INSTALLATION GUIDE

Document Sample
INSTALLATION GUIDE Powered By Docstoc
					INSTALLATION GUIDE
Connecting detectors & call-points to a zone:

                       + in        + out            + in     + out            + in        + out         + in        + out          + in      + out
    +

PANEL
   _

                        - in       - out         - in          - out          - in        - out           - in      - out      - in            - out   END OF LINE MODULE




Connecting only call-points to a zone:

                       + in        + out            + in     + out            + in        + out
    +

PANEL                                                                                                                       END OF LINE MODULE
   _

                        - in       - out            - in     - out            - in        - out



Connecting detectors only to a zone:
                      + in      + out               + in     + out            + in        + out         + in        + out
    +

PANEL
   _

                        - in       - out         - in          - out          - in        - out           - in      - out                 END OF LINE MODULE


 The Mag panel recognises 470 ohms as fire condition.

 It is recommended that all detection devices that are used on a Mag panel are fitted with a 470 ohms monitoring resistor as standard.

 All detector bases should be fitted with a SCHOTTKY diode (diode type: BYV-1060)

				
DOCUMENT INFO
Shared By:
Categories:
Tags:
Stats:
views:32
posted:9/1/2012
language:English
pages:1