									Z-015 Temporary equipment – check list

G - Container for diesel enginer
                                                                                                Rev. 3, june 2004



Contractor:                                              Contact person contractor/telephone:

Container/equipment ID number                            Approve for location in zone:
                                                         (Zone 1, Zone 2 or non-hazardous area)
Company/installation container intended for:             Contact person/requisitioner in the company:


                       Person in the company responsible for prior approval, see 4.8.3:
Name:                                                    Telephone:           Date approval received:



Status: OK=Approved, NA=Not Applicable, NC=Not Checked, D=Defective or missing
                                                                       Ref. Status Receiving         Remarks
                                                                      Z-015 supplier control
                                                                                    (company)
     1-MECHANICAL
 1.1 Signs tagging/labelling                                           4.6
 1.2 Annual control (lifting equipment, cert.)                        4.4.1
 1.3 Mech. Cond. (lifting eyes/points, structure)                     4.4.1
 1.6 Self-closing doors                                               4.4.1
 1.8 Mechanical ventilation                                           4.4.7
 1.9 Noise                                                            4.4.8
     2-FIRE, GAS AND SAFETY
 2.1 Gas detector in air inlet                                        4.4.3
 2.2 Fire/smoke detector                                              4.4.2
 2.4 Portable fire extinguisher                                       4.4.2
 2.6 Alarm and shutdown if loss of pressurisation/ventilation         4.4.7
 2.7 Room fire extinguishing system                                   4.4.2
     3-ELECTRICAL
 3.1 Cables, nipples, equipment etc.                               4.4.6.1
 3.2 Insulation resistance - megging                                  4.8.1
 3.3 Earthing (NB bonding of structure)                            4.4.6.3
 3.4 All external installation Ex-proof                            4.4.6.2
 3.5 All internal installation Ex-proof                            4.4.6.2
 3.6 Emergency lighting                                            4.4.6.2
     4-HOOK-UP TO INSTALLATION
 4.1 Power supply (voltage, freq., plugs)                              4.7
 4.4 Alarm signal to control room with plug                            4.7
 4.5 Shutdown (ESD) from CCR (for battery system etc.)                4.4.3



                                                                                                    Side 1 of 2
Z-015 Temporary equipment – check list

G - Container for diesel enginer
                                                                    4.4.6.4
     5-EQUIPMENT
 5.1 Manual emergency stop                                          4.4.8
 5.2 Manual shutdown of diesel supply                               4.3.1
 5.3 Drip trays                                                     4.3.1
 5.4 "Rig saver" in combustion air inlet                            4.3.1
 5.5 Shutdown if loss o foil pressure                               4.3.1
 5.6 Shutdown if high cooling water temperature                     4.3.1
 5.7 Shutdown if overspeed                                          4.3.1
 5.8 Diesel engine approved for zone 2                              4.3.1
 5.9 Gas detector in combustion air inlet                           4.3.1
5.10 Flame arrester in exhaust pipe                                 4.3.1
5.11 Spark arrester in exhaust pipe                                 4.3.1
     6-DOCUMENTATION
 6.1 Lifting certificate                                             4.8
 6.2 Other technical doc. (drawings, data.)                          4.8
 6.3 Certificate for equip. With special requ.                       4.8
 6.4 Maintenance programme                                           4.8
 6.5 Maintenance journal                                             4.8
 6.6 User manual                                                     4.8


            Competent                                Supplier                            Company
person for lifting gear/mechanical                  electrician                       receiving control
              devices
 Date:                                  Date:                                 Date:
          Signature                              Signature                            Signature

          Name in capitals                       Name in capitals                     Name in capitals


General commentary: