Ritz Instrument Transformer_2

Document Sample
Ritz Instrument Transformer_2 Powered By Docstoc
					RITZ MESSWANDLER
RITZ INSTRUMENT TRANSFORMERS

Product information for Medium Voltage CT’s and VT’s up to U m = 72,5 kV

For more information, please click on your favourite transformer type


CONTENTS
Current Transformers                                                    Um

   Indoor Post Type

                 GSW 10...30                                            12...38      kV
                 GSW 45...72.5                                          52; 72.5     kV
                 GSS(O) 10...20 (with and without busbar)               12...24      kV

   Outdoor Post Type

                 GSWF 10/0...20/0                                       12...24    kV
                 GSWF 10...72.5                                         12...72.5 kV
                 VSWF 45...72.5                                         up to 72.5 kV

   Indoor Bushing Type (through-the-wall-type)

                 GTDSO 10...30                                          12...38.5    kV

   Outdoor Bushing Type (through-the-wall-type)

                 GTDSOF 10/0..30 (for outdoor use)                      12...38      kV
                 GTDSOFI 10...30 (for outdoor-indoor use)               12...38      kV


Voltage Transformers

   For Indoor use

                 GSE 10...45                                            12...52      kV
                 GSZ 10...30 (double-pole insulated)                    12...38.5    kV
                 GSE 72.5

   For Outdoor use

                 GSEF 10/0...30/0                                       12...38.5    kV
                 GSEF 10...45                                           12...52      kV
                 GSZF 10...30 (double-pole insulated)                   12...38      kV
                 GSEF 72.5                                              up to 72.5   kV


Medium Voltage Transformers                                             KG Ritz Messwandler GmbH
                                                                        20.08.1999 – VMI/Sh.
ELECTRICAL              DATA
STANDARDS:    All national and international standards such as AS, BS, CSA,
    IEC, IEEE (ANSI), NBN, CVE, SS, UTE and VDE.

INSULATION       LEVELS:       GSW 10         up to 12/36/ 75kV
                               GSW 20         up to 24/55/l 25kV
                               GSW 30         up to 38/75/200kV

PRIMARY       CURRENT:      Up to 1500A maximum        continuous    service current.

SECONDARY        CURRENT:       5A or IA, or any other value on request.

CHANGING      OF RATIO: With primary winding in two sections intended for
   connection    either in series or in parallel, forming a double ratio 1 : 2
                                                        up to 2 x 600/5A (or IA),
   with primary winding in four sections intended for connection either in
   series or in series-parallel   or in parallel, forming a triple ratio 1:2:4
                                                        up to 4 x 150/5A (or IA),                                  GSW 20 size 01
   or by secondary taps .. .... ...... ..... ..._. e.g. 1 OOO-800-600/5A (or IA).

FREQUENCY:          50Hz or 60Hz. Any other value on request.

CORE DATA: Up to three independent toroidal cores:
   For measuring   purposes with small instrument security factor (FS), e.g. 15VA, class 0.2 (or cl. 0.5 or cl. 1 .O), FS5.
   For protection purposes with high accuracy limit factor (ALF), e.g. 30VA, class IOPIO (ALF=lO) or lOP20 (ALF=20).

SHORT-TIME       CURRENT RATING: To specification.
    Thermal     rating: up to IOOkA for 1 second (up to 58kA for 3 seconds).                 Dynamic (mechanical         rating): maximum       IOOkA.

TESTS: Routine       tests in compliance    with applicable    standard.      Measurement     of internal partial discharges     is performed     as a
    routine test.



CONSTRUCTION
GENERAL:       Post type with wound    primary, insulated     by brown epoxy resin. (Grey resin on request).

PRIMARY TERMINALS:            Details are shown overleaf. All terminals are of nickel plated copper.
    Type “D”: for direct connection of primary conductor.
    Type “H”: horizontal palms with one bolt of metric size Ml 2 (up to 600A) or two bolts Ml2 (>600... 1500A). Any other
               palms or NEMA pads on request.
    Type “V”: vertical palms with one bolt Ml2 (up to 600A) or two bolts Ml2 (>600 .. . 1500A).
    Type “F”: flat, upright terminals (up to 800A) with one bolt M12.
    CT’s with series-parallel    primary winding have a transparent and sealable cap at the top to cover the links for changing
    of ratio.

SECONDARY       TERMINALS:        Screws of nickel plated brass of size M6. For details of terminal box see below.

BASE: Standard     design:      two mounting     brackets     of galvanized     steel. Without   secondary    terminal    box. Earthing   at one of
    the mounting brackets.
         Special design:      mounting base and secondary terminal box of aluminium alloy. Terminal box with transarent and
    sealable cover. Grade      of protection: IP52 in compliance with DIN 40050 and IEC 529. Each secondary terminal can be
    earthed by means of       a “screw-through-connection”     inside the box. Three cable glands Pg16 for cables up to 16mm
    diameter are provided.    One earthing bolt of size M8 on the opposite side to the terminal box.

MOUNTING:      In any position, even upside down.

MECHANICAL       STRENGTH:       2500N.                                                     TROPICALIZED       DESIGN:      At a small surcharge.

COMMISSIONING:         Units are supplied   ready for service. Just connect to system. Special tools are not necessary.
                                                          options of primary terminals,                         with bolt(s)                            Ml2

       (HI (horizontal)                                            Ivl   (vertical)                                             IFI      (flat,                outside)                                         IFI       (flat,   inside)
                                                                                                                                                            p--150-                                                          8r     l--90-
                                                                                                284----
I          r
           I        w---220-~
                                       284--
                                                                              r        r-220-




                          Standard              design                                                                                Special                                    design
       q       (direct)                                                                                            q          (direct)
                                                        cnty
                          trllqarentcapforpnmxyrecomectlo”                                                                                 tmnsporent           cap   for   pfwmry   r*comctlon         only




                                                                                                                                                                                                                      MlO(10dia)          15de !ep




                                                               I
                           -e2                 _I                                                                                     l-------e,                                     A

Type   I I
       Size        bl     1 b2
                                    Dimensions
                                   1 d 1 el
                                                     in mm
                                                      1 e2 1 h                    I
                                                                                      Weight
                                                                                      I kg I
                                                                                                          Type

                                                                                                                   I
                                                                                                                       Size

                                                                                                                          11
                                                                                                                                      bl                1 b2
                                                                                                                                                                             Dimensions
                                                                                                                                                                            1 d 1 el
                                                                                                                                                                                                           in mm
                                                                                                                                                                                                           1 e2 1 h
                                                                                                                                                                                                           1 155 1 ---
                                                                                                                                                                                                                                         IWeight]
                                                                                                                                                                                                                                   1 I 1 kg 1
                                                                                                                                                                                                                                   1 277 1 12 1
                                                                                                          GswiEI                      180               1 170               1 14           1 155           w       y:              ml

                                                                                                           lo      1 22 1 240                           1 210               1 A,.          1 200           1 275      1300*6/       392 1 28




                                                                                                          GSW
                                                                                                           20
                                                                                                                                                                                                                                    ---

                                                                                                                t 31 1 290      I                       1 250
                                                                                                                                                        I                   1 -            1 250           1 %I 1390
                                                                                                                                                                                                           I          I       *8   1 367 1           i
                                                                                                                1 00 1 180                              1 200               1 14           1 155           1 155 1 ---             1 277 1 17
                                                                                                                                                                                                                                         I           I
                                                                                                          G?!!w   01
                                                                                                                  02   240                                210                 a.                           12001~:‘.“,0            t3171   22        I
                                                                                                                                                                                                  2oc




RITZ MESSWANDLER                                                                                                                                                                         Phone:                49 - 40 - 511 23 0
       P. 0. Box 20 22 51                                                                                                                                                                Fax:                  49 - 40 - 511 23 286
D-20243 Hamburg - Germany
INDOOR                CURRENT                    TRANSFORMER
GSW 45.m72.5 ;;E;;insu’ated 1up to
                             upto
                                                                                                         72.5 kV
                                                                                                         1500A


ELECTRICAL            DATA
TYPE DESIGNATION:
     GSW 45 -     max. system voltage 52 kV
     GSW 72.5 - max. system voltage 72.5 kV
       No difference in dimensions.

STANDARDS:      All national and international standards, such as ANSI, AS,
       BS, CSA, IEC, NBN, NEN, &/E, SEN, UTE and VDE.

INSULATION         LEVELS: Up to 72.5 / 140 / 350 kV.
PRIMARY CURRENTS: Up to 1500A maximum continuous service current.

SECONDARY          CURRENT: 5A or 1A or any other value on request.

CHANGING OF RATIO: With primary winding             in two sections intended for
       connection either in series or in parallel up to 2 x 600A.
       Or by secondary taps, e.g. 1 OOO-750-500A.

FREQUENCY: 50Hz or 60Hz. Other values on request.
CORE DATA: Up tothree independent toroidal cores.
       For measuring purposes .....
       ... .. to ANSI and CSA e.g. class 0.6 B-O.1 to B-O.9
              to AS e.g. 3OVA, class 0.5M
              to BS and IEC e.g. 3OVA, class 0.5 (Fs5)
       For protection purposes .....
       ..... to ANSI e.g. C200, to CSA e.g. 1 OL200
              to AS e.g. lOP2OOF20
              to BS and IEC e.g. 30VA class 1 OP20

THERMAL AND DYNAMIC (MECHANICAL)                           RATING: According to specification. Maximum thermal current: 1OOkA for
       1 second.

TESTS: Routine tests in compliance       with applicable     standard.   Measurement      of internal partial discharges   is performed   as
       a routine test.

CONSTRUCTION              DETAILS
GENERAL: Post type with wound        primary. The core-and-coil   assembly is completely enclosed in epoxy resin. Colour
        of resin: Brown   RAL 8016. Grey resin on special request, e.g. ANSI 70. Practically non-inflammable.

PRIMARY TERMINALS:              Details are shown     overleaf. All terminals   are of nickel plated copper.
       Type ‘ID”: for direct connection of primary conductor.
       Type “H”: horizontal palms, with one holes (up to 600A) or two holes (>600...1500A)         of 14mm diameter.
                 NEMA pads on special request.
       Type “R”: horizontal stems of 30 mm diameter, (up to 600A of nickel plated brass, >600...1500A of nickel plated copper).

BASE: Consisting      of two strong mounting    brackets     of hot dip galvanized     steel.

SECONDARY        TERMINAL BOX: Of aluminium alloy. With transparent and sealable cover. With 3 cable glands of size
       Pg 16 for cables up to 16mm diameter. Secondary terminals of metric size M6 (6mm diameter).  Each terminal
       can be earthed by means of a simple link inside the terminal box.

GROUNDING: One bolt Ml2 at the opposite              side of the terminal    box.

TROPICALISATION:           At a small surcharge.

MOUNTING: Vertical        erect only.

COMMISSIONING:            Units are supplied   ready for service. Just connect to system. Special tools are not necessary.
INDOOR            CURRENT                     TRANSFORMER
                                                  cast resin insulated            up to 72.5 kV
GSw             45mmm72B5                         post type                     1 up to 1500 A




             Options of
             primary terminals:                             0H   (horizontal)            1D 1 (direct)


                                          . . .600 A               750.. .I500 A             . ..1500A




                                                                                         q     (round)




                   pg




                                                                         014
                                                                                                         ‘M   10, 18deep




                        Veight: approx.     140 kg




RITZ      MESSWANDLER
P.O.Box 20 22 51, D-20243 Hamburg
             GERMANY
Phone: @O)51 123-0, Fax: (40) 51 123 286
  INDOOR CURRENT TRANSFORMERS
  GSSO IO.. .2O without busbars                                      1 maximum system voltage 24kV
  GSS IO...20 with busbars                                           (      rated service current up to 4000A




ELECTRICAL             DATA
STANDARDS:    All national and international standards such as AS; BS, CSA,
    IEC, IEEE (ANSI), NBN, CVE, SS, UTE and VDE.

INSULATION    LEVELS:
     GSS 10 and GSSO 10, sizes 1 and 2:                            up to 12/36/75kV
     GSSO 10, size 3 and GSSO 17.5:                                up to 17.5/38/95kV
     GSS 20, size 1 and GSSO 20, sizes 1 and 2:                    up to 24/55/l 25kV

PRIMARY     CURRENT:       1000 to 4000A.

SECONDARY        CURRENT:         5A or IA, or any other value on request.

CHANGING     OF RATIO: By secondary          taps, e.g. 4000-3000-2000/5A       (or IA).

FREQUENCY:       50Hz or 60Hz. Any other value on request.

CORE DATA: Up to three independent cores.
    for measuring purposes with small instrument          security factor (FS),
                                                        e.g. 30VA, class 0.5, FSIO                                        GSS 20
    for protection   purposes with high accuracy limit factor (ALF),                                              with 2 busbars 80x10 mm
                                                 e.g. 6OVA, class 5P20 (ALF = 20)
SHORT-TIME       CURRENT RATING:
    thermal:                 > 1 OOkA for 1 second.
    dynamic (mechanical):    practically unlimited

TESTS: Routine tests in compliance            with applicable   standard.    Measurement     of internal   partial discharges      is performed         as
    a routine test.


CONSTRUCTION
GENERAL:     Post type, insulated by brown epoxy resin. (Grey resin on request).
    Types GSS 10, sizes 1 and 2 as well as type GSS 20 size 1 have busbars of nickel plated copper. For dimensions please see
                     overleaf. These bars are guided by caps with appropriate orifices. Caps are of aluminium alloy.
    Types GSSO.. have no busbars. Guiding caps for busbars can be provided on GSSO 10, sizes 1 and 2 as well as on
                     GSSO 20, size 1. Dimensions of available caps are shown overleaf.
    The guiding caps can be shifted to put the busbars either in horizontal or in vertical position. This applies to GSSO.. as
    well as to GSS..

APERTURES:     For available dimensions please see overleaf.
    The inner surface of both the GSSO.. and the GSS.. consists of a brass tube which is fitted with a flexible terminal to be
    connected to the primary conductor to keep the CT on the same potential level. (GSS.. are supplied with that terminal
    already connected to one of the busbars).

SECONDARY         TERMINAL     BOX: Of aluminium alloy, with transparent and sealable cover. Grade of protection: IP52 in
    compliance     with DIN 40050 and IEC 529. Terminals are of nickel plated brass of size M6. Each terminal can be earthed
    by means of a “screw-through-connection”     inside the box. Three cable glands Pg16 for cables up to 16mm diameter
    are provided.

BASE:   Of aluminium    alloy.                                                                               MOUNTING:          In vertical position.

EARTHING:     One earthing       bolt of size M8 on the opposite   side to the terminal box.

MECHANICAL       STRENGTH:          2500N.                                                 TROPlCALlZED       DESIGN: At a small surcharge.

COMMISSIONING:         Units are supplied    ready for service. Just connect to system. Special tools are not necessary.
GSSO IO...20
                                                                                      optional
                                                                                      on GSSO IO, size 1 and size 2
                                                                                      on GSSO 20, size 1:




                                                                                      ii--
                                                                                      caps with orifices to guide busbars




                                                                                      a        I
                                                                                                                ix   80xiOmm
                                                                                                             or 1 x 100 x 10 m m




              I     + /MB
                                   rating   plate



                                                                                      a  ---                 or2x
                                                                                                                 2x 50xlOmm
                                                                                                                      80xlOmm
                                                                                                             or2x100x10mm



                                                                                                                 3x 80xlOmm
                                                                                                             or3x100xlOmm(upperand
                                                                                                                 lower bar to be diminished
                                                                                                                 to a witdh of 87 mm)




3xPg16




GSS IO...20

                             For vertical   position                                   busbar      arrangements



                                                                                                                 Ix    80xlOmm
                                                                                                              or1x100x10mm




                                                                                                                 2x 50xiOmm
                                                                                                              or2x     80x10mm
                                                                                                              or2x100x10mm




                                                                                                                 3x 80xiOmm
                                                                                                              or3x100x10mm)




                                Drawing     shows CT with 2 busbars   50 x 10 mm.



3xPg16




 RITZ MESSWANDLER                                                                   Phone:          49 - 40 - 511 23 0
        P. 0. Box 20 22 51                                                          Fax:            49-40-511     23286
 D-20243 Hamburg - Germany
OUTDOOR                    CURRENT                    TRANSFORMER
GSWF                      1 o/o...~o/o                                   maximumsystemvoltage24kV
                                                                         max. cont. service current 1500A




ELECTRICAL            DATA
STANDARDS:    All national and international standards such as AS, BS, CSA,
    IEC, IEEE (ANSI), NBN, CVE, SS, UTE and VDE.

INSULATION      LEVELS:    Up to 24/55/l   50kV.

PRIMARY      CURRENT:     Up to 1500A      maximum        continuous     service current.

SECONDARY       CURRENT:      5A or IA, or any other value on request.

CHANGING OF RATIO: With primary winding in two sections intended                         for
    connection  either in series or in parallel, forming a double ratio                 I:2
                                                        up to 2 x 600/5A (or           IA),
    or by secondary taps ,...................... e.g. IOOO-750-500/5A    (or           IA).

FREQUENCY:       50Hz or 60Hz. Any other value on request.

CORE DATA: This type of CT is a one-core design:
    either for measuring      purposes     with small instrument    security
                                     factor (FS), e.g. 15VA, class 0.5, FS5
    or for protection   purposes with high accuracy limit factor (ALF)
                                        e.g. 15VA, class IOPIO (ALF = 10)
                                                                                                                          GSWF 10/0...20/0
SHORT-TIME   CURRENT RATING: To specification.                                                                        ‘) type designation:
                                                                                                                         GSWF 1 O/O up to 12kV system   voltage
    Thermal rating: up to 1 OOkA for 1 second (up to 58kA for 3 seconds).                                                GSWF 20/O up to 24kV system    voltage
    Dynamic (mechanical) rating: maximum 1 OOkA.

TESTS: Routine tests in compliance      with applicable      standard.    Measurement          of internal partial discharges     is performed      as a
   routine test.




CONSTRUCTION
GENERAL: Post type with wound primary, insulated by weather-proof          cycloaliphatic epoxy resin. Colour of resin: brown RAL
   8017. (Grey resin on request).
   Special features: Good ability to withstand ultra-violet rays. Practically non-inflammable.   Cycloaliphatic resin does not split
   off carbon under influence of surface ionisation.

PRIMARY TERMINALS:          Details are shown overleaf.
   Type “D”: of nickel plated brass, for direct connection of primary conductor.
   Type “H”: horizontal palms of nickel plated copper, with one hole of 14mm diameter (up to 600A) or two holes of 14mm
              diameter (>600...1500A).     Any other palms or NEMA pads on request.
   Type “R”: horizontal stems of 30mm diameter, up to 600A of nickel plated brass, for >600... 1500A of nickel plated copper.

SECONDARY        TERMINAL     BOX: Corrosion-proof    aluminium alloy, painted grey RAL 7033. With sealable cover. Grade of
   protection: IP54 in compliance with DIN 40050 and IEC 529. Terminals are of nickel plated brass of metric size M6.
   One cable gland (for cables of IO to 14mm diameter) and one blind plug both sized Pg16 belong to the regular equipment.
   Optional: size Pg21 for cables of 14 to 18mm diameter. As a further option: One gland on each side of the terminal box.

MOUNTING:     Vertical erect or (terminal     box downwards)           in horizontal    position. The mounting       plate is of galvanized         steel
  painted grey RAL 7033.

EARTHING:     There is an internal connection between           the earthing     bar inside the terminal box and the base plate of the CT.
   Thus earthing is possible at the base plate.

COMMISSIONING:        Units are supplied    ready for service. Just connect to system. Special tools are not necessary.
OUTDOOR                              CURRENT                      TRANSFORMER
GSWF 10/0...20/0 ~:~~~::.:~~:~:2~:,“~~::




                                                                                              Options         of primary terminals
q   for direct          connection
    of primary           conductor



                                              e   (L.P2,H2)             bl   (horizontal)
                                                  7           4




                                                                        q    (round)
                 L---      110   +
                                      pklie
          /_             140 d
                                                                                            I+-----“““1                                       ’




                                                                                                      Weight:             approx.     22 kg

                                                                                                          Creepage   distance:      530 mm




RITZ MESSWANDLER
       p. O.Box2022 51
D-20243 Hamburg - Germany

Phone:    49 - 40 - 511 230
Fax:      49 - 40 - 511 23286
ELECTRICAL            DATA
STANDARDS:   All national and international standards, such as ANSI, AS,
        BS, CSA, IEC, NBN, NEN, CVE, SEN, UTE and VDE.

INSULATION      LEVELS:     Up to 72.5 / 140 / 350 kV (see over-leaf).

PRIMARY      CURRENTS:      Up to 1500Amaximum       continuous    service current.

SECONDARY        CURRENT:      5A or IA, or any other value on request.

CHANGING OF RATIO: Either by double ratio with primary winding in two
        sections intended for connection either in series or in parallel up
        to 2 x 600A.
        Or by secondary taps, e.g. 1 OOO-750-500A.

FREQUENCY:       50Hz or 60Hz. Other values on request.

CORE DATA: 1 OkV to 36kV units can comprise       up to four independent
       toroidal cores. For higher system voltages three cores are possible.
       For measuring purposes with small instrument security factor (Fs),
       e.g. 15VA, class 0,5, Fs5.
       For protection   purposes with high accuracy limit factor (ALF)
       e.g. 15VA, class lOP20 (ALF=20)

THERMAL       AND DYNAMIC       (MECHANICAL)      RATING:   According    to
           specification. Maximum    thermal current: 1 OOkAfor 1 second.
                                                                                                    GSWF 45 (BIL 250kV)
TESTS:     Routine tests in compliance      with applicable    standard.                          for primary series-parallel
           Measurement   of internal partial discharges     is performed         as a                      connection
           routine test.                                                                         with primary terminal palms


CONSTRUCTION
GENERAL:      Post type with wound primary. The core-and-coil        assembly is completely enclosed in weather-proof cycloaliphatic
           epoxy resin. Colour of resin: Brown RAL 8017. Grey resin on special request, e.g. ANSI 70.
           Special features: Good ability to withstand   ultra-violet rays.
           Practically non-imflammable.   Cycloaliphatic   resin does not split off carbon under influence of surface ionisation.

PRIMARY      TERMINALS:      Details are shown overleaf. All terminals are of nickel plated copper.
           Type “D”: for direct connection    of primary conductor.
           Type “H”: horizontal palms, with one hole (up to 600A) or two holes (>600...15OOA) of 14mm diameter.
                     NEMA pads on special request.
           Type “R”: horizontal stems of 30 mm diameter, (up to 600A of nickel plated brass, >600....1500A of nickel
                     plated copper).

BASE:    Consisting   of two strong   mounting   brackets    of hot dip galvanized      steel.

SECONDARY     TERMINAL    BOX: The terminal box is a part of the whole cast resin body (homogeneous      casting). The cover
       is sealable. The terminals are nickel plated and of metric size M6 (6mm=0.24”diam.). Each terminal can be grounded
       by means of a simple link inside the terminal box.
       Two cable glands Pg 16 (for cables of IO to 14mm diam.) are provided. On request: cable glands Pg 21 (for cables
       of 14 to 18mm diam.)

GROUNDING:        One bolt Ml2     (12mm diameter)    at the opposite     side of the terminal   box.

MOUNTING:        GSWF       IO sizes 1 and 21
                 GSWF      20 size 1             vertical   erect or (terminal   box downward)     in horizontal   position.
                 GSWF      30 size 0
                 Other    types and sizes:       vertical   erect only.
 INSULATION                  LEVELS                     GSWF 10                     GSWF 20                       GSWF 30                              GSWF 45                  GSWF 72.5

Highest voltage
for equipment                         up to                   12KV                    24KV                          38KV                                   52KV                           72.5KV


One-minute power
frequency te$J voltage up to                                   36kV                    55kV                         75kV                                  105kV                            140kV


 Lightning impulse
 test voltage (BIL)                   up to                   95kV                    150kV                        200kV                             250kV                                 350kV
                                                                                                                                                 __--..                                      -___I_

                                      IHI    (horizontal)                                          options   of                                  m        (round)
                                                                                                    primary
                                                                                                   terminals                          F--350.                             I




                                      q      (direct)




                    h -10




                                                                                                                                                                               Pg21
                                                                                                                                                                              an reauest




                                                                                                                    b




                                   approx.      creapage        flash-over   number                                           dimensions              in m m
                                    weight       distance         distance      of
           Type                       kg             mm               mm      sheds            b             d          el                       e2            I    h     I          'I            I    '*


 GSWF     10 size     1               3%                575          265        4

 GSWF     20 size     1
                                      42                700          310        5        326                            280                     126                                142                 150
 GSWF     10 size     21

 GSWF     30 size     0               50                945          405

 GSWF     30 size     1                                                         7        400
                                      80           1010              440
 GSWF     lo...20     size    31
  GSWF    30 size     2                                                                                     18
                                    155            1060              440                 500
  GSWF    lo...20     size    32
  GSWF    45                                                         590       10
                                    100            1405
  GSWF    30 size     40                                                                 400

                                      13Q          1830              770       13                           18          350                     190                 834   1        184             1   180   1
  GSWF    72.5
                                                                                           _        -


     RITZ            MESSWANDLER
P.O.Box     20 22 51 . D-20243               Hamburg          . Germany
Phone:    (040)     - 511 23 - 0 . Fax: (040)             - 511 23 286
OUTDOOR
VSWF 45m.72.5
with porcelain
                             CURRENT

                            insulator
                                                             TRANSFORMER
                                                              dry type                       up to 72.5 kV
                                                                                             upto1500A                                 e    RITZ


GENERAL           DESCRIPTION
Post type C.T., dry type. Inner insulation and head of outdoor-proof
cycloaliphatic   epoxy resin having excellent   mechanical   and electrical
properties. Outer insulation by a brown (RAL 8016) porcelain insulator with
plain sheds to DIN 48115. The space between porcelain and resin is filled with
polyurethane foam.
The primary windings and the cores with secondary windings are cast under
vacuum in one working process and subsequently hardened under pressure.


ELECTRICAL           FEATURES
STANDARDS:    In compliance with all national or international standards, such
      as ANSI, AS, BS, CSA, IEC, NBN, NEN, OVE, SEN, SEV, UTE, VDE
      and to any special requirements.

INSULATION     LEVEL: System voltages up to 725kV.
       One-minute power-frequency     test voltage up to 140kV.
       Basic impulse insulation level (BIL) up to 380kV.

FREQUENCY:       50 Hz or 60 Hz or any other value.

RATED     PRIMARY     CURRENT:         Up to 1500A maximum          continuous      service current.

RATED SECONDARY            CURRENT:        5A or 1A or any other value

CHANGING OF RATIO: Either by double ratio with primary winding                 in two
      sections  intended     for connection    in series or in parallel,    up to 2 x
      600A. Or by quadruple        ratio with primary winding       in four sections                                     VSWF 72.5
      intended   for connection     in series or in series-parallel     or in parallel,                         with primary terminal palms
      up to 4 x 300A. Or by secondary         taps, e.g. lOOO-750-500A.

CORE DATA: One, two or three cores for measuring               or protection     purposes,
     e.g. core 1: 30 VA, class 0.5 (class 0.6 B-l .O)
          core 2: 30 VA, class 1 OP20 (class Cl 00)

THERMAL      AND DYNAMIC (MECHANICAL)               RATING: According to specification. Maximum thermal current: 1OOkA for 1 second.

TESTS:    Routine tests in compliance      with applicable     standard.       Measurement     of internal   partial discharges    is performed      as
         a routine test.


CONSTRUCTION               DETAILS
PRIMARY TERMINALS:        Details are shown overleaf. All terminals are nickel plated.
      Type “H”: horizontal palms of copper. NEMA pads on special request.
      Type “R”: horizontal stems of 30 mm diameter. Up to 600 A of brass, >600...1500                            A of copper.

SECONDARY      TERMINAL     BOX: Of aluminium alloy. One or two cable glands Pg21 (for cables of 14 to 18 mm
      diameter) are provided.
      Secondary terminals are bolts of metric size Ml0 (10 mm diameter) of electrolytic copper, complete with nuts
      and washers. Each terminal can be earthed by means of a link inside the terminal box.

EARTHING:      Two bolts Ml2 at the terminal         box and one bolt Ml2 at the opposite              side of the terminal     box.

CREEPAGE       DISTANCE:       Up to 2070mm.

RATING PLATE AND INFORMATION                   PLATE(S):     Of aluminium.      Markings are applied photographically         and are weatherproof
      due to anodic oxidation.

MOUNTING:       In vertical position   only.

COMMISSIONING:          Units are supplied      ready for service. Just connect to system.
OUTDOOR                      CURRENT                    TRANSFORMER
VSWF 45...72.5                                           dry type             up to 72.5 kV                                      RITZ
                                                                              upto1500A                               e
with porcelain               insulator

                                                              Options
                         El = stems 4-
                          R                            of primary terminals           *       q        = palms




                                                                                                                                                  max.




                                                                                                      600A     (      . ..60kA+.)          @I4
                                                                                                  0     1500A(60...       120 kAth)2    ~014




                                                                                                  -248432/t-



              Pg 21
                I




                                                               325




                                                                                                                          Dimensions             in mm



I                        I                       I                        I               I                                  I
    Lightning impulse              Minimum                 Minimum            Number
    test voltage (BIL)       creepage distance       flashover distance       of sheds        Dimehnsion

      up to 250 kv               1440 mm                  570 mm                                      675 mm                           130 kg

      up to 380 kv               1860 mm                  730 mm                 16                   840 mm                           140 kg

      up to 380 kv               2070 mm                  810 mm                 18                   920 mm                           145 kg


 RITZ        MESSWANDLER
 P.O.Box 20 22 51, D-20243 Hamburg
                GERMANY
 Phone: (40) 51 123-0, Fax: (40) 51 123 286
BUSHING                             TYPE CURRENT TRANSFORMERS            ’
GTDSO                                10.. .30 ( for indooryse 1up to 38.5kv
                                                                                             cast resin Insulated                              up      to 10,000 A



ELECTRICAL                           DATA
STANDARDS:        All national           and international               standards,          such as ANSI,
               AS, BS, CSA,             IEC, NBN, NEN,                  CVE, SEN,            UTE and VDE.
HIGHEST       EQUIPMENT               VOLTAGE:             38 5 kV.

PRIMARY       CURRENTS:               1000      to 10,000         A.
SECONDARY           CURRENTS:                 5 or 1 A. Other               values       on request.

CHANGING         OF RATIO:             By secondary               tap(s),       e.g.     5000-2500/5A.

FREQUENCY:          50 or 60 Hz. Other                   values         on request.

CORES:       Up to four independent       toroidal    cores.
               For measuring     purposes      with small instrument       security   factor (Fs),
               e.g. 3OVA, class 0.5, F, 10              or to ANSIKSA         e.g. class 0.6B1.8
               For protection    purposes     with high accuracy      limit factor (ALF),
               e.g. 6OVA, class lOP20                   or to ANSIXSA         e.g. class C200




                                                                                                                                                                                 GTDSO     20
                                                                                                                                                                                   size 62




THERMAL         RATING:          > 100 kA for 1 second.

DYNAMIC        (MECHANICAL)                    RATING:        Practically              unlimited.

TESTS:      Routine    tests      in accordance              with ANSI, AS, BS, CSA, IEC, VDEoranyotherstandard.                                       Measurement     of internal   partial discharges
           is performed           as a routine           test. Type tests or measurement      of dielectric      loss                         factor    tan 8 on request,     at a surcharge.

INSULATION         LEVELS:            Up to 38.5/75/200      kV. For details see overleaf.
                (Maximum            test voltage    for the insulated  neutral end is 3 kV for 1 min.)


CONSTRUCTION
GENERAL:Bushing              type(through-the-walltype)                                insulated    by epoxy       resin. Without     primaryconductor.                  CT’s    can be supplied  complete
         with two         or three     nickel      plated               copper         bars 80x10       or lOOxlOmm           or only with caps with                 orifices     to guide the bars. Other
         dimensions          to be agreed          upon.               Designs         for airtight   installation      are also available.

APERTURES:        From 115 to 380mm   diameter, coated with                                         brass sheet       which   is fitted   with a flexible      terminal      for connection     to the   primary
        conductor      to keep the CT on the same potential                                           level.

SECONDARY      TERMINAL    BOX: Of aluminium                                   alloy, with sealable and transparent       cover. The terminals                            are of nickel plated brass and of
        metric  size M6. Each terminal    can                                be earthed    by means   of a simple   screw-through     connection                             inside the terminal   box.
        Two cable glands    Pg16 for cables                                  up to max. 16mm diameter       are provided.
EARTHING:         One     bolt      of metric       size    M8         is provided           at the terminal      box.

MOUNTING:          In any        position.

COMMISSIONING:                 Units         are supplied          ready        for service.         Just   connect       to system.      Special      tools   are    not necessary.

MAINTENANCE:              Units       are maintenance-free.
TROPICALIZED            DESIGN:              At a small      surcharge.
BUSHING                                     TYPE CURRENT TRANSFORMERS
GTDSO                                        10.. s 30 1for indooruse 1up to 383 kv
                                                                                            cast resin Insulated                                       up to 10,000 A



                                                                                                                               Highest                       Power frequency         Impulse      test voltage
                              Type                                  Insulation      Class                               equipment      voltage                  test voltage            (BIL),    full wave

                                                  ANSI: 8.32kV.         CSA: 10kV
                                                                                                                                 12kV                          up to 35 kV                 up to 90 kV
                          GTDSo             lo    AS/BS/IEC/VDE:           12kV.
                                                  ANSI: 13.8, 25kV. CSA: 15, 275kV
                                                                                                                               27.5kV                          up to 55 kV                upto15OkV
                          GTDSo             2o    AS/BS/IEC/VDE:    17.5,24kV.
                                                  ANSI: 34.5kV.         CSA: 35kV
                                                                                                                               38,5kV                          up to 75 kV                up to 200 kV
                          GTDSo             3o    AS/BS/IEC/VDE:           36kV.


      upto               kV           168
      upto               kV           225
      Up     t0   38,s   kV           305




optional:                                                                                                                                                                                                 terminal  M5 to keep
                                                                                                                                                                                                         the CT on the same
orifices   ~
                                                                                                                                                                                                          potential  level
to guide
the bar(s)



                                                                                                                                                                                                         _ rating   plate




                                                                                     a” is not limited.

                         Dimensions          in mm. Drawing     shows   type     GTDSO    20 size    32.



                                                                                                           Dimensions        in mm                                                                 Approx.
                              Size
                                                                                                                           GTDSO     10    GTDSO        20      GTDSO    30                         weight
                                                 a max.        b        QC           e              I1          I2              h                 h                 h          @d                      kg
                                11                 10                                                                         285                399               559                            30..       . 50
                                                              295       278         255         210            235                                                             115
                                I2                 60                                                                         360                474               634                            45..       . 70
                                21                 10                                                                         285                399               559                            50..       . 75
                                                              370       356         325         248            273                                                             115
                                22                 60                                                                         360                474               634                            70..       * 95
                                31                 10                                                                         285                399               559                            45..       . 70
                                                              370       356         325         248            273                                                             155
                                32                 60                                                                         360                474               634                            65..       . 90
                                41                 10                                                                         285                399               559                            65..       s 95
                                                              440       440         400         290            315                                                             205
                                42                 60                                                                         360                474               634                            85...110
                                51                 10                                                                          285               399               559                            85...120
                                                              530       530         490         335            360                                                             297
                                52                 60                                                                         360                474               634                           110...150
                                61                 10                                                                         285                399               559                            80...115
                                                              530       530         490         335            360                                                             310
                                62                 60                                                                         360                474               634                           105...145
                                72                 60                                                                                                              634                           150...170
                                                              650       650         600         395            420                                                             380
                                73                180                                                                                                              754                           185...210

                         RITZ                     MESSWANDLER
                         2000 Hamburg      20,               GERMANY
                         Salomon-Heine-Weg      72, P. 0. Box 20 22 51
                         Phone: (40) 5 1 I 23-O         Telex: 212 933
                         Telefax:                    (40) 5 11 23-286
BUSHING TYPE CURRENT TRANSFORMERS
GTDSOF I O/O.. .3O for outdoor use
GTDSOFI   IO...30 for outdoor-indoor                                         use
                                                                                           up   to

                                                                                           up to IO,OOOA
                                                                                                         38 kV
                                                                                                                           Q   RITZ


ELECTRICAL             DATA
STANDARDS:     All national and international standards      such as AS, BS,CSA,
   IEC, IEEE (ANSI), NBN, CVE, SS, UTE and VDE.

INSULATION       LEVELS:     Up to 38/75/200kV.    For details please see overleaf.

PRIMARY     CURRENT:       Up to 10,OOOA.

SECONDARY        CURRENT:      5A or IA, or any other value on request.

CHANGING       OF RATIO:     By secondary   taps, e.g. 8000-6000-4000/5A      (or IA).

FREQUENCY:       50Hz or 60Hz. Any other value on request.

CORE DATA: Up to four independent cores:
   for measuring purposes with small instrument        security factor (FS),
                                                       e.g. 30VA, class 0.5, FSIO
   for protection   purposes with high accuracy limit factor (ALF),
                                               e.g. 60VA, class 5P20, (ALF = 20)
SHORT-TIME       CURRENT RATING:
   thermal:                 > 1 OOkA for 1 second.
   dynamic (mechanical):    practically unlimited.
                                                                                                          GTDSOFI 30
TESTS: Routine tests in compliance with applicable standard.          Measurement                                size 41
   of internal partial discharges is performed as a routine test.


CONSTRUCTION

GENERAL:       Bushing type (through-the-wall   type), insulated by weather-proof    cycloaliphatic epoxy resin. Colour of resin: brown.
   (Grey resin on request). Special features: Good ability to withstand ultra-violet rays. Practically non-inflammable.     Cycloaliphatic
   resin does not split off carbon under the influence of surface ionisation.
   Generally without busbars. Caps with orifices to guide the primary conductor can be provided for outdoor units. Outdoor-
   indoor units have such guiding caps as a regular equipment. The caps, of aluminium or resin, prevent ingress of water to
   the building. Dimensions of required orifices to be advised when inquiring. - Nickel plated copper bars or any other conductors
   can be provided to customer’s specification.       - For airtight installation we can modify the outdoor-indoor    units appropriately.

APERTURES:     Type GTDSOF 1 O/O: 134mm diameter. Other types: 205 or 297mm diameter.
   The inner surface consists of an aluminium tube which is fitted with a flexible terminal for connection         to the primary conductor
   to keep the CT on the same potential level.

SECONDARY       TERMINAL     BOX: GTDSOF 1 O/O: The terminal box is part of the resin body (homogeneous           casting). The other
   designs have a terminal box of aluminium alloy. All boxes have a sealable cover. Terminals are of nickel plated brass of size M6.
   All terminal boxes are provided with cable glands of size Pg16. Location of glands is shown overleaf. Pg16 is suitable for
   cables up to 16mm diameter (outdoor-indoor       units) and for cables of 10 to 14mm (outdoor units). Optional for outdoor units:
   Pg21 for cables of 14 to 18mm diameter. On request: X-inch-conduit        hubs.
   All the CT’s have secondary terminals which can be earthed inside the terminal box, either by means of a “screw-through-
   connection” or by a link.

MOUNTING:     The resin flange of the outdoor CT’s is equipped with four corner pieces of aluminium alloy. Outdoor-indoor  units
   have a projecting flange of aluminium alloy. This flange prevents ingress of water to the building. Mounting in any position.
  (When outdoor units are horizontally mounted: terminal box downwards).

EARTHING: Type GTDSOF IO/O can be earthed at one of the corner pieces. The other types have one earthing bolt of metric size
   M8 at the terminal box.

MECHANICAL    STRENGTH: When installing our regular equipment, any mechanical forces are to be absorbed by post insulators
   supporting the primary conductor. As a non-standard    option, the CT’s can be equipped with special guiding caps and extra
   strong mounting flanges suitable to withstand mechanical forces up to 6000N.

TROPICALIZED       DESIGN:    On outdoor    units free of charge. On outdoor-indoor      units at a small surcharge.
I                                            I                                     INSULATION                   LEVELS                                                          I                                               I


I           Type                                              Highest
                                                       equipment      voltage
                                                                                                                        Power frequency
                                                                                                                           test voltage
                                                                                                                                                                                            Impulse
                                                                                                                                                                                               (BIL),
                                                                                                                                                                                                        test voltage
                                                                                                                                                                                                        full wave               I


I   GTDSOF
    GTDSOF(I)
                   1 O/O
                      10
                                                            up to 15kV
                                                            up to 15kV
                                                                                                                                  up to 36kV
                                                                                                                                  up to 36kV
                                                                                                                                                                                                 up to 1lOkV
                                                                                                                                                                                                 up to 1lOkV                    I

I GTDSOF(I)            20                    I              up to 24kV                              I                             up to 55kV                                    I                up to 150kV                    I

I GTDSOF(I)            30                    I              up to 38kV                              I                             up to 75kV                                    I                up to 200kV                    I




GTDSOF IO/O...30                                                                                                                                   term4    to keep   the
                                                                                                                                                                            /

                                                                                                                                                   CT on the same
(Drawing        shows                                                                                                                                  level
                                                                                                                                                   potential
GTDSOF           10...30,      size 41)




GTDSOFI IO...30
(Drawing        shows         size 41)                                        l d*mmwm   of wif~a   of qutdnp   raps   to be dvlsed




Minimum        creepage  distance  of each outdoor                     section:              GTDSOF                    10/O: 410 mm, others:                          984 mm
Number        of sheds of each outdoor    section:                                           GTDSOF                    lo/O: 3       others:                          7


Types GTDSOF    10, GTDSOF   20, GTDSOF    30: Identical  dimensions.                                                           Inner     insulation           according                to insulation      level.
The same applies to types GTDSOFI   10, GTDSOFI      20 and GTDSOFI                                                              30.

                                         I           I awrox.      I                                                                  dimensions          in mm                                                                 I
                                                        weight
                                             size         p<s            al                                                                                                                                              S2F

    GTDSOF          1 O/O                        -   1 40...45                                                                                                                                                           160

    GTDSOF          lo...30                                                              324            1 440             1 440            1 440               205                  1 400      1 400      1 1014         225

                                                                                         324                440                 440          440               205                  1 400      1 400      1 1089

                                                                                         369                530                 530          530               297                    490        490        1014         225

                                                                                         369                530                 530          530               297                    490        490        1089

    GTDSOFI         lo...30                                                              315                560                 560          440               205                    500        500        800

                                                                                         315                560                 560          440               205                    500        500        875




RITZ MESSWANDLER                                                                                                                                                            Phone:            49 - 40 - 511 23 0
       P. 0. Box 20 22 51                                                                                                                                                   Fax:              49 - 40 - 511 23 286
D-20243 Hamburg - Germany

CI lhiert   tn rhanrm           withnl   It nntirn                                                                                                                                            GTDOSOF/I         3.96/l    .sT
INDOOR VOLTAGE TRANSFORMERS
GSE10...45                                                      9 single-pole                               insulated,                   up to 52 kV
GSZ10...30                                                      y double-pole                                    insulated,                up to 38.5 kV



ELECTRICAL                            DATA
INSULATION           LEVELS:          Please see overleaf.

RATED       PRIMARY           VOLTAGE:
            Single-pole  design GSE (for connection between                                                        phase and earth):
            up to 52000@     Volts highest system voltage.
            Double-pole design GSZ (for connection between                                                         phases):
            up to 38500 Volts highest system voltage.
RATED SECONDARY VOLTAGE: Any value up to 660 Volts. Tapped                                                                        versions
      are also possible, e.g. 110-63.5 Volts.
SECONDARY WINDINGS:         One or two separate windings for measuring, for
      protection orforearthfault  detection. In certain casessingle-pole units
      with three windings are available.
ACHIEVABLE            RATED       BURDENS                 AND        ACCURACY                   CLASES:

            Rating at 50H2, in compliance                                             Rating at 60 Hz, in compliance
            with e.g. IEC, BS or VDE*)                                                with ANSI or CSA*)
            class 0.2            60   VA       ( 30     VA)                           class          0.3 WXY (WX)
            class 0.5           120   VA       (I 00    VA)                           class          0.6 WXYZ (WXY)
                                300   VA       (200     VA)                           class           1.2 WXYZ (WXYZ)                                                                                   GSE 20
            class   1
            class 3             600   VA       (400     VA)                           error          -t3% WXYZ and ZZ
            *) Values in brackets                   only refer to types GSE 10 and GSZ 10.
THERMAL           RATING        (temperature                rise less than 55°C):
            GSE 10 and GSZ 10:           600 VA continuous. 1800 VA for 6 minutes.
            GSE 20.. 45, GSZ 20.. 30: 800 VA continuous. 2400 VA for 6 minutes.
            Earth fault winding of single-pole  design: 6.. . 9 A up to 8 hours.
FREQUENCY:             50 or 60 Hz. Other values on request
ADDITIONAL           APPLICATION:                   The V. T.‘s can be supplied                                  for discharging            capacitor          banks and transmission                           lines. Details on request.
TESTS: Routine tests in accordance with ANSI, BS, CSA, IEC, VDE or any other standard. Measurement of internal partial discharges
       is performed as a routine test. Type tests or measurement of dielectric loss factor tan 19on request, at a surcharge.


CONSTRUCTION
GENERAL:         Core and windings are completely enclosed                                                         in cast resin (epoxy resin). The strong base, complete                                                   with secondary
            terminal box, is of high-quality aluminium alloy.‘)
PRIMARY        TERMINALS:    Bolts Ml0 (1Omm diameter, metric thread).*) The single-pole design has one fully insulated primary terminal.
            The other end of the primary winding is insulated to withstand a power frequency test voltage up to 2.5 kV. This earthed end is
            located in the secondary terminal box. The double-pole      version has two fully insulated primary terminals.
SECONDARY TERMINALS: Located in a sealable terminal box with transparent cover.3) The terminals are nickel plated and of metric
      size M6 (6mm diameter). Each terminal can be directly earthed inside the terminal box which has three cable glands
      Pg 16 for cables of max. 16 mm diameter.3)
EARTHING:          One bolt M8 (8mm diameter,                                metric thread)                      at the opposite            side of the terminal                       box.4)
MOUNTING:           GSE/GSZ           10 . . . 20 and GSE 30: in any position.                                             GSZ 30 and GSE 45: in vertical position                                      only.
COMMISSIONING:                  Units are supplied                       ready for service. Just connect                                 to system. Special                       tools are not necessary.
MAINTENANCE:               Units are maintenance-free.                                                                                                                            TROPICALISATION:      At a small surcharge.

1) except     GSZ 30 having     a terminal          box which      is part of a whole               cast   resin    body    (homogeneous           casting).     The base           consists    of two strong    mounting   brackets   of hot-dip
   galvanized     steel.
2) except   GSZ    30 which     has stems       of nickel       plated     and    tinned      brass        (22mm     diameter,     55 m m long).
3) except   GSZ    30 having    a cover      which      is not transparent.           The terminal               box has one     cable     gland     Pg 16 and       one    blind      gland   Pg 16.
4) except   GSZ    30 which     has one      bolt    M 12 (12mm           diameter,        metric      thread)      at the opposite        side    of the terminal         box.
INDOOR VOLTAGE TRANSFORMERS
GSE 10             n   n      n     45 y single-pole                         insulated,                up to 52 kV
GSZ10...30                                  y double-pole                      insulated,                   up to 38.5 kV


                                                                                                  Highest                Power frequency           Impulse          test voltage
          Type                         Insulation        Class                                    system                    test voltage              (BIL),        full wave

     GSE     10        ANSKSA:          8.7 kV                                                                                                      GSE:       up to 95 kV
     GSZ     10        BS/IEC:       12 kV. VDE:         10 N                                  up to 12 kV                     up to 35 kV          GSZ:       up to 75 kV

     GSE 20            ANSKSA:            1518   kV                                                                                                 GSE:       up to 150 kV
     GSZ 20            BS/IEC:       17.5,24   kV. VDE:          15 N, 20 N                    up to 24 kV                     up to 55 kV          GSZ:       up to 125 kV

     GSE 30            ANSI/GSA:    25, 34.5 kV                                         GSE:      up to 36 kV
     GSZ 30            BS/IEC:   36 kV. VDE: 25 N, 30 N                                 GSZ:      up to 38.5 kV                up to 75 kV              up to 200          kV


     GSE 45            ANSI/GSA:    46 kV                                                      up to 52 kV                     up to 95 kV              up to 250          kV
                       BS/IEC:   52 kV. VDE:             45 N


   GSE10...45                                                          GSZ10...20                                                                       GSZ 30
   single-pole    insulated                                           double-pole         insulated                                           double-pole               insulated




                                                                                                                  2




                                                                                     Dimensions        in mm                                                             Weight
           Type             bl         b2           C             d             el           e2           e3              h           I1      I2               I3           kg

                                                                                                                                                                            27
     GSE     10            195          -           12            11          175           225               -       240f5          192     140           215
     GSZ     10                       182                                                                   150                                                             26
                                                                                                                                                                            38
     GSE     20            230          -                                     200           250               -       300f6          212     155           235
     GSZ     20                       246           15                                                      210                                                             40
     GSE     30            255         -                          14          225           300              -        33Ot-6         213     175           236              45
     GSZ     30            260        445           25                        220           160             340       645f6          205     215           245              76

     GSE     45            255         -            15                        225           300              -        590+6          213     175           236              58

   RITZ                MESSWANDLER
   2000     Hamburg           20,   WEST       GERMANY
   Salomon-Heine-Weg             72, P. 0. Box 202251
   Phone:      (040)       51123-0,     Telex:     212933
   Telefax:                             (040) 5 1123-111
VOLTAGE TRANSFORMERS up to 72.5 kV
GSE 72.5 for indoor use   for line-to-earth connection
GSEF 72.5 for outdoor use insulated epoxy resin
                                      by




STANDARDS:    All national and international standards, such as ANSI,
           AS, BS, CSA, IEC, NBN, NEN, tjVE, SEN, UTE and VDE.
INSULATION   LEVELS:     Up to 72.5/140/350 kV.
           (Maximum test voltage for the neutral end is 3 kV for 1 min.)
RATED PRIMARY      VOLTAGE:     up to 70/&kV.
RATED      SECONDARY      VOLTAGE:     any value up to 660/& Volts. Tapped versions
               are also possible, e.g. 115-69 Volts.
SECONDARY         WINDINGS:     One or two separate windings for measuring, for protection or for
               earth fault detection . In certain cases even 3 windings can be accommodated.
ACHIEVABLE          RATED      BURDENS       AND   ACCURACY         CLASSES:
                 Class         Rating at 50H2, in compliance with e.g. IEC, BS or VDE
                               with one winding for measuring,      with one winding for measuring,
                               without winding for earth fault      (data below), and with additional
                               detection                            winding for earth fault detection
                                                                    rated for 4...9A up to 8 hours
                                    GSE 72.5          GSEF       72.5          GSE   72.5       GSEF   72.5
                  0.2             50 VA            30 VA             50 VA            30 VA
                  0.5            15OVA            IOOVA             150VA            1OOVA
                  1 .o           300 VA           200 VA            300 VA           200 VA
                  3.0           1000 VA           800 VA            700 VA           500 VA
               Rating at 60H2, in compliance with ANSI and CSA with one or two secondary
               windings (burden divided in any proportion between the two windings):
               GSE     72.5: class 0.3 WXY and 0.6Z, or class 0.6Z and I.222
               GSEF 72.5: class 0.3WX and 0.6Y, or class 0.6Y and 1.22.
THERMAL        RATING:
               GSE   72.5: up to IOOOVA continuously (3000VA for Gminutes).
               GSEF  72.5: up to 800VA continuously (2400VA for Gminutes).
               Temperature rise: less than 55°C at 30°C ambient temperature.
                                                                                                                                   GSEF 72.5
VOLTAGE       FACTOR:        Any voltage factor up to 1.9 for 8 hours.
TESTS:      Routine tests in compliance        with applicable     standard. Measurement    of internal partial discharges is performed as a routine test.




CONSTRUCTION
GENERAL:         Core and windings are completely enclosed in cast resin (GSE 72.5: aromatic epoxy resin. GSEF 72.5: weather-proof cycloali-
                phatic epoxy resin).Colour of resin: brown, grey resin on request. Special features of cycloaliphatic epoxy resin: Good ability to
                withstand ultra-violet rays. Practically non-inflammable. Does not split off carbon under the influence of surface ionisation.
LINE     TERMINAL:        Vertical stem of nickel plated brass, 20mm diameter, 55mm long.
INSULATED-NEUTRAL-TERMINAL:               The terminal of the primary winding intended to be earthed in service is located in the secondary
                terminal box. The terminal is insulated to withstand a power frequency test voltage up to 3 kV. It is of nickel plated brass and of
                metric size M6.
SECONDARY          TERMINAL         BOX:
                GSE    72.5: Of aluminium alloy. With transparent and sealable cover. With 3 cable glands Pg16 for cables up to 16mm diameter.
                GSEF 72.5:  The terminal box is part of the epoxy resin body (homogeneous casting). The cover is sealable. The box is provided with
                one cable gland Pg16. Two cable glands of size Pg21 (for cables up to 21 mm diameter) or l/2-inch conduit hub(s) on request.
SECONDARY          TERMINALS:    Of nickel plated brass and of metric size M6. Each terminal can be earthed inside the terminal box (GSE 72.5:
                by means of a “screw-through connection”, GSEF 72.5: by means of a simple link).
BASE:      Consisting of two mounting brackets of hot-dip galvanized             steel.
EARTHING:        One bolt of size Ml2 (GSE 72.5: of electrogalvanized           steel. GSEF 72.5: of stainless steel) on the opposite side of the terminal box.
MOUNTING:            In vertical position.
COMMISSIONING:             Units are supplied ready for service. Just connect to system. Special tools are not necessary.
TROPICALIZED            DESIGN:   At a small surcharge.
VOLTAGE TRANSFORMERS up to 72.5 kV
GSE 72.5 for indoor use   for line-to-earth connection
GSEF 72.5 for outdoor use insulated epoxy resin
                                      by




               L265-1
                                                                     rating   plate




terminal marking
to applicable
standard      \                             terminal marking
                                            to applicable
                                            standard




                        GSE 72.5                               GSEF 72.5




RITZ         MESSWANDLER
P.O.Box    20 22 51 D-20243     Hamburg
Phone: (40) 51 123 0 Fax: (40) 51 123 286
     OUTDOOR VOLTAGE TRANSFORMERS
                                                                                                   ir iection



     ELECTRICAL              DATA
     STANDARDS: All national and international standards, such as ANSI,
              AS, BS, CSA, IEC, NBN, NEN, CVE, SEN, UTE and VDE.



     RATED PRIMARY VOLTAGE: up to 35/&kV.
     RATED SECONDARY VOLTAGE: any value up to 660/d Volts. Tapped versions
              are also possible, e.g. 115-69 Volts.
     SECONDARY WINDINGS: One or two separate windings for measuring, for
              protection or for earth fault detection.
     ACHIEVABLE RATED BURDENS AND ACCURACY CLASSES:
               Rating at 50H2, in compliance with e.g. IEC, BS or VDE *)
“y             with one winding for measuring,        with one winding for measuring
               without winding for earth fault        (data below), and with additional
               detection                              winding for earth fault detection
                                                      rated for 6A up to 8 hours

                 class 0.2 25VA ( 25VA)                  class 0.2 20VA      ( 25VA)
                 class 0.5 75VA ( 75VA)                  class 0.5 60VA      ( 75 VA)
                 class 1 .O 150 VA (150 VA)              class 1 .O 120 VA   (150 VA)
                 class 3.0 180VA (200VA)                 class 3.0 150VA     (200VA)                               GSEF IO/O
                 *) Values in brackets refer to type GSEF 10/O.

                 Rating at 60H2, in compliance with ANSI and CSA
                 with one or two secondary windings (burden divided in any proportion between the two windings):
                 class 0.3 WX, or class 0.6 or 1.2 WXY, or 3 % error at WXYZ.
     THERMAL     RATING: 400VA continuously (12OOVA for 6minutes).
                 Temperature rise: less than 55°C.
     VOLTAGE FACTOR: any voltage factor up to 1.9 for 8 hours.
     TESTS: Routine tests in compliance with applicable standard. Measurement           of
               internal partial discharges is performed as a routine test.


 -   CONSTRUCTION
     GENERAL:     Core and windings are completely enclosed in weather-proof cycloaliphatic epoxy resin. Colour of resin: brown. (Grey resin on
                 request). Special features: Good ability to withstand ultra-violet rays. Practically non-inflammable. Cycloaliphatic resin does not
                 split off carbon under the influence of surface ionisation.
                 The voltage transformer is tropicalized.
     LINE TERMINAL: Insert nut of metric size MlO, of nickel plated brass, complete with bolt of stainless steel, 25mm long. (Other terminals
               on request, e.g. vertical bolt of nickel plated brass of 20mm diameter).
     INSULATED-NEUTRAL-TERMINAL:          The terminal of the primary winding intended to be earthed in service is located in the secondary
               terminal box. This terminal is insulated to withstand a power frequency test voltage up to 3kV. It is of nickel plated brass and of
               metric size M6.
     SECONDARY TERMINAL BOX: The terminal box is part of the epoxy resin body (homogeneous casting). The cover is sealable. The
              terminals are of nickel plated brass and of metric size M6. Each terminal can be earthed by means of a simple link inside the
               terminal box.
               One cable gland (for cables of 10 to 14 mm diameter) and one blind plug both sized Pg16 are provided as a
               standard. Optional size Pg21 for cables of 14 to 18 mm. One cable gland on each side of the terminal box on
               request.
     BASE: Consisting of two strong mounting brackets of hot-dip galvanized steel.
     EARTHING:    One bolt of stainless steel of size M12, on the opposite side of the terminal box.
     MOUNTING: In vertical or horizontal position (terminal box: face downwards).
     COMMISSIONING: Units are supplied ready for service. Just connect to system. Special tools are not necessary.
I                                                            INSULATION LEVELS                                                     I
                                                   Highest                  Power frequency                Impulse test voltage        ‘isi
            We                               equipment voltage                test voltage                   (BIL), full wave

    GSEF IO/O                                  up to 15kV                        up to 36 kV                   up to 11OkV

    GSEF 20/O                                  up to 24 kV                       up to 55 kV                   up to 150kV
    GSEF 30/O                                  up to 38.5 kV                     up to 75 kV                   up to 200 kV



                                                  MlOx25




                                                                                                               h



                rating pla                                               &M 12
                                                             Pg 16




                       t = terminal marking
                             to applicable    standard
                                                                                                                                       w
                                                  Drawing         shows type GSEF 30/O.




Types GSEF 10/O and GSEF 20/O: Identical dimensions. Inner insulation according to insulation level.


         type                    number               approx. weight       dimension h         creepage              *)flashover
                                 of sheds                                                       distance               distance
                                                             kg                  mm                mm                     mm

    GSEF 20/O
    GSEF IO/O                        5                       42                  404               770                   418

    GSEF 30/O                        7                       50                  496             1015                    508

RITZ         MESSWANDLER
P.O.Box    20 22 51 D-20243     Hamburg
Phone: (40) 51 123 0 Fax: (40) 51 123 286
OUTDOOR                     VOLTAGE                       TRANSFORMERS
GSEF 10                         n n   n   45           for connection           line-to-earth              up to 52kV

GSZF                10          ...       30           for connection           line-to-line               up to 38kV




STANDARDS:    All national and international standards such as AS, BS,CSA,
   IEC, IEEE (ANSI), NBN, CVE, SS, UTE and VDE.

INSULATION      LEVELS:     Please see overleaf.

METHOD OF CONNECTION:
   GSEF 10 .. . 45: for connection        between      phase and earth.
   GSZF 10 ... 30: for connection         between      phases.

RATED PRIMARY VOLTAGE:
   GSEF (one-pole design): for line-to-earth connection up to 46/J3 kV
                                         (highest equipment voltage: 52kV)
  GSZF (two-pole  design): for line-to-line connection      up to 34.5 kV
                                       (highest equipment voltage 385kV)

RATED SECONDARY          VOLTAGE:     One or two secondary windings for
    measuring, for protection or (on type GSEF) for earth fault indication.
    Tapped versions are possible, e.g. 115-69 Volts.

FREQUENCY:        50Hz or 60Hz. Any other value on request.

MAXIMUM      ACHIEVABLE   BURDENS:
    e.g. to IEC or BS - 50Hz                        to IEEE (ANSI) or CSA - 60Hz
    class 0.2       60VA                            class 0.3 WXYZ
    class 0.5    200VA                              class 0.6 WXYZ
    class 1 .O 500VA                                class 1.2 WXYZ and ZZ                                                     GSEF 30

THERMAL     RATING      (temperature       rise less than 55” C): Standard          design: 9OOVA continuously     (2500VA    for 6 minutes). Special
    design: 1500VA      continuously      (2500VA for 20 minutes).

VOLTAGE      FACTOR:      Up to 1.2 continuously.        One-pole   units: up to 1.9 for 8 hours.

ADDITIONAL      APPLICATION:     For use as discharge reactors on capacitor banks. When inquiring                     please advise the bank’s Mvar
      rating to be discharged as well as the intended number and time intervals of discharges.

TESTS:    Routine tests to applicable      standard.     Measurement      of internal partial discharges    is performed   as a routine test.

CONSTRUCTION
GENERAL:      Core and windings are completely enclosed in weather-proof       cycloaliphatic epoxy resin. Colour of resin: brown RAL
   8017. (Grey resin on request). Special features: Extremely long creepage distance. Good ability to withstand ultra-violet rays.
   Practically non-inflammable. Cycloaliphatic resin does not split off carbon under influence of surface ionisation. Units are suitable
   use in heavily polluted and coastal areas.

PRIMARY TERMINAL(S):         Stem(s) of 20mm diameter, 55mm long, of nickel plated and tinned brass. Clamp type connectors on
     request. Type GSZF has two fully insulated primary terminals. Type GSEF has one. The other end of the primary winding is
    insulated to withstand a power-frequency   test voltage of 3kV. This grounded end is located inside the secondary terminal box.
    On request: GSEF with insulated neutral terminal in compliance with IEEE (ANSI) and CSA, i.e. the primary winding withstands
    an applied test voltage of 19kV - the neutral end is routed to a separate terminal on the opposite side to the terminal box.

SECONDARY        TERMINAL       BOX: The terminal box is part of the resin body (homogeneous    casting).               The cover is sealable. Grade
   of protection: IP 54 to      DIN 40050 and IEC 529. Terminals are of nickel plated brass of size                    M6. They can be earthed by
   a link inside the terminal   box. One cable gland (for cables of IO to 14mm diameter) and one blind                  plug both sized Pg16 belong
   to the regular equipment.     Optional: plug size Pg21 for cables of 14 to 18mm diameter. On request:                conduit hubs up to one inch.

BASE: Two strong mounting brackets of hot-dip galvanized steel.                           EARTHING:   One bolt M12, opposite to the terminal box.

MOUNTING:      Vertical erect or (terminal box downwards)           in horizontal     position.

COMMISSIONING:         Units are supplied     ready for service. Just connect to system. Special tools are not necessary.
I                                                            INSULATION                 LEVELS
                                                      Highest                              Power frequency                                impulse test voltage
              Type                              equipment voltage                            test voltage                                    (BIL), full wave
    GSEF / GSZF       IO                         upto        kV                                 up to 36 kV                                      upto110kV
    GSEF / GSZF       20                         up to24     kV                                 up to 55 kV                                      upto150kV
I GSEF/GSZF           30                         up to 38    kV                                 up to 75 kV                                      up to 200 kV
/ GSEF                45              1          up to52     kV                   I             up to 95 kV                      I               up to 250 kV

                                   GSEF 10 . . . 45                                                       GSZF 10 . . . 30




                                                                          lPg21
                                                                          3n request)




                                                                                          Drawing       shows      GSEF 30 and GSZF 30.




                                                                                                                                 RITZ MESSWANDLEW
                                                                                                                                              P. 0. Box 20 22 51
                                                                                                                                 D-20243         Hamburg   - Germany

                                                                                                                                 Phone:          49 - 40 - 511 23 0
                                                                                                                                 Fax:            49 - 40 - 511 23 286



     Type     dimensions    in mm      number       weight           flash              Type                    dimensions   in mm                      number   weight
                                          of          kg             over                                                                                  of      kg
                       creepage                                                                                                      creepage
               h                        sheds                     distance                          h        b           e                               sheds
                        distance                                                                                                      distance

GSEF   10     520          780            2           72          420mm               GSZFlo
                                                                                                                                                                 7 73


GSEF


GSEF
       20


       30
              655


              880
                           1055


                           1615
                                          5


                                          10
                                                      73


                                                       77
                                                             -
                                                                  550mm


                                                                  760mm
                                                                                  I
                                                                                           -
                                                                                      GSZF 20
                                                                                           ~
                                                                                      GSZF30
                                                                                                  I-
                                                                                                  865     / 560      / 455   1         1595         1    2x10
                                                                                                                                                                  176


                                                                                                                                                                   82     1
GSEF   45

				
DOCUMENT INFO
Shared By:
Categories:
Stats:
views:395
posted:4/5/2012
language:English