AHERA Re-Inspection for Glair E. Gale Jr. High School 2011

Document Sample
AHERA Re-Inspection for Glair E. Gale Jr. High School 2011 Powered By Docstoc
					                      AHERA Re-Inspection for Glair E. Gale Jr. High School                         2011

Introduction

On August 25, 2011, Mr. Bruce Moss of Idaho Falls School District 91 conducted an asbestos 3-year re-
inspection at the Clair E. Gale Jr. High School located at 955 Garfield Street, Idaho Falls, Idaho. The
purpose of the re-inspection was to evaluate materials previously identified as being asbestos
containing building materials (ACBM) and assess their condition. The facility was visually inspected for
ACBM, all surfaces, structures, and mechanical systems were examined. All suspected ACBM, where
possible, was touched to determine friability. Findings during this re-inspection are detailed the tables
following this summary.

Summary of Findings

The Original AHERA Inspection Information Abstracted from the Management Plan form was completed
using information from the original inspection that occurred in August of 1988. All ACBM remaining in
the school after renovations, abatements, and testing resulting in a no asbestos determination was then
identified on the Re-Inspection of ACBM: Findings and Management Planner Recommendations form
which was then taken to the school to perform the physical re-inspection. Remaining ACBM in the
school will be detailed on the individual homogeneous area descriptions located in the Asbestos
Management Plan on the district Environmental Health & Safety website.

Additional bulk samples were collected from the following areas:

    •   Boiler room - from the gasket of flanged fittings found throughout the HVAC system, sample ID#
        234-2011-202-02. Asbestos is 55% Chrysotile.
    •   Roof - from the vibration boot of the large air circulation fan, sample ID# 235-2011-202-02.
        Asbestos is 80% woven Chrysotile. (Vibration boots removed)
    •   Roof-from the vibration boot of the small air circulation fan, sample ID# 236-2011-202-02.
        Asbestos is 80% woven Chrysotile. (Vibration boots removed)
    •   Weld shop - from the fire bricks used to line the table top, sample ID# 242-2011-202-02.
        Asbestos is none detected.
    •   Sound control room in auditorium - from the transite board that surrounds the auditorium,
        previously the gymnasium at the tension line, sampled ID# 243-2011-202-02. Asbestos is 15%
        Chrysotile.

No new homogeneous areas were identified during this re-inspection.

Each homogeneous area of ACBM has been assessed for existing damage, accessibility, potential for
disturbance, and assigned a hazard ranking which includes a response action. The hazard ranking is also
based on assessment category and damage category. A description of the assessment categories and
damage categories can be found in the Inspection and Re-inspection Protocol for each Asbestos
Management Plan on the district website.
                     AHERA Re-Inspection for Glair E. Gale Jr. High School                      2011

Signatures

The following AHERA accredited inspector conducted the re-inspection and assessment. The
certifications can be found in the Asbestos Management Plan.




Bruce/Moss                                       bate'

AHERA Accredited Inspector




The following AHERA accredited Management Planner made recommendations for handling the ACBM
found in this building based on the re-inspection information. The certifications can be found in the
Asbestos Management Plan.




                                                          It-
Bruce/Moss                                       tfate

AHERA Accredited Management Planner
Original AHERA Inspection Information Abstracted from the Management Plan
                                                                                                                                                     Page                       of

School:                    Clair E. Gale                       Building:              School                   Date(s) of Original AHERA Inspection:                          8/88



      Homogeneous Sampling Areas                                                                                   AHERA
                                                                                                                                         Recorded locations of           Response actions taken/
                                                       Material                                                  Assessment
                                                                           Asbestos Content       Friability                               material for each               renovations/ other
                                                       Category                                                 Category (1-7,
                                                                                                                                         assessment category                   comments
ID Number              Material Description                                                                       X, None)


                                                                                              *    F
                                                                                                                                                                       Continue O&M with 6 month
                                                       TSI                  Assumed                              ACBM with
                                                                                                                                     Throughout the original               surveillance and 3 year
       1                     Floor Tile            Surf.                      Yes                 NF       *     potential for
                                                                                                                                                                      reinspections to maintain in an
                                                                                                                                     building and all additions
                                                   Misc.                       No                 X                damage                                                intact and good condition
                                                                    *
                                                                            Assumed           *    F             ACBM with           Boiler room entrance doors        Continue O&M with 6 month
                                                       TSI
                                                                                                                                     and exterior entrance doors           surveillance and 3 year
       2                     Fire Doors                Surf.                  Yes                 NF       *     potential for
                                                                                                                                     and any door with less than      reinspections to maintain in an
                                                   Misc.            *          No                 X                damage                  100 in2 windows               intact and good condition
                                                    TSI                     Assumed           *    F              ACBM wit
                                                                                                                                                                      Sampled and determined to
       3                     Safe Door             Surf.                      Yes                 NF             potential for                Off ice area
                                                                                                                                                                        be non-ACBM - 9/92
                                                   Misc.            *          No                 X        *       damage

                                                                    *                         *    F
                                                                                                                                                                       Continue O&M with 6 month
                      Gaskets in HVAC              TSI                      Assumed                              ACBM with            Throughout the HVAC
                                                                                                                                                                           surveillance and 3 year
      4            Equipment and Flanged           Surf.                      Yes                 NF       *     potential for        system in the original
                                                                                                                                                                      reinspections to maintain in an
                          Fittings                 Misc.                       No                 X                damage            building and all additions          intact and good condition
                                                                                                                                      Ceiling in halls, ceiling and
                                                                                              *                                        walls in office complex,
                                                       TSI                  Assumed                F            ACBM with                                             Sampled and determined to
                       Plasterboard (Original                                                                                       concession room, restrooms,
      5                                            Surf.                      Yes                 NF            potential for
                                                                                                                                    library, industrial arts room,
                                                                                                                                                                        be non-ACBM -7/88,
                              Building)
                                                   Misc.                       No                 X               damage                music complex, chall                 10/89, 1/90
                                                                    *                                      *                          classrooms, and cafeteria
                                                    TSI                     Assumed       *        F            ACBM with               Ceiling and walls of
                        Plasterboard (A Hall                                                                                                                          Sampled and determined to
     5A                                            Surf.                      Yes                 NF            potential for       classrooms and hallway of
                             Addition)                                                                                                                                 be non-ACBM - 11/3/89
                                                   Misc.                       No                 X               damage                  A hall addition
                                                                    *                                      *


Information abstracted by:                Bruce Moss                                                                             Date:                         8/18/11

Friability: F = friable, NF = nonfriable, X = not applicable (material is non-ACBM)

AHERA assessment category: 1 = Damaged or significantly damaged TSI ACBM, 2 = Damaged friable surfacing ACBM, 3 = Significantly damaged friable surfacing ACBM, 4 =
Damaged or significantly damaged friable miscellaneous ACBM, 5 = ACBM with potential for damage, 6 = ACBM with potential for significant damage, 7 = Any remaining friable
ACBM or friable suspected ACBM, X = not applicable (material is non-ACBM or nonfriable surfacing or miscellaneous material), None = No assessment category provided in
original inspection.
Original AHERA Inspection Information Abstracted from the Management Plan
                                                                                                                                                 Page                     of

School:                    Clair E. Gale                   Building:              School                   Date(s) of Original AHERA Inspection:                        8/88



      Homogeneous Sampling Areas                                                                               AHERA
                                                                                                                                     Recorded locations of       Response actions taken/
                                                       Material                                              Assessment
                                                                       Asbestos Content       Friability                               material for each           renovations/ other
                                                       Category                                             Category (1-7,
                                                                                                                                     assessment category               comments
ID Number              Material Description                                                                   X, None)

                                                                                                       #                                                         Continue O&M with 6 month
                                                        TSI       *     Assumed                F             Damaged or
                   Heat Pipe Insulation with                                                                                         Pipe chases and ceiling         surveillance and 3 year
       6                                               Surf.              Yes             *   NF             significantly
                    Mudded Joint Fittings                                                                                                    cavities           reinspections to maintain in an
                                                       Misc.               No                 X              damaged TSI                                           intact and good condition

