					                              WECC SUBSTATION TROUBLE REPORT FORMS
revision date Jan 21, 2011
                                                                                                                     Year:        2011

                                                                           (drop-down box) Company 3 or 4 character ID: unknown

                                                                                                                Your name:

                                                                                                         Phone Number:

                                                                                                         E-Mail Address:

This spreadsheet is an electronic form used by members of WECC (Western Electricity Coordinating Council).
The WECC trouble report forms are intended to allow sharing of information between members about substation
equipment failures and misoperations. All failures of EHV equipment should be reported, regardless of whether
an outage occurred or not. Additionally, members should report failures of any substation equipment that
caused a customer outage greater than 15 minutes in duration. Members may choose to report other
non-outage failures which they feel are of interest to the Substation Working Group members. These
substation trouble reports must be submitted to the WECC working group chairman or his designated
representative by April 5 each year. This will give adequate time to process the reports in time for the WECC
Substation Working Group meeting that is typically held in early May.


Instructions on using the electronic trouble report form:
1. Find out the 3 or 4 character identification code for your utility (example, SCE for Southern Calif. Edison). If you
   don't know the ID code, they are listed on the WECC web site at the address listed below:
http://www.wecc.biz/modules.php?op=modload&name=Web_Links&file=index&req=viewlink&cid=1&min=0&orderby=titleA&show=20
2. Save and rename this spreadsheet as XXXXyyyy, where XXXX is your company code and yyyy is the four digit year.
    Example, for Snohomish Public Utility District, 2011 report, the spreadsheet name would be SNPD2011.
3. On this instruction sheet, enter the year for which the reports are being submitted, your name, your phone number and
   e-mail address. Select the company ID from the drop-down box, accessed by clicking on the down-pointing arrow to
   the right of cell C5. This information will be copied as the default for all the reports. You can type over the default
   information if someone else prepares the report.
4. Enter data on the worksheets in the tabs numbered Rept01 through Reptzz (where zz is your last report). There are
   40 blank sheets available for input. To move from one sheet to another (for example, from the "Instructions" sheet to
   the first report sheet "Rept1"), you can either left click once on the worksheet tab at the bottom of the screen, or else
    use Ctrl-PgDn and Ctrl-PgUp to move between sheets. If you need more than 40 report sheets, you can copy Rept40
   and re-name it Rept41, etc. To copy an entire sheet, hold Ctrl, click the tab with the sheet name, and drag it to a
   new location. Then double-click the newly created tab to re-name that sheet.
5. Make entries in the YELLOW OR LIGHT BLUE HIGHLIGHTED CELLS only. These highlighted cells are the only areas
    where user input is expected. Yellow cells are for all equipment types, the blue are special fields that apply only
   when reporting failure of a transformer or cable. Other spreadsheet cells are protected. The Tab key will move you
   to the next highlighted cell within that sheet. Hit Ctrl-PageDown to move on to the next report.
6. There are drop-down lists for many of the entry items. The drop-down list can be identified by a down-pointing
   arrow on the right-hand side of the cell when it is selected. If the cell has a drop down list, you must choose
   one of the items from that list. If you do not find the value you want on the drop-down list, do not delete it
   and type in something else. There are choices like "unknown" and "other" in all lists you may choose instead.
7. When you fill in data on the Rept01 through Reptzz worksheet tabs, it will automatically populate the
   sheet called "Summary". DO NOT CHANGE DATA OR ENTER ITEMS DIRECTLY ON THE SUMMARY
   WORKSHEET! If you want to make any changes, make them on the Rept01 through Rept40 sheets
   instead, and the change will be reflected on the Summary sheet.
8. The data is entered in the cell to the right of description. You can find out more information about entry into
   most cells by selecting that cell in the first report (Rept01), then reading the comment next to it.
9. To scroll through the worksheets Rept01 - Rept40, use the forward and backward buttons just to the left of the tab at
   the bottom of this sheet called "Instructions". You can also move between sheets by Ctrl-Page Up or Ctrl-Page Down.
10. No data entry or changes are permitted on the Summary, PivotTable, or the ValidData sheets. The purpose of the
   ValidData sheet is to produce items for the drop-down lists on sheets Rept01 through Reptzz.
11. The "Summary" sheet is located after sheet Rept40. It provides a concise one-page summary of all reports
    (Rept01 through Rept40) for your company. This summary data will be combined with other companies
    summary data to produce reports for WECC.
12. The "PivotTable" sheet (next after the "Summary" sheet) creates a table by equipment type (rows) and voltage
    range (columns) that gives a count of equipment trouble reports. You will need to refresh the pivot table after entering
    new data. To refresh the pivot table, choose Data, Refresh Data from the top menu.
13. Unused report sheets may be deleted if desired, although it is not necessary. For example, if you used Rept01
    through Rept14, you may delete sheets Rept15 through Rept40. If sheets are deleted, you will see REF# errors on
   the summary sheet in rows associated with those missing reports, but this is OK.
14. After you have completed filling out the forms on sheets Rept01 through Reptzz, save and back up your
   work. See step #2 for instructions on how the file should be named.
15. Photos may be included as part of your trouble report. The preferred method is to receive the photos in
   the JPEG electronic format. If you do not have digital photos, please investigate if your pictures may be
   scanned into JPEG format instead. If this is not possible, please provide 40 hard copies of the photo instead.
16. Before sending photos, please rename the JPEG file so that it can easily be identified to the trouble report.
   If there is only one photo associated with that trouble report, name the file XXXXyyyy_Reptzz.JPG.
   (where XXXX is the company code, yyyy is the 4 digit year, and zz is the associated report number).
17. If there are multiple photos, add letters A, B, C, etc after the zz part described in #8 above.
18. E-mail the trouble report file and associated digital photo files to the Substation Working Group chairman
   or his designated representative by April 5th so that this information can be presented at the working
   group meeting.
19. If you have questions about the spreadsheet setup, contact Steve Larson, Snohomish PUD, (425) 783-5576.
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 01      YEAR      2011
                  Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor        Application:


