      DESCRIPTION                                                                     UNITS                          VALUE
      Chiller Model                                                                                                ED 10B TCU
      Cooling Capacity (±3%)                                                            TR                             56
                                                                                      BTU/hr                         675604



                                                                                                                                              3
                                                                      THERMAX


A     CHILLED WATER CIRCUIT:
1.    Chilled Water Inlet Temperature             °F                54.0
2.    Chilled Water Outlet Temperature            °F                44.0
3.    Chilled Water Flow Rate                    GPM                135.0
4.    Passes in Evaporator                       Nos.                3.0
5.    Chilled Water Circuit Friction Loss       ft WC                5.6
6.    Glycol in Chilled Water                                        NA
7.    Concentration of Glycol                      %                  0
8.    Fouling Factor                         ft² hr °F/BTU         0.0001
9.    Connection Diameter (Indicative)           Inches              3.2
10.   Maximum Working Pressure                    PSI g             116.0

B     COOLING WATER CIRCUIT:
1.    Cooling Water Inlet Temperature             °F                 85.0
2.    Cooling Water Outlet Temperature            °F                 96.1
3.    Cooling Water Flow Rate                    GPM                220.0
4.    Cooling Water Bypass Flow                  GPM                  NA
5.    Passes in Absorber / Condenser             Nos.              40238.0
6.    Cooling Water Circuit Friction Loss       ft WC                 8.2
7.    Glycol in Cooling Water                                         NA
8.    Concentration of Glycol                      %                   0
9.    Fouling Factor                         ft² hr °F/BTU         0.00025
10.   Connection Diameter (Indicative)           Inches               4.0
11.   Maximum Working Pressure                    PSI g             116.0

C     EXHAUST GAS CIRCUIT:
1.    Engine Type                                                    Gas
2.    Engines Connected                          Nos.                 1.0
3.    Exhaust Flow Rate                         lbs/hr             10555.9
4.    Exhaust Gas Inlet Temp.                     °F                536.0
5.    Exhaust Gas Outlet Temp.                    °F                338.0
6.    Average Cp of Exhaust Gas               BTU/lb °F             0.265
7.    Exhaust Flow Rate @ 100%                  lbs/hr             10555.9
8.    Exhaust Flow Temp @ 100%                    °F                536.0
9.    Engine Loading                              %                 100.0
10.   Pressure Drop in Exhaust Gas Furnace    Inch WC                 4.0
11.   Connection Diameter (Indicative)         Inches                14.0

D     ELECTRICAL DATA:
1.    Power Supply (3 Phase + N)                V, Hz        460 (±10%) 60 (±5%)
2.    Absorbent pump - 1                        kW(A)               1.1 (3.4)
3.    Refrigerant pump                          kW(A)               0.3 (1.4)
4.    Vacuum pump                               kW(A)              0.75 (1.8)
5.    Power consumption                          kVA                   6.0

E     PHYSICAL DATA (APPROXIMATE, ±10%):
1.    Length                                    Inches              114.2
2.    Width                                     Inches              90.6
3.    Height                                    Inches              90.6



                                                                                   4
                                                                                          THERMAX
4.      Dry Weight                                                 lbs                  9921.0
5.      Operating Weight                                           lbs                 13448.0

F       TUBE METALLURGY:
1.      Evaporator                                                                Enhanced Copper
2.      Absorber                                                                  Enhanced Copper
3.      Condenser                                                                   Plain Copper


     Note:   1.   This Selection is valid for Insulated Chiller only.
             2.   For Non-Insulated Chiller, the Capacity & Heat Source Consumption will vary.
             3.   Plant room temperature should be from +5°C to +45°C (41°F to 113°F).
             4.   Please contact Thermax representative/office for Customized Specifications.
             5.   The Selection is as per ARI 560-2000.




                                                                                                    5
                                                                            THERMAX


II. Scope of Supply Double Effect Exhaust Fired
Vapor Absorption Chiller
1.   LOWER SHELL
     - Split Evaporator                            - Absorber
     - Gravity feed tray arrangement               - Eliminators
     - Base                                        - Refrigerant & Absorber level control

2.   UPPER SHELL
     - Low Temperature Generator           - Condenser            - Eliminator

3.   HIGH TEMPERATURE GENERATOR
     - Generator                   - Eliminators
     - High temperature generator level box

4.   REGENERATIVE HEAT EXCHANGERS
     - High temperature heat exchanger
     - Low temperature heat exchanger
     - Drain heat exchanger

5.   PUMPS
     - Absorbent pump with isolating valves
     - Refrigerant pump with isolating valves

6.   PURGE RECOVERY DEVICE
     - Storage tank   - Air separation device
     - Ejector device - Liquid trap           - Piping and various valves

7.   PIPING AND INTERCONNECTING WIRING
     - Refrigerant and absorbent piping - Internal power and control wiring

8.   VACUUM PUMP SET

9.   CONTROL PANEL:
-    Panel unit
     Operator Terminal having Keypad facility for sequential operation of the unit
-    The following keys will be provided -
     a) Machine start/stop
     b) Vacuum pump start/stop
     c) Refrigerant pump start/stop
     d) Refrigerant pump auto/manual selector
     e) Damper auto/manual selector, if applicable
     f) Burner auto/manual selector, if applicable
     g) Set point local/remote
     h) Machine local/remote
     i) Cooling/simultaneous mode selector
     j) Alarm acknowledge/re-set



                                                                                        6
                                                                             THERMAX
      The following displays will be provided –
       Display of Chilled and Cooling water inlet temperatures, High temperature
         generator outlet temperature and other heat exchanger temperatures for machine
         operation
       Display of chilled water set point entries and entries of safety set points, PID
         settings etc.
       Display of alarm messages for abnormal conditions
       Potential free contacts for machine run and trip indications
       Main circuit breaker
       Micro-processor based PLC (Programmable Logic Controller) including PID
         temperature control and high temperature cut-out for Generator
       Alarm buzzer
       Level relay for Evaporator, Absorber and Generator
       Transformer
       Terminal strip

10.      LOCALLY MOUNTED CONTROLS AND INSTRUMENTS BY FACTORY:
         -    Electrically operated 3-way Gas Diverter Damper.
         -    Burner – for fuel as mentioned, if applicable.
              Oil based               : fuel oil filter, flexible hose, as applicable
              Natural gas based       : gas train, as applicable
              Note: Burner applicable only for EDG models.
         -    Chilled water flow switch
         -    Chilled water DP (differential pressure) switch
         -    Temperature sensors (RTD type)
         -    Level electrodes for sensing level at Evaporator, Absorber and at High
              temperature generator
         -    Mercury Manometer

11.      INITIAL CHARGE:
-        Lithium Bromide duly inhibited         1 Lot
-        Refrigerant water with octyl alcohol   1 Lot

12.      PAINTING
-        Main Unit     : Rust Preventive Paint
-        Control Panel : Finish Paint

13.      PACKING          -     THERMAX standard packing

14.      TECHNICAL        -     Instruction and service manual (Operation & Maintenance)




                                                                                           7
                                                                                   THERMAX



III. Thermax Battery Limits
Exhaust Gas            -      At Exhaust gas inlet / outlet nozzle flange of generator
                       -      At Exhaust gas inlet / outlet / bypass nozzle flange of gas
                              diverter damper

Fuel (if applicable)   -      Fuel inlet nozzle on burner
(Supplementary)        -      Exhaust outlet flange on generator
                       -      Inlet/outlet flange of fuel filter/gas train as applicable.

Chilled water          -      At Inlet nozzle flanges of evaporator water box
                       -      At Outlet nozzle flange of evaporator water box

Cooling water          -      At Inlet nozzle flange of absorber water box
                       -      At Outlet nozzle flange of condenser water box

Power                  -      Terminal connections on control panel

Earthing               -      Terminal connections on control panel
                              Note: Separate instrumentation earthing for PLC panel



IV. Scope of Supply of the Purchaser
   Unloading, transportation & insurance after agreed delivery terms
   Unloading and moving the solutions, refrigerants near chiller
   Providing helper for charging the solutions in chiller
   Building and civil foundations
   Chilled water and cooling water piping work including various safety valves, globe
    valves, isolating valves etc.
   Insulation of chiller and piping
   Electrically/pneumatically operated cooling water on/off valve if cooling water Pump is
    not used exclusively for Absorption machine
   Low cooling water temperature, cooling tower fan cutout switch
   Various temperature / pressure gauges for water lines
   Cooling tower and water pumps
   External wiring for interlocks with cooling, chilled water pumps
   Rated power supply to control panel
   Dry, oil free, & dirt free air supply for valves, if required
   Cooling, chilled water, Exhaust gas and Fuel supply at rated conditions
   Soft water make up for cooling, & chilled water
   Nitrogen gas for pressure testing
   Finish painting of the machine
   Cooling water flow switch / DP Switch




                                                                                             8
                                                                               THERMAX
   ENGINE EXHAUST GAS - Main energy
         o Gas diverter damper support structure with fabricated service platform as
            per installation drawings. Thermal insulation (LRB Mineral wool 6.9 lb/ft3
            density 6 to 10 inches thick with 22 SWG Al cladding) for personal
            protection and heat conservation.
         o Butterfly isolation damper / Guillotine damper at the absorption machine
            inlet, expansion joints, exhaust gas ducting suitably designed to offer
            minimum back pressure on prime mover.
         o Suitable thermal insulation for heat conservation (or human protection) as
            required.
         o Silencer, bypass ducting, main chimney as per local norms.
         o Differential Pressure and temperature measurement instruments.

   FUEL OIL : Supplementary fuel, If applicable
          o Main storage tank, fuel unloading and transfer system, any statutory
              approvals and related fees, if any.
          o Day tank with level gauge, level controller, overflow and drain, manhole,
              fuel filter, isolation valves, piping fittings, pressure, and flow measurement
              instruments, fuel supply and return piping, as per standard engineering
              practices / system P & I .
          o Day oil tank bottom height from burner level: 6.6 Ft minimum required.

                                               and/or –

   NATURAL GAS : Supplementary fuel, If applicable
         o Gas supply system including Pressure Reducing Station with gas filter,
            Slam shut off Safety valve, Pressure Reducing Valve with impulse tubing,
            creep relief valve with vent tubing, isolation valve, pressure, temperature
            and flow measurement instruments, suitably designed as per standard
            engineering practices / system P & I.
         o Gas inlet pressure at burner train : 0.58 to 1.45 PSI
         o Any statutory approvals and related fees, if any.

   EXHAUST FLUE GAS DUCTING WORK :
         o Suitably designed flue gas ducting with minimum bends (No sharp bends
            to avoid system back pressure) connected to chimney, installed as per
            local pollution control norm/ statutory authority.
         o Expansion joints to avoid thermal stresses, pressure measurement point,
            flue gas analysis point, and temperature measurement instruments, as
            per standard engineering practices / system P & I.
         o Thermal insulation of ducting for human protection or heat conservation
            as may be applicable, corrosion protection silver paint for chimney.

   Chimney inspection door.




                                                                                           9
                                                                        THERMAX


V. Standard Instruments & Components Makes
Programmable Logic Controller (PLC)      : Siemens

Operator Interface                       : Siemens

Level Relay                              : Omron, Japan

Level Electrodes                         : Omron, Japan

Flow Switch                              : Saginomiya, Japan

Differential Pressure Switch             : Switzer, India

PT-100 Sensors (RTD type)                : Nutech, India

Diaphragm valve                          : Saunders

Manometer                                : Technoflow

Vacuum Pump                              : Indowoosung

Solution & Refrigerant pumps             : Teikoku Electric, / Chunin

Damper (if applicable)                   : Shanrod or Equivalent

Burner (If applicable)                   : Weishaupt / Powerflame


Note – If due to some unforeseen situation, it is not possible to use these makes,
Thermax may choose other equivalent makes.




                                                                                  10
                                                                                THERMAX


VI. Performance Criteria at Site
The following inputs to be provided by the purchaser.

A)     Steady load

B)     Inlet parameters:

 I)    Cooling water inlet temperature not above rated conditions but above 50 Deg. F.
ii)    Chilled water inlet temperature not below rated temperature
iii)   Chilled water & cooling water as per specifications mentioned. Alternatively,
       Thermax approval for water quality at site
iv)    Water flow rates: Chilled water within ±5% of rated flow.
                          Cooling water within +5% -0% of rated flow
v)     Heat source (i. e. Exhaust gas, and Fuel – oil / gas if applicable) at rated flow rate
       and rated condition (Exhaust back pressure, temperature, Fuel Calorific value )
       Tolerance allowed is ± 5%




                                                                                          11
                                                                                  THERMAX


VII. Site Test and Standard Water Quality
SITE TEST:

Performance trials will be carried out within 15 days of commissioning the machine, at
available load. In case load or rated utilities are not available, the unit will be deemed as
handed over after performance trials are taken on available parameters.


                       Standard Water Quality (for copper tubes)

(Maximum allowable range for circulating chilled and cooling water)
 Description                                               Unit       Valve
 pH (25°C)                                                            7.0 - 8.5
 TDS                                                       PPM        < 1500
 TSS(Turbidity)                                            PPM        < 10
 M Alkalinity                                              PPM        < 100
 Chloride Ion CI -                                         PPM        < 400
 Sulphates Ion SO4 -- (For scaling only)                   PPM        < 500
 Silica                                                    PPM        < 75
 Total Hardness                                            PPM        < 300
 Calcium Hardness                                          PPM        < 200
 Total Iron Fe                                             PPM        < 0.1
 Sulphide Ion S --                                         PPM        Not detected
 Ammonium Ion NH4 +                                        PPM        <1
 Biological Oxygen Demand (BOD)                            PPM        < 50
 Chemical Oxygen Demand (COD)                              PPM        < 100
 Free Chorine                                              PPM        < 0.1
 Oil & Grease                                              PPM        <1
 Other contaminations like Phenol, cyanide, lead,
                                                             PPM       Not detected
 manganese etc
Notes:
1.     The circulating water should be clean with Turbidity < 10 to avoid under deposit
       corrosion.
2.     Avoid stagnant water in the chiller for longer duration. In case of more than 1 day
       stoppage, it is recommended to circulate the water for about 30 minutes every day.
       In case the stoppage is for a longer duration, it is recommended to drain the water
       from the chiller and keep the chiller in dry condition.




                                                                                            12
                                                             THERMAX


VIII. Materials of Construction
1. Lower Shell

                   ITEM                       MATERIAL
                   Shell               IS 2062 Gr B or equivalent
                 Tube Plate            IS 2062 Gr B or equivalent
                   Baffle                     IS 2062 Gr B
                 Eliminator                     SS 430
                   Tray                            SS 430
                                      DLP Grade Copper (Enhanced)
                                   0.63 inches OD , 0.0224 inches(bare
                                                  tube)thk
           Evaporator Tubes             (for models 100 – 500 NTR)
                                  0.748 inches OD , 0.0224 inches (bare
                                                 tube) thk
                                       (for models 550 – 1680 NTR)
                                      DLP Grade Copper (Enhanced)
                                   0.63 inches OD , 0.0256 inches(bare
                                                  tube)thk
            Absorber Tubes              (for models 100 – 500 NTR)
                                  0.748 inches OD , 0.0256 inches (bare
                                                 tube) thk
                                       (for models 550 – 1680 NTR)

