					Installation and Maintenance Manual
                                                                             Air Cooled
                                                                            Mini-Chillers
                                                                       Basic and Pack Versions
                                                                 Models WMC 06 and 08 (Cooling only)
                                                              Models WMC 06R and 08R (Reverse cycle)
                                                                              with HCFC 22 and HFC 407C




                                                                                                  F
                                                                                                 GB
                                                                                                  D
                                                                                                  I
                                                                                                  E




                                                                                                      R


                                      IMW WMC1.1M/05.01
                                      Supersedes : IMW WMC.0M/08.00
                                                                   Table of Contents

Introduction ................................................................................................................................................ p. 3

Safety Precautions ..................................................................................................................................... p. 3

General ....................................................................................................................................................... p. 4
    Presentation .............................................................................................................................................................. p. 4
    Inspection .................................................................................................................................................................. p. 4
    Technical Data .......................................................................................................................................................... p. 4
    Refrigerant Charge ................................................................................................................................................... p. 5
    Operating Limits ........................................................................................................................................................ p. 5

Dimensional Data ....................................................................................................................................... p. 6

Installation .................................................................................................................................................. p. 7
    Unit Handling ............................................................................................................................................................ p. 7
    Installation Instructions ............................................................................................................................................. p. 7

Water Connections ..................................................................................................................................... p. 9
    Water Piping ............................................................................................................................................................. p. 9
    Safety Differential Pressure Switch .......................................................................................................................... p. 9
    Hydronic Module ....................................................................................................................................................... p. 10
    Unit Manometric Head Curves ................................................................................................................................. p. 10
    Pressure Drop in Tubes and Accessories ................................................................................................................ p. 11
    Heat Exchangers Water Pressure Drop ................................................................................................................... p. 12
    Principle Diagram of Water Circuit ........................................................................................................................... p. 12

Field Wiring ................................................................................................................................................ p. 13

Controls ...................................................................................................................................................... p. 15
    Temperature Controller ............................................................................................................................................. p. 15
    Antifreeze Function ................................................................................................................................................... p. 15
    Low Ambient Operation Function ............................................................................................................................. p. 15

Start-up ....................................................................................................................................................... p. 16
    Pre Start-up ............................................................................................................................................................... p. 16
    Unit Start-up .............................................................................................................................................................. p. 16
    Set-point Change ...................................................................................................................................................... p. 17
    Main Alarms List ....................................................................................................................................................... p. 17

Maintenance ............................................................................................................................................... p. 18

Main Spare Parts List ................................................................................................................................. p. 19

In-warranty Return Material Procedure ..................................................................................................... p. 19

Service and Spare Parts Order .................................................................................................................. p. 19




Page 2
                                                 1 - Introduction

The purpose of this manual is to provide the installation, start-up, operating and maintenance rules to the users of WMC
units.
It does not give a full description of all maintenance works assuring the long life and reliability of this type of equipment.Only
the services of qualified personnel, member of a registered maintenance company, can guarantee a reliable and durable
running of the machine.



                                           2 - Safety Precautions

Before installing the unit, please read the following safety precautions carefully.


                         Warning                                                             Caution
 Installation and maintenance must be performed by qualified          Avoid access of non qualified and non authorized
 personnels who are familiar with local codes and regulations         persons at the chiller installation site.
 and experienced with this type of equipment.



                         Warning                                                             Caution
 All field wiring must be installed in accordance with the            It is forbidden to undertake any work on electrical
 national wiring regulations.                                         components of the unit before disconnecting the power
                                                                      supply.

                         Warning
 Ensure that the unit name plate is in conformity with the                                   Caution
 supply voltage available at site, before carrying out wiring
 according to electrical diagram supplied with the unit.              It is forbidden to undertake any work on electrical
                                                                      components of the unit, if there is presence of water and
                                                                      humidity.
                         Warning
 The unit must be GROUNDED to prevent possible
 hazards due to insulation failures.                                                         Caution
                                                                      All works on piping and components of refrigerant circuit
                                                                      under pressure must be only performed by authorized
                         Warning                                      and qualified persons.
 All wiring must not touch the hot refrigerant piping,
 compressor or any moving parts of fan motor.

                                                                                             Caution
                         Warning                                      When undertaking water connection, make sure that any
                                                                      foreign matters will not be introduced into water piping.
 Make certain that the unit is switched OFF before
 installing or servicing it.

                                                                                             Caution
                         Caution
                                                                      Strainer must be placed in the water lines just prior to
 Handling of the unit must be done by using the systems               the inlets of water pump and heat exchanger (see Fig. 4
 designed to support its weight.                                      on page 9).