                                                                  *                                    *    Damaged or                                           Continue O&M with 6 month
                                                        TSI             Assumed                F
                  Domestic Water Pipe with                                                                                           Pipe chases and ceiling         surveillance and 3 year
      7A                                               Surf.              Yes             *   NF            significantly
                                                                                                                                                                reinspections to maintain in an
                   Mudded Joint Fittings                                                                                                    cavities
                                                       Misc.               No                  X            damaged TSI                                            intact and good condition
                                                                                                                                  Routed down through the
                                                                  *                                    *
                                                                                                                                 walls and only visible above   Approximately 21 LF remain
                                                    TSI                 Assumed                F            Damaged or
                  Roof Drains with Mudded                                                 *                                      ceiling level except in boys      of the original 75 LF.
      7B                                           Surf.                  Yes                 NF            significantly
                                                                                                                                 locker room, office storage
                        Joint Fittings                                                                                                                              Continue O&M on
                                                   Misc.                   No                 X             damaged TSI           room and electrical panel              remaining
                                                                                                                                            room
                                                    TSI           *     Assumed                F       *    Damaged or                                             All boiler components
                                                                                                                                 North boiler in the boiler
     8A                    North Boiler            Surf.                  Yes             *   NF            significantly                                        proven non-ACBM except
                                                                                                                                           room
                                                   Misc.                   No                 X             damaged TSI                                           auger housing cement

                                                    TSI           *     Assumed                F       *    Damaged or                                             All boiler components
                                                                                                                                 South boiler in the boiler
     SB                    South Boiler            Surf.                  Yes             *   NF            significantly                                        proven non-ACBM except
                                                                                                                                           room
                                                   Misc.                   No                 X             damaged TSI                                            auger housing cement

                                                    TSI           *     Assumed                F            Damaged or                                          ACBM in this area removed
                       Boiler Room Chimney
     8C                                            Surf.                  Yes         *       NF            significantly                 Boiler room               prior to the 1994
                               Ducts
                                                   Misc.                   No                 X
                                                                                                       *
                                                                                                            damaged TSI                                               reinspection


Information abstracted by:                Bruce Moss                                                                         Date:                        8/22/11


Friability: F = friable, NF = nonfriable, X = not applicable (material is non-ACBM)

AHERA assessment category: 1 = Damaged or significantly damaged TSI ACBM, 2 = Damaged friable surfacing ACBM, 3 = Significantly damaged friable surfacing ACBM, 4 =
Damaged or significantly damaged friable miscellaneous ACBM, 5 = ACBM with potential for damage, 6 = ACBM with potential for significant damage, 7 = Any remaining friable
ACBM or friable suspected ACBM, X = not applicable (material is non-ACBM or nonfriable surfacing or miscellaneous material), None = No assessment category provided in
original inspection.
Original AHERA Inspection Information Abstracted from the Management Plan
                                                                                                                                                        Page                         of

School:                     Clair E. Gale                       Building:              School                   Date(s) of Original AHERA Inspection:                              8/88

                                                                                                                    AHERA
       Homogeneous Sampling Areas                                                                                                         Recorded locations of               Response actions taken/
                                                        Material                                                  Assessment
                                                                            Asbestos Content       Friability                               material for each                   renovations/ other
                                                        Category                                                 Category (1-7,
ID Number               Material Description                                                                                              assessment category                       comments
                                                                                                                   X, None)

                                                         TSI                 Assumed           *    F               Damaged
                        Surface Coat (Library
       9                                                Surf.        *         Yes                 NF                friable          Library workroom ceiling                ACBM removed in 1990
                             Workroom)
                                                        Misc.                   No                  X            surfacing ACM
                                                                                                            *
                                                         TSI
                                                                     #       Assumed                F              ACBM with
                                                                                               *
                                                                                                                                                                            Sampled and determined to
      10                     Incinerator                Surf.                  Yes                 NF             potential for                Boiler room                    ho nnn ATRM     fi/*?Q/Qd
                                                        Misc.                   No                  X       *        damage
                                                                                                                   Damaged or
                                                         TSI                 Assumed                F              significantly
                   Vibration Boots (Original
      11                                                Surf.                  Yes             *   NF            damaged friable       B-hall mechanical room                 ACBM removed in 1989
                           Building)
                                                        Misc.                   No                 X              miscellaneous
                                                                     *                                      *         ACBM
                                                                                                                                          Custodial office, roof above
                                                                                                                                      kitchen, C-hall mechanical room,
                                                                                                                                     industrial arts wood storage room,     Vibration boots removed in
                                                     TSI                     Assumed                F             ACBM with               girls and boys locker rooms,
                                                                                                                                                                              1989 except roof boots
     11A                  Vibration Boots           Surf.                      Yes             *   NF             potential for         mechanical area above faculty
                                                                                                                                       lounge, little theater stage area,     which were removed in
                                                    Misc.                       No                 X                damage
                                                                                                                                         room 107 storage, north and                   2011
                                                                     *                                      *                        south gym mechanical rooms, and
                                                                                                                                                 cafeteria kitchen

                                                     TSI                     Assumed       *        F             ACBM with
                       Ceiling Tile (Armstrong                                                                                       In the classrooms of A-hall            Sampled and determined to
      12                                            Surf.                      Yes                 NF             potential for
                                 942)
                                                                                                            #                                 and B-hall.                     ho nnn ATRM     7/1fi/fi8
                                                    Misc.                       No                 X                damage
                                                                     *
                                                     TSI                     Assumed       *        F            ACBM with
                   Ceiling Tile (2'x4' Square                                                                                                                               Sampled and determined to
      13                                            Surf.                      Yes                 NF            potential for                    Library
                            Pattern)                                                                                                                                          he nnn-ATRIVI   7/1fi/8R
                                                    Misc.                       No                 X        •      damage
                                                                     *

Information abstracted by:                 Bruce Moss                                                                             Date:                             8/23/11

Friability: F = friable, NF = nonfriable, X = not applicable (material is non-ACBM)

AHERA assessment category: 1 = Damaged or significantly damaged TSI ACBM, 2 = Damaged friable surfacing ACBM, 3 = Significantly damaged friable surfacing ACBM, 4 =
Damaged or significantly damaged friable miscellaneous ACBM, 5 = ACBM with potential for damage, 6 = ACBM with potential for significant damage, 7 = Any remaining friable
ACBM or friable suspected ACBM, X = not applicable (material is non-ACBM or nonfriable surfacing or miscellaneous material), None = No assessment category provided in
original inspection.
Original AHERA Inspection Information Abstracted from the Management Plan
                                                                                                                                                    Page                         of

School:                     Clair E. Gale                      Building:              School                   Date(s) of Original AHERA Inspection:                           8/88



      Homogeneous Sampling Areas                                                                                   AHERA
                                                                                                                                         Recorded locations of            Response actions taken/
                                                       Material                                                  Assessment
                                                                           Asbestos Content       Friability                               material for each                renovations/ other
                                                       Category                                                 Category (1-7,
                                                                                                                                         assessment category                    comments
ID Number               Material Description                                                                      X, None)


                                                       TSI                  Assumed           *    f             ACBM with
                       Ceiling Tile (12" Square                                                                                      Classrooms and hallway          Sampled and determined to
      14                                               Surf.                  Yes                 NF             potential for
                                Glued)                                                                                                      forA-hall                 be non-ACBM- 7/16/88
                                                       Misc.                   No                  X               damage
                                                                    *                                      *
                                                        TSI         *       Assumed                F             Damaged or
      15                Heat Exchange Tank             Surf.                  Yes             *   NF             significantly               Boiler room                  ACBM removed in 1990
                                                       Misc.                   No                  X       *     damaged TSI

                                                                    *
                                                        TSI                 Assumed                F             Damaged or
                        Domestic Hot Water
      16                                               Surf.                  Yes             *   NF             significantly               Boiler room                  ACBM removed in 1990
                          Storage Tank
                                                       Misc.                   No                 X              damaged TSI
                                                                                                           *
                                                    TSI                     Assumed           *    F
                                                                                                                                    Trailer removed. See RMC          Trailer removed. See RMC
      17                Plasterboard (Trailer)     Surf.                      Yes                 NF                None
                                                                    •
                                                                                                                                             11-12 AMP                         11-12 AMP
                                                   Misc.                       No                 X        *
                                                                                                           *                                                           Continue O&M with 6 month
                                                       TSI                  Assumed                F
                       Cafeteria Surface Coat                       #                         #                                           Cafeteria above the              surveillance and 3 year
      18                                           Surf.                      Yes                 NF                None
                                                                                                                                                                      reinspections to maintain in an
                              Residue                                                                                                      header of the wall
                                                   Misc.                       No                 X                                                                      intact and good condition
                                                                                                           *                         Throughout the school -          Continue O&M with 6 month
                                                       TSI                  Assumed                F
                       Surface Coat Residue                                                                                            Cleaned: penetrant/                surveillance and 3 year
      19                                           Surf.            *         Yes             *   NF                None
                        (Original Building)                                                                                         encapsulant applied -July        reinspections to maintain in an
                                                   Misc.                       No                 X                                                                     intact and good condition
                                                                                                                                              1992