2. Upper Shell

                   ITEM                       MATERIAL
                   Shell               IS 2062 Gr B or equivalent
                 Tube Plate            IS 2062 Gr B or equivalent
                   Baffle                     IS 2062 Gr B
                 Eliminator                     SS 430
                                          Carbon steel (Enhanced)
         Low Generator Tubes    0.748 inches OD ,0.0472 inches(bare tube)
                                                    thk
                                         DLP Grade Copper (Plain)
                                    0.63 inches OD , 0.0224 inches thk
           Condenser Tubes              (for models 100 – 500 NTR)
                                   0.748 inches OD , 0.0224 inches thk
                                       (for models 550 – 1680 NTR)

3. High Temperature Generator



                                                                          13
                                                                                  THERMAX


                    ITEM                                          MATERIAL
                    Shell                                 IS 2062 Gr B or equivalent
                 Tube Plate                              IS 2062 Gr B or equivalent
                    Baffle                                       IS 2062 Gr B
                 Eliminator                                         SS 430
                                                               Carbon Steel
                   Tubes *                              1 inches OD ,0.08 inches thk
* We may provide 0.748 inches OD (0.08 inches thick), 1.25 inches OD (0.104 inches thick), 1.5
inches OD (0.104 inches thick) plain / finned tubes based on exhaust gas characteristics

4. Heat Exchanger: (LTHE & DHE)

                    ITEM                                          MATERIAL
                    Type                                 Plate type Heat Exchanger
                   M.O.C                                SS plates with Copper brazing

5. Heat Exchanger: (HTHE)

                    ITEM                                          MATERIAL
                    Type                                 Plate type Heat Exchanger
                   M.O.C                                         Carbon steel


6. Nozzle Flange Ratings:

       Chilled Water                   -       ANSI B 16.5 CLASS 150
       Cooling Water                   -       ANSI B 16.5 CLASS 150
       Exhaust Outlet                  -       ANSI B 16.5 CLASS 150

7. Insulation Details:

        Insulation of the machine is not in standard scope. However, the same can be
offered at extra price

       Suggested Material:
       Hot Insulation      -           Mineral Wool
                                       2.953 inches thk in Generator
                                       1.968 inches thk in Heat Exchanger
                                       OR
                                       EPDM Rubber foam insulation material 3/4” thick

       Cold Insulation         -       Nitrile Rubber foam insulation material 3/4” thick



                                                                                             14
                                                                                  THERMAX


X. Commercial offer
SL NO    QTY   UNIT                          DESCRIPTION                           UNIT PRICE, US$
  01      1     No.   Supply of Thermax Trigenie series exhaust gas driven              US$ 115,600
                      double effect chiller model ED 10C TCU-S, selected as
                      per specs given above
  02       1    Lot   Factory supervised start up services, on site testing and                Included
                      Operator Training (5 consecutive working days max), per
                      chiller
  03       1    Lot   Seaworthy Packing and Ocean Freight up to jobsite                        Included
  04       1    Lot   Cooling water auto-shut off valve, if pumps are not                      Included
                      dedicated to chiller
  05       1    No.   First charge of Lithium Bromide and liquids                              Included
  06       1    Lot   12 months Parts & Labor Warranty from startup or 18                      Included
                      months from shipment, whichever earlier
  07       1    Lot   Siemens OP7 PLC based control panel with MODBUS-                         Included
                      RTU protocol based Control interface
  08       1    Lot   Purge assembly complete with purge pump                                   Included
  09       1    No.   Three way exhaust gas diverter damper, suitably sized                     Included
  10       1    Lot   Cold & Hot insulation                                                 Not Included

Price basis:   DDP Jobsite (FOB Destination) in USA




                                                                                              15
                                                                              THERMAX


XI. Terms & Conditions
1 Contract Finalization:
The Final offer and technical check list will be the binding document for execution of the
project. This document supersedes all previous written or oral commitments.

2. SPECIFICATIONS ETC.
Specifications, dimensions, description, shades of paints etc. are not binding on us in
minute details and are subject to reasonable alterations without notice. Construction
drawings will be supplied after receipt of order and submittal approval typically within
eight (8) weeks; quote drawings should not be used for installation purpose.