                                                                                                                           Page 3
                                                        3 - General

                                                                       operation.
                   3.1 - Presentation

The WMC air cooled mini-chillers have been designed for
outdoor installation and for reliable and efficient operation.                                3.2 - Inspection
They are mainly suitable for the air conditioning applications
required in the residential and tertiary sectors.                      Check all items carefully against the bill of lading. Inspect
These mini-chillers offer 2 ranges : cooling only and                  all units for damage upon arrival. Report shipping damage
reverse cycle. Each range is available in Basic version
                                                                       and file a claim with the carrier.
(without hydronic module) and Pack version (equipped
with hydronic module).                                                 Check the unit name plate before unloading, making certain
All units are completely assembled, factory wired, charged             it agrees with the power supply available. The manufacturer
with oil and refrigerant. Before shipping, the units are
                                                                       is not responsible for physical damage after unit leaves the
carefully checked and tested, with pure water higher
than 0 °C, in accordance with normal conditions of                     factory.



                  3.3 - Technical Data


COOLING ONLY Models                                                                      06                           08
Nominal cooling capacity (1) - HCFC 22 / HFC 407C                         kW          5.7 / 5.6                    7.5 / 7.5
Nominal power input (1) - HCFC 22 / HFC 407C                              kW          1.9 / 2.3                    2.8 / 3.3
Number of refrigerant circuit                                                            1                             1
Refrigerant charge - HCFC 22 / HFC 407C                                    kg        1.9 / 1.95                    2.3 / 2.0
Compressor
Type                                                                                   Scroll                          Scroll
Condenser fan and motor
Number / Fan diameter                                                    mm            1 / 450                         1 / 450
Fan rotational speed                                                     rpm             850                             850
Motor nominal power input                                                  W             150                             150
Nominal air flow                                                         m3/h           2850                            2850
Air cooled condenser coil
Total face area                                                            m2           0.71                            0.71
Number of rows                                                                           2                                2
Evaporator
Type                                                                                   plates                        plates
Nominal water flow (1) - HCFC 22 / HFC 407C                                 l/h       980 / 963                   1290 / 1290
WPD at nominal water flow (Basic version) - HCFC 22 / HFC 407C            kPa        11.8 / 11.5                   12.0 / 12.0
Water tank volume (Pack version)                                        liters           25                            25
Electrical data
Standard supply voltage (V/Ph/Hz)                                                     230/1/50              230/1/50           400/3/50+N
Unit maximum current                                                        A            14                   18.8                  8
Maximum inrush current                                                      A            63                   102                  48
Water connections
Inlet                                                                                    1"                              1"
Outlet                                                                                   1"                              1"
Weight
Shipping weight - Basic version                                            kg           123                             127
Shipping weight - Pack version                                             kg           130                             134
(1) Data based on entering / leaving chilled water temperatures of 12 / 7 °C and ambient air temperature of 35 °C. Power input given for
    compressor only.




Page 4
                                                3 - General (cont'd)

REVERSE CYCLE Models                                                                     06R                           08R
Nominal cooling capacity (1) - HCFC 22 / HFC 407C                          kW          5.6 / 5.5                     7.4 / 7.3
Nominal power input (1) - HCFC 22 / HFC 407C                               kW          1.9 / 2.2                     2.8 / 3.2
Nominal heating capacity (2) - HCFC 22 / HFC 407C                          kW         6.8 / 7.0                      9.05 / 9.1
Nominal power input (2) - HCFC 22 / HFC 407C                               kW         2.2 / 2.8                       2.9 / 3.4
Number of refrigerant circuit                                                            1                                1
Refrigerant charge - HCFC 22 / HFC 407C                                     kg       2.75 / 2.40                     3.0 / 2.97
Compressor
Type                                                                                    Scroll                         Scroll
Condenser fan and motor
Number / Fan diameter                                                    mm            1 / 450                        1 / 450
Fan rotational speed                                                     rpm             850                            850
Motor nominal power input                                                  W             150                            150
Nominal air flow                                                         m3/h           2850                           2850
Air cooled condenser coil
Total face area                                                             m2           0.71                          0.71
Number of rows                                                                            2                              2
Evaporator
Type                                                                                   plates                         plates
Nominal water flow (1) - HCFC 22 / HFC 407C                                  l/h      963 / 946                     1273 / 1256
WPD at nominal water flow (Basic version) - HCFC 22 / HFC 407C             kPa       11.5 / 11.2                    11.7 / 11.5
Water tank volume (Pack version)                                         liters          25                             25
Electrical data
Standard supply voltage (V/Ph/Hz)                                                     230/1/50             230/1/50           400/3/50+N
Unit maximum current                                                         A           14                  18.8                  8
Maximum inrush current                                                       A           63                  102                   48
Water connections
Inlet                                                                                     1"                             1"
Outlet                                                                                    1"                             1"
Weight
Shipping weight - Basic version                                             kg           123                            127
Shipping weight - Pack version                                              kg           130                            134
(1) Data based on entering / leaving chilled water temperatures of 12 / 7 °C and ambient air temperature of 35 °C. Power input given for
    compressor only.
(2) Data based on entering / leaving hot water temperatures of 40 / 45 °C and ambient air temperature of 7 °C. Power input given for
    compressor only.