TRANSFORMER DATA (skip this section if not a transformer)
                 MVA rating:                               Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown            Taps?: N/A
           Low Side voltage: unknown                                BIL: unknown            Taps?: N/A
             Tertiary voltage: N/A                                   BIL: N/A                Taps?: N/A
               (if applicable)                            (if applicable)            (if applicable)
                  Core/Shell: N/A                              LTC mfg: unknown           LTC type:
                                                          (if applicable)            (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                   Shield: N/A
             Conductor Size:                                Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):                Weather: Clear
                   Outage or                                   Previous
               Disturbance?: none                             Trouble?: No             Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No          Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


           Corrective Action:


                 Comments:




UTILITY INFORMATION:             (kept confidential)
                Reported By:                                   Phone #:                     e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 02      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 03      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 04      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 05      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 06      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 07      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 08      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 09      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 10      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 11      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 12      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 13      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 14      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 15      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 16      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 17      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 18      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 19      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 20      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 21      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 22      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 23      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 24      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 25      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 26      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 27      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 28      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 29      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 30      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 31      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 32      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 33      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 34      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 35      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 36      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 37      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 38      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 39      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
                                 WECC SUBSTATION TROUBLE REPORT
                                   Report 40      YEAR      2011
                   Company: unknown

IDENTIFICATION DATA
            Equipment Type: unknown                           Year Mfg:               Year Install:
               Manufacturer: unknown                             Model:                   Serial #:
                     Voltage: unknown                           Current:              Interrupting:
                         BIL: unknown                  Indoor/Outdoor?: outdoor       Application:


TRANSFORMER DATA (skip this section if not a transformer)
                  MVA rating:                              Connections: N/A               Cooling: N/A
           High Side voltage: unknown                               BIL: unknown           Taps?: N/A
            Low Side voltage: unknown                               BIL: unknown           Taps?: N/A
             Tertiary voltage: N/A                                    BIL: N/A             Taps?: N/A
               (if applicable)                             (if applicable)          (if applicable)
                  Core/Shell: N/A                               LTC mfg: unknown         LTC type:
                                                           (if applicable)          (if applicable)


