									                           Sageon Control Unit Front Panel Parameter Settings (24 V System)
                                                                 Flooded Cell Battery Configuations
                                DCU          DJ         JC          KCT      2LCT-840     LCT      LCT II-1700   LCT-HP     LCY Tele    MCT II    MCTC II
             Base (Home) System Menu

              Ambient Temp
                Alarm (°C)        55         55         55           55         55        55           55          55         55         55         55
             Volts High Alarm
                    (V)          28.50      28.50      28.50        28.50     28.50      28.50       28.50        28.50      28.50      28.50      28.80
             Volts Low Alarm
                    (V)          24.00      24.00      24.00        24.00     24.00      24.00       24.00        24.00      24.00      24.00      24.00
             Failsafe Alarms
                   on/off         off        off        off          off        off       off          off         off        off        off        off
             Bat Cur Sensor
                   on/off       Note *1    Note *1    Note *1      Note *1   Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
               SBM Muxing
                mode (0-7)         0          0          0            0          0         0            0           0          0          0          0
              Security on/off     off        off        off          off        off       off          off         off        off        off        off
Parameters




             Number of SMRs     Note *1    Note *1    Note *1      Note *1   Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1

             Num of Batteries    Note *1   Note *1    Note *1      Note *1   Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
                 FS Battery
                 current (A)     Note *1   Note *1    Note *1      Note *1   Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
                Load Sensor
                   on/off          off       off        off          off        off       off          off         off        off        off        off
               Alarm Report
                   on/off          off       off        off          off        off       off          off         off        off        off        off
               Modem on/off        off       off        off          off        off       off          off         off        off        off        off
                Audio Alarm
                   on/off          off        off        off         off        off        off        off           off        off        off        off
                  CBK Input     Used-N/O   Used-N/O   Used-N/O    Used-N/O   Used-N/O   Used-N/O   Used-N/O      Used-N/O   Used-N/O   Used-N/O   Used-N/O
              Bat Switch Input Used-N/O    Used-N/O   Used-N/O    Used-N/O   Used-N/O   Used-N/O   Used-N/O      Used-N/O   Used-N/O   Used-N/O   Used-N/O
                 LVDS Input     Used-N/O   Used-N/O   Used-N/O    Used-N/O   Used-N/O   Used-N/O   Used-N/O      Used-N/O   Used-N/O   Used-N/O   Used-N/O
             Auxiliary Unit Submenu
              1-ph AC Monitor
                   on/off          off       off        off          off        off       off          off         off        off        off        off
              3-ph AC Monitor
                   on/off          off       off        off          off        off       off          off         off        off        off        off
                             Sageon Control Unit Front Panel Parameter Settings (24 V System)
                                                                   Flooded Cell Battery Configuations
                                    DCU        DJ         JC          KCT       2LCT-840     LCT      LCT II-1700   LCT-HP     LCY Tele    MCT II    MCTC II
              Battery Monitor
                   on/off           on         on         on           on         on         on          on           on          on        on         on
                Bat Config        12 Cells   12 Cells   12 Cells     12 Cells   12 Cells   12 Cells    12 Cells     12 Cells   12 Cells   12 Cells   12 Cells
              BCM Batteries       Note *1    Note *1    Note *1      Note *1    Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1

             Cell Vhi Alarm (V)     2.35       2.35       2.35        2.35        2.35       2.35        2.35         2.35       2.35       2.35       2.40

             Cell Vlo Alarm (V)     2.00       2.00       2.00        2.00        2.00       2.00        2.00         2.00       2.00       2.00       2.00
              Cell +dVc Alarm
                     (%)             5          5          5            5          5          5           5            5          5          5          5
              Cell -dVc Alarm
                     (%)             5          5          5            5          5          5           5            5          5          5          5
               Site Monitior
                    on/off          off        off        off          off         off       off          off         off        off        off        off
             RECT Menu
               SMR V high
                 Alarm (V)         28.50      28.50      28.50        28.50      28.50      28.50       28.50        28.50      28.50      28.50      28.80
             SMR V low Alarm
Parameters




                     (V)            24.00      24.00      24.00       24.00       24.00      24.00      24.00         24.00      24.00      24.00      24.00
              SMR HVSD (V)          28.70      28.70      28.70       28.70       28.70      28.70      28.70         28.70      28.70      28.70      29.00
                                  5A/100Ah   5A/100Ah   5A/100Ah    5A/100Ah    5A/100Ah   5A/100Ah   5A/100Ah      5A/100Ah   5A/100Ah   5A/100Ah   5A/100Ah
              SMR I Limit (A)       rating     rating     rating      rating      rating     rating     rating        rating     rating     rating     rating
             BATT Menu
               BATT Disch
                 Alarm (V)         25.50      25.50      25.50        25.50      25.50      25.50       25.50        25.50      25.50      25.50      25.50
             Batt Temp Alarm
                    (°C)            40         40         40           40          40        40           40          40         40         40         40
              *Battery Rating
                    (Ah)          Note *2    Note *2    Note *2      Note *2    Note *2    Note *2     Note *2      Note *2    Note *2    Note *2    Note *2
                BTC Coeff.
               (mV/cell/°C)         -3.6       -3.6       -3.6         -3.6       -3.6       -3.6        -3.6         -3.6       -3.6       -3.6       -3.6

             BTC Nominal (°C)       25         25         25           25          25        25           25          25         25         25         25

              Number of Cells       12         12         12           12          12        12           12          12         12         12         12
                            Sageon Control Unit Front Panel Parameter Settings (24 V System)
                                                               Flooded Cell Battery Configuations
                                   DCU       DJ        JC         KCT      2LCT-840    LCT      LCT II-1700   LCT-HP    LCY Tele   MCT II    MCTC II

             BILim Vb<Vdd (A) Note *1      Note *1   Note *1     Note *1   Note *1    Note *1    Note *1      Note *1   Note *1    Note *1   Note *1
               Vdd Level (V)       1.75      1.75      1.75        1.75      1.75       1.75       1.75         1.75      1.75       1.75      1.75
             BILim Vb<Vfl (A)    Note *1   Note *1   Note *1     Note *1   Note *1    Note *1    Note *1      Note *1   Note *1    Note *1   Note *1
             System Float (V)     26.40     26.52     26.40       26.40     26.64      26.40      26.28        26.52     26.40      26.64     27.12
              System V Drop
                     (V)            0.5      0.5       0.5         0.5       0.5        0.5         0.5         0.5       0.5        0.5       0.5
                Equalisation
                    on/off          off     off       off          off       off       off         off         off        off       off        off
               LVDS Trip (V)      21.00    21.00     21.00        21.00     21.00     21.00       21.00       21.00      21.00     21.00      21.00
                LVDS mode
Parameters




               (closed, open,
                    Auto)         Auto      Auto      Auto        Auto       Auto      Auto        Auto        Auto       Auto      Auto      Auto
             Temp Sen Alarm
                    on/off          on       on        on          on         on        on          on          on        on         on        on
              Batt Disch Test
                    on/off          off      off       off         off        off       off         off         off       off        off       off
             Additional Information

             Equalize Voltage
               Range (V)           27.96   27.96     27.96        27.96     27.96     27.96       27.96       27.96      27.96     27.96      28.56

             Notes:
             *1. Site specific
             *2. Config specific
                                                     SageView Parameter Settings (24V system)
                                                                         Flooded Cell Battery Configuations
                                 DCU          DJ          JC       KCT       2LCT-840    LCT      LCT II-1700   LCT-HP    LCY Tele   MCT II    MCTC II
             Sageon Control Unit Parameters Window
                Float Voltage
                 Range (V)       26.40      26.52        26.40     26.40      26.64      26.40      26.28        26.52     26.40      26.64     27.12
                 EQ Enable
              (check/uncheck)  uncheck     uncheck      uncheck   uncheck    uncheck    uncheck    uncheck      uncheck   uncheck    uncheck   uncheck
                EQ Per Wks
              (check/uncheck)  uncheck     uncheck      uncheck   uncheck    uncheck    uncheck    uncheck      uncheck   uncheck    uncheck   uncheck
                  Drop (V)        0.50       0.50         0.50      0.50       0.50       0.50       0.50         0.50      0.50       0.50      0.50
                No. of RECs     Note *1    Note *1      Note *1   Note *1    Note *1    Note *1    Note *1      Note *1   Note *1    Note *1   Note *1

             Sys high Voltage
                Alarm (V)         28.50      27.60       28.50     28.50      28.50      28.50      28.50        27.60     28.50      28.50     28.80

             Sys Low Voltage
                 Alarm (V)        24.00      24.00       24.00     24.00      24.00      24.00      24.00        24.00     24.00      24.00     24.00
               BATT Disch
                 Alarm (V)        25.50      25.50       25.50     25.50      25.50      25.50      25.50        25.50     25.50      25.50     25.50
Parameters




             Disch Diff I Alarm
                    (A)           Note *1   Note *1     Note *1   Note *1     Note *1   Note *1    Note *1      Note *1   Note *1    Note *1   Note *1

              Ambient Temp
                 Alarm (F)         131       131         131       131         131       131         131         131        131       131       131
             Batt Temp Alarm
                    (F)            104       104         104       104         104       104         104         104        104       104       104
             Bat Temp sensor
                   Alarm
              (check/uncheck)   Note *1     Note *1     Note *1   Note *1     Note *1   Note *1    Note *1      Note *1   Note *1    Note *1   Note *1
               Battery Monitor
               check/uncheck    Note *1     Note *1     Note *1   Note *1     Note *1   Note *1    Note *1      Note *1   Note *1    Note *1   Note *1
               Bat Disch Test
              (check/uncheck)   uncheck     uncheck     uncheck   uncheck    uncheck    uncheck    uncheck      uncheck   uncheck    uncheck   uncheck
             Battery Parameters Window

             Number of Strings    Note *1   Note *1     Note *1   Note *1     Note *1   Note *1    Note *1      Note *1   Note *1    Note *1   Note *1

             Number of Cells        12        12          12        12          12        12          12          12        12         12        12
             *Battery Rating
                  (Ah)            Note *3   Note *3     Note *3   Note *3     Note *3   Note *3    Note *3      Note *3   Note *3    Note *3   Note *3
                                                      SageView Parameter Settings (24V system)
                                                                        Flooded Cell Battery Configuations
                                  DCU          DJ          JC        KCT      2LCT-840     LCT      LCT II-1700   LCT-HP     LCY Tele    MCT II    MCTC II
Parameters




             Deep Discharge
                   (V)           21.00        21.00      21.00      21.00      21.00      21.00       21.00        21.00      21.00      21.00      21.00
              LVDS Trip (V)      21.00        21.00      21.00      21.00      21.00      21.00       21.00        21.00      21.00      21.00      21.00
             Battery Current
               Sensor (A)        Note *1     Note *1     Note *1   Note *1    Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1

             Deep Discharge
             Recovery I Lim
                  (A)            Note *1     Note *1     Note *1   Note *1    Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1