             3.4 - Refrigerant Charge

All units are designed for use with HCFC-22 and HFC 407C. See nameplate for specific refrigerant used. Units are shipped
with an operating charge.



                3.5 - Operating Limits

Water and air temperatures - Cooling only units                        Water and air temperatures - Reverse cycle units
             All sizes                 Min. ( C)    Max. ( C)                       All sizes                  Min. ( C)         Max. ( C)
Leaving chilled water temp. (1)           5           15                Leaving hot water temperature             25              55 (1)
Water delta T                             4            6                Water delta T                              4                6
Ambient air temperature                   15          46                Ambient air temp. (heat mode)             -5               25
(1) Without glycol.                                                    (1) Refer to table of performance data indicated in unit technical
                                                                           brochure.


                                                                                                                                     Page 5
                                           4 - Dimensional Data (in mm)

Models 06 / 08 and 06R / 08R




                                                                                                                     905
                                                                        4
                       20                                                                                    20

                                                                       1141.6


                                                                        Face view

                                              400.5



                                                       6
                            3

                                 82
                                       5           1                            1   Water inlet
                                                           105
                                                                                2   Water outlet (Basic version)
     845




                                                                                3   Water outlet (Pack version)
           590




                                                                                4   Ø 13 mm fixing holes (x 4 nos)
                                                   2
                                                                                5   Power supply cable entry
                                                                 105
                 120




                                                                                6   Main disconnect switch (optional)


                                               4
                                22.5          349


                                  Side view


Page 6
                                                   5 - Installation

                 5.1 - Unit Handling

                                                                                          800 mm
                                                                          40
                         Warning                                            0
                                                                                m
                                                                                   m
 Sharp edges and coil surfaces are a potential hazard.
 Avoid contact with them.                                                                                                         m
                                                                                                                          400 m

Be careful to avoid rough handling of the unit. Do not push
                                                                               m
or pull the unit anything other than the base. Block the             500 m                                       80
pushing vehicle away from the unit to prevent damage to                                                               0
                                                                                                                          m
the sheet metal cabinet and end frame (see Figure 1).                                                                         m


                                                                                                     200 mm*

               Blocking required across
                                                                                       * for reverse cycle models only.
               full width                                        Fig. 2


                                                                 circulation across the unit (se figure hereafter).
                                                                 Care should be taken, at the time of installation, to leave
                                                                 enough clearances around the unit for maintenance works.
                                                                 The minimum clearances are shown on figure 2 and must
                                                                 be considered, both to ensure that the unit operates
                                                                 correctly and to allow easy access.
                                                                 The units should be installed on a flat and hard, preferably
Fig.1                                                            concrete base.
                                                                 When fixing the unit, a slope of 1 cm/m is recommended to
                                                                 allow draining of rain water.
                                                                 For reverse cycle models, if the outdoor temperature is
         5.2 - Installation Instructions                         likely to fall below +1 °C, provide a system to prevent the
                                                                 condensates from freezing (e.g. heating cord).
                                                                 For installation in difficult climates, temperatures below
Unit placement                                                   0 °C, snow or humidity, it is recommended to elevate the
                                                                 unit about 20 cm above the floor.
The WMC water chillers are cooled by air. Thereby, they
must be installed in the open air, in an area where the flow
of air to and from the condenser coil must not be limited. A
                                                                                            Warning
space restriction, which reduces the air flow, will decrease
the cooling capacity, increase the power input and, in some
                                                                  The plastic grille is used to protect the operators from
cases, prevent the unit from operating because of an excess
                                                                  injury risks on heat exchanger at the time of handling
of condensation pressure.
                                                                  and installation.
The WMC water chillers are equipped with propeller type           However, risks of clogging by freeze or hoar frost can be
condenser fan. Therefore, they will not operate with              occured on reverse cycle units installed in cold or
ductwork on the fan outlet.                                       mountainous regions and exposed to the elements.
In case of installation in an area subject to be hit by strong    To prevent all risks, a shelter is to be provided or simply
wind, direct effect of the wind on the discharge surface of       remove the protective grille.
the fan should be avoided. Arrows show the direction of air




                                                                                                                                  Page 7
                                         5 - Installation (cont'd)

   5.2 - Installation Instructions (cont'd)

Fixing dimensions
The fixing dimensions of the unit are shown on the figure
opposite.