3. PRICES
The prices are FOB destination.

4. MODE OF DELIVERY
The shipment may be made in one or separate lots at our option. The delivery will be
complete once the shipment reaches the ship-to address mentioned in the PO. It will be
the buyer’s responsibility to inspect the shipment with the packing list and report
deviation within 2 weeks from the date of delivery at the ship-to address. No adverse
claims will be allowed after this period.

5. PACKING
Packing for shipment, whenever necessary will be in accordance with our standard
practice and is included in the order value

6. INSPECTION
If necessary, the goods will be offered for visual inspection only at our works/our
supplier's works. The date of inspection will be intimated by us about 15 days in
advance and confirmed by the purchaser accordingly. If inspection is not carried
out on the date so advised, we shall be free to ship consignment as per terms of
delivery. Travel and associated costs related to visits to our/supplier’s works will be
borne by the customer.

7. DELIVERY PERIOD
 The goods will be ready for delivery approximately 5 months from the final
confirmation by our factory of the Purchaser`s Order along with the requisite advance
(if applicable) and with all technical and commercial points duly clarified. Deliveries
subject to "Force Majeure" as defined in clause 10.
Specific customer delivery requirements must be agreed in writing and may involve
additional cost related to expediting the order. Thermax makes no guarantee concerning
delivery date and accepts no liability on account of delivery date. Purchaser should allow
adequate contingency in setting the desired delivery date.

8. PAYMENT TERMS
50% Advance and 50% within 30 days from chiller delivery


9. GENERAL LIEN


                                                                                           16
                                                                                 THERMAX
We shall be entitled to general lien on goods in our possession or shipped for all
money due to us by the purchaser, both under this contract or any other account and
we shall also be entitled to apply any money in our hands under any contract due to
us under any other contract or contracts.

10. FORCE MAJEURE
Should any circumstance arise which prevent complete or partial fulfillment by any of the
parties of their respective obligation under the present contract, namely : fire, natural
calamities, blockade, prohibitions of export or import, strikes in manufacturing plants or
any other circumstances beyond the control of the parties, the time stipulated for the
fulfillment of the obligation will be extended for a period equal to that during which such
circumstances and their consequences will remain in force.
Should the above circumstances and their consequences continue to be in force more
than 3 months each party will have the right to refuse any further fulfillment of the
obligations under the contract and in such case neither of the parties will have the right
to make a demand upon the other party for the compensation of any possible damage.
The party, for whom it becomes impossible to meet their obligations under the present
contract, is to immediately advise the other party in regard to the beginning and the
cessation of the circumstances preventing the fulfillment of their obligations.
The certificates issued by the respective Chambers of Commerce of the Seller’s or the
Buyer’s country will be sufficient proof of above mentioned circumstances and their
duration.

11. WARRANTY
All our equipment are thoroughly inspected/tested before shipment and therefore,
can be depended upon for long and trouble free service. We undertake to make
good      by replacement or repair defects arising of faulty design, materials or
workmanship within 12 months of the date of shipment, provided that if we so
require, the parts in respect of which a claim is made, must be sent at purchaser's
expense to our works before liability can be entertained under this clause. Such
expense will be refunded if our liability is admitted. It is advised that the purchaser enters
in to annual maintenance contract with Thermax immediately after commissioning of
equipment.
Purchased components are guaranteed by us only to the extent of guarantees given to
us by our suppliers. Electrical components, such as heaters; motors; contractors; AC
Drive; rubber components; consumables such as Lithium Molybdate; Octyl Alcohol etc.;
and instruments such as pressure gauges; thermometers; combi-stats; etc. are not
covered under this warranty. This warranty is valid subject to installation having been
completed within 3 months of shipment of the equipment; - the supply/installation
having been formally accepted as per the Handing Over clause (No.15 below);
- the equipment or part thereof not being subject to accident, alteration, abuse or
misuse;
- the installation having been made in proper manner as per our installation instructions;
- the equipment being operated and maintained as per our Operation and
Maintenance instructions.


12. COMMISSIONING
Commissioning service offered is for 5 consecutive days in one visit.
The pre-commissioning check-list should be duly filled and sent to us.


                                                                                           17
                                                                               THERMAX
The customer should give a 15 days’ notice period prior to the date of commissioning of
the unit.
In case the unit is not commissioned on account of default at customer’s end extra days
will be chargeable @ $190/hr. In case of any issues from customer’s side beyond 15
days delay, the unit is deemed to have handed over.

13. HANDING OVER
Unless otherwise specified in the order and accepted, handing over of the equipment
and/or installation would be considered as completed and a formal completion certificate
shall be issued by the buyer/user if:
(a) The equipment has been supplied as per terms of scope of supply or with agreed
deviations, if any;
(b) Erection, if involved, has been completed generally as per terms of order or with
unavoidable deviations;
(c) The equipment has been commissioned, if applicable generally as agreed;
(d) The equipment and/or installation have been put to commercial use either with
or without help of our engineer.

The buyer/user is expected to put the equipment to commercial use only after issuing a
formal completion certificate. Our responsibility in terms of warranty shall cease
straightaway if the equipment is put to use without formal acceptance by the buyer.

14. CANCELLATION
Orders received and acknowledged by us shall not be subject to cancellation or
modification either wholly or partly for any reason whatsoever without our consent.


15. JURISDICTION
All contracts between purchasers and ourselves are deemed to be entered into in
Michigan and shall be interpreted and the rights and liabilities of the parties shall be
determined in accordance with the laws of the State of Michigan, including the Uniform
Commercial Code as adopted by Michigan. Buyers agree to subject itself to the
jurisdiction of Oakland County, Michigan to the Federal Eastern District Court of
Michigan.

16. VALIDITY
While every effort will be made to keep our quotation valid for acceptance for a period
of 30 days from the date hereof, we may be constrained to modify this offer within this
period due to circumstances beyond our control.

17. GENERAL
Any condition or other matters relating to this quotation not expressly stipulated will be a
matter of mutual discussion and a formal signed agreement at the time of accepting the
order. If this quotation is accepted and an order placed, all the above conditions of sale
stand automatically accepted by the buyer.

18. SALES TAX:
Sales Tax certificate for resale required

19. DELIVERY DISCLAIMERS:


                                                                                         18
                                                                              THERMAX


LIMITATIONS OF DDP DELIVERY TERMS

Thermax Inc will make every attempt to deliver shipments of chillers, parts and
accessories in a reasonable time frame after custom clearance procedures get over.

Thermax Inc does not accept any responsibility on account of delays in custom
clearance of shipments due to external circumstances including, but not limited to
intensive custom examination, port congestion, weather related issues, non availability
of suitable trucks/trailers and Force Majeure etc.

Thermax Inc also does not accept any responsibility for delay on account of obtaining
road/city/county permits etc. for road transportation of shipment.

Thermax Inc’s freight forwarder will make an attempt to give 48 hrs notice to designated
rigger before actual delivery. Thermax Inc will not be liable for costs related to manpower
or equipment deployment by rigging company, in case of delays in delivery due to
external circumstances cited above.

It is the responsibility of the rigging company to unload the shipment and to return the
container in the proper manner on the agreed date with Thermax’s freight forwarder. Any
expenses incurred due to rigging company not accepting the delivery of equipment on
agreed day, will be charged to customer’s account.


For THERMAX INC.


Piyush Patel


ACCEPTANCE:

Purchaser hereby accepts this Commercial Offer No. T.INC/PP/202/NT/0612 and agrees
to accept the stated Terms and Conditions. Purchase shall mention this offer no. in his
purchase order.
In case of Conflict between this document and purchaser’s Purchase Order this
document will take precedence.
Items not specifically included in this offer are deemed to be excluded.

Authorized Signatory




Printed Name                  Title                         Signature              Date




                                                                                          19

				
DOCUMENT INFO
Shared By:
Categories:
Tags:
Stats:
views:17
posted:11/26/2012
language:Unknown
pages:19