             Float Bat I Lim (A) Note *1    Note *1      Note *1   Note *1    Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
              EQ Bat I Lim (A)   Note *1    Note *1      Note *1   Note *1    Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
              BTC (mV/cell/F)
                  (Note *2)        -3.6      -3.6         -3.6       -3.6       -3.6       -3.6        -3.6         -3.6       -3.6       -3.6       -3.6
              BTC Center (F)        77        77           77         77         77         77          77           77         77         77         77
             Battery Cell Monitoring Window
                 Cell Config
               SBM Batteries        *3
               Vhigh Cell (V)      2.35      2.35         2.35       2.35       2.35       2.35        2.35         2.35       2.35       2.35       2.40
                Vlow Cell (V)       2.0       2.0         2.0        2.0        2.0        2.0         2.0          2.0        2.0        2.0        2.0
               Cell +dVc (%)         5         5           5          5          5          5           5            5          5          5          5
               Cell -dVc (%)         5         5           5          5          5          5           5            5          5          5          5

             Log Interval (min)  Note *1   Note *1       Note *1   Note *1    Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
              Cell rail polarity
                 (positive /     Not used Not used      Not used   Not used   Not used   Not used    Not used     Not used   Not used   Not used   Not used
                 negative)        defined  defined       defined    defined    defined    defined     defined      defined    defined    defined    defined
             Discharge Test Parameters Window

              Site Specific Bat
              Disch Test must
                 be checked      Note *1     Note *1     Note *1   Note *1    Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
             Additional Information
               Cell Equalize
                 Voltage (V)
             Equalize Voltage
                     (V)          27.96        27.96      27.96      27.96      27.96      27.96      27.96         27.96      27.96      27.96      28.56
                Max Charge      5A/100Ah     5A/100Ah   5A/100Ah   5A/100Ah   5A/100Ah   5A/100Ah   5A/100Ah      5A/100Ah   5A/100Ah   5A/100Ah   5A/100Ah
                 Current (A)      rating       rating     rating     rating     rating     rating     rating        rating     rating     rating     rating

             Notes:
             *1. Site specific
             *2 temp is actually mV/cell/C
                                SageView Parameter Settings (24V system)
                                            Flooded Cell Battery Configuations
                     DCU   DJ       JC    KCT   2LCT-840   LCT   LCT II-1700   LCT-HP   LCY Tele   MCT II   MCTC II
*3 config specific
                             Sageon Control Unit Front Panel Parameter Settings (48 V System)
                                                                  Flooded Cell Battery Configuations                                                           DJ   DCU   JC   KCT   LCT   LCY   MCT
                                DCU           DJ         JC          KCT       2LCT-840     LCT      LCT II-1700   LCT-HP     LCY Tele    MCT II    MCTC II    3     6    5     6    13     4     4
             Base (Home) System Menu

              Ambient Temp
                Alarm (°C)          55         55         55          55          55         55          55           55         55         55         55
             Volts High Alarm
                    (V)           57.00      57.00      57.00        57.00      57.00      57.00       57.00        57.00      57.00      57.00      57.40
             Volts Low Alarm
                    (V)           48.00      48.00      48.00        48.00      48.00      48.00       48.00        48.00      48.00      48.00      48.00
             Failsafe Alarms
                   on/off           off        off        off         off         off        off         off          off        off        off        off
             Bat Cur Sensor
                   on/off         Note *1   Note *1    Note *1      Note *1    Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
               SBM Muxing
                mode (0-7)           0          0          0           0           0          0           0            0          0          0          0
              Security on/off       off        off        off         off         off        off         off          off        off        off        off
Parameters




             Number of SMRs       Note *1   Note *1    Note *1      Note *1    Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1

             Num of Batteries   Note *1     Note *1    Note *1      Note *1    Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
                 FS Battery
                 current (A)    Note *1     Note *1    Note *1      Note *1    Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
                Load Sensor
                   on/off         off          off        off         off         off        off         off          off        off        off        off
               Alarm Report
                   on/off         off          off        off         off         off        off         off          off        off        off        off
               Modem on/off       off          off        off         off         off        off         off          off        off        off        off
                Audio Alarm
                   on/off         off          off        off         off         off        off        off           off        off        off        off
                  CBK Input    Used-N/O     Used-N/O   Used-N/O    Used-N/O    Used-N/O   Used-N/O   Used-N/O      Used-N/O   Used-N/O   Used-N/O   Used-N/O
              Bat Switch Input Used-N/O     Used-N/O   Used-N/O    Used-N/O    Used-N/O   Used-N/O   Used-N/O      Used-N/O   Used-N/O   Used-N/O   Used-N/O
                 LVDS Input    Used-N/O     Used-N/O   Used-N/O    Used-N/O    Used-N/O   Used-N/O   Used-N/O      Used-N/O   Used-N/O   Used-N/O   Used-N/O
             Auxiliary Unit Submenu
              1-ph AC Monitor
                   on/off         off          off        off         off         off        off         off          off        off        off        off
              3-ph AC Monitor
                   on/off         off          off        off         off         off        off         off          off        off        off        off
              Battery Monitor
                   on/off         on          on         on           on         on         on          on           on         on         on         on
                 Bat Config     24 Cells    24 Cells   24 Cells     24 Cells   24 Cells   24 Cells    24 Cells     24 Cells   24 Cells   24 Cells   24 Cells
               BCM Batteries    Note *1     Note *1    Note *1      Note *1    Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1

             Cell Vhi Alarm (V)    2.35       2.35       2.35        2.35        2.35       2.35        2.35         2.35       2.35       2.35       2.40
                             Sageon Control Unit Front Panel Parameter Settings (48 V System)
                                                                   Flooded Cell Battery Configuations                                                          DJ   DCU   JC   KCT   LCT   LCY   MCT
                                    DCU        DJ         JC          KCT      2LCT-840     LCT      LCT II-1700   LCT-HP     LCY Tele    MCT II    MCTC II    3     6    5     6    13     4     4

             Cell Vlo Alarm (V)     2.00       2.00       2.00        2.00       2.00       2.00        2.00         2.00       2.00       2.00       2.00
              Cell +dVc Alarm
                     (%)             4          4          4           4          4          4           4            4          4          4          4
              Cell -dVc Alarm
                     (%)             4          4          4           4          4          4           4            4          4          4          4
               Site Monitior
                    on/off          off        off        off          off        off       off          off         off        off        off        off
             RECT Menu
               SMR V high
                  Alarm (V)        57.00      57.00      57.00        57.00     57.00      57.00       57.00        57.00      57.00      57.00      57.40
             SMR V low Alarm
Parameters




                     (V)            48.00      48.00      48.00       48.00      48.00      48.00      48.00         48.00      48.00      48.00      48.00
              SMR HVSD (V)          57.40      57.40      57.40       57.40      57.40      57.40      57.40         57.40      57.40      57.40      58.00
                                  5A/100Ah   5A/100Ah   5A/100Ah    5A/100Ah   5A/100Ah   5A/100Ah   5A/100Ah      5A/100Ah   5A/100Ah   5A/100Ah   5A/100Ah
              SMR I Limit (A)       rating     rating     rating      rating     rating     rating     rating        rating     rating     rating     rating
             BATT Menu
               BATT Disch
                 Alarm (V)         51.00      51.00      51.00        51.00     51.00      51.00       51.00        51.00      51.00      51.00      51.00
             Batt Temp Alarm
                    (°C)            40         40         40           40         40        40           40          40         40         40         40
              *Battery Rating
                    (Ah)          Note *2    Note *2    Note *2      Note *2   Note *2    Note *2     Note *2      Note *2    Note *2    Note *2    Note *2
                BTC Coeff.
               (mV/cell/°C)         -3.6       -3.6       -3.6        -3.6       -3.6       -3.6        -3.6         -3.6       -3.6       -3.6       -3.6

             BTC Nominal (°C)       25         25         25           25         25        25           25          25         25         25         25

             Number of Cells        24         24         24           24         24        24           24          24         24         24         24
              BILim Vb<Vdd
                   (A)            Note *1    Note *1    Note *1      Note *1   Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
              Vdd Level (V)        1.75       1.75       1.75         1.75      1.75       1.75        1.75         1.75       1.75       1.75       1.75
             BILim Vb<Vfl (A)     Note *1    Note *1    Note *1      Note *1   Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1

