									Medium Voltage Distribution




Application Catalogue
A tool for all MV equipment designers

May 2008
Application Catalogue         Contents
A tool for all MV equipment
designers



                              Presentation
                              General                4

                              User guide             5

                              Selection tables       6



                              Application
                              Substation feeder     10

                              Substation incomer    12

                              Bus tie               14

                              Bus riser             16

                              Busbar VT’s           17

                              Transformer feeder    18

                              Transformer incomer   22

                              Motor feeder          24

                              Generator incomer     26




DEAI06EN.indd                                        3
Presentation   General



               The Medium Voltage Application Catalogue is a tool for all Medium Voltage
               equipment designers.



               Purpose
               b To help you produce Medium Voltage switchgear assemblies which include
               Schneider Electric components
               b To help you specify standard solutions.



               How?
               By offering you standard applications for the protection of different Medium
               Voltage network configurations.
               By providing you with a guarantee of the full protection chain composed
               of different Schneider Electric components.

               b With specification of the equipment required for each standard application
               b And the complete wiring diagram of the Medium Voltage equipment
               for each application.




4                                                                                   DEAI06EN.indd
Presentation    User guide



                Step 1: Selection table
                Using the selection table, you select your application from the different
                standard applications offered:

                b Based on the network component to be protected:
                substation incomer or feeder, transformer, motor or generator
                b Based on the formulated protection, metering and monitoring
                requirements
                The application chosen from the selection table is detailed in the application
                pages.



                Step 2: Application page
                Each standard application is presented in a page which includes:

                b A single-line diagram of the application, with the different components
                to be combined:
                v Switching device
                v Measurement sensors
                v Protection unit
                v Details of the functions offered by the protection unit:
                v Protection functions
                v Monitoring and control functions
                b Optional functions available
                b Reference of the complete wiring diagram for the application.



                Step 3: Wiring diagrams
                A diagram library on CD-ROM contains the wiring diagrams,
                in AutoCad format, of all the standard applications offered.

                Each diagram:
                b Corresponds to a standard application
                b Contains all the information required for the complete wiring, power
                and control current, of the Medium Voltage equipment
                b May be easily adapted by you to match the options you choose
                and your particular needs.




DEAI06EN.indd                                                                                    5
Presentation                                                       Selection tables



Application                                                                        Line or substation
                                                                                   Feeder                         Incomer
Protection and control type                                                        S1     S2      S2      S2      S3      S3      S3      S4
Page No.                                                                           10     11      11      11      12      12      12      13
Sepam series 20                                                                    S20                                                    S20
Sepam series 40                                                                           S40     S41     S42     S40     S41     S42
NEX 17.5 kV diagram 5130…                                                          7350   7356    7358    7360    7357    7359    7361
NEX 24 kV diagram 5130…                                                            7373   7378                    7379                    7374
 Protection function                                                ANSI code
Phase overcurrent                                                   50/51          b      b       b       b       b       b       b       b
Voltage-restrained phase overcurrent                                50V/51V
Earth fault,                                                        50N/51N
                                                                                   b      b       b       b       b       b       b       b
sensitive earth fault                                               50G/51G
Breaker failure                                                     50BF                  b       b       b       b       b       b
Negative sequence/unbalance                                         46             b      b       b       b       b       b       b       b
Directional phase overcurrent                                       67                                    b (1)                   b
Directional earth fault                                             67N/67NC                      b       b               b       b
Directional active overpower                                        32P                           b (1)   b (1)           b       b
Directional reactive overpower                                      32Q/40
Thermal overload                                                    49RMS
Phase undercurrent                                                  37
Excessive starting time, locked rotor                               48/51LR/14
Starts per hour                                                     66
Positive sequence undervoltage                                      27D
Remanent undervoltage                                               27R
Undervoltage                                                        27/27S                b       b       b       b       b       b
Overvoltage                                                         59                    b       b       b       b       b       b
Neutral voltage displacement                                        59N                   b (1)   b (1)   b (1)   b       b       b
Negative sequence overvoltage                                       47                    b (1)   b (1)   b (1)   b       b       b
Overfrequency                                                       81H                   b (1)   b (1)   b (1)   b       b       b
Underfrequency                                                      81L                   b (1)   b (1)   b (1)   b       b       b
Rate of change of frequency                                         81R
Recloser (4 cycles)                                                 79             v      v       v       v                               v
Temperature monitoring (8 to 16 RTDs, 2 set points per RTD)         38/49T
Thermostat/Buchholz/DGPT
 Measurement and diagnostic
Phase current I1; I2; I3 RMS, residual current I0                                  b      b       b       b       b       b       b       b
Average current I1; I2; I3; peak demand current IM1, IM2, IM3                      b      b       b       b       b       b       b       b
Voltage U21; U32; U13; V1; V2; V3; residual voltage V0                                    b       b       b       b       b       b
Positive sequence voltage Vd/rotation direction; neg. seq. voltage Vi (only S40)          b       b       b       b       b       b
Frequency                                                                                 b       b       b       b       b       b
Active; reactive and apparent power P. Q. S
Peak demand power PM. QM                                                                  b       b       b       b       b       b
Power factor
Calculated active and reactive energy ( +/-W.h. +/- var.h)                                b       b       b       b       b       b
Active and reactive energy by pulse counting ( +/-W.h. +/- var.h)                         v (1)   v (1)   v (1)   v (1)   v (1)   v (1)
Temperature
 Network and machine diagnosis
Tripping context                                                                          b       b       b       b       b       b
Tripping current Trip1; Trip2; Trip3; Trip0                                        b      b       b       b       b       b       b       b
Unbalance ratio/negative sequence current Ii                                       b      b       b       b       b       b       b       b
Phase displacement ϕ0; ϕ1; ϕ2; ϕ3                                                         b       b       b       b       b       b
Disturbance recording                                                              b      b       b       b       b       b       b       b
Thermal capacity used
Remaining operating time before overload tripping
Waiting time after overload tripping
Running hours counter/operating time
Start current and time
Start inhibit time delay, number of starts before inhibition

b Standard
v According to parameter setting and MES module or MET module
(1) Not used in schematic diagram




6                                                                                                                                  DEAI06EN.indd
Bus tie        Bus riser Busbar VT’s Transformer                                                             Motor          Generator
                                     Feeder                                  Incomer                         Feeder         Incomer
S5     S6      B2       B1     B1      T1     T2     T3      T3      T6      T4      T4      T5      T5      M1     M2      G1
14     15      16       17     17      18     19     20      20      21      22      22      23      23      24     25      26
S20            B22      B21    B22     T20    T20                                                                   M20
       S40                                           T40     T42     T40     T40     T42     T40     T42     M41            G40
                        7354   7355    7351   7352   7362    7365            7363    7366    7364    7367    7353   7368    7369
7372   7377    7371            7370    7375   7376   7380            7382    7381            7383

b      b                               b      b      b       b       b       b       b       b       b       b      b       b
                                                                                                                            b

b      b                               b      b      b       b       b       b       b       b       b       b      b       b

b      b                                             b       b       b       b       b       b       b              b       b
b      b                                             b       b       b       b       b       b       b       b      b       b
                                                             b (1)                   b               b
                                                             b                       b               b              b
                                                                                                                    b       b
                                                                                                                    b       b
                                       b      b      b       b       b       b       b       b       b       b      b       b
                                                                                                             b      b
                                                                                                             b      b
                                                                                                             b      b
               b        b      b                                                                                    b
               b        b      b                                                                                    b
       b       b        b      b                     b       b       b       b       b       b       b              b       b
       b       b        b      b                     b       b       b       b       b       b       b              b       b
       b (1)   b        b      b                     b (1)   b (1)   b (1)   b (1)   b (1)   b (1)   b (1)          b       b
       b (1)   b (1)    b      b (1)                 b (1)   b (1)   b (1)   b (1)   b (1)   b (1)   b (1)          b       b
       b (1)   b        b      b                     b (1)   b (1)   b (1)   b (1)   b (1)   b (1)   b (1)          b (1)   b
       b (1)   b        b      b                     b (1)   b (1)   b (1)   b (1)   b (1)   b (1)   b (1)          b (1)   b
                               b

                                       v                             v                       v       v       v      v       v
                                              v      v       v               v       v

b      b                               b      b      b       b       b       b       b       b       b       b      b       b
b      b                               b      b      b       b       b       b       b       b       b       b      b       b
       b       b        b      b                     b       b       b       b       b       b       b              b       b
       b       b        b      b                     b       b       b       b       b       b       b              b       b
       b       b        b      b                     b       b       b       b       b       b       b              b       b

       b                                             b       b       b       b       b       b       b              b       b

       b                                             b       b       b       b       b       b       b              b       b
       v (1)                                         v (1)   v (1)   v (1)   v (1)   v (1)   v (1)   v (1)          v (1)   v (1)
                                       v      v      v (1)   v (1)   v (1)   v (1)   v (1)   v (1)   v       v      v       v

       b                                             b       b       b       b       b       b       b              b       b
b      b                               b      b      b       b       b       b       b       b       b       b      b       b
b      b                               b      b      b       b       b       b       b       b       b       b      b       b
       b                                             b       b       b       b       b       b       b              b       b
b      b       b        b      b       b      b      b       b       b       b       b       b       b       b      b       b
                                       b      b      b       b       b       b       b       b       b       b      b       b
                                       b      b      b       b       b       b       b       b       b       b      b       b
                                       b      b      b       b       b       b       b       b       b       b      b       b
                                       b      b      b       b       b       b       b       b       b       b      b       b
                                                                                                             b      b
                                                                                                             b      b




DEAI06EN.indd                                                                                                                       7
Presentation                                                    Selection tables (cont.)