Information abstracted by:                Bruce Moss                                                                             Date:                          8/24/11

Friability: F = friable, NF = nonfriable, X = not applicable (material is non-ACBM)

AHERA assessment category: 1 = Damaged or significantly damaged TSI ACBM, 2 = Damaged friable surfacing ACBM, 3 = Significantly damaged friable surfacing ACBM, 4 =
Damaged or significantly damaged friable miscellaneous ACBM, 5 = ACBM with potential for damage, 6 = ACBM with potential for significant damage, 7 = Any remaining friable
ACBM or friable suspected ACBM, X = not applicable (material is non-ACBM or nonfriable surfacing or miscellaneous material), None = No assessment category provided in
original inspection.
Original AHERA Inspection Information Abstracted from the Management Plan
                                                                                                                                              Page                      of

School:                  Clair E. Gale                  Building:                 School                 Date(s) of Original AHERA Inspection:                        8/88



      Homogeneous Sampling Areas                                                                             AHERA
                                                                                                                                   Recorded locations of         Response actions taken/
                                                    Material                                               Assessment
                                                                     Asbestos Content       Friability                               material for each             renovations/ other
                                                    Category                                              Category (1-7,
                                                                                                                                   assessment category                 comments
ID Number            Material Description                                                                   X, None)


                                                    TSI                Assumed          *    F             ACBM with
                     Hard Plaster (Original                                                                                    Entrances to the gym and     Sampled and determined to
      20                                           Surf.       *         Yes                NF             potential for
                           Building)                                                                                                 the north hall          be non-ACBM - 10/3/91
                                                   Misc.                  No                 X               damage
                                                                                                     *
                                                    TSI                Assumed          *    F             ACBM with
                     Gym Ceiling Tectum                                                                                                                     Sampled and determined to
      21                                           Surf.                 Yes                NF             potential for               Gym ceiling
                          Panels                                                                                                                             be non-ACBM 10/3/91
                                                   Misc.       *          No                 X
                                                                                                     *
                                                                                                             damage

                                                                                        *                                       Ceilings throughout all
                                                    TSI                Assumed               F             ACBM with
                                                                                                                              hallways except A-hall and    Sampled and determined to
     22A           Surface Texture Material        Surf.       *         Yes                NF             potential for
                                                                                                                               in classrooms in the gym      be non-ACBM - 10/3/91
                                                   Misc.                  No                 X               damage
                                                                                                     *                                    wing

                                                                                        *                                      Walls in the band room,
                                                    TSI                Assumed               F             ACBM with                                        Sampled and determined to
                                                                                                                               vocal room and cafeteria
     22B           Surface Texture Material        Surf.       *         Yes                NF             potential for                                     be non-ACBM - 2/20/90
                                                                                                                                and ceiling in the little
                                                   Misc.                  No                 X
                                                                                                     *       damage                                               and 10/3/91
                                                                                                                                        theater
                                                                       Assumed          *                  ACBM with          In gym at the tension ring     Continue O&M with 6 month
                                                    TSI                                      F
                     TransiteType Boards                                                                                                                         surveillance and 3 year
     23                                            Surf.                 Yes                NF       *     potential for        approximately 22 feet
                      (Original Building)                                                                                                                   reinspections to maintain in an
                                                   Misc.       *          No                 X               damage                above the floor             intact and good condition
                                                                       Assumed          *                  ACBM with                                         Continue O&M with 6 month
                                                    TSI                                      F
                   Transite Type Boards (A                                                                                    Above and below windows            surveillance and 3 year
      24                                           Surf.                 Yes                NF       *     potential for
                        Hall Addition)                                                                                        in the 1980 A-hall addition   reinspections to maintain in an
                                                   Misc.       *          No                X                damage                                            intact and good condition


Information abstracted by:             Bruce Moss                                                                          Date:                       8/24/11

Friability: F = friable, NF = nonfriable, X = not applicable (material is non-ACBM)

AHERA assessment category: 1 = Damaged or significantly damaged TSI ACBM, 2 = Damaged friable surfacing ACBM, 3 = Significantly damaged friable surfacing ACBM, 4 =
Damaged or significantly damaged friable miscellaneous ACBM, 5 = ACBM with potential for damage, 6 = ACBM with potential for significant damage, 7 = Any remaining friable
ACBM or friable suspected ACBM, X = not applicable (material is non-ACBM or nonfriable surfacing or miscellaneous material), None = No assessment category provided in
original inspection.
Original AHERA Inspection Information Abstracted from the Management Plan
                                                                                                                                             Page                       of        6

School:                     Clair E. Gale                Building:                School                Date(s) of Original AHERA Inspection:                         8/88


      Homogeneous Sampling Areas                                                                            AHERA
                                                                                                                                  Recorded locations of          Response actions taken/
                                                      Material                                            Assessment
                                                                     Asbestos Content      Friability                               material for each              renovations/ other
                                                      Category                                           Category (1-7,
                                                                                                                                  assessment category                  comments
ID Number               Material Description                                                               X, None)


                                                    TSI                Assumed              F             ACBM with
                        Under Floor Air Duct                                                                                      Under the floor in the     Sampled and determined to
      25                                           Surf.                 Yes               NF             potential for
                         (Original Building)                                                                                        original building         be non-ACBM-9/30/91
                                                   Misc.                  No                X               damage

                                                    TSI                Assumed              F             ACBM with               Under the floor in the
                       Under Floor Air Duct (A                                                                                                               Sampled and determined to
      26                                           Surf.                 Yes               NF             potential for            classroom building
                           Hall Addition)                                                                                                                      be non-ACBM-9/3/91
                                                   Misc.                  No                X               damage                       addition

                                                                                                                                                                 212 LF removed in 2004
                   Electrical Wire Insulation       TSI                Assumed              F             ACBM with
                                                                                                                               Light fixtures above the            during renovation.
      27            and Stage Lights (Little       Surf.                 Yes               NF             potential for
                                                                                                                              stairs of the little theater         Continue O&M on
                            Theater)               Misc.                  No                X               damage
                                                                                                                                                                  remaining insulation
                                                                                                                             Under floor air duct of the
                                                                       Assumed                            ACBM with          B-hall fan room area. 12"        Continue O&M with 6 month
                                                    TSI                                     F
                                                                                                                                                                  surveillance and 3 year
      28                   Tuff Spun Pipe          Surf.                 Yes               NF             potential for       dia. pipe that is routed
                                                                                                                                                             reinspections to maintain in an
                                                   Misc.                  No                X               damage            east and west crossing            intact and good condition
                                                                                                                                 through air duct.




Information abstracted by:               Bruce Moss                                                                       Date:                        8/24/11

Friability: F = friable, NF = nonfriable, X = not applicable (material is non-ACBM)

AHERA assessment category: 1 = Damaged or significantly damaged TSI ACBM, 2 = Damaged friable surfacing ACBM, 3 = Significantly damaged friable surfacing ACBM, 4 =
Damaged or significantly damaged friable miscellaneous ACBM, 5 = ACBM with potential for damage, 6 = ACBM with potential for significant damage, 7 = Any remaining friable
ACBM or friable suspected ACBM, X = not applicable (material is non-ACBM or nonfriable surfacing or miscellaneous material), None = No assessment category provided in
original inspection.
Reinspection of ACBM: Findings and Management Planner Recommendations
                                                                                                                                         Page                   of



School:                    Clair E. Gale               Building:              School                     Date(s) of Original AHERA Inspection:                8/88

Homogeneous Sampling Area: Material Description                         Floor Tile, Fire Doors, Gaskets                 ID Number                       1,2,4


                                       REINSPECTION FINDINGS FOR ACBM                                                         MANAGEMENT PLANNER RECOMMENDATIONS
                                                             Assess-                                                                                                 Schedule
                                                              ment                                           Change       Preventive measures, response
  Location(s) of ACBM by                           Fria-                     Justification of
                                     Quantity                 cate-                                        in assess-      actions, and initial/additional                 Com-
   assessment category                             bility                 assessment category                                                                    Begin
                                                             gory (1-                                         ment                   cleanings                             plete
                                                              7,X)
                                                  F                       There is potential for           Yes
          1- Floor Tiles              49,000                       5                                                                 Continue O&M
                                                 NF     *               damage due to accessibility        No      *
                                                  F                       There is potential for           Yes
          2 -Fire Doors                    16                      5                                                                 Continue O&M
                                                 NF     *               damage due to accessibility        No      *
                                                                        There is very little potential
                                                  F                                                        Yes
    4 -Gaskets in HVAC                     100                     5        for damage due to
                                                                                                                   *                 Continue O&M
                                                 NF     *                                                  No
                                                                               inaccessibility

Were additional samples of this ACBM collected?                                                             Date of management planner review:
                                                              Yes                 No          *

 Inspector Name                   Bruce Mo^s^,-A                                                            Management Planner Name              Bruce MQfV//

 Inspector Signature
                                     ^3?3J£^
                                       ff^Jf
                                                                                     8/25/11
                                                                                                            Management Planner Signature            ^V^K^^ -^
                                  Utah/Idaho                                                                                                     Utah/Idaho
 Accreditation** /State                                                                                     Accreditation ft/State
                                  7/29/2012                                                                                                      7/29/2012
 Expiration Date                                                                                            Expiration Date


 1, the LEA's Designated Person, have read and understood the recommendations made above: Cj JLt/jCht^                                       Date:     / /J-£J/J^~>
                                                                                                                                                        /    (
Reinspection of ACBM: Findings and Management Planner Recommendations
                                                                                                                                           Page                    of



School:                 Clair E. Gale                Building:                   School                   Date(s) of Original AHERA Inspection:                 8/88

                                                            Heat p
Homogeneous Sampling Area: Material Description                      'pe insulation, Domestic water Pipe and Roof Drains   ID Number                   6, 7(A&B), 8(A&B)
                                                                         w/MJF, Boiler Auger Housing Cement



                                    REINSPECTION FINDINGS FOR ACBM                                                              MANAGEMENT PLANNER RECOMMENDATIONS
                                                          Assess-                                                                                                       Schedule
                                                           ment                                                Change       Preventive measures, response
     Location(s) of ACBM by                     Fria-                           Justification of
                                  Quantity                 cate-                                             in assess-      actions, and initial/additional                  Com-
      assessment category                       bility                       assessment category                                                                   Begin
                                                          gory (1-                                              ment                   cleanings                              plete
                                                           7,X)
     6 - Heat Pipe Insulation                    F                          There is potential for            Yes
                                   1976 LF                       5                                                                     Continue O&M
             w/MJF                              NF                        damage due to accessibility         No      *
                                                      *
 7(A&B) - Domestic Water
                                                 F                          There is potential for            Yes
   Pipes w/MFJ and Roof             72 LF                        5                                                                     Continue O&M
                                                NF                        damage due to accessibility         No
       Drains w/MJF                                   *                                                               *


  8(A&B) -Auger Housing                          F                          There is potential for            Yes
                                        2ft 2                    5                                                                     Continue O&M
      Cement (Boiler)                           NF    *                   damage due to accessibility         No
                                                                                                                      *




Were additional samples of this ACBM collected?                                                               Date of management planner review:
                                                           Yes                       No          *

 Inspector Name                 Bruce Moss v / .                                                              Management Planner Name              Bruce Mjass j £/

                                                                                                                                                       Jffi/l 7J^ 1/17/12
 Inspector Signature                /{v^J                                                                     Management Planner Signature             jr/0*C_
                                   / ^^                                                                                                               / u
       .. • *,<.                Utah/Idaho                                                                          .. .       ,„                  Utah/Idaho
 Accreditation** /State                                                                                       Accreditation ft/State

 r  . . r,                      7/29/2012                                                                     c • • ^ *                            7/29/2012
 Expiration Date                                                                                              Expiration Date


 1, the LEA's Designated Person, have read and understood the recommendations made above:                Of^>rrjL                              Date:      /A-//-
                                                                                                                                                           '
Reinspection of ACBM: Findings and Management Planner Recommendations
                                                                                                                                         Page                   of



School:                Clair E. Gale               Building:                 School                    Date(s) of Original AHERA Inspection:                  8/88


Homogeneous Sampling Area: Material Description          Cafeteria Surface Coat Residue, Original Building Surface Coat   ID Number                    18, 19, 23
                                                                           Residue, Transite Boards




