326.1 ARTICLE 326 - INTEGRATED GAS SPACER CABLE: TYPE IGS
ARTICLE 326 326.80 Ampacity. The ampacity of Type IGS cable shall (
not exceed the values shown in Table 32Q.80.
Integrated Gas Spacer Cable: Type IGS
Table 326.80 Ainpacityof Type IGS Cable
I. General
Am eres
326.1 Scope. This article covers the use, installation, and 376 /
construction specifications for integrated gas spacer cable, 412
Type IGS. 429
445
326.2 Definition. 461
Integrated Gas Spacer Cable, Type IGS. A factory 476
assembly of one or more conductors, each individually 491
insulated and enclosed in a loose fit, nonmytallic flexible 505
519
conduit as an integrated gas spacer cable rated 0 through
600 volts.
II. Installation III. Construction Specifications
326.10 Uses Permitted. Type IGS cable shall be permitted 326.104 C~nductors. The conductors shall be solid
for use under ground; including direct burial in the earth, as aluminum rods, laid parallel, yonsistiI).g, of one to nineteen
the following: 12.7 mm (Yz in.) diameter rods. The minimum conductor
size shall be 250 kcmil, and the maximum size shall be
(1) Service-entrance conductors 4750 kcmil.
(2) Feeder or branch-circuit conductors 326.112 Insulation. The insulation shall be dry kraft paper
326~12 Uses Not Permitted. Type IGS cable sball not be tapes and a pressurized sulfur hexafluoride gas (SF6), both
used as interior wiring or be exposed in contact with approved for electrical use. The nominal gas pressure shall
buildings. be 138 kPa gauge (20 pounds per square inch gauge). The
\,
326.24 Bending Radius. Where the coilable nonmetallic thickness of the paper spacer shall be as specified in Table
conduit and cable is bent for installation purposes or is 326.112.
flexed or bent dUring shipment or installation, the radii of
bends measured to' the inside of the' bend shall not be less
than specified in Table 326.24. Table 326.112 Paper Spacer Thickness
Thickness
SiZe (kcmil) mm in.
Table 326.24 Minimum Radii of Bends 250-1000 1.02 0.040
Conduit Size Minimum Radii 1250-4750 1.52 0.060
Metric Designator Trade Size mm in.
53 2 600 24 326.116 Conduit. The conduit shall be a medium density
78 3 900 35
103 4 1150 45 polyethylene identified as suitable for use with natural gas
rated pipe in metric designator 53,78, or 10~ (trade size 2,
3, or 4). The percent fill dimensions for the conduit are
326.26 Bends. A run of Type IGS cable between pull shown in Table 326.116.
boxes or terminations shall not contain more than the
The size of the conduit permitted f6r each conductor
equivalent of four quarter bends (360 degrees total),
size shall be calculated for a percent fill not to exceed those
including those bends located immediately at the pull box
found in Table 1, Chapter 9.
or terminations. .
326.1~0 Marking. The cable shall be marked in
326.40 Fittings. Terminations and splices for Type IGS
accordance with 310.11(A), 310.11(B)(I), and 310.11(D).
cable shall be identified as a type that is suitable for
maintaining the gas pressure within the conduit. A valve
and cap shall be provided for each length of the cable and
conduit to check the gas pressure or to inject gas into the
conduit.
70-174 2007 California Electrical Code