CABLE DATA (skip this section if not a cable)
             Type Insulation: N/A                        Insulation mils:                  Shield: N/A
             Conductor Size:                                 Installation: N/A


DETAILS OF TROUBLE
                        Date:                            Time (military):               Weather: Clear
                   Outage or                                    Previous
               Disturbance?: none                              Trouble?: No           Reported?: No
                        Cost: $           15,000       Mfgr. Consulted?: No         Photo Attach: No
                                                                                   Photo filename:
                 Part Failing:


            Cause of Failure:


            Corrective Action:


                  Comments:




UTILITY INFORMATION:             (kept confidential)

                Reported By:                                   Phone #:                    e-mail:
                    Location:                              Company ID:               Report Date:
Company   Rept #         Eq. Type        Mfg.   Model       Year Mfg.    Voltage   Current    MVA   Date        Outage   Part       Photo
unknown         1   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown         2   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown         3   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown         4   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown         5   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown         6   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown         7   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown         8   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown         9   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        10   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        11   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        12   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        13   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        14   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        15   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        16   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        17   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        18   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        19   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        20   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        21   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        22   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        23   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        24   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        25   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        26   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        27   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        28   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        29   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        30   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        31   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        32   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        33   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        34   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        35   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        36   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        37   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        38   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        39   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
unknown        40   unknown         unknown             0           0   unknown           0         01/00/00   none             0           0
Company        (All)

Count of Rept # Voltage
Eq. Type        Grand Total
Grand Total
Companies   Equipment               Voltages     BIL
unknown     unknown                 unknown      unknown
ACC         Transformer             0-5 kV       0-70 kV
ADOE        Ckt. breaker - SF6      6-10 kV      71-100 kV
AEPC        Ckt. breaker - oil      11-15 kV     101-150 kV
AES         Ckt. breaker - vacuum   16-20 kV     151-200 kV
AESC        Ckt. breaker - air      21-25 kV     201-300 kV
ANHM        Switch                  26-35 kV     301-400 kV
APA         Circuit Switcher        36-50 kV     401-500 kV
APS         Insulator               51-100 kV    501-600 kV
APX         Arrester                101-150 kV   601-700 kV
ATCO        Battery                 151-200 kV   701-800 kV
AVA         Bus                     201-250 kV   801-900 kV
AWEA        Bushing - xfrmr         251-300 kV   901-1000 kV
BCHA        Bushing - ckt brkr      301-350 kV   > 1000 kV
BCME        Bushing - other         351-400 kV   N/A
BCUC        Capacitor               401-450 kV
BEPC        Cable                   451-500 kV
BHP         CCVT                    > 500 kV
BOE         CT                      N/A
BPAP        Generator
BPAT        Insulating Fluid
BURB        Motor
CALP        PT
CAWC        Reactor
CDWR        Regulator
CEC         Relay
CERT        other
CFBF
CFE
CHPD
CINE
CISO
COPC
CORA
CORL
CPSI
CPUC
CRGL
CSU
DENA
DETM
DGT
DOPD
DPU
DYN
EKT
EMC
EMCU
EMMT
EPE
EPME
ESL
EWEB
EXPT
FARM
FPLE
GBPP
GCPD
GEO
GLEN
HESI
HHWP
HPLP
IGI
IID
IPC
IPT
IPUC
LAC
LDWP
LLC
MDEQ
MICRON
MID
MIEC
MIR
MPSC
MWD
MWEC
NAPG
NCA
NCPA
NEVP
NMPRC
NPPC
NRG
NTUA
NVOE
NVPUC
NWMT
OOE
OPUC
OTED
PAC
PACM
PACW
PAND
PASA
PERC
PG&E
PGE
PNEG
PNM
POUC
PPLM
PPOA
PRPA
PSC
PSE
PWEC
PWX
RDNG
REI
RVSD
RWE
SC2G
SCE
SCL
SDGE
SER
SETC
SFG
SMUD
SNCL
SNPD
SPR
SRP
SWPG
SWTC
TAA
TANC
TAUC
TCP
TEMI
TEP
TES
TID
TNP
TNSK
TPWR
TSGT
TURN
TXUE
UAMP
UBSW
UCCS
UEO
UFBF
UMPA
UPSC
USBR
WAPA
WEMT
WPSC
WTED
WUTC
other1
other2
other3
other4
other5
other6
other7
other8
other9
TransConn           Cooling     CoreShell   Taps
N/A                 N/A         N/A         N/A
unknown             dry         Core        none
Single Phase        OA          Shell       NLTC
Delta-Delta         OA/FA       other       LTC
Delta-Wye           OA/FA/FA    unknown     unknown
Wye-Delta           OA/FA/FOA
Wye-Wye             other
Open Delta          unknown
Delta-Delta-Delta
Delta-Wye-Delta
Wye-Delta-Delta
Wye-Wye-Delta
other
Mfgr            Weather            InOut     Disturb       Insulation
unknown         Clear              outdoor   none          N/A
A.B. CHANCE     Cloudy             indoor    Load Loss     XLPE
ABB             Windy              unknown   Line Out      EPR
ACME            Rain                         Disturbance   HMWPE
AEG             Lightning                    other         Oil/paper
AETNA           Heat (excessive)             unknown       SF6 gas
AGASTAT         Snow                                       other
ALCAN           Other                                      unknown
ALCAN           unknown
ALCOA
ALLIS
ALSTOM
AMERICAN
ANACONDA
ANDERSON
ASEA
ASSOCIATED
BALDWIN
BASLER
BROWN BOVERI
CABLEC
CANADA
CENTRAL
CONTINENTAL
COOPER
CYPRESS
DELTA-STAR
EASTERN
ELASTIMOLD
ELCO
ELECTROMAX
ELECTROSWITCH
ELIN
ENERTEC
ERMCO
ESSEX
FERRANTI
FPE
FUJI
FULLER
G&W
GE
GEC
GEN CABLE
GNB
GOULD
GTE
HAEFLY
HATHAWAY
HENDRIX
HEVI DUTY
HITACHI
HOWARD
HUBBEL
HVB
HYOSUNG
HYUNDAI
IBC
IEM
ILLINOIS
INTERSTATE
ITE
ITT
JEFFERSON
JOHNSON
JOSLYN
KAISER
KEARNY
KELMAN
KERITE
KUHLMAN
LAPP
LINE MATERIAL
LOCKE
MAGNETEK
MCGRAW
MEP
MERLIN
MITSUBISHI
MOLONEY
MOTOROLA
NATIONAL
NATIONAL
NGK
NIAGRA
NORTH AMER.
OHIO BRASS
OHIO TRANSF.
OKONITE
other
PACIFIC
PASSONI
PAUWELS
PENNSYLVANIA
PHELPS
PIONEER
PIRELLI
PORTER
POTTER & BRUM
POWELL
PROLEC
QUALITROL
RAYCHEM
REINHAUSEN
RELIANCE
REYNOLDS
RFL
ROME
ROYAL
RTE
S&C
SANGAMO
SCHLUMBERGER
SCHWEITZER
SEDIVER
SEL
SIEMENS
SIMPLEX
SMIT
SOUTHWEST
SQUARE D
STANDARD
SUMITOMO
SUNBELT
SYLVANIA
TOSIBA
TRAFO
TRENCH
TURNER
UPTEGRAFF
US TRANSF.
UTILITY
VIRGINIA
WAGNER
WAUKESHA
WESTINGHSE
z_NONE
zzz1
zzz2
zzz3
zzz4
zzz5
zzz6
zzz7
zzz8
Shield             CableInstall
N/A                N/A
bare conc. neut.   conduit
jacketed CN        conduit/concrete
tape shield        direct buried
lead/paper         pipe type
submarine          submarine
other              other
unknown            unknown

				