Amsterdam Airport Schiphol

Document Sample
Amsterdam Airport Schiphol Powered By Docstoc
					Amsterdam
Airport Schiphol                                                                                0
Guidelines with respect to the type of materials that can be used for promotional purposes

Introduction
This is a summary of an internal Schiphol airport working paper containing a description of the materials tested on
the basis of their fire safety and use in the Terminal complex. All materials should be tested by Schiphol airport to see
if they comply with the airport’s fire safety requirements. All parts have to meet fire class 1 with a smoke density of ≤
5.4 m–1 or class 2 with a smoke density of ≤ 2.2 m–1, in which case the 5% rule applies.
The information provided is subject to changes in insights and circumstances.
If you would like to have some advice on materials that do not appear on the list or on alternatives, please contact the
Schiphol Media Traffic Manager, Ronny Haimé, tel. +31.20.601.3059, mail haime_r@schiphol.nl.
The tests shall be executed in accordance with NEN 6066 and NEN 6065 or CE conform.

Materials:

Metals

Permitted
•   Steel
•   Stainless steel
•   Aluminium, both normal and anodized
•   Brass

Wood and wood products

Permitted
•   Widowplan 2 (www.wilhelmi.de/brandschutz/brand_dyn/bs_widoplan.htm)

Generally permitted
•   Abet (HPL, Laminate and “Print HPL”) consisting of chipboard, MDF and wood.
•   Bergron: Only the 30 minutes fire-resistant version filled with solid flax fibre should be used.
•   Birch Plywood
•   Brillant sandwich panels (Fire protection Vermiculite Brillant A1)
•   Chipboard
•   Chipboard: Mabsol Par (laminate – chipboard - laminate)
•   Decometal: www.formica.co.nz
•   Duropal HPL -F :(www.Duropal-online.nl)
•   Ecophon Focus DG (ceiling panels: www.ecophon.com)
•   Egger products
    1. Egger laminate
    2. Egger decorative laminate
•   Formica VFP
•   Hardwood with a density of around 790 kg per m2
•   Wood that has been impregnated with a fire retardant substance. Fire class 1 or 2 according to NEN 6065
•   Triplex and woodlike sheeting materials. Fire class 1 or 2 according to NEN 6065
•   Sheeting materials
    1. MDF - FR treated with fire-retardant substance. Fire class 1 or 2 according to NEN 6065
    2. Chipboard treated with fire-retardant substance in fire class 1 or 2 according to NEN 6065
    3. OSB (Oriented Strand Board) treated with fire-retardant substance in fire class 1 or 2 according to NEN 6065
•   Hygiene sealed and hygiene baffle (insulation sheets)
•   Inotec pyroex P and inotec pyroex P coated
•   MDF FR
•   MDF fyrax FR-MDF (for the benefit of walls and display cabinets)
•   Polyrey Pur Métal
•   Piriv F-1 (laminate)
•   TRESPA Meteon and TRESPA Meteon FR panels.
•   Hardwood

Not Permitted
•   Pinewood


Glass

Permitted
•   Laminated glass
•   Floatglas
•   Toughened glass




Amsterdam Airport Schiphol, Passengers Management, Doc.Nr. 2004121 E, d.d. 10-12-2004                                  1
Amsterdam
Airport Schiphol                                                                               0
•   Flame-resistant glass

Not permitted
•   Wired glass

Plastics

Generally permitted
•   VIVAK
•   3M Scotscall 3630 foil
•   3M Controltac Elektrostatische folie 8635 C
•   Corian (synthetic)
•   CMHR 40 Rosa (Combustion Modified High Resilience)
•   Polyester (DTEX polyester)

Occasionally permitted
•   Hostaglass
•   Spectar (UV)
•   Veralite 100
•   Veralite 200
Remark: The materials mentioned above are only to be used when the use of VIVAK is proven to be impracticable.

Not permitted
The most important ones are
•   Plexiglas
•   Vorex
•   Lexaan
•   Polycarbonaat
•   Polystereen
•   Vinyl folie
•   PVC
Remark: due to its favourable characteristics and the lacking of alternative materials, on some occasions the use of
Neschen, a material containing PVC, will be permitted.

Textiles

Permitted
•   Boyamide / Aramide

Generally permitted
•   NURFLEX blackout FR 10920 and FR 10950
•   Unica VAEV
•   Trevira
•   Polyester / polyamide / Wool
•   Solvotex arist 250
•   Valmex
•   Frontlit

Paint and Coatings

Generally permitted
•   Water-based paints and varnishes
•   Fire retardant varnishes
•   Transparent D.D. Varnish
•   Lignal-PUR-B1-Lack met Lignal-PUR-Harter
•   Alexit FST varnish
•   Emulsion paint, Deluxe Colour Dimensions

Rubber

Generally permitted
•   DaLsouple (www.dalsouple.com)
•   Pirelli Rolfloor 279 FR 21

Never permitted
Rubber products that are not fire-resistant may not be used.




Amsterdam Airport Schiphol, Passengers Management, Doc.Nr. 2004121 E, d.d. 10-12-2004                                  2
Amsterdam
Airport Schiphol                                                                                0
Adhesives
There are no known types of adhesive that can be used without testing

Flooring and floor covering

Generally permitted
•   Polyamides (PA) treated with a fire-retardant substance
•   Polypropylene (PP) treated with a fire-retardant substance
•   Carpets (Bottega DV 256)
•   Bolidt floors
•   Desso torso (carpet tiles)
•   Forbo marmoleum
•   Esco carpet tiles (8)
•   Noraplan Choutch / rubber fire –resistant
•   Hardwood

Not permitted
•   Gerflor Mipolan PVC
•   Pine wood



Furniture
In general furniture can not be used without testing. When ordering a piece of furniture, however, it is generally
possible to request a fire certificate to be made.

Miscellaneous materials
Paper: Paper advertisements are tolerated because the fire load per advertisement is limited.
Leather: Leather is non-flammable and is permitted.


Supplementary Information was derived from the following documents:
K:\TERMINAL\TFS\HTBA\ADVI\PMN\Brandbeveiliging\Brandtechnische eigenschappen materialen\Beoordelingen-

         -Betr.020332PromotieautoLexusopBCcorridor.doc
         -IC030747-6SchiphoPlazaPP2PromotiestandSixtbrandveiligematerialen.doc
         -IC 020273 mobiele promotie AT&T in reclaim 3_.doc
         -IC 030622 Schiphol Plaza Promotiestand PP2.doc
         -IC 030682-2 object bannier Holland Casino-2.doc
         -IC 030702 Plaza Promotieplaats PP4 KLM Stand toetsing materialen.doc
         -IC 030747-2 Plaza Promotieplaats PP2 Sixt toetsing materialen.doc
         -IC 030747-3 Plaza Promotieplaats PP2 Sixt toetsing materialen.doc
         -IC 030747-7 200453TB SchiphoPlaza PP2 Promotiestand Sixt brandveilige materialen.doc
         -IC 041276 200486TB Lounge 1 KLM Banier materialen.doc
         -IC 041329 SPL Plaza VP 1 Promotie locatie Politie brandveilige materialen.doc
         -IC 200482 TB 031022 reclame uitingen etalages plaza, richting JD-plein.doc
         -IC 200488TB 041383 Reclaim 2 Hema-Banieren toetsing materialen.doc
         -IC 200489TB 041373 Reclaim aankomstenhallen EU-Banieren toetsing materialen.doc
         -IC 2004110TB 041361 Terminal 2 nabij Medische Dienst Vertrek 2 Reclame object toetsing materialen.doc
         -IC Integrale Risico inschatting Bannier doek SPL. Plaza. EK.doc
         -Betr.020332PromotieautoLexusopBCcorridor.doc

Other References:
        -Basisdocument Brandtechnische Eigenschappen Materialen Terminalcomplex Deel 1
        -Basisdocument Brandtechnische Eigenschappen Materialen Terminalcomplex Deel 2

Approved by P. van Moerkerken 12-10-2004




Amsterdam Airport Schiphol, Passengers Management, Doc.Nr. 2004121 E, d.d. 10-12-2004                                3

				