Application                                                                 Line or substation
                                                                            Feeder                          Incomer
Protection and control type                                                 S1      S2      S2      S2      S3      S3      S3      S4
Page No.                                                                    10      11      11      11      12      12      12      13
Sepam series 20                                                             S20                                                     S20
Sepam series 40                                                                     S40     S41     S42     S40     S41     S42
NEX 17.5 kV diagram 5130…                                                   7350    7356    7358    7360    7357    7359    7361
NEX 24 kV diagram 5130…                                                     7373    7378                    7379                    7374
 Switchgear diagnostic                                          ANSI code
Cumulative breaking current                                                 b       b       b       b       b       b       b       b
Trip circuit supervision                                                    v       v       v       v       v       v       v       v
Number of operations, operating time, charging time                         v       v       v       v       v       v       v       v
CT/VT supervision                                               60FL                b       b       b       b       b       b
 Control and monitoring
Circuit breaker/contactor control                               94/69       v       v       v       v       v       v       v       v
Latching/acknowledgment                                         86          b       b       b       b       b       b       b       b
Logic discrimination                                            68          v       v       v       v       v       v       v       v
Switching of groups of settings                                             b (1)   b (1)   b (1)   b (1)   b (1)   b (1)   b (1)   b (1)
Logic equation editor                                                               b       b       b       b       b       b
 Optional features
8 temperature sensor inputs - MET148-2 module                               v       v       v       v       v       v       v       v
1 low level analog output - MSA141 module                                   v       v       v       v       v       v       v       v
Logic inputs/outputs - MES114 (10I/4O) module                               v       v       v       v       v       v       v       v
RS485 interface - ACE949-2 (2-wire) or ACE959 (4-wire) module               b       b       b       b       b       b       b       b
Test box                                                                    b       b       b       b       b       b       b       b
Local remote/switch                                                         b       b       b       b       b       b       b       b
 CT’s option
LPCT sensors                                                                b       b       b       b       b       b       b       b
Core balance CT                                                             v       v       v       v       v       v       v       v

b Standard
v According to parameter setting and MES module or MET module
(1) Not used in schematic diagram




8                                                                                                                            DEAI06EN.indd
Bus tie         Bus riser Busbar VT’s Transformer                                                                Motor           Generator
                                      Feeder                                     Incomer                         Feeder          Incomer
S5      S6      B2       B1      B1      T1      T2      T3      T3      T6      T4      T4      T5      T5      M1      M2      G1
14      15      16       17      17      18      19      20      20      21      22      22      23      23      24      25      26
S20             B22      B21     B22     T20     T20                                                                     M20
        S40                                              T40     T42     T40     T40     T42     T40     T42     M41             G40
                         7354    7355    7351    7352    7362    7365            7363    7366    7364    7367    7353    7368    7369
7372    7377    7371             7370    7375    7376    7380            7382    7381            7383

b       b                                b       b       b       b       b       b       b       b       b       b       b       b
v       v       v (1)    v (1)   v (1)   v       v       v       v       v       v       v       v       v       v       v       v
v       v                                v       v       v       v       v       v       v       v       v       v       v       v
        b                                                b       b       b       b       b       b       b               b       b

v       v       v (1)    v (1)   v (1)   v       v       v       v       v       v       v       v       v       v       v       v
b       b       b        b       b       b       b       b       b       b       b       b       b       b       b       b       b
v       v                                v       v       v       v       v       v       v       v       v       v       v       v
b (1)   b (1)                            b (1)   b (1)   b (1)   b (1)   b (1)   b (1)   b (1)   b (1)   b (1)   b (1)   b (1)   b (1)
        b                                                b       b       b       b       b       b       b               b       b

                                         v       v (1)   v (1)   v (1)   v       v (1)   v (1)   v       v       v       v       v
v       v       v        v       v       v       v       v       v       v       v       v       v       v       v       v       v
v       v       v        v       v       v       v       v       v       v       v       v       v       v       v       v       v
v       v       v        v       v       v       v       v       v       v       v       v       v       v       v       v       v
b       b       b        b       b       b       b       b       b       b       b       b       b       b       b       b       b
b       b                                b       b       b       b       b       b       b       b       b       b       b       b

b       b                                b       b       b       b       b       b       b       b       b       b       b       b
                                         b       b       b       b       b       b       b       b       b       b       b       b




DEAI06EN.indd                                                                                                                            9
          Application                                       Substation feeder S1



          b Protection against phase to phase               Protection
          and phase to earth short circuits                 Sepam S20
          b Detecting of unbalanced power supplied          b 50/51: overcurrent - IDMT, DT (4 settings)
          b Recloser                                        b 50N/51N: earth fault - IDMT, DT (4 settings)
                                                            b 46: negative sequence overcurrent.
          b It suited for integration into a supervisory
          system using Modbus serial interface.
          Several standard options are available
          to ensure maximum flexibility and cost
          effectiveness in meeting the requirements
                                                            Measurement and diagnostic
                                                            Sepam S20, LCD display LED (Light Emitting Diode)
          of different systems.                             b Phase current: I1, I2, I3 RMS
                                                            b Residual current: I0
                                                            b Average currents: I1, I2, I3
                                                            b Peak demand phase currents
                                                            b Tripping currents: I1, I2, I3, I0
DE56380




                                                            b Unbalance ratio/negative sequence current Ii
                                                            b Disturbance recording.
                      Trip/close(1)                         CT’s option
                                                            b CLP1: LPCT sensors 100 A to 1250 A
                                                            b Core balance CT: CSH120 or CSH200.
                             50/51           A      86
                             50N/51N        MD      74
                             46                     30
                                                    79(1)
                                                    68      Control
                                                             Sepam S20                                       Basic       MES114 module
                                                                                                             apparatus   (10 I/4 O)
                                                            Cumulative breaking current                      b           b
                                                            Trip CB output (O1)                              b           b
                                                            Closing lockout (O2)                             b           b
                     Analog Output                          Logic discrimination block send (O3)             b           b
                                                            Watch dog (O4)                                   b           b
                     Remote UMI
                                                            CB control (86)                                  b           b
                     Modbus RS485                           CB open/closed status indication                             b
                                                            Number of operations, operating time                         b
          Substation feeder S1                              Logic discrimination block receive                           b
                                                            External tripping                                            b
                                                            Trip circuit supervision (74)                                b
                                                            Fault and alarm contact (O11(2) to O14)                      b
                                                            Recloser 4 cycles (79)                                       b
          (1) Close by communication and recloser           External network time synchronization                        b
          (2) O11 reserved for closing order
                                                            External trip                                                b
                                                            Local/remote control selection                               b
                                                            Inhibition recloser                                          b

                                                            Optional features
                                                            b Communication interface module, 2 wires (ACE949-2) Modbus
                                                            b Communication interface module, 4 wires (ACE959) Modbus
                                                            b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
                                                            b Remote advanced UMI (type DSM303)
                                                            b Test box
                                                            b Local/remote switch
                                                            b Logic inputs and outputs module MES114 (10I/4O).