Vibration isolators are recommended for all roof mounted
installation or wherever vibration transmission is a
consideration.

Figure 3 shows the location of each isolator.                      Fig. 3


Maintenance access
After installation, each side of the unit must allow easy         expansion tank are accessible after removing the panel 2
access for periodic maintenance works.                            (see photo 3).
The removal of panel 1 allows access to compressor,               Remark : The panel 1 is removable independently of other
refrigerant circuit as well as hydronic module (for Pack          panels and allows a start-up by maintaining the operating
version) (see photo 2). The fan-motor assembly and                characteristics of the unit.



         1                         2




                                                           Water tank                                 Expansion tank
  Photo 1                                       Photo 2                               Photo 3




Page 8
                                          6 - Water Connections

                 6.1 - Water Piping                                                               Caution
                                                                      It is not our policy to make recommendations on water
Local authorities can supply the installer with the proper            treatment. The general contractor or owner should
                                                                      contact a local water treatment company regarding water
building and safety codes required for safe and proper
                                                                      treatment. However, this topic is critical and care should
installation.                                                         be taken to make sure it is done properly to prevent
                                                                      problems related to flow. A fouled water system will lead
Recommendations : Install piping with minimum bends                   to premature component failure.
and changes in elevation to minimize pressure drop.
Consider the following when installing water piping :
                                                                                                  Caution
1.   Vibration eliminators to reduce vibration and noise              Water connections could be damaged by an important
     transmission to the building. Check the free volume              stress when screwing them. Use a second spanner to
     expansion of the connection piping.                              compensate the stress of tightening.

2.   Shut-off valves to isolate the unit from the piping
     system during unit servicing.

3.   Manual or automatic air vent valves at the highest                                                     Remote On/Off
                                                                             Departure
     points of the chilled water piping.                                                                    (not supplied)

4.   A means of maintaining adequate system water
                                                                                                             Power supply
     pressure (expansion tank or regulating valve).                                                          cable entry

5.   Temperature and pressure indicators located at the
     unit to aid in unit servicing.
                                                                                                            Remote
6.   To avoid all risks of penetration of foreign matters                                                   Summer/Winter
     and to keep system performance up, it is                                                               (not supplied)
     mandatory to install a strainer (with mesh lower
     than 1 mm) at the inlet of the unit (see figure 4).

Protection from freezing
It is recommended to protect the water system from freezing                                                      Return
whatever the model used (cooling only or reverse cycle).
The table below shows the anti-freeze concentration to be             The set of water
used depending on the minimum outdoor temperature.                    filter/shut-off   valve
                                                                      (accessory) is to be
   Minimum                                                            connected at the inlet of
                                                                      the machine by keeping
    outdoor         0      -5     -10    -15     -25    -30           the sieve of the filter
  temp. in C                                                          turned downwards.
 Concentration
                    10     20     30      40     50     60             Fig. 4             Drain
     in %



 6.2 - Safety Differential Pressure Switch

A safety differential pressure switch (ref. 6) is factory mounted on water inlet piping of evaporator, in order to ensure adequate
water flow to evaporator before starting up the unit.
It comes into operation in case of drop in water flow owing to the fact that the pump failed to operate.
The safety differential pressure switch is the main protective device of the machine.




                                                                                                                             Page 9
                                                     6 - Water Connections (con't)

                                    6.3 - Hydronic Module

The hydronic module requires no particular maintenance. Installation of water filter (accessory) on the inlet of unit water piping is mandatory
(see paragraph 6.1).
Remark : Make certain all unit components are protected for freezing caused by low outdoor temperature. Make sure that, in case of
accidental power failure, this information is recorded.
Important : For all air conditioning installation with a chilled water distribution, it is necessary that the whole distribution system must be sized
to restore a volume of 15 liters/kW installed.


               8                                                                 Principle diagram - Models 06/08 & 06R/08R

                                                                                             Legend :
                                                                                             1. Water tank
                                                              5
           7                                                                                 2. Expansion tank (2 liters)
                                                                                             3. Inflation valve
                                                                                             4. Heat exchanger
                                                                                             5. Water pump
                                                                                             6. Safety differential pressure switch
           4                                                                                 7. Manometer & Relief valve
                                                 8                 1                         8. Manual air venting
                                                                                             9. Drain

                                                 6                                           Note : standard safety valve is calibrated at 3.0 bar.


 9                                                                  2

                                                                             3




     6.4 - Unit Manometric Head Curves

                                                       Models 06 / 06R (without water filter)
                                        70