                                   REINSPECTION FINDINGS FOR ACBM                                                            MANAGEMENT PLANNER RECOMMENDATIONS
                                                         Assess-                                                                                                     Schedule
                                                          ment                                            Change           Preventive measures, response
  Location(s) of ACBM by                      Fria-                        Justification of
                                 Quantity                 cate-                                          in assess-         actions, and initial/additional                Com-
   assessment category                        bility                    assessment category                                                                      Begin
                                                        gory (1-                                            ment                      cleanings                            plete

18 - Cafeteria Surface Coat                                           There is very little potential
                                               F                                                          Yes
Residue (Above the header          100 ft 2                               for damage due to                                        Continue O&M
                                              NF                                                          No
        of the wall)                                                         inaccessibility
                                                                     There is very little potential
   19 -Original Building                       F                                                          Yes
                                   100 ft 2                              for damage due to                                         Continue O&M
   Surface Coat Residue                       NF                                                          No
                                                                            inaccessibility
 23 - Transite Type Boards                                            Holes have been drilled in
                                               F                                                          Yes             Patch holes and seal with CP-10
(Gym at tension ring ~22 ft       1200 ft 2                           the transite at eye level in                                                              9/1/11   9/14/11
                                              NF                                                          No                   bridging encapsulant
          off floor)                                                   the sound control room


Were additional samples of this ACBM collected?                                                            Date of management planner review:
                                                         Yes                     No


 Inspector Name               Bruce Mos                                                                    Management Planner Name              Bruce Mqj^s

                                                                                   8/25/11
 Inspector Signature                                                                                       Management Planner Signature
                                                                                                                                                 V
                              Utah/Idaho                                                                                                        Utah/Idaho
 Accreditations/State                                                                                     Accreditation ft/State

                                                                                                                                                7/29/2012
 Expiration Date                                                                                           Expiration Date


 1, the LEA's Designated Person, have read and understood the recommendations made above:                                                    Date:
Reinspection of ACBM: Findings and Management Planner Recommendations
                                                                                                                                          Page                   of



School:                Clair E. Gale                 Building:                 School                     Date(s) of Original AHERA Inspection:                8/88

Homogeneous Sampling Area: Material Description                  Transite Boards, Wire Insulation, Tuff Spun Pipe        ID Number                      24, 27, 28


                                     REINSPECTION FINDINGS FOR ACBM                                                          MANAGEMENT PLANNER RECOMMENDATIONS
                                                          Assess-                                                                                              Schedule
                                                           ment                                              Change        Preventive measures, response
  Location(s) of ACBM by                       Fria-                          Justification of
                                   Quantity                cate-                                            in assess-      actions, and initial/additional          Com-
   assessment category                         bility                      assessment category                                                              Begin
                                                          gory (1-                                             ment                   cleanings                      plete
                                                           7,X)
  24 - Transite Type Boards
                                               F                           There is potential for           Yes
(Above and below windows            240 ft2                      5                                                                    Continue O&M
                                              NF      *                  damage due to accessibility        No      *
     in A(C)-hall addition)
      27 -Electrical Wire                      F                         There is very little potential
                                                                                                            Yes
 Insulation and Stage Lights           4LF                       5           for damage due to                                        Continue O&M
                                              NF      *                                                     No      *
        (Little Theater)                                                        inaccessibility
28 - Tuff Spun Pipe (Under                     p                         There is very little potential
                                                                                                            Yes
  floor air duct in B-hall fan     ~100 LF                       5           for damage due to                                        Continue O&M
                                              NF      *                                                     No      *
          room area)                                                            inaccessibility


Were additional samples of this ACBM collected?                                                              Date of management planner review:
                                                           Yes                     No          *

 Inspector Name                  Bruce Moss/ j ft\                                                           Management Planner Name          C Bruce MosS y-_

 Inspector Signature               >MT
                                    /    ^
                                                                                                             Management Planner Signature         /^~-~Jj/ ^ j
               „.„               Utah/Idaho                                                                                                       Utah/Idaho
 Accreditation** /State                                                                                      Accreditation ft/State
                                 7/29/2012                                                                                                        7/29/2012
 Expiration Date                                                                                             Expiration Date


 1, the LEA's Designated Person, have read and understood the recommendations made above: Q                  J\ <_Ji^ ^ V^^-^-_.              Date:      //;^C_Y/J)
                                                                                                              B                                          /       I'

				
DOCUMENT INFO
Shared By:
Categories:
Tags:
Stats:
views:9
posted:3/4/2012
language:English
pages:12