          10                                                                                                               DEAI06EN.indd
          Application                                         Substation feeder S2



          b Protection against phase to phase                 Measurement and diagnostic
          and phase to earth short circuits                   Sepam S40/S41/S42, LCD display LED (Light Emitting Diode)
          b Detecting of unbalanced power supplied            b Phase current: I1, I2, I3 RMS
          b Recloser                                          b Residual current: I0
                                                              b Average currents: I1, I2, I3
          b It suited for integration into a supervisory      b Peak demand phase currents
          system using Modbus serial interface.               b Line voltage: U21, U32, U13
          Several standard options are available              b Phase to neutral voltage: V1, V2, V3
          to ensure maximum flexibility and cost              b Residual voltage: V0
                                                              b Positive sequence voltage/rotation direction
          effectiveness in meeting the requirements           b Frequency
          of different systems.                               b Active, reactive and apparent power: P, Q, S
                                                              b Peak demand power PM, QM and power factor
                                                              b Active and reactive energy
                                                              b Tripping currents: I1, I2, I3, I0
                                                              b Unbalance ratio/negative sequence current Ii
DE56385




                     To Busbar VT’s                           b Phase displacement
                                                              b Disturbance recording
                                                              b Tripping context.
                                50/51               A    94
                                50N/51N             V    69   CT’s option
                                50BF                F    86   b CLP1: LPCT sensors 100 A to 1250 A
                     Open/close
                                46                 MD    74
                                                              b Core balance CT: CSH120 or CSH200.
                        trip
                                                   KW    30
                                    67N/67NC(1)   KVAR 68
                                                   KVA 60LF
                                    27/27S
                                    59
                                                   PF
                                                  KW.h
                                                         79
                                                              Control
                                                  KVar.h       Sepam S40/S41/S42                          Basic           MES114 module
                                                                                                          apparatus       (10 I/4 O)
                                                              Cumulative breaking current                 b               b
                                                              Trip CB output (O1)                         b               b
                                                              Closing lockout (O2)                        b               b
                                                              Logic discrimination block send (O3)        b               b
                             Analog Output                    Watch dog (O4)                              b               b
                                                              CB control (86)                             b               b
                             Remote UMI                       CB open/closed status indication                            b
                             Modbus RS485                     Number of operations, operating time                        b
                                                              Trip circuit supervision (74)                               b
          Substation feeder S2                                Logic discrimination block receive Bl1                      b
                                                              CB closing order                                            b
                                                              Fault and alarm contact (O11(2) to O14)                     b
                                                              Recloser 4 cycles (79)                                      b
          Protection                                          CB opening order                                            b
          Sepam S40/S41/S42                                   Inhibit closing                                             b
          b 50/51: overcurrent - IDMT, DT (4 settings)        External tripping                                           b
          b 50N/51N: earth fault - IDMT, DT (4 settings)      Local/remote control selection                              b
          b 50BF: breaker failure
                                                              Inhibition recloser                                         b
          b 46: negative sequence overcurrent - IDMT,
          DT (2 settings)                                     External network time synchronization                       b
          b 67N/67NC: directional earth fault (1) - IDMT,
          DT (2 settings)                                     Optional features
          b 27/27S: undervoltage (2 settings)                 b Communication interface module, 2 wires (ACE949-2) Modbus
          b 59: overvoltage (2 settings).                     b Communication interface module, 4 wires (ACE959) Modbus
                                                              b Logic inputs and outputs module MES114 (10I/4O)
                                                              b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
                                                              b Remote advanced UMI (type DSM303)
          (1) On Sepam S41 and S42                            b Test box
          (2) O11 reserved for closing order                  b Local/remote switch.




          DEAI06EN.indd                                                                                                                 11
          Application                                        Substation incomer S3



          b Protection against phase to phase                Measurement and diagnostic
          and phase to earth short circuits                  Sepam S40/S41/S42, LCD display LED (Light Emitting Diode)
          b Detecting of unbalanced power supplied           b Phase current: I1, I2, I3 RMS
          b It suited for integration into a supervisory     b Residual current: I0
                                                             b Average currents: I1, I2, I3
          system using Modbus serial interface.              b Peak demand phase currents
          Several standard options are available             b Line voltage: U21, U32, U13
          to ensure maximum flexibility and cost             b Phase to neutral voltage : V1, V2, V3
          effectiveness in meeting the requirements          b Residual voltage: V0
                                                             b Positive sequence voltage/rotation direction
          of different systems.                              b Frequency
                                                             b Active, reactive and apparent power: P, Q, S
                                                             b Peak demand power PM, QM and power factor
                                                             b Active and reactive energy
                                                             b Tripping currents: I1, I2, I3, I0
                                                             b Unbalance ratio/negative sequence current Ii
DE56386




                            Modbus RS485                     b Phase displacement
                                                             b Disturbance recording
                            Remote UMI                       b Tripping context.
                            Analog Output                    CT’s option
                                                             b CLP1: LPCT sensors 100 A to 1250 A
                                                             b Core balance CT: CSH120 or CSH200.
                                50/51         A    94
                                50N/51N       V    69
                                50BF          F    86
                                46
                                67(1)
                                             MD
                                             KW
                                                   74
                                                   30
                                                             Control
                                67N/67NC(2) KVAR 68           Sepam S40/S41/S42                          Basic           MES114 module
                                32P          KVA 60LF                                                    apparatus       (10 I/4 O)
                                27/27S       PF              Cumulative breaking current                 b               b
                                59          KW.h             Trip CB output (O1)                         b               b
                                59N         KVar.h
                                                             Closing lockout (O2)                        b               b
                                47
                     Open/close 81H                          Logic discrimination block send (O3)        b               b
                        trip    81L                          Watch dog (O4)                              b               b
                                                             CB control (86)                             b               b
                                                             CB open/closed status indication                            b
                                                             Number of operations, operating time                        b
          Substation incomer S3
                                                             Trip circuit supervision (74)                               b
                                                             Logic discrimination block receive Bl1                      b
                                                             CB closing order                                            b
          Protection                                         Fault and alarm contact (O11(3) to O14)                     b
          Sepam S40/S41/S42                                  CB opening order                                            b
          b 50/51: overcurrent - IDMT, DT (4 settings)       Inhibit closing                                             b
          b 50N/51N: earth fault - IDMT, DT (4 settings)     External tripping                                           b
          b 50BF: breaker failure
          b 46: negative sequence overcurrent - IDMT,        Local/remote control selection                              b
          DT (2 settings)                                    External network time synchronization                       b
          b 67: directional phase overcurrent (1) - IDMT,
          DT (2 settings)                                    Optional features
          b 67N/67NC: directional earth fault (2) - IDMT,    b Communication interface module, 2 wires (ACE949-2) Modbus
          DT (2 settings)                                    b Communication interface module, 4 wires (ACE959) Modbus
          b 32P: directional active overpower (2)            b Logic inputs and outputs module MES114 (10I/4O)
          b 27/27S: undervoltage (2 settings)                b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
          b 59: overvoltage (2 settings)                     b Remote advanced UMI (type DSM303)
          b 59N: neutral voltage displacement (2 settings)   b Test box
          b 47: negative sequence overvoltage                b Local/remote switch.
          b 81H: overfrequency (2 settings)
          b 81L: underfrequency (4 settings).


          (1) On Sepam S42 only
          (2) On Sepam S41 and S42
          (3) O11 reserved for closing order




          12                                                                                                               DEAI06EN.indd
          Application                                         Substation incomer S4



          b Protection against phase to phase                 Protection
          and phase to earth short circuits                   Sepam S20
          b Detecting of unbalanced power supplied            b 50/51: overcurrent - IDMT, DT (4 settings)
          b It suited for integration into a supervisory      b 50N/51N: earth fault - IDMT, DT (4 settings)
                                                              b 46: negative sequence overcurrent.
          system using Modbus serial interface.
          Several standard options are available
          to ensure maximum flexibility and cost
          effectiveness in meeting the requirements
          of different systems.
                                                              Measurement and diagnostic
                                                              Sepam S20, LCD display LED (Light Emitting Diode)
                                                              b Phase current: I1, I2, I3 RMS
                                                              b Residual current: I0
                                                              b Average currents: I1, I2, I3
                                                              b Peak demand phase currents
                                                              b Tripping currents: I1, I2, I3, I0
DE56381




                           Modbus RS485                       b Unbalance ratio/negative sequence current Ii
                                                              b Disturbance recording.
                           Remote UMI                         CT’s option
                           Analog Output                      b CLP1: LPCT sensors 100 A to 1250 A
                                                              b Core balance CT: CSH120 or CSH200.

                                  50/51             A
                                  50N/51N
                                                         86
                                                    MD   74   Control
                                                         30    Sepam S20                                       Basic       MES114 module
                                                         68                                                    apparatus   (10 I/4 O)
                                                              Cumulative breaking current                      b           b
                                                              Trip CB output (O1)                              b           b
                                                              Closing lockout (O2)                             b           b
                                                              Logic discrimination block send (O3)             b           b
                     Open/close                               Watch dog (O4)                                   b           b
                        trip
                                                              CB control (86)                                  b           b
                                                              CB open/closed status indication                             b
                                                              Number of operations, operating time                         b
          Substation incomer S4                               Logic discrimination block receive                           b
                                                              External tripping                                            b
                                                              Trip circuit supervision (74)                                b
                                                              Fault and alarm contact (O11(2) to O14)                      b
          (1) Close by communication and recloser             External network time synchronization                        b
          (2) O11 reserved for closing order                  External trip                                                b
                                                              Local/remote control selection                               b
                                                              Inhibition recloser                                          b

                                                              Optional features
                                                              b Communication interface module, 2 wires (ACE949-2) Modbus
                                                              b Communication interface module, 4 wires (ACE959) Modbus
                                                              b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
                                                              b Remote advanced UMI (type DSM303)
                                                              b Test box
                                                              b Local/remote switch
                                                              b Logic inputs and outputs module MES114 (10I/4O).