             System Float (V)      52.80      53.04      52.80        52.80     53.28      52.80       52.56        53.04      52.80      53.28      54.24
              System V Drop
                    (V)             0.5        0.5        0.5          0.5       0.5        0.5          0.5         0.5        0.5        0.5        0.5
               Equalisation
                   on/off           off        off        off          off       off        off         off          off        off        off        off
              LVDS Trip (V)        42.00      42.00      42.00        42.00     42.00      42.00       42.00        42.00      42.00      42.00      42.00
Parameters




               LVDS mode
              (closed, open,
                   Auto)            Auto       Auto       Auto        Auto       Auto       Auto        Auto         Auto       Auto       Auto       Auto
                             Sageon Control Unit Front Panel Parameter Settings (48 V System)
Parameters


                                                           Flooded Cell Battery Configuations                                                 DJ   DCU   JC   KCT   LCT   LCY   MCT
                                   DCU      DJ      JC        KCT     2LCT-840   LCT     LCT II-1700   LCT-HP   LCY Tele   MCT II   MCTC II   3     6    5     6    13     4     4
             Temp Sen Alarm
                   on/off           on      on      on         on        on       on         on          on       on        on        on
              Batt Disch Test
                   on/off           off     off     off        off       off      off        off         off      off       off       off
             Additional Information

             Equalize Voltage
               Range (V)           55.92   55.92   55.92      55.92    55.92     55.92     55.92       55.92     55.92     55.92     57.12

             Notes:
             *1. Site specific
             *2. Config specific
                                                     SageView Parameter Settings (48V system)
                                                                         Flooded Cell Battery Configuations
                                 DCU          DJ          JC       KCT       2LCT-840    LCT      LCT II-1700   LCT-HP    LCY Tele   MCT II    MCTC II
             Sageon Control Unit Parameters Window
                Float Voltage
                 Range (V)       52.80      53.04       52.80      52.80      53.28      52.80      52.56        53.04     52.80      53.28     54.24
                 EQ Enable
              (check/uncheck)  uncheck     uncheck     uncheck    uncheck    uncheck    uncheck    uncheck      uncheck   uncheck    uncheck   uncheck
                EQ Per Wks
              (check/uncheck)  uncheck     uncheck     uncheck    uncheck    uncheck    uncheck    uncheck      uncheck   uncheck    uncheck   uncheck
                  Drop (V)        0.50       0.50        0.50       0.50       0.50       0.50       0.50         0.50      0.50       0.50      0.50
                No. of RECs    Note *1     Note *1     Note *1    Note *1    Note *1    Note *1    Note *1      Note *1   Note *1    Note *1   Note *1

             Sys high Voltage
                Alarm (V)         56.00      56.00      56.00      56.00      56.00      56.00      56.00        56.00     56.00      56.00     57.60

             Sys Low Voltage
                 Alarm (V)        48.00      48.00      48.00      48.00      48.00      48.00      48.00        48.00     48.00      48.00     48.00
               BATT Disch
                 Alarm (V)        51.00      51.00      51.00      51.00      51.00      51.00      51.00        51.00     51.00      51.00     51.00
Parameters




             Disch Diff I Alarm
                    (A)           Note *1   Note *1     Note *1   Note *1     Note *1   Note *1    Note *1      Note *1   Note *1    Note *1   Note *1

              Ambient Temp
                Alarm (F)          131       131         131       131         131       131         131         131        131       131       131
             Batt Temp Alarm
                    (F)            104       104         104       104         104       104         104         104        104       104       104
             Bat Temp sensor
                    Alarm
              (check/uncheck)   Note *1     Note *1     Note *1   Note *1     Note *1   Note *1    Note *1      Note *1   Note *1    Note *1   Note *1
               Battery Monitor
               check/uncheck    Note *1     Note *1     Note *1   Note *1     Note *1   Note *1    Note *1      Note *1   Note *1    Note *1   Note *1
               Bat Disch Test
             (check/uncheck)    uncheck     uncheck    uncheck    uncheck    uncheck    uncheck    uncheck      uncheck   uncheck    uncheck   uncheck
             Battery Parameters Window
                 Number of
                   Strings      Note *1     Note *1     Note *1   Note *1     Note *1   Note *1    Note *1      Note *1   Note *1    Note *1   Note *1

             Number of Cells        24        24          24        24          24        24          24          24        24         24        24
             *Battery Rating
                  (Ah)            Note *3   Note *3     Note *3   Note *3     Note *3   Note *3    Note *3      Note *3   Note *3    Note *3   Note *3
             Deep Discharge
                   (V)            42.00      42.00      42.00      42.00      42.00      42.00      42.00        42.00     42.00      42.00     42.00
                                                      SageView Parameter Settings (48V system)
                                                                           Flooded Cell Battery Configuations
                                  DCU          DJ          JC          KCT         2LCT-840     LCT      LCT II-1700   LCT-HP     LCY Tele    MCT II    MCTC II
              LVDS Trip (V)       42.00       42.00       42.00        42.00         42.00     42.00       42.00        42.00      42.00      42.00      42.00
              Battery Current
                Sensor (A)       Note *1      Note *1    Note *1      Note *1      Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1

              Deep Discharge
              Recovery I Lim
                     (A)         Note *1      Note *1    Note *1      Note *1      Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
              Float Bat I Lim
                     (A)         Note *1      Note *1    Note *1      Note *1      Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
             EQ Bat I Lim (A)    Note *1      Note *1    Note *1      Note *1      Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
              BTC (mV/cell/F)
                 (Note *2)         -3.6        -3.6        -3.6        -3.6          -3.6       -3.6        -3.6         -3.6       -3.6       -3.6       -3.6
              BTC Center (F)        77          77          77          77            77         77          77           77         77         77         77
             Battery Cell Monitoring Window
                Cell Config
Parameters




               SBM Batteries     Note *1      Note *1    Note *1      Note *1      Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
               Vhigh Cell (V)      2.35        2.35       2.35         2.35         2.35       2.35        2.35         2.35       2.35       2.35       2.40
               Vlow Cell (V)        2.0         2.0        2.0          2.0          2.0        2.0         2.0          2.0        2.0        2.0        2.0
               Cell +dVc (%)         5           5          5            5            5          5           5            5          5          5          5
               Cell -dVc (%)         5           5          5            5            5          5           5            5          5          5          5

             Log Interval (min)  Note *1   Note *1       Note *1      Note *1      Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
              Cell rail polarity
                 (positive /     Not used Not used       Not used    Not used      Not used   Not used    Not used     Not used   Not used   Not used   Not used
                 negative)       defined   defined       defined     defined       defined    defined     defined      defined    defined    defined    defined
             Discharge Test Parameters Window

              Site Specific Bat
              Disch Test must
                 be checked      Note *1      Note *1    Note *1      Note *1      Note *1    Note *1     Note *1      Note *1    Note *1    Note *1    Note *1
             Additional Information

             Equalize Voltage
                Range (V)          55.92      55.92       55.92        55.92         55.92      55.92      55.92         55.92      55.92      55.92      57.12
               Max Charge        5A/100Ah   5A/100Ah    5A/100Ah     5A/100Ah      5A/100Ah   5A/100Ah   5A/100Ah      5A/100Ah   5A/100Ah   5A/100Ah   5A/100Ah
               Current (A)         rating     rating      rating       rating        rating     rating     rating        rating     rating     rating     rating

             Notes:
             *1. Site specific
              *2 Displayed temp is actually mV/cell/C in Sageview 2.15 and lower
             *3 config specific

								
To top