                                        60
               Manometric head in kPa




                                        50                                       Sp
                                                                                   ee
                                                                                     d
                                                                             Sp          3
                                        40
                                                                               ee
                                                                                 d
                                                                                     2
                                        30
                                                                   Sp
                                                                     ee




                                        20
                                                                       d
                                                                         1




                                        10


                                         0
                                             0       500          1000               1500                  2000                2500

                                                                   Water flow in l/h



Page 10
                                                          6 - Water Connections (con't)

    6.4 - Unit Manometric Head Curves
                  (con't)

                                                                 Models 08 / 08R (without water filter)
                                        70


                                        60

                                                                                                      Sp
               Manometric head in kPa




                                        50                                                              ee
                                                                                                 Sp       d3
                                                                                                   ee
                                                                                                     d
                                        40                                                               2


                                        30
                                                                                       Sp
                                                                                         ee
                                                                                           d
                                                                                           1

                                        20


                                        10


                                         0
                                             0                 500               1000              1500               2000                2500

                                                                                  Water flow in l/h

                                                                                               flows and the diameter of standard copper pipes for
     6.5 - Pressure Drop in Tubes and                                                          hydraulic installations.
                Accessories                                                                    The grey area shows pressure drop in mm of water
                                                                                               gauge / m and the velocity in m/s recommended for various
To determine the appropriated pipe section, see table n° 1                                     flows and diameters.
which shows the values of pressure drop for various water
                                                                                               Intermediate values are determined through interpolation.
Table n° 1                                                                                     Values outside the grey area correspond to excessive
                                             Pressure drop (mm WG / m)                         pressure drops and should be avoided.
  Flow
  (l/h)                                            Velocity (m/s)                              Table n° 2 shows the equivalent length pipe with the same
                                                 Nominal diameter                              diameter, of a few common accessories for this type of
             13 x 15                         16 x 18   20 x 22       26 x 28   33 x 35         installation.
               86                              32
  400                                                                                          Table n° 2
              0.84                            0.55
              172                              65        22                                                              Equivalent length (m)
  600
              1.25                            0.83      0.53
              286                             108        37            10                       Accessories               Nominal diameter
  800                                                                                                          13 x 15 16 x 18 20 x 22 26 x 28 33 x 35
              1.67                            1.11      0.71          0.42
                                              158        55            16         5              Ball check
  1000                                                                                                          0.2          0.2   0.3           0.4    0.5
                                              1.38      0.88          0.52      0.32               valve
                                              216        75            22         7                 45
  1200                                                                                                          0.2          0.2   0.26      0.35       0.5
                                              1.65      1.06          0.63      0.39               Bend
                                              284        99            28         9                 90
  1400                                                                                                          0.4          0.4   0.5           0.7     1
                                              1.93      1.24          0.73      0.45               Bend
                                                        124            36        12
  1600                                                                                              90
                                                        1.41          0.84      0.52                            0.3          0.3   0.4           0.6    0.86
                                                        133            44        14               Curve
  1800                                                                                            T-piece       0.8          0.8    1            0.5     2
                                                        1.59          0.94      0.58
                                                        184            52        17
  2000
                                                        1.77          1.04      0.65           1 mm WG = 9.81 Pa.
                                                        217            62        20
  2200
                                                        1.94          1.15      0.71
                                                        254            72        23
  2400
                                                        2.12          1.25      0.78


                                                                                                                                                       Page 11
                                                  6 - Water Connections (con't)

                                                6.6 - Heat Exchangers Water Pressure Drop
                           Pressure drop, kPa




                                                                                                A      WMC 06 / 06R


                                                                                                B      WMC 08 / 08R




                                                       Water flow, l/s



                                                  6.7 - Principle Diagram of Water Circuit
Maximum height 15 meters




                                                                         The WMC water chillers are to be connected with the terminal
                                                                         units such as fan coil units, cassettes or wall mounted units.
                                                                         Each terminal unit connected with the WMC water chiller and
                                                                         provided with its own control is therefore completely independent
                                                                         of the chiller (see diagram of principle on the left).
                                                                         * If the terminal unit is on a lower level than the WMC water chiller,
                                                                         make sure the water pressure in the chiller is at least 0.5 bar.
                   *




Page 12
                                               7 - Field Wiring

Power Supply Connections                                     screw driver point of 3.5 mm x 0.5 mm in the square hole as
                                                             shown on photo n° 5.
Check before connecting the unit that the power supply       The wires must be bare 7 mm in length.
characteristics correspond to the data mentioned on the
unit name plate and in the table of unit electrical
characteristics.                                                                     Warning
Important : It is for Contractor to install close to the      Field wiring must be installed according to unit wiring
machine a protective and disconnect device adapted to         diagram located inside the unit control box.
the unit capacity (see table of unit electrical data on
pages 4 and 5). This device is available as accessory.
Please consult us.
The electrical connections should be made with the main                              Warning
power supply disconnected, by using the rule book.            Use only copper wire for all power lead terminations at
To perform the electrical connections :                       the unit. Aluminium or copper can be used for all other
                                                              wiring. Wiring must be sized in accordance with the
   -   Remove the inspection panel which gives access
                                                              IEC Codes.
       to the electrical box.
   -   Pass the power supply cable through the cable entry
       located on the unit.
                                                                                     Warning
   -   Put in place the end pieces that fit the section of
       connecting cable, to guarantee a good contact.         Unit must be grounded through terminal provided inside
                                                              electrical panel.
Remark : The electrical panel is equipped with a spring
type terminal block (photo 4) which allows a quick and
reliable setting to work without requiring any
maintenance by comparison with the srew type terminal                                Warning
block.
                                                              The supply voltage must not vary more than 10 %. the
All connections are done on terminal block without screws.    unbalance between the phases must not exceed 3 %.
To insert the cables into the terminal block, introduce a




                        Terminal
                        block
 Photo 4                                                      Photo 5




                                                                                                                Page 13
                               7 - Field Wiring (cont'd)

Example of wiring diagram, sizes 06 / 06R and 08 / 08R - 230 V / 1 ph / 50 Hz




                ALWAYS REFER TO THE UNIT WIRING DIAGRAM LOCATED INSIDE THE
                                    ELECTRICAL PANEL


Page 14
                                                      8 - Controls

          8.1 - Temperature Controller                                              8.2 - Antifreeze Function

The controller fitted on COOLING ONLY units is factory                  On all units, the antifreeze protection (ensured by controller)
calibrated for operation on return water temperature. For               puts them in safety shutdown if the leaving water
this reason, the controller sensor is located at the evaporator         temperature is equal or lower than +4 °C.
inlet in order to control the system cooling load. The
                                                                        The antifreeze protection completes the action of differential
necessary setting of the controller is the set point adjustment         pressure switch (see paragraph 6.2).
only; this can be adjusted in a setting range from +10 °C to
+21 °C. The factory setting is +12 °C for COOLING ONLY
units. In the case of REVERSE CYCLE units, the controller
                                                                          8.3 - Low Ambient Operation Function
can be adjusted in a setting range from +10 °C to +21 °C
with factory setting at +12 °C (cooling mode) and in a setting
range from +21 °C to +49 °C with factory setting at +40 °C              The low ambient operation function is provided as standard
(heating mode).                                                         on all versions. It allows the operation in summer mode
                                                                        with outdoor temperatures relatively low.
Note : for set points lower than +10 °C (on return water),
consult the factory about the precautions to be considered              It modulates the rotational speed of condenser fan in
for a good operation of the machine (use of glycol in water             response to the condensation temperature measured by
circuit is mandatory).                                                  the sensor. This function is managed by the main controller.


Controller display panel

      A         B        E               F

                                                                               Leds
          1 2                                                                  - Compressor 1 led       A    :
                                                    mode                          • BLINK : time delay is in progress,
                                                                                  • ON if compressor 1 is active,
                                                                  set             • OFF if compressor 1 is off.
                                                                               - Compressor 2 led        B : not used.
                                                    on off                     - Defrost led     C :

                                        MICROTECH                                 • BLINK : demand is in progress,
                                                                                  • ON : defrosting is in progress,
            D C                                                                   • OFF : defrosting is disabled or has been
                                                                                      completed.
The controller provides information on status of operation,
configuration and alarms through a display and LEDs on the front               - Electric heater led     D : not used.
panel.                                                                         - Heating led E ("Sun" symbol) : ON if heating
                                                                                 mode has been selected.
Display
It allows mainly to show :                                                     - Cooling led F ("Snow" symbol) : ON if cooling
                                                                                 mode has been selected.
- the entering water temperature of the unit in tenths of degrees
  Celsius with a decimal point,                                                If neither the HEATING led nor the COOLING led is
- the alarm code if at least one alarm is active.                              on, the controller is in STAND-BY mode.




                                                                                                                              Page 15
                                                         9 - Start-up

                  9.1 - Pre Start-up                                                 9.2 - Unit Start-up

Before starting up the unit, a certain number of verifications   After checking all electrical connections and the conformity
                                                                 with the standards, proceed the start-up as follows :
must be performed on the installation to ensure that the         - With the power supplied to the unit, if the decimal point
unit will operate under the best possible conditions. The          appears on the display, it means that the controller is in
                                                                   OFF position.
check list below is not exhaustive and should only be used
                                                                 - Hold down the ON-OFF key for 2 seconds to turn the
as a minimum reference basis.                                      controller to ON position. The return water temperature
                                                                   value is then displayed on the screen.
1.   Make certain fan rotates freely.                            - Cooling only units :

2.   Inspect all water piping for flow direction and correct        • Press the MODE key to start-up the unit; the Cooling
                                                                       led is on. When the Compressor led blinks, it means
     connections at the evaporator.                                    that the unit is on a call for cooling.
                                                                    • To stop, press again the MODE key.
3.   Verify all system piping is correct for operation as per
                                                                    • Each time the MODE key is pressed, the following
     installation requirements.                                        sequence occurs :

4.   Verify minimum cooling load equal or above 60 % of                Standby !" Cooling !" Standby
                                                                 - Reverse cycle units :
     maximum load is available at the start-up.
                                                                    • For operation during summer, proceed as the cooling
5.   Check voltage of the unit power supply and make                   only units.

     certain voltage is within authorized limitations.              • For operation in heating mode, press a second time
                                                                       the MODE key; the Heating led is on. To stop, press
6.   Make sure unit is properly grounded.                              again the same key.
                                                                    • Each time the MODE key is pressed, the following
7.   Check the presence of protective and disconnect                   sequence occurs :
     device.                                                           Standby !" Cooling !" Heating !" Standby

8.   Check all electric connections for tightness.               Note : In case of fault status occurs, a 24 volts AC signal is
                                                                 generated between 2 terminals (n° 7 and 8) provided for
9.   Check all piping for leaks and vent the air from the        that effect.

     evaporator as well as from the system piping before
                                                                                          Warning
     starting the compressor. When using glycol solution,
                                                                  Do not turn suddenly the heating position to the cooling
     make sure that the water/glycol mixture is well              one, but wait for the system water temperature to fall
                                                                  down below +25 °C.
     proportioned.




Page 16
                                             9 - Start-up (cont'd)

             9.3 - Set-point Change                                           9.4 - Main Alarms List

- Put the unit into standby mode (with the help of              E01 : High pressure fault.
  MODE key).                                                    E02 : Low pressure fault.
- Cooling only units :                                          E41 : Lack of water flow fault.
  1) Press simultaneously the MODE and ON-OFF keys              E42 : Antifreeze fault of leaving chilled water.
     and release them immediately : the message "SET"           For information on other alarms, consult our After-Sales
     is displayed on the screen.                                Department.
  2) Repeat action 1) : the message "Coo" will appear on        After eliminating the faults, reset alarms by pressing the
     the display.                                               ON-OFF key.
  3) Repeat action 1) to display the set-point. To modify it,
     use key UP or DOWN.                                                                 Warning
     To memorize the modification, press simultaneously          On the 3-phase models, the Scroll compressors
     the MODE and ON-OFF keys for 5 seconds; the                 compress the refrigerant gas only by rotating in one
     message "Coo" will appear on the display. Repeat            direction.
     this action a second time to display the                    To make sure that the direction of rotation is correct, it is
                                                                 sufficient to check a decrease of the suction pressure
     message "SET", a third time to return to the normal
                                                                 and a rise of the discharge pressure at the start-up of the
     display.                                                    compressor.
- Reverse cycle units :                                          When the compressor turns in the opposite direction,
  # Do steps 1) and 2) as described above, then press            the sound level is much more higher and the absorbed
                                                                 current is much more lower than the values indicated in
     one of the two UP and DOWN keys to display the
                                                                 the documentations.
     message "HEA".
                                                                 There is no risk of deterioration of the compressor that is
  # Do step 3) to change the heating set-point, then return      protected by an internal device.
     to the normal display.




                                                                                                                       Page 17
                                                 10 - Maintenance

Maintenance on this equipment are to be performed by                                        Warning
qualified personnel. Causes for repeated tripping of safety
controls must be investigated and corrected.                       Disconnect all power before doing any maintenance
                                                                   works inside the unit.
The units are designed to operate for long periods of time
with a minimum of maintenance. However, certain preventive
maintenance operations must be performed at least evey
six months and after any extended shut down period (cold          Evaporator
period).                                                          Evaporator is a dry expansion, high efficiency, brazed plate-
These operations are mostly routine checks such as                to-plate type heat exchanger consisting of stainless steel
inspection of set points and cutoff points, inspection of         plates brazed together. No particular maintenance is
voltages and currents, inspection of water flow rates             required, but it is mandatory to install a strainer (with
and temperatures, etc.                                            mesh lower than 1 mm) on the inlet of evaporator water
                                                                  piping to prevent foreign matters from entering and
Extended shutdown                                                 clogging the heat exchanger. Check regularly the
The following recommendations may be considered for               cleanness of the strainer.
extended shutdown of unit:
                                                                  Capillary tube
- After the compressor has pumped down, turn off the chilled
  water pump(s).                                                  The capillary tube does not require any particular
                                                                  maintenance.
- Disconnect all electrical power supply to the unit and to
  the chilled water pump(s).
                                                                  Reverse cycle 4-way valve (MHP units)
- If glycol is not used in the system, drain all water from the
  machine and chilled water piping, if the unit is to be shut     The 4-way valve allows the cycle reversal for the defrosting
  down during winter.                                             (hot water production mode) and the operation in chilled
                                                                  water production mode. This valve is factory calibrated and
Fan motor bearings                                                wired; it does not require any particular maintenance.

The fan motor bearings are of permanently lubricated type.        Expansion tank of hydronic module
No lubrication is required. However, check all moving parts
for important vibration and for wear and tear every 6             Check annually the gas pressure inside the expansion tank.
months and replace them if necessary.
                                                                  The pressure of the expansion tank should be 0.5 bar lower
                                                                  than the water filling pressure of the installation. The
Electrical terminal block
                                                                  pressure of the expansion tank should be adjusted before
The terminal block is a spring type one which does not            filling the unit with water.
require any maintenance.
                                                                  If the installation is located on a roof or at the same level as
Condenser coils                                                   the terminal units, the pressure should be at least 0.5 bar.

Condenser coils do not require any particular maintenance         If there is a height difference between the chiller and the
except the occasional removal of dirt and debris from the         terminal units, the pressure is equal to the height difference
outside surface of the fins. In case of corrosive atmosphere,     of water plus 0.2 bar (mini 0.5 bar).
provide a corrosion protection accordingly. Coils may be
cleaned with a low pressure water supply and mild                 To avoid untimely opening of the safety valve, the maximum
detergent.                                                        pressure of water circuit, when operating in heating mode,
                                                                  should not exceed 2.5 bar.




Page 18
                                       11 - Main Spare Parts List *


Models                                                                        06 / 06R                       08 / 08R
Condenser coil                                                              Q5FSTT250                      Q5FSTT250

Single phase compressor                                                     Y3CPGF091                      Y3CPGF092

3-phase compressor                                                                -                        Y3CPGF080

Evaporator                                                                  F4DEVP055                      F4DEVP056

Water pump                                                                  Y2MELE063                      Y2MELE063

Water tank                                                                  Q5FSTT253                      Q5FSTT253

Motor                                                                       M4ALDA240                      M4ALDA240

Propeller fan                                                               V3THEC909                      V3THEC909

High pressure switch                                                        R2PBPR049                      R2PBPR049

Low pressure switch                                                         R2PBPR048                      R2PBPR048

Controller                                                                  R1TSEC167                      R1TSEC167

Sensor                                                                      R1TSEC166                      R1TSEC166

Water filter + isolating valve                                              C8F006001                       C8F006001

Safety differential pressure switch                                         R2PMRP050                      R2PMRP050

Expansion tank                                                              F4VRND015                      F4VRND015

Fan protective grille                                                       V3RGRP749                      V3RGRP749

* Consult our Spare Parts Department for other parts.




                         12 - In-Warranty Return Material Procedure

Material must not be returned without permission of our After Sales Department. To return the material, contact your nearest
sales office and ask for a "return voucher". This return voucher shall be sent out with the returned material and shall contain
all necessary information concerning the problem encountered. The return of the part does not constitute an order for
replacement. Therefore, a purchase order must be entered through your nearest distributor or regional sales office. The order
should include part name, part number, model number and serial number of the unit involved.
Following our personal inspection of the returned part, and if it is determined that the failure is due to faulty material or
workmanship, and in warranty, credit will be issued on customer's purchase order. All parts shall be returned to the our factory,
transportation charges prepaid.




                                 13 - Service and Spare Parts Order

The model number, the confirmation number and the unit serial number indicated on the name plate must be provided
whenever service works or spare parts are ordered.
For any spare part order, indicate the date of unit installation and date of failure. Use the part number as shown in the table
above or, if it is not available, provide full description of the part required.




                                                                                                                         Page 19
With a concern for a constant improvement, our products can be modified without notice. Photos non contractual.


                                                                        Your distributor :


                                                           R




                                                                     îôèñ (095) 797-9988                ñàéò www.ventrade.ru
                                                                     ñåðâèñ (095) 787-3315             ïî÷òà info@ventrade.ru


       Wesper S.A. - 42 cours Jean Jaurès - 17800 Pons - Tel : +33-5 46 92 33 33 - Fax : +33-5 46 91 26 44 - www.wesper.com

				
DOCUMENT INFO
Shared By:
Categories:
Tags:
Stats:
views:3
posted:10/23/2012
language:English
pages:20