          DEAI06EN.indd                                                                                                                 13
          Application                                      Bus tie S5



          b Protection against phase to phase              Protection
          and phase to earth short circuits                Sepam S20
          b Detecting of unbalanced power supplied         b 50/51: overcurrent - IDMT, DT (4 settings)
          b It suited for integration into a supervisory   b 50N/51N: earth fault - IDMT, DT (4 settings)
                                                           b 46: negative sequence overcurrent.
          system using Modbus serial interface.
          Several standard options are available
          to ensure maximum flexibility and cost
          effectiveness in meeting the requirements
          of different systems.
                                                           Measurement and diagnostic
                                                           Sepam S20, LCD display LED (Light Emitting Diode)
                                                           b Phase current: I1, I2, I3 RMS
                                                           b Residual current: I0
                                                           b Average currents: I1, I2, I3
                                                           b Peak demand phase currents
                                                           b Tripping currents: I1, I2, I3, I0
DE56382




                                                           b Unbalance ratio/negative sequence current Ii
                                                           b Disturbance recording.
                       Trip/close(1)                       CT’s option
                                                           b CLP1: LPCT sensors 100 A to 1250 A
                                                           b Core balance CT: CSH120 or CSH200.
                              50/51        A        86
                              50N/51N     MD        74
                                                    30

                                                    68     Control
                                                            Sepam S20                                       Basic       MES114 module
                                                                                                            apparatus   (10 I/4 O)
                                                           Cumulative breaking current                      b           b
                                                           Trip CB output (O1)                              b           b
                                                           Closing lockout (O2)                             b           b
                   Analog Output                           Logic discrimination block send (O3)             b           b
                                                           Watch dog (O4)                                   b           b
                   Remote UMI
                                                           CB control (86)                                  b           b
                   Modbus RS485                            CB open/closed status indication                             b
                                                           Number of operations, operating time                         b
          Bus tie S5                                       Logic discrimination block receive                           b
                                                           External tripping                                            b
                                                           Trip circuit supervision (74)                                b
                                                           Fault and alarm contact (O11(2) to O14)                      b
          (1) Close by communication and recloser          External network time synchronization                        b
          (2) O11 reserved for closing order               External trip                                                b
                                                           Local/remote control selection                               b
                                                           Inhibition recloser                                          b

                                                           Optional features
                                                           b Communication interface module, 2 wires (ACE949-2) Modbus
                                                           b Communication interface module, 4 wires (ACE959) Modbus
                                                           b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
                                                           b Remote advanced UMI (type DSM303)
                                                           b Test box
                                                           b Local/remote switch
                                                           b Logic inputs and outputs module MES114 (10I/4O).




          14                                                                                                              DEAI06EN.indd
          Application                                      Bus tie S6



          b Protection against phase to phase              Protection
          and phase to earth short circuits                Sepam S40
          b Detecting of unbalanced power supplied         b 50/51: overcurrent - IDMT, DT (4 settings)
          b Recloser                                       b 50N/51N: earth fault - IDMT, DT (4 settings)
                                                           b 50BF: breaker failure
          b It suited for integration into a supervisory   b 46: negative sequence overcurrent - IDMT, DT (2 settings).
          system using Modbus serial interface.
          Several standard options are available
          to ensure maximum flexibility and cost
          effectiveness in meeting the requirements        Measurement and diagnostic
          of different systems.                            Sepam S40, LCD display LED (Light Emitting Diode)
                                                           b Phase current: I1, I2, I3 RMS
                                                           b Residual current: I0
                                                           b Average currents: I1, I2, I3
                                                           b Peak demand phase currents
DE56383




                   To Busbar VT’s                          b Line voltage: U21, U32, U13
                                                           b Phase to neutral voltage: V1, V2, V3
                                50/51            A    94
                                                           b Residual voltage: V0
                                50N/51N          V    69
                                                           b Positive sequence voltage/rotation direction
                                                           b Frequency
                                50BF             F    86
                    Open/close                             b Active, reactive and apparent power: P, Q, S
                            (1) 46              MD    74
                       trip                                b Peak demand power PM, QM and power factor
                                                KW    30
                                                           b Active and reactive energy
                                               KVAR 68
                                                           b Tripping currents: I1, I2, I3, I0
                                                KVA 60LF
                                                           b Unbalance ratio/negative sequence current Ii
                                                PF
                                                           b Phase displacement
                                               KW.h
                                                           b Disturbance recording
                                               KVar.h
                                                           b Tripping context.
                                                           CT’s option
                                                           b CLP1: LPCT sensors 100 A to 1250 A
                                                           b Core balance CT: CSH120 or CSH200.


                            Analog Output

                            Remote UMI                     Control
                                                            Sepam S40                                      Basic          MES114 module
                            Modbus RS485                                                                   apparatus      (10 I/4 O)
          Bus tie S6                                       Cumulative breaking current                     b              b
                                                           Trip CB output (O1)                             b              b
                                                           Closing lockout (O2)                            b              b
                                                           Logic discrimination block send (O3)            b              b
                                                           Watch dog (O4)                                  b              b
                                                           CB control (86)                                 b              b
                                                           CB open/closed status indication                               b
                                                           Number of operations, operating time                           b
                                                           Trip circuit supervision (74)                                  b
                                                           Logic discrimination block receive Bl1                         b
                                                           CB closing order                                               b
                                                           Fault and alarm contact (O11(2) to O14)                        b
                                                           CB opening order                                               b
                                                           Inhibit closing                                                b
          (1) Close by communication                       External tripping                                              b
          (2) O11 reserved for closing order               Local/remote control selection                                 b
                                                           Inhibition recloser                                            b
                                                           External network time synchronization                          b

                                                           Optional features
                                                           b Communication interface module, 2 wires (ACE949-2) Modbus
                                                           b Communication interface module, 4 wires (ACE959) Modbus
                                                           b Logic inputs and outputs module MES114 (10I/4O)
                                                           b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
                                                           b Remote advanced UMI (type DSM303)
                                                           b Test box
                                                           b Local/remote switch.


          DEAI06EN.indd                                                                                                               15
          Application                                      Bus riser B2



          b Detecting of variation in network voltage      Protection
          or frequency                                     Sepam B22
          b It suited for integration into a supervisory   b 27D/47: positive sequence undervoltage (2 sets)
          system using Modbus serial interface.            b 27R: remanent undervoltage
                                                           b 27: phase to phase undervoltage (2 sets)
          Several standard options are available           b 27S: phase to neutral undervoltage
          to ensure maximum flexibility and cost           b 59: phase to phase overvoltage (2 sets)
          effectiveness in meeting the requirements        b 59N: neutral voltage displacement (2 sets)
          of different systems.                            b 81H: overfrequency
                                                           b 81L: underfrequency (2 sets)
                                                           b 81R: rate of change of frequency (B22 only).




                                                           Measurement and diagnostic
DE56384




                                                           Sepam B22, LCD display LED (Light Emitting Diode)
                                                           b Line voltage: U21, U32, U13
                                                           b Phase to neutral voltage: V1, V2, V3
                                                           b Residual voltage: V0
                         27D/47      V    86               b Positive sequence voltage/rotation direction
                         27R         F    30               b Frequency
                         27                                b Disturbance recording.
                         27S
                         59
                         59N
                         81L
                         81H                               Control
                         81R (B22)                          Sepam B22                                     Basic        MES114 module
                                                                                                          apparatus    (10 I/4 O)
                    Analog Output                          Trip CB output (O1)                            b            b
                                                           Closing lockout (O2)                           b            b
                    Remote UMI
                                                           Logic discrimination block send (O3)           b            b
                                                           Watch dog (O4)                                 b            b
                    Modbus RS485
                                                           Fault and alarm contact (O11 to O14)           b            b
          Bus riser B2                                     External network time synchronization                       b

                                                           Optional features
                                                           b Communication interface module, 2 wires (ACE949-2) Modbus
                                                           b Communication interface module, 4 wires (ACE959) Modbus
                                                           b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
                                                           b Remote advanced UMI (type DSM303)
                                                           b Test box
                                                           b Logic inputs and outputs module MES114 (10I/4O).




          16                                                                                                             DEAI06EN.indd
          Application                                      Busbar VT’s B1



          b Detecting of variation in network voltage      Protection
          or frequency                                     Sepam B21/B22
          b It suited for integration into a supervisory   b 27D/47: positive sequence undervoltage (2 sets)
          system using Modbus serial interface.            b 27R: remanent undervoltage
                                                           b 27: phase to phase undervoltage (2 sets)
          Several standard options are available           b 27S: phase to neutral undervoltage
          to ensure maximum flexibility and cost           b 59: phase to phase overvoltage (2 sets)
          effectiveness in meeting the requirements        b 59N: neutral voltage displacement (2 sets)
          of different systems.                            b 81H: overfrequency
                                                           b 81L: underfrequency (2 sets)
                                                           b 81R: rate of change of frequency (B22 only).




                                                           Measurement and diagnostic
DE56387




                                                           Sepam B21/B22, LCD display LED (Light Emitting Diode)
                                                           b Line voltage: U21, U32, U13
                                                           b Phase to neutral voltage: V1, V2, V3
                                                           b Residual voltage: V0
                           27D/47      V    86             b Positive sequence voltage/rotation direction
                           27R         F    30             b Frequency
                           27                              b Disturbance recording.
                           27S
                           59
                           59N
                           81L
                           81H                             Control
                           81R (B22)                        Sepam B21/B22                                 Basic        MES114 module
                                                                                                          apparatus    (10 I/4 O)
                     Analog Output                         Trip CB output (O1)                            b            b
                                                           Closing lockout (O2)                           b            b
                     Remote UMI
                                                           Logic discrimination block send (O3)           b            b
                                                           Watch dog (O4)                                 b            b
                     Modbus RS485
                                                           Fault and alarm contact (O11 to O14)           b            b
          Busbar VT’s B1                                   External network time synchronization                       b

                                                           Optional features
                                                           b Communication interface module, 2 wires (ACE949-2) Modbus
                                                           b Communication interface module, 4 wires (ACE959) Modbus
                                                           b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
                                                           b Remote advanced UMI (type DSM303)
                                                           b Test box
                                                           b Logic inputs and outputs module MES114 (10I/4O).




          DEAI06EN.indd                                                                                                              17
          Application                                                   Transformer feeder T1



          b Protection against internal faults and                      Protection
          overload protection                                           Sepam T20
          b It also monitors the winding temperature                    b 50/51: overcurrent - IDMT, DT (4 settings)
          by probes providing local and remote                          b 50N/51N: earth fault - IDMT, DT (4 settings)
                                                                        b 46: negative sequence overcurrent
          indication of operation                                       b 49RMS: thermal overload (2 settings)
          b It suited for integration into a supervisory                b 38/49T: temperature monitoring (2 settings/probe).
          system using Modbus serial interface.
          Several standard options are available
          to ensure maximum flexibility and cost
          effectiveness in meeting the requirements                     Measurement and diagnostic
          of different systems.                                         Sepam T20, LCD display LED (Light Emitting Diode)
                                                                        b Phase current: I1, I2, I3 RMS
                                                                        b Residual current: I0
                                                                        b Average currents: I1, I2, I3
DE56388




                                                                        b Peak demand phase currents
                                                                        b Temperature measurement
                                                                        b Tripping currents: I1, I2, I3, I0
                       Trip/close(1)
                                                                        b Unbalance ratio/negative sequence current Ii
                                                                        b Disturbance recording
                              50/51              A    86                b Running hours counter/operating time
                              50N/51N           MD    74                b Thermal capacity used
                              49RMS            Temp   30                b Remaining operating time before overload trip
                              38/49T                  68                b Waiting time after overload tripping.
                                                                        CT’s option
                                                                        b CLP1: LPCT sensors 100 A to 1250 A
                                                           Inter trip




                                                                        b Core balance CT: CSH120 or CSH200.




                       Temp Sensor
                                                                        Control
                                                                         Sepam T20                                      Basic       MES114 module
                       Analog Output                                                                                    apparatus   (10 I/4 O)
                       Remote UMI                                       Cumulative breaking current                     b           b
                                                                        Trip CB output (O1)                             b           b
                       Modbus RS485                                     Closing lockout (O2)                            b           b
                                                                        Logic discrimination block send (O3)            b           b
          Transformer feeder T1
                                                                        Watch dog (O4)                                  b           b
                                                                        CB control (86)                                 b           b
                                                                        CB open/closed status indication                            b
                                                                        Number of operations, operating time                        b
                                                                        Logic discrimination block receive                          b
                                                                        External tripping                                           b
          (1) Close by communication                                    Trip circuit supervision (74)                               b
          (2) O11 reserved for closing order                            Fault and alarm contact (O11(2) to O14)                     b
                                                                        Local/remote control selection                              b
                                                                        Inhibition thermal overload                                 b

                                                                        Optional features
                                                                        b Communication interface module, 2 wires (ACE949-2) Modbus
                                                                        b Communication interface module, 4 wires (ACE959) Modbus
                                                                        b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
                                                                        b 8 temperature sensor inputs (38/49T) MET148-2 module
                                                                        b Logic inputs and outputs module MES114 (10I/4O)
                                                                        b Remote advanced UMI (type DSM303)
                                                                        b Test box
                                                                        b Local/remote switch.




          18                                                                                                                          DEAI06EN.indd
          Application                                                 Transformer feeder T2



          b Protection against internal faults and                    Protection
          overload protection                                         Sepam T20
          b It also monitors the winding temperature                  b 50/51: overcurrent - IDMT, DT (4 settings)
          and Buchholz providing local and remote                     b 50N/51N: earth fault - IDMT, DT (4 settings)
                                                                      b 46: negative sequence overcurrent
          indication of operation                                     b 49RMS: thermal overload (2 settings)
          b It suited for integration into a supervisory              b Thermostat/Buchholz.
          system using Modbus serial interface.
          Several standard options are available
          to ensure maximum flexibility and cost
          effectiveness in meeting the requirements                   Measurement and diagnostic
          of different systems.                                       Sepam T20, LCD display LED (Light Emitting Diode)
                                                                      b Phase current: I1, I2, I3 RMS
                                                                      b Residual current: I0
                                                                      b Average currents: I1, I2, I3
DE56389




                                                                      b Peak demand phase currents
                                                                      b Tripping currents: I1, I2, I3, I0
                                                                      b Unbalance ratio/negative sequence current Ii
                       Trip/close(1)
                                                                      b Disturbance recording
                                                                      b Running hours counter/operating time
                              50/51             A   86                b Thermal capacity used
                              50N/51N          MD   74                b Remaining operating time before overload trip
                              49RMS                 30                b Waiting time after overload tripping.
                              Thermos               68                CT’s option
                              Buchholz                                b CLP1: LPCT sensors 100 A to 1250 A
                                                                      b Core balance CT: CSH120 or CSH200.
                                                         Inter trip




                                                                      Control
                                                                       Sepam T20                                       Basic       MES114 module
                                                                                                                       apparatus   (10 I/4 O)
                       Analog Output                                  Cumulative breaking current                      b           b
                                                                      Trip CB output (O1)                              b           b
                       Remote UMI                                     Closing lockout (O2)                             b           b
                                                                      Logic discrimination block send (O3)             b           b
                       Modbus RS485                                   Watch dog (O4)                                   b           b
          Transformer feeder T2                                       CB control (86)                                  b           b
                                                                      CB open/closed status indication                             b
                                                                      Number of operations, operating time                         b
                                                                      Logic discrimination block receive                           b
                                                                      External tripping                                            b
                                                                      Trip circuit supervision (74)                                b
                                                                      Fault and alarm contact (O11(2) to O14)                      b
                                                                      External tripping (Buchholz)                                 b
                                                                      External tripping (Winding temperature)                      b
          (1) Close by communication                                  Buchholz alarm                                               b
          (2) O11 reserved for closing order                          Winding temperature alarm                                    b
                                                                      Local/remote control selection                               b
                                                                      Inhibition thermal overload                                  b

                                                                      Optional features
                                                                      b Communication interface module, 2 wires (ACE949-2) Modbus
                                                                      b Communication interface module, 4 wires (ACE959) Modbus
                                                                      b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
                                                                      b Logic inputs and outputs module MES114 (10I/4O)
                                                                      b Remote advanced UMI (type DSM303)
                                                                      b Test box
                                                                      b Local/remote switch.




          DEAI06EN.indd                                                                                                                         19
          Application                                                      Transformer feeder T3



          b Protection against internal faults and                         Measurement and diagnostic
          overload protection                                              Sepam T40 or T42, LCD display LED (Light Emitting Diode)
          b It also monitors pressure device providing                     b Phase current: I1, I2, I3 RMS
          local and remote indication of operation                         b Residual current: I0
                                                                           b Average currents: I1, I2, I3
          b It suited for integration into a supervisory                   b Peak demand phase currents
          system using Modbus serial interface.                            b Line voltage: U21, U32, U13
          Several standard options are available                           b Phase to neutral voltage: V1, V2, V3
          to ensure maximum flexibility and cost                           b Residual voltage: V0
                                                                           b Positive sequence voltage/rotation direction
          effectiveness in meeting the requirements                        b Frequency
          of different systems.                                            b Active, reactive and apparent power: P, Q, S
                                                                           b Peak demand power PM, QM and power factor
                                                                           b Active and reactive energy
                                                                           b Tripping currents: I1, I2, I3, I0
                                                                           b Unbalance ratio/negative sequence current Ii
DE56390




                     To Busbar VT’s                                        b Phase displacement
                                                                           b Disturbance recording
                                                                           b Running hours counter/Operating time
                                50/51               A    94                b Thermal capacity used
                                50N/51N             V    69                b Remaining operating time before overload trip
                                50BF                F    86                b Waiting time after overload tripping
                     Open/close
                                46                 MD    74                b Tripping context.
                        trip
                                                   KW    30
                                    67N/67NC(1)   KVAR 68
                                                                           CT’s option
                                    49RMS          KVA 60LF
                                                                           b CLP1: LPCT sensors 100 A to 1250 A
                                    27/27S         PF
                                                                           b Core balance CT: CSH120 or CSH200.
                                    59            KW.h
                                                  KVar.h
                                                              Inter trip




                                    DGPT2
                                                                           Control
                                                                            Sepam T40 or T42                           Basic           MES114 module
                                                                                                                       apparatus       (10 I/4 O)
                                                                           Cumulative breaking current                 b               b
                                                                           Trip CB output (O1)                         b               b
                                                                           Closing lockout (O2)                        b               b
                             Analog Output                                 Logic discrimination block send (O3)        b               b
                                                                           Watch dog (O4)                              b               b
                             Remote UMI                                    CB control (86)                             b               b
                             Modbus RS485                                  CB open/closed status indication                            b
                                                                           Number of operations, operating time                        b
          Transformer feeder T3
                                                                           Trip circuit supervision (74)                               b
                                                                           Logic discrimination block receive BI1                      b
          Protection                                                       CB closing order                                            b
          Sepam T40 or T42                                                 Fault and alarm contact (O11(2) to O14)                     b
          b 50/51: overcurrent - IDMT, DT (4 settings)                     CB opening order                                            b
          b 50N/51N: earth fault - IDMT, DT (4 settings)                   Pressure alarm                                              b
          b 50BF: breaker failure                                          Pressure tripping                                           b
          b 46: negative sequence overcurrent - IDMT,
                                                                           Thermostat alarm                                            b
          DT (2 settings)
          b 67: directional phase overcurrent (1) - IDMT,                  Thermostat tripping                                         b
          DT (2 settings)                                                  External network time synchronization                       b
          b 67N/67NC: directional earth fault (1) - IDMT,
          DT (2 settings)                                                  Optional features
          b 49RMS: thermal overload (2 settings)                           b Communication interface module, 2 wires (ACE949-2) Modbus
          b 27/27S: undervoltage (2 settings)                              b Communication interface module, 4 wires (ACE959) Modbus
          b 59: overvoltage (2 settings)                                   b Logic inputs and outputs module MES114 (10I/4O)
          b 59N: neutral voltage displacement (2 settings).                b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
                                                                           b Remote advanced UMI (type DSM303)
                                                                           b Test box
                                                                           b Local/remote switch.
          (1) On Sepam T42 only
          (2) O11 reserved for closing order




          20                                                                                                                             DEAI06EN.indd
          Application                                                      Transformer feeder T6



          b Protection against internal faults and                         Measurement and diagnostic
          overload protection                                              Sepam T40, LCD display LED (Light Emitting Diode)
          b It also monitors the windings by probes                        b Phase current: I1, I2, I3 RMS
          providing device local and remote indication                     b Residual current: I0
                                                                           b Average currents: I1, I2, I3
          of operation                                                     b Peak demand phase currents
          b It suited for integration into a supervisory                   b Line voltage: U21, U32, U13
          system using Modbus serial interface.                            b Phase to neutral voltage: V1, V2, V3
          Several standard options are available                           b Residual voltage: V0
                                                                           b Positive sequence voltage/rotation direction
          to ensure maximum flexibility and cost                           b Frequency
          effectiveness in meeting the requirements                        b Active, reactive and apparent power: P, Q, S
          of different systems.                                            b Peak demand power PM, QM and power factor
                                                                           b Active and reactive energy
                                                                           b Tripping currents: I1, I2, I3, I0
                                                                           b Unbalance ratio/negative sequence current Ii
DE56390




                     To Busbar VT’s                                        b Phase displacement
                                                                           b Disturbance recording
                                                                           b Running hours counter/operating time
                                50/51               A    94                b Thermal capacity used
                                50N/51N             V    69                b Remaining operating time before overload trip
                                50BF                F    86                b Waiting time after overload tripping
                     Open/close
                                46                 MD    74                b Tripping context.
                        trip
                                                   KW    30
                                    67N/67NC(1)   KVAR 68
                                                                           CT’s option
                                    49RMS          KVA 60LF
                                                                           b CLP1: LPCT sensors 100 A to 1250 A
                                    27/27S         PF
                                                                           b Core balance CT: CSH120 or CSH200.
                                    59            KW.h
                                                  KVar.h
                                                              Inter trip




                                    DGPT2
                                                                           Control
                                                                            Sepam T40                                  Basic           MES114 module
                                                                                                                       apparatus       (10 I/4 O)
                                                                           Cumulative breaking current                 b               b
                                                                           Trip CB output (O1)                         b               b
                                                                           Closing lockout (O2)                        b               b
                             Analog Output                                 Logic discrimination block send (O3)        b               b
                                                                           Watch dog (O4)                              b               b
                             Remote UMI                                    CB control (86)                             b               b
                             Modbus RS485                                  CB open/closed status indication                            b
                                                                           Number of operations, operating time                        b
          Transformer feeder T6
                                                                           Trip circuit supervision (74)                               b
                                                                           Logic discrimination block receive BI1                      b
          Protection                                                       CB closing order                                            b
          Sepam T40                                                        Fault and alarm contact (O11(2) to O14)                     b
          b 50/51: overcurrent - IDMT, DT (4 settings)                     CB opening order                                            b
          b 50N/51N: earth fault - IDMT, DT (4 settings)                   Pressure alarm                                              b
          b 50BF: breaker failure                                          Pressure tripping                                           b
          b 46: negative sequence overcurrent - IDMT,
                                                                           Thermostat alarm                                            b
          DT (2 settings)
          b 67: directional phase overcurrent (1) - IDMT,                  Thermostat tripping                                         b
          DT (2 settings)                                                  External network time synchronization                       b
          b 67N/67NC: directional earth fault (1) - IDMT,
          DT (2 settings)                                                  Optional features
          b 49RMS: thermal overload (2 settings)                           b Communication interface module, 2 wires (ACE949-2) Modbus
          b 27/27S: undervoltage (2 settings)                              b Communication interface module, 4 wires (ACE959) Modbus
          b 59: overvoltage (2 settings)                                   b Logic inputs and outputs module MES114 (10I/4O)
          b 59N: neutral voltage displacement (2 settings)                 b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
          b 38/49T: temperature monitoring.                                b 8 temperature sensor inputs (38/49T) MET148-2 module
                                                                           b Remote advanced UMI user machine interface (type DSM303)
                                                                           b Test box
          (1) On Sepam T42 only                                            b Local/remote switch.
          (2) O11 reserved for closing order




          DEAI06EN.indd                                                                                                                              21
          Application                                                      Transformer incomer T4



          b Protection against internal faults and                         Measurement and diagnostic
          overload protection                                              Sepam T40 or T42, LCD display LED (Light Emitting Diode)
          b It also monitors the winding temperature                       b Phase current: I1, I2, I3 RMS
          and Buchholz device providing local and                          b Residual current: I0
                                                                           b Average currents: I1, I2, I3
          remote indication of operation                                   b Peak demand phase currents
          b It suited for integration into a supervisory                   b Line voltage: U21, U32, U13
          system using Modbus serial interface.                            b Phase to neutral voltage: V1, V2, V3
          Several standard options are available                           b Residual voltage: V0
                                                                           b Positive sequence voltage/rotation direction
          to ensure maximum flexibility and cost                           b Frequency
          effectiveness in meeting the requirements                        b Active, reactive and apparent power: P, Q, S
          of different systems.                                            b Peak demand power PM, QM and power factor
                                                                           b Active and reactive energy
                                                                           b Tripping currents: I1, I2, I3, I0
                                                                           b Unbalance ratio/negative sequence current Ii
DE56391




                             Modbus RS485                                  b Phase displacement
                                                                           b Disturbance recording
                             Remote UMI                                    b Running hours counter/Operating time
                             Analog Output                                 b Thermal capacity used
                                                                           b Remaining operating time before overload trip
                                                                           b Waiting time after overload tripping
                                                                           b Tripping context.
                                                                           CT’s option
                                50/51         A    94                      b CLP1: LPCT sensors 100 A to 1250 A
                                                              Inter trip




                                50N/51N       V    69                      b Core balance CT: CSH120 or CSH200.
                                50BF          F    86
                                46           MD    74
                                67(1)        KW    30
                                67N/67NC(1) KVAR 68
                                49RMS        KVA 60LF                      Control
                                27/27S       PF
                                59          KW.h                            Sepam T40 or T42                           Basic           MES114 module
                                59N         KVar.h                                                                     apparatus       (10 I/4 O)
                                Thermost                                   Cumulative breaking current                 b               b
                     Open/close Buchholz                                   Trip CB output (O1)                         b               b
                        trip                                               Closing lockout (O2)                        b               b
                                                                           Logic discrimination block send (O3)        b               b
                                                                           Watch dog (O4)                              b               b
                                                                           CB control (86)                             b               b
          Transformer feeder T4
                                                                           CB open/closed status indication                            b
                                                                           Number of operations, operating time                        b
                                                                           Trip circuit supervision (74)                               b
                                                                           Logic discrimination block receive BI1                      b
          Protection                                                       CB closing order                                            b
          Sepam T40 or T42                                                 Fault and alarm contact (O11(2) to O14)                     b
          b 50/51: overcurrent - IDMT, DT (4 settings)                     CB opening order                                            b
          b 50N/51N: earth fault - IDMT, DT (4 settings)                   Buchholz alarm                                              b
          b 50BF: breaker failure                                          Buchholz tripping                                           b
          b 46: negative sequence overcurrent - IDMT,
                                                                           Thermostat alarm                                            b
          DT (2 settings)
          b 67: directional phase overcurrent (1) - IDMT,                  Thermostat tripping                                         b
          DT (2 settings)                                                  External network time synchronization                       b
          b 67N/67NC: directional earth fault (1) - IDMT,
          DT (2 settings)                                                  Optional features
          b 49RMS: thermal overload (2 settings)                           b Communication interface module, 2 wires (ACE949-2) Modbus
          b 27/27S: undervoltage (2 settings)                              b Communication interface module, 4 wires (ACE959) Modbus
          b 59: overvoltage (2 settings)                                   b Logic inputs and outputs module MES114 (10I/4O)
          b 59N: neutral voltage displacement (2 settings).                b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
                                                                           b Remote advanced UMI user machine interface (type DSM303)
                                                                           b Test box
                                                                           b Local/remote switch.
          (1) On Sepam T42 only
          (2) O11 reserved for closing order




          22                                                                                                                             DEAI06EN.indd
          Application                                                      Transformer incomer T5



          b Protection against internal faults and                         Measurement and diagnostic
          overload protection                                              Sepam T40 or T42, LCD display LED (Light Emitting Diode)
          b It also monitors the winding by probes                         b Phase current: I1, I2, I3 RMS
          providing device local and remote indication                     b Residual current: I0
                                                                           b Average currents: I1, I2, I3
          of operation                                                     b Peak demand phase currents
          b It suited for integration into a supervisory                   b Line voltage: U21, U32, U13
          system using Modbus serial interface.                            b Phase to neutral voltage: V1, V2, V3
          Several standard options are available                           b Residual voltage: V0
                                                                           b Positive sequence voltage/rotation direction
          to ensure maximum flexibility and cost                           b Frequency
          effectiveness in meeting the requirements                        b Active, reactive and apparent power: P, Q, S
          of different systems.                                            b Peak demand power PM, QM and power factor
                                                                           b Active and reactive energy
                                                                           b Tripping currents: I1, I2, I3, I0
                                                                           b Unbalance ratio/negative sequence current Ii
DE56392




                            Modbus RS485                                   b Phase displacement
                                                                           b Disturbance recording
                            Remote UMI                                     b Running hours counter/operating time
                                                                           b Thermal capacity used
                            Analog Output                                  b Remaining operating time before overload trip
                            Temp Sensor                                    b Waiting time after overload tripping
                                                                           b Tripping context.
                                                                           CT’s option
                                    50/51           A    94                b CLP1: LPCT sensors 100 A to 1250 A
                                                              Inter trip




                                    50N/51N         V    69                b Core balance CT: CSH120 or CSH200.
                                    50BF            F    86
                                    46             MD    74
                                    67(1)          KW    30
                                    67N/67NC(1)   KVAR 68
                                    49RMS          KVA 60LF
                                                                           Control
                                    27/27S         PF                       Sepam T40 or T42                           Basic           MES114 module
                                    59            KW.h                                                                 apparatus       (10 I/4 O)
                                    59N           KVar.h                   Cumulative breaking current                 b               b
                                    38/49T        Temp
                                                                           Trip CB output (O1)                         b               b
                     Open/close
                        trip                                               Closing lockout (O2)                        b               b
                                                                           Logic discrimination block send (O3)        b               b
                                                                           Watch dog (O4)                              b               b
                                                                           CB control (86)                             b               b
          Transformer feeder T5                                            CB open/closed status indication                            b
                                                                           Number of operations, operating time                        b
                                                                           Trip circuit supervision (74)                               b
                                                                           Logic discrimination block receive BI1                      b
          Protection                                                       CB closing order                                            b
          Sepam T40 or T42                                                 Fault and alarm contact (O11(1) to O14)                     b
          b 50/51: overcurrent - IDMT, DT (4 settings)                     CB opening order                                            b
          b 50N/51N: earth fault - IDMT, DT (4 settings)                   Inhibit closing                                             b
          b 50BF: breaker failure                                          External tripping                                           b
          b 46: negative sequence overcurrent - IDMT,
                                                                           Local/remote control selection                              b
          DT (2 settings)
          b 67: directional phase overcurrent - IDMT,                      Inhibition thermal overload                                 b
          DT (2 settings)                                                  External network time synchronization                       b
          b 67N/67NC: directional earth fault - IDMT,
          DT (2 settings)                                                  Optional features
          b 49RMS: thermal overload (2 settings)                           b Communication interface module, 2 wires (ACE949-2) Modbus
          b 27/27S: undervoltage (2 settings)                              b Communication interface module, 4 wires (ACE959) Modbus
          b 59: overvoltage (2 settings)                                   b Logic inputs and outputs module MES114 (10I/4O)
          b 59N: neutral voltage displacement (2 settings)                 b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
          b 38/49T: temperature monitoring.                                b 8 temperature sensor inputs (38/49T) MET148-2 module
                                                                           b Remote advanced UMI user machine interface (type DSM303)
                                                                           b Test box
                                                                           b Local/remote switch.
          (1) O11 reserved for closing order




          DEAI06EN.indd                                                                                                                              23
          Application                                      Motor feeder M1



          b Protection against internal faults and         Protection
          loads faults                                     Sepam M20
          b Monitoring of motor starting conditions        b 50/51: overcurrent - IDMT, DT (4 settings)
          and winding temperature by probes                b 50N/51N: earth fault - IDMT, DT (4 settings)
                                                           b 46: negative sequence overcurrent
          providing local and remote indication of         b 49RMS: thermal overload (2 settings)
          operation                                        b 37: undercurrent
          b It suited for integration into a supervisory   b 48/51LR: exces. start. time, locked rotor
          system using Modbus serial interface.            b 66: starts per hour
                                                           b 38/49T: temperature monitoring.
          Several standard options are available
          to ensure maximum flexibility and cost
          effectiveness in meeting the requirements
          of different systems.
                                                           Measurement and diagnostic
                                                           Sepam M20, LCD display LED (Light Emitting Diode)
DE56393




                                                           b Phase current: I1, I2, I3 RMS
                                                           b Residual current: I0
                                                           b Average currents: I1, I2, I3
                       Trip/close(1)
                                                           b Peak demand phase currents
                                                           b Temperature measurement
                               50/51        A    86        b Tripping currents: I1, I2, I3, I0
                               50N/51N     MD    74        b Unbalance ratio/negative sequence current Ii
                               49RMS      Temp   30        b Disturbance recording
                               46                68        b Running hours counter/operating time
                               37                          b Thermal capacity used
                               48/51LR/14                  b Remaining operating time before overload trip
                               66                          b Waiting time after overload tripping
                               38/49T                      b Starting current and time/overload
                                                           b Start inhibit time delay/numb. start before inhibition.
                                                           CT’s option
                                                           b CLP1: LPCT sensors 100 A to 1250 A
                                                           b Core balance CT: CSH120 or CSH200.
                M      Temp Sensor
                       Analog Output
                       Remote UMI
                                                           Control
                       Modbus RS485                         Sepam M20                                       Basic       MES114 module
                                                                                                            apparatus   (10 I/4 O)
          Motor feeder M1
                                                           Cumulative breaking current                      b           b
                                                           Trip CB output (O1)                              b           b
                                                           Closing lockout (O2)                             b           b
                                                           Logic discrimination block send (O3)             b           b
                                                           Watch dog (O4)                                   b           b
                                                           CB control (86)                                  b           b
                                                           CB open/closed status indication                             b
                                                           Number of operations, operating time                         b
                                                           External trip                                                b
                                                           Trip circuit supervision (74)                                b
                                                           Fault and alarm contact (O11(2) to O14)                      b
                                                           Motor reacceleration                                         b
          (1) Close by communication                       Motor shaft rotation                                         b
          (2) O11 reserved for closing order               Local/remote control selection                               b
                                                           Inhibition thermal overload                                  b
                                                           External network time synchronization                        b

                                                           Optional features
                                                           b Communication interface module, 2 wires (ACE949-2) Modbus
                                                           b Communication interface module, 4 wires (ACE959) Modbus
                                                           b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
                                                           b 8 temperature sensor inputs (38/49T) MET148-2 module
                                                           b Remote advanced UMI (type DSM303)
                                                           b Test box
                                                           b Local/remote switch
                                                           b Logic inputs and outputs module MES114 (10I/4O).


          24                                                                                                              DEAI06EN.indd
          Application                                          Motor feeder M2



          b Protection against internal faults, network        Measurement and diagnostic
          related and loads faults                             Sepam M41, LCD display LED (Light Emitting Diode)
          b Monitoring of motor starting conditions            b Phase current: I1, I2, I3 RMS
          and the winding temperature                          b Residual current: I0
                                                               b Average currents: I1, I2, I3
          b It suited for integration into a supervisory       b Peak demand phase currents
          system using Modbus serial interface.                b Line voltage: U21, U32, U13
          Several standard options are available               b Phase to neutral voltage: V1, V2, V3
          to ensure maximum flexibility and cost               b Residual voltage: V0
                                                               b Positive sequence voltage/rotation direction
          effectiveness in meeting the requirements            b Frequency
          of different systems.                                b Active, reactive and apparent power: P, Q, S
                                                               b Peak demand power PM, QM and power factor
                                                               b Active and reactive energy
                                                               b Tripping currents: I1, I2, I3, I0
DE56394




                     To Busbar VT’s
                                                               b Unbalance ratio/negative sequence current Ii
                                                               b Phase displacement
                                50/51        A    94           b Disturbance recording
                                50N/51N      V    69           b Running hours counter/operating time
                                50BF         F    86           b Thermal capacity used
                                46          MD    74           b Remaining operating time before overload trip
                                                               b Waiting time after overload tripping
                     Open/close 67N/67NC    KW    30
                                32P        KVAR 68             b Starting current and time
                        trip
                                32Q/40      KVA 60LF           b Start inhibit time delay/number of start before inhibition
                                49RMS       PF                 b Tripping context.
                                37         KW.h                CT’s option
                                48/51LR/14 KVar.h              b CLP1: LPCT sensors 100 A to 1250 A
                                66         Temp                b Core balance CT: CSH120 or CSH200.
                                27D
                                27R
                                27/27S
                                59
                                59N                            Control
                                47
                                                                Sepam M41                                         Basic       MES114 module
                                38/49T
                                                                                                                  apparatus   (10 I/4 O)
                            Temp Sensor                        Cumulative breaking current                        b           b
                M
                                                               Trip CB output (O1)                                b           b
                            Analog Output                      Closing lockout (O2)                               b           b
                            Remote UMI                         Logic discrimination block send (O3)               b           b
                                                               Watch dog (O4)                                     b           b
                            Modbus RS485                       CB control (86)                                    b           b
                                                               CB open/closed status indication                               b
          Motor feeder M2
                                                               Number of operations, operating time                           b
                                                               Trip circuit supervision (74)                                  b
                                                               Motor rotation detection                                       b
          Protection                                           CB closing order                                               b
          Sepam M41
                                                               Fault and alarm contact (O11(1) to O14)                        b
          b 50/51: overcurrent - IDMT, DT (4 settings)
          b 50N/51N: earth fault - IDMT, DT (4 settings)       CB opening order                                               b
          b 50BF: breaker failure                              Inhibit closing                                                b
          b 46: negative sequence overcurrent                  External tripping                                              b
          b 67N/67NC: directional earth fault - IDMT,          Local/remote control selection                                 b
          DT (2 settings)                                      Inhibition thermal overload                                    b
          b 32P: directional active overpower
          b 32Q/40: directional reactive overpower             External network time synchronization                          b
          b 49RMS: thermal overload (2 settings)
          b 37: phase undercurrent                             Optional features
          b 48/51LR/14: exces. start. time, locked rotor       b Communication interface module, 2 wires (ACE949-2) Modbus
          b 66: starts per hour                                b Communication interface module, 4 wires (ACE959) Modbus
          b 27D: positive sequence undervoltage (2 settings)   b Logic inputs and outputs module MES114 (10I/4O)
          b 27R: remanent undervoltage                         b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
          b 27/27S: undervoltage (2 settings)                  b 8/16 temperature sensors inputs MET148-2 module
          b 59: overvoltage (2 settings)                       b Remote advanced UMI (type DSM303)
          b 59N: neutral voltage displacement (2 settings)     b Test box
          b 47: negative sequence overvoltage                  b Local/remote switch.
          b 38/49T: temperature monitoring.

          (1) O11 reserved for closing order


          DEAI06EN.indd                                                                                                                   25
          Application                                        Generator incomer G1



          b Protection against faults, network and           Measurement and diagnostic
          loads faults                                       Sepam G40, LCD display LED (Light Emitting Diode)
          b Monitoring of winding temperature                b Phase current: I1, I2, I3 RMS
          b It suited for integration into a supervisory     b Residual current: I0
                                                             b Average currents: I1, I2, I3
          system using Modbus serial interface.              b Peak demand phase currents
          Several standard options are available             b Line voltage: U21, U32, U13
          to ensure maximum flexibility and cost             b Phase to neutral voltage: V1, V2, V3
          effectiveness in meeting the requirements          b Residual voltage: V0
                                                             b Positive sequence voltage/rotation direction
          of different systems.                              b Frequency
                                                             b Active, reactive and apparent power: P, Q, S
                                                             b Peak demand power PM, QM and power factor
                                                             b Active and reactive energy
                                                             b Tripping currents: I1, I2, I3, I0
DE56395




                                50/51            A    94
                                                             b Unbalance ratio/negative sequence current Ii
                                50V/51V          V    69
                                                             b Phase displacement
                                50G/51G          F    86
                                                             b Disturbance recording
                                50BF            MD    74
                                                             b Running hours counter/operating time
                     Open/close 46              KW    30
                                                             b Thermal capacity used
                        trip    32P            KVAR 68
                                                             b Remaining operating time before overload trip
                                32Q/40          KVA 60LF
                                                             b Waiting time after overload tripping
                                49RMS           PF
                                                             b Tripping context.
                                27/27S         KW.h
                                59             KVar.h        CT’s option
                                59N            Temp          b CLP1: LPCT sensors 100 A to 1250 A
                                47                           b Core balance CT: CSH120 or CSH200.
                                81H
                                81L
                                38/49T

                                                             Control
                                                              Sepam G40                                  Basic           MES114 module
                                                                                                         apparatus       (10 I/4 O)
                G           Temp Sensor                      Cumulative breaking current                 b               b
                            Analog Output                    Trip CB output (O1)                         b               b
                                                             Closing lockout (O2)                        b               b
                            Remote UMI
                                                             Logic discrimination block send (O3)        b               b
                                                             Watch dog (O4)                              b               b
                            Modbus RS485
                                                             CB control (86)                             b               b
          Generator incomer G1                               CB open/closed status indication                            b
                                                             Number of operations, operating time                        b
                                                             Trip circuit supervision (74)                               b
                                                             Logic discrimination block receive Bl1                      b
          Protection                                         CB closing order                                            b
          Sepam G40                                          Fault and alarm contact (O11(1) to O14)                     b
          b 50/51: overcurrent - IDMT, DT (4 settings)       CB opening order                                            b
          b 50G/51G: earth fault - IDMT, DT (4 settings)
          b 50BF: breaker failure                            Inhibit closing                                             b
          b 46: negative sequence overcurrent                External tripping                                           b
          b 32P: directional active overpower                Local/remote control selection                              b
          b 32Q/40: directional reactive overpower           Inhibition thermal overload                                 b
          b 49RMS: thermal overload                          External network time synchronization                       b
          b 27/27S: undervoltage (2 settings)
          b 59: overvoltage (2 settings)
                                                             Optional features
          b 59N: neutral voltage displacement (2 settings)
                                                             b Communication interface module, 2 wires (ACE949-2) Modbus
          b 47: negative sequence overvoltage
                                                             b Communication interface module, 4 wires (ACE959) Modbus
          b 81H: overfrequency (2 settings)
                                                             b Logic inputs and outputs module MES114 (10I/4O)
          b 81L: underfrequency (4 settings)
                                                             b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module
          b 38/49T: temperature monitoring.
                                                             b 8/16 temperature sensors inputs MET148-2 module
                                                             b Remote advanced UMI (type DSM303)
                                                             b Test box
                                                             b Local/remote switch.
          (1) O11 reserved for closing order




          26                                                                                                               DEAI06EN.indd
                                                                                                                                     ART.960249 © Schneider Electric Industries SAS - All rights reserved




Schneider Electric Industries SAS   As standards, specifications and designs change from time to time, please ask for confirmation
89, boulevard Franklin Roosevelt    of the information given in this publication.
F-92505 Rueil-Malmaison Cedex
Tel.: +33 (0)1 41 29 85 00                This document has been printed
www.schneider-electric.com                on ecological paper

                                    Publishing: Schneider Electric Industries SAS
                                    Production: Graphème
                                    Printing: