Power Meter (PDF)

Document Sample
Power Meter (PDF) Powered By Docstoc
					Power Meter
       The PowerLogic    Features
       Power Meter is    Economical Metering Solution
       cost effective,   s A single, economical electronic device that replaces a full complement of
                         analog meters
       high              s Accurate true rms metering of distorted currents and voltages up to the 31st
       performance       harmonic
                         s THD readings for each metered phase of current and voltage to assist in
       meter. It can     measurement of power quality data
       operate as a      s Neutral current monitoring to detect overload neutrals
                         s Individual machine load monitoring
       stand-alone       s Available feeder capacity monitoring (peak demand current)
                         s Load monitoring for predictive maintenance/troubleshooting
       device or as      s Departmental kWh cost allocation
       part of a         s Remote meter reading and data logging from a personal computer using
                         PowerLogic System Manager™ software and RS-485 communications
       PowerLogic
       system.           Ease of Installation
                         s Display mounts in panel cutout of many analog meters
                         s Separate meter and display modules allows flexible mounting options (model
                         PM-600 and higher)
                         s Easy retrofit into existing power equipment
                         s Standard IEC dimensions, 144 x 144 mm (PM-100, PM-150, PM-300)


                         Direct Connect Up to 600 V
                         s No PTs required up to 600 V
                         s No separate control power required on up to 600 V circuits


                         Communications Options
                         s PowerLogic communications for integration with a PowerLogic Power Monitoring
                         System
                         s Modbus® RTU communication for integration with other systems
                         s Energy pulse initiator for communication to energy management systems


                         2-Line LCD Display
                         s Mounts back-to-back or up to 15 meters from Power Meter module (PM-600,
                         PM-620, PM-650)
                         s Use as a portable power meter programmer (PM-600, PM-620, PM-650)
                         s Simultaneous display of phase A, B, C quantities
                         s Provides setup and display of metering information
                         s Provides optical isolation from 600 V metering connection


                         Designed for Reliability
                         s Tested for compliance with UL, and NOM, CSA requirements
                         s CE mark
                         s Testing in accordance with stringent IEC 1000 series of electrical tests
                         s FCC compliant (Class A)
                         s Vibration and temperature tested




8
Instrumentation Summary                            Basic Metering Solution and More
s   Real-Time Readings                             The PowerLogic Power Meter is designed for use in basic power metering
s   Current (per phase, N, G, 3-phase)             applications. It can replace conventional metering devices such as ammeters,
s   Current (neutral, N)                           voltmeters, and watt-hour meters while providing powerful capabilities not offered
s   Voltage (L-L, L-N)                             by analog metering. The Power Meter’s true rms readings (31st harmonic
s   Real Power (per phase, 3-phase)                response) accurately reflect non-linear circuit loading more than conventional
s   Reactive Power (per phase, 3-phase)            analogue metering devices. The Power Meter calculates the neutral current, which
s   Apparent Power (per phase, 3-phase)            can assist in identifying overloaded neutrals due to either unbalanced single
s   Power Factor (per phase, 3-phase)              phase loads or triplen harmonics. Circuits can be closely monitored for available
s   Frequency                                      capacity by keeping track of the peak average demand current. Accurate circuit
                                                   loading information is essential to get the most out of existing power equipment
s  Demand Readings                                 while maintaining power system reliability.
s  Demand Current (per-phase present, peak)        The Power Meter provides a full complement of accurate true rms metering
s  Average Power Factor (3-phase total)            values through its display, or via the standard RS-485 communication port to
s  Demand Real Power (3-phase total)               a PowerLogic Power Monitoring and Control System. Refer to the tables for
s  Demand Reactive Power (3-phase total)           information about the metering values reported by each model. A relay output is
s  Demand Apparent Power (3-phase total)           included to communicate energy and demand information to third party energy
s  Coincident Readings                             management systems.
s  Predicted Demands
s  Advenced demand option (Synch to comms,
sliding block calculation                          Mounting Flexibility
s   Energy Readings                                The Power Meter’s small size and variety of mounting configurations allow it to be
s   Accumulated Energy, Real                       readily installed in new equipment or retrofit into existing equipment. The Power
s   Accumulated Energy, Reactive                   Meter module can be mounted onto a 35mm DIN rail, or it can be mounted on
s   Accumulated Energy, Apparent                   any flat surface using its four mounting feet. For added simplicity in retrofit
s   Bi-directional Readings                        installations, the panel mounting hole patterns for both the Power Meter module
                                                   and the Power Meter display match the conventional ammeter/voltmeter spacing
s Other monitoring functions                       so the meter and the display can be mounted back-to-back on opposite sides of
s Energy pulse relay output                        a panel surface. In metering installations of 600 V and below, the Power Meter
s RS-485 PowerLogic and Modbus RTU                 provides additional savings in both cost and mounting space by eliminating the
communications                                     need for PTs and control power transformers.
s THD, voltage & current (A, B, C)
s Date/time stamping (Peak demands, power
up/restart, resets)                                Versatile Display
s Onboard alarms (Under/over conditions, phase
unbalance conditions)                              The optional Power Meter display for models PM-600, PM-620, PM-650 mounts
s Min/max readings (Frequency, current, voltage,   in the same space as conventional meters and is connected to the Power Meter
power, power factor, THD)                          module with a communication cable. With the 2-line by 16-character LCD display,
s Data and event logs                              the user can view metering data, and access the password protected meter setup
                                                   and resets menus. Since the Power Meter display can be mounted up to 15 m
                                                   away from the Power Meter module, power metering can now be installed in tight
                                                   equipment spaces without sacrificing convenient and affordable local display.
                                                   The communications port on the Power Meter display is optically isolated from
                                                   the 600 V metering connections.




                                                                                                                                    9
Power Meter
              Powerful Functionality
              The Power Meter accepts inputs from standard 5 A CTs and has full scale input
              of 10 A. The voltage inputs can be directly connected to 3 phase circuits of 600 V
              and below without the need for PTs or CTs. For higher voltage circuits, the Power
              Meter accepts a full range of PT primary values with control power derived from
              the PTs or from a separate source of ac or dc control power. Setup and resets
              are password protected and are easily done through the Power Meter display
              or via the network using System Manager software. PowerLogic or Modbus RTU
              protocols can be selected. All readings are scaled to their actual values without
              the need for a multipler.


              Advanced Functionality
              In addition to the basic metering functions, the Power Meter increases its value to
              you with advanced functionality features.
              Power Quality Readings - Total Harmonic Distorsion (THD) for current and voltage
              readings indicate potential power quality problems, which unchecked, could
              disrupt critical processes or damage equipment.
              Min/Max readings - Min/max readings provide measurements of extreme meter
              values needed for maintenance purposes. These readings can be viewed and
              reset from the display. Min/max resets are password protected.
              Alarm/Relay Functions - The PM-650 has on-board alarms. Alarm functions
              include over/under conditions for voltage, current, frequency, and phase
              unbalances. In addition, these alarms can be assigned to operate the solid-state
              output.
              Event logging - When an alarm condition occurs, the PM-650 Power Meter logs
              the event in nonvolatile memory. These events can be viewed from the display or
              PowerLogic software.
              Data Logging - As part of a comprehensive power system, the PM-650 expands
              metering capabilities with data logging. Values are stored in nonvolatile memory,
              preserving critical data for the interval between logging updates via
              communications with the system computer. All metered values are available for
              recording at user defined intervals, offering total flexibility. A typical log
              configuration is recording demand readings for kW, kVAR, and kVA, at hourly
              intervals, storing 3 days of information. The meter is pre-configured from the
              factory to log values.


              PowerLogic system Compatibility
              The Power Meter supports standard PowerLogic RS-485 communications up
              to 19,200 Baud with communications links up to 3300 m. A meter can quickly be
              installed into any existing PowerLogic system.
              The Power Meter has been fully integrated into the latest PowerLogic application
              software, System Manager. SMS software enables users to manage their electrical
              distribution systems by providing tabular and graphical data displays, alarms, real
              time and historical time trend tables and graphs, and reports. Power Meter setup
              and reset operations and wiring diagnostics can also be performed from a remote
              personal computer using System Manager software.
              PowerLogic power monitoring devices and systems assist in equipment
              monitoring for cost allocation, troubleshooting, predictive maintenance, planning,
              and more. The lower installed cost of the Power Meter makes it possible for
              facilities to monitor many smaller, less critical feeder circuits enabling whole
              facility power monitoring.




10
                                                            Models PM-600, PM-620, PM-650

Dimensions                                                  Typical Wiring Diagram(1)

                  3.81                                      Aø
        6.03      96.7
        153                                                 Bø
                                                     LINE                                                                      LOAD
                                                            Cø

                              4.50
                                                            N
                              114

4.62
117                                                                                                             NOTE: CONTROL POWER
                                                                                                                CAN BE DRAWN FROM FUSED
                                                                                     FUSES                      VOLTAGE INPUTS L-L OR L-N
                                                                                                                OR AN EXTERNAL SOURCE

                                                                                                                L1-L2 100-300 VDC
                                                                                                                       90-600 VAC

                     Inches
                                                                                                     TOP
       3.63          mm
                     pulgadas
       92.1          milímetros




                                                                                                 A   B   C N                PULSE
                                                                                        8        9   10 11 12
                                                                                                     VOLTAGE       19       OUTPUT
                     4.50                                                               L2 7                       20
                     114                                                                             CONTROL       21
                                                                                        L1 6
                                                                                                     POWER



                     1.26                                                                         A- B- C-
          4.50       32.0                                                                        13 14 15           22
          114                                                                       +IN 5        CURRENT                    DISPLAY
                                                                                                 16 17 18
                                                                                    –IN 4        A+ B+ C+                   CONNECTOR
                                                                        COMM’S      +OUT 3
                                                                                    –OUT 2
                                                                                    SHLD 1




                                                            (1) 3-Phase, 4-Wire WYE. (3-Wire Delta and other system types supported.)




Technical Specifications                                    Ordering Information
Metering Specifications                                     Type                      Description
s Current Inputs:                                           3020 PM600-MG             Power Meter Module, Basic Instrumentation
s Current Range               0–10A                         3020 PM620-MG             Power Meter Module, Basic Instrumentation, plus Demand,
s Nominal Current             5A                                                      THD, Date/Time Stamping, Neutral Current
s Overcurrent                                               3020 PM650-MG             Power Meter Module, Min/Max, Alarms, Event and Data
Withstand                     500 A, 1 second                                         Storage, plus PM-620 Features
s Voltage Inputs:                                           3020   PMD32-MG           Power Meter Display with 0.3 m Cable
s Voltage Range               20–600 Vac/115-500V*          3020   SC104-MG           Optional 1.2 m Cable
s Frequency Range                                           3020   SC112-MG           Optional 3.6 m Cable
(50/60 Hz)                    45–65 Hz                      3020   SC130-MG           Optional 9 m Cable
s Accuracy:
s Current, voltage            0.25% / 1%*
s Power, energy               0.50% / 1.5%*
s Power Factor                1.00% / 1.5%*
s Frequency 50/60 Hz          0.02 Hz

Control Power Input Specifications
s Input Range, ac        90–600 Vac / 115-500 Vac*
s Frequency Range        45–65 Hz
s Input Range, dc        100–300 Vdc / NA*

Temp. Range (operating)
s PM-100, 150, 300      -20 to 55° C
s Meter Module          0 to 60° C
s Meter Display         0 to 55° C

Weight
sPM-100, 150, 300             0.3 kg
sPM-600, 620, 650             0.5 kg
sPower Meter Display          0.2 kg

* PM-100, PM-150, PM-300




                                                                                                                                            11
 Power Meter
                                                 Models PM-100, PM-150, PM-300

 Dimensions                                      Typical Wiring Diagram(1)

                                                                                                                  Ph1 Ph2 Ph3 N



                                                                                                                  S1
      P                      F
                             P                   (B') RD
                                   175
                                                 (A') RD+
                                 144             (B) TD-                                                             S2 S1
   Param.


                                                 (A) TD+
                                                                                                                        S2   S1



                                                                                                                             S2
                                                    PM300           18 17     16    14          S1S2S1S2S1S2
                   144
                                                             RC                                 1     2      3
                                                                                                                       15 / 6300A
                                                              K1            K2
                                                                                         V1     V2    V3     N
                                                            1 2 3     4 5 6               7      9    11     13

                                                                                                protection

136,5                                                                                     (2)




                                                                    shunt release
                                                                         MX


            42,5
              51




                                                 Ordering Information
                                                 Type                     Description
                                                 PM-100                   Power Meter, stand-alone
                                                 PM-150                   Power Meter, internal bus communications
                                         138,5   PM-300                   Power Meter, Modbus communications




                     138,5




 12

				