IMPORTANT by linxiaoqin

VIEWS: 121 PAGES: 394

									                                             NAVFAC
                                          SPECIFICATION

                                           WO #5490419
                                         MET Facility Design

                                         AMENDMENT #0003




               IMPORTANT
This amendment should be acknowledged when
your proposal is submitted. Failure to
acknowledge the amendment may constitute
grounds for rejection of the proposal.

If your proposal has been submitted prior to the
receipt of this amendment, acknowledgement
should be made by telegram, which should state
whether the price contained in your proposal is to
remain unchanged, is to be decreased by an
amount, or is to be increased by an amount. The
acknowledgement must be received prior to
proposal opening time.
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT                                                                  1. CONTRACT ID CODE                PAGE     OF PAGES
                                                                                                                                                        1              1
2. AMENDMENT/MODIFICATION NO.                  3. EFFECTIVE DATE                   4. REQUISITION/PURCHASE REQ. NO.                  5. PROJECT NO. (If applicable)
    0003                                                 7/12/2011
6. ISSUED BY                                     Code      N40085                  7. ADMINISTERED BY (If other than item 6.)                   Code
      CG MCAS Cherry Point
      FACILITIES, ROICC
      B-163, CURTIS ROAD
      PSC BOX 8006
      CHERRY POINT, NC 28533
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)                                        9A. AMENDMENT OF SOLICITATION
                                                                                                                       PROJECT #5490419
                                                                                                                   9B. DATED (SEE ITEM 11) 1/28/2010
      AMENDMENT MUST BE ACKNOWLEDGED WITH YOUR PROPOSAL                                                            10A. MODIFICATION OF CONTRACT/ORDER NO.

                                                                                                                   10B. DATED (SEE ITEM 13)
CODE                                                     FACILITY CODE
                                              11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
      The above numbered solicitation is amended as set forth in item 14. The hour and date specified for receipt of Offers      is extended       is not extended. Offers must
acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods: (a) By completing items 8 and 15,
and returning 1 copy of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or telegram which includes
a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF
OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already
submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the
opening hour and date specified.


12. ACCOUNTING AND APPROPRIATION DATA (if required)




                              13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
                                  IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
      A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14. ARE MADE IN THE
      CONTRACT ORDER NO. IN ITEM 10A.
      B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATION CHANGES (such as changes in paying
      office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103 (b).
      C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

      D. OTHER: (specify type of modification and authority)


E. IMPORTANT: Contractor is not   is required to sign this document and return original to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

PROJECT #5490419, MET FACILITY DESIGN , MARINE CORPS AIR STATION, CHERRY POINT, NORTH CAROLINA

This modification is issued to make the following changes to the solicitation:

1. Revised scope of work and drawings are attached.

2. Revised bid structure is as follows:
Bid Item 001 includes the entire work complete in accordance with the drawings and specifications, but not including work described or
specified to be provided under any other bid item.

Bid Item 002 includes the addition of the following: exterior wall sheathing to fully enclose structure as depicted; building insulation (wall
and roof); exterior doors as depicted; exterior bollards; ventilation system as depicted on Sheet M-1, included electrical as depicted on
sheet E-2, exterior lights, energy, lights and associated wiring as depicted on E-2; and exterior sidewalks.

3. Best and final offers are due no later than 1400 on 26 July 2011.


15A. NAME AND TITLE OF SIGNER (Type or print)                                           16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

15B. CONTRACTOR/OFFEROR (Same as Item 8)                     15C. DATE SIGNED           16B. UNITED STATES OF AMERICA                                  16C. DATE SIGNED
                                                                                        BY
     (Signature of person authorized to sign)                                                       (Signature of Contracting Officer)
NSN 7540-01-152-8070                                         30-105                     STANDARD FORM 30 (REV.1-83)                                              0224-3(10-90)
PREVIOUS EDITION UNUSABLE                                                               Prescribed by GSA
Design MET Facility                                                         5490419


                               PROJECT TABLE OF CONTENTS

 DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS

 00 01 15               LIST OF DRAWINGS

 DIVISION 01 - GENERAL REQUIREMENTS

 01   11   00           SUMMARY OF WORK
 01   12   00           CUTTING AND PATCHING
 01   13   00           TRAFFIC SAFETY
 01   14   00           WORK RESTRICTIONS
 01   20   00.00   20   PRICE AND PAYMENT PROCEDURES
 01   30   00           ADMINISTRATIVE REQUIREMENTS
 01   31   50           TRANSFER AND ACCEPTANCE OF MILITARY REAL PROPERTY
 01   32   16           CONSTRUCTION PROGRESS DOCUMENTATION
 01   33   00           SUBMITTAL PROCEDURES
 01   35   29           SAFETY AND OCCUPATIONAL HEALTH REQUIREMENTS
 01   42   00           SOURCES FOR REFERENCE PUBLICATIONS
 01   45   10           QUALITY CONTROL
 01   50   00.00   20   TEMPORARY FACILITIES AND CONTROLS
 01   57   19.00   20   TEMPORARY ENVIRONMENTAL CONTROLS
 01   77   00.00   20   CLOSEOUT PROCEDURES
 01   78   23           OPERATION AND MAINTENANCE DATA
 01   80   00           REPORTS

 DIVISION 02 - EXISTING CONDITIONS

 02 41 00               DEMOLITION
 02 82 30               RE-ESTABLISHING VEGETATION

 DIVISION 03 - CONCRETE

 03 30 00               CAST-IN-PLACE CONCRETE

 DIVISION 05 - METALS

 05 40 00               COLD-FORMED METAL FRAMING

 DIVISION 07 - THERMAL AND MOISTURE PROTECTION

 07 21 16               MINERAL FIBER BLANKET INSULATION
 07 92 00               JOINT SEALANTS

 DIVISION 08 - OPENINGS

 08 11 13               STEEL DOORS AND FRAMES
 08 33 23               OVERHEAD COILING DOORS
 08 71 00               DOOR HARDWARE

 DIVISION 09 - FINISHES

 09 90 00               PAINTS AND COATINGS

 DIVISION 10 - SPECIALTIES

 10 44 16               FIRE EXTINGUISHERS

 DIVISION 13 - SPECIAL CONSTRUCTION


                           PROJECT TABLE OF CONTENTS Page 1
Design MET Facility                                                      5490419



 13 12 50             BLEACHERS
 13 34 19             METAL BUILDING SYSTEMS

 DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING

 23 03 00.00 20       BASIC MECHANICAL MATERIALS AND METHODS

 DIVISION 26 - ELECTRICAL

 26   00   00.00 20   BASIC ELECTRICAL MATERIALS AND METHODS
 26   20   00         INTERIOR DISTRIBUTION SYSTEM
 26   51   00         INTERIOR LIGHTING
 26   56   00         EXTERIOR LIGHTING

 DIVISION 27 - COMMUNICATIONS

 27 10 00             STRUCTURED TELECOMMUNICATIONS CABLING AND PATHWAY SYSTEM

 DIVISION 31 - EARTHWORK

 31 11 00             CLEARING AND GRUBBING
 31 23 00.00 20       EXCAVATION AND FILL

 DIVISION 33 - UTILITIES

 33 82 00             TELECOMMUNICATIONS OUTSIDE PLANT (OSP)

 -- End of Project Table of Contents --




                         PROJECT TABLE OF CONTENTS Page 2
Design MET Facility                                                           5490419



                                   DOCUMENT 00 01 15

                                      LIST OF DRAWINGS
                                            04/06

PART 1     GENERAL

1.1     SUMMARY

 This document lists the drawings for the project pursuant to contract
 clause "DFARS 252.236-7001, Contract Drawings, Maps and Specifications."

1.2     DFARS 252.236.7001,CONTRACT DRAWINGS,MAPS AND SPECIFICATIONS (AUG 2000)

 (a) The Government will provide to the Contractor, without charge, one set
 of contract drawings and specifications, except publications incorporated
 into the technical provisions by reference, in electronic or paper media as
 chosen by the Contracting Officer.

 (b)     The Contractor shall-

         (1)    Check all drawings furnished immediately upon receipt;

         (2) Compare all drawings and verify the figures before laying out the
             work;

         (3)    Promptly notify the Contracting Officer of any discrepancies;

         (4)    Be responsible for any errors that might have been avoided by
               complying with this paragraph (b); and

         (5)    Reproduce and print contract drawings and specifications as
               needed.

 (c)     In general-

         (1)    Large-scale drawings shall govern small-scale drawings; and

         (2)    The Contractor shall follow figures marked on drawings in
               preference to scale measurements.

 (d) Omissions from the drawings or specifications or the misdescription of
 details of work that are manifestly necessary to carry out the intent of
 the drawings and specifications, or that are customarily performed, shall
 not relieve the Contractor from performing such omitted or misdescribed
 details of the work. The Contractor shall perform such details as if fully
 and correctly set forth and described in the drawings and specifications.

 The work shall conform to the specifications and the contract drawings.

 Contract drawings are as follows:

      DRAWING    REVISION   NAVFAC     SHEET   TITLE
        NO.         NO.     DWG NO.

      01 of 16      N/A     12562172    G-1    Title Sheet
      02 of 16      N/A     12562173    C-1    Site Demolition Plan
      03 of 16      N/A     12562174    C-2    Site Layout, Grading &


                               DOCUMENT 00 01 15       Page 1
Design MET Facility                                                               5490419



      DRAWING        REVISION   NAVFAC     SHEET   TITLE
        NO.             NO.     DWG NO.
                                                    Erosion Control Plan
      04   of   16      N/A     12562175    C-3    Details - Tent Disassembly
      05   of   16      N/A     12562176    C-4    Details
      06   of   16      N/A     12562177    A-1    Floor Plan & Roof Plan
      07   of   16      N/A     12562178    A-2    Exterior Elevations & Sections
      08   of   16      N/A     12562179    A-3    Wall Sections
      09   of   16      N/A     12562180    A-4    Enlarged Floor Plan, Interior
                                                     Elevations & Details
      10   of   16      N/A     12562181    S-1    General Notes
      11   of   16      N/A     12562182    S-2    Foundation Plan
      12   of   16      N/A     12562183    S-3    Details
      13   of   16      N/A     12562184    M-1    Mechanical Plan, Schedules, Notes &
                                                    Details
      14 of 16          N/A     12562185    E-1    Site Electrical Plan
      15 of 16          N/A     12562186    E-2    Electrical Power and Lighting Plan
      16 of 16          N/A     12562187    E-3    Electrical Details and Schedules


1.3     SUPPLEMENTARY DRAWINGS

 These supplementary drawings may not be a part of the contract but are
 included with the drawings for information.

1.3.1       Boring Logs

 The Government does not guarantee that borings indicate actual conditions,
 except for the exact locations and the time that they were made.

</SPT =1.3.3><SPT =1.3.4>1.3.4             Subsurface Data

 The soils report is included as part of the solicitation.

   -- End of Document --




                                  DOCUMENT 00 01 15        Page 2
Design MET Facility                                                        5490419




                                    SECTION 01 11 00

                                    SUMMARY OF WORK

                                         09/08


PART 1        GENERAL

1.1     WORK COVERED BY CONTRACT DOCUMENTS

1.1.1     Project Description

 The work includes one pre-engineered metal buildings, site improvements,
 and incidental related work.

1.1.2     Location

 The work shall be located at the MCAS Cherry Point (MCASCP), North Carolina,
  approximately as shown. The exact location will be indicated by the
 Contracting Officer.

1.2     EXISTING WORK

 In addition to "FAR 52.236-9, Protection of Existing Vegetation,
 Structures, Equipment, Utilities, and Improvements":

         a.    Remove or alter existing work in such a manner as to prevent
               injury or damage to any portions of the existing work which remain.

         b.    Repair or replace portions of existing work which have been
               altered during construction operations to match existing or
               adjoining work, as approved by the Contracting Officer. At the
               completion of operations, existing work shall be in a condition
               equal to or better than that which existed before new work started.

1.3     LOCATION OF UNDERGROUND FACILITIES

 The Contractor will be responsible for obtaining the services of a
 professional utility locator to scan the construction site with
 electromagnetic or sonic equipment, and mark the surface of the ground
 where existing underground utilities are discovered. Verify the elevations
 of existing piping, utilities, and any type of underground obstruction not
 indicated or specified to be removed but indicated or discovered during
 scanning in locations to be traversed by piping, ducts, and other work to
 be installed. Verify elevations before installing new work closer than
 nearest manhole or other structure at which an adjustment in grade can be
 made.

1.3.1     Notification Prior to Excavation

 Notify the Contracting Officer 48 hours prior to starting excavation work
 in order to permit making arrangements with public works personnel to scan
 the area for unmarked utilities. Obtain station digging permits prior to
 starting excavation work.




                                SECTION 01 11 00   Page 1
Design MET Facility                                                  5490419


1.4   MERCHANTABLE TIMBER REMOVAL


 The Government will have the option to remove merchantable timber from the
 construction site prior to the Contractor starting his clearing
 operations. The Contractor shall provide the Government a minimum 3 weeks
 written notice prior to the start of his clearing operations. The
 Government will take approximately 2 weeks to remove the merchantable
 timer, and will leave approximately 2 feet of stump for Contractor
 removal. Stumps, limbs, and smaller trees shall be left on site for the
 Contractor to dispose of. Merchantable timber shall remain the property of
 the Government.

PART 2     PRODUCTS

 Not used.

PART 3     EXECUTION

 Not used.

         -- End of Section --




                                SECTION 01 11 00   Page 2
Design MET Facility                                                    5490419



                                    SECTION 01 12 00

                                  CUTTING AND PATCHING

                                         01/07



PART 1     GENERAL

1.1   CUTTING

 Shall be done by sawing along straight lines. The amount cut out shall be
 the minimum necessary to accommodate the new work. No flame cutting will
 be permitted without written permission of the Officer in Charge of
 Construction.

1.2   HOLES

 Shall be rotary drilled. The size shall be the minimum necessary to
 accommodate the new work.

1.3   PATCHING

 Shall be done with materials which match the existing in color, quality and
 surface texture when finished.

PART 2     PRODUCTS

 Not used.

PART 3     EXECUTION

 Not used.

         -- End of Section --




                                SECTION 01 12 00   Page 1
Design MET Facility                                                        5490419



                                    SECTION 01 13 00

                                     TRAFFIC SAFETY

                                         01/07



PART 1     GENERAL

1.1     REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to in the text by basic
 designation only.

            U.S. FEDERAL HIGHWAY ADMINISTRATION (FHWA)

 FHWA SA-89-006                        (2009) Manual on Uniform Traffic Control
                                       Devices for Streets and Highways

1.2     MAINTENANCE FOR TRAFFIC

 The existing road or an approved bypass shall be kept open to all traffic
 while undergoing improvements . The Contractor shall furnish, erect ,light,
  and maintain barricades, warning and informational signs, delineators, and
 flagmen in accordance FHWA SA-89-006.

1.2.1     TEMPORARY APPROACHES

 Temporary approaches or crossings and intersections with trails, roads,
 streets, residences, and parking lots shall be maintained in a safely
 passable condition.

1.3     PUBLIC CONVENIENCE AND SAFETY

 The Contractor shall at all times so conduct his work as to assure the
 safety and convenience of the users and of those along the streets and
 roads and to assure the protection of persons and property.

1.4     WARNING SIGNS

 Warning signs shall be erected in advance of any place on the project where
 operations may interfere with the use of the road by traffic, and at all
 intermediate points where the new work crosses or coincides with an exist
 ing road.

1.4.1     INFORMATIONAL SIGNS

 The Contractor shall furnish, erect, maintain, and remove, when directed,
 any informational identification indicated.

1.4.2     CONSTRUCTION WARNING SIGNS

 Construction warning signs shall be displayed only when a crew is actually
 working at the site. "Men Working" or "Flagman" signs shall be removed
 from view of traffic when not needed.



                                SECTION 01 13 00   Page 1
Design MET Facility                                                   5490419


1.5   TRAFFIC REROUTING PLANS

 Traffic rerouting plans shall be submitted for approval seven calendar days
 before the anticipated rerouting, and shall not be implemented before
 approval. The Contractor shall erect and remove all detour signs.

1.6   PAINTING -- TEMPORARY AND PERMANENT

 Painting on each street or roadway shall begin within 48 hours after
 pavement is placed and shall be placed continuously during daylight hours,
 except during rain, until completion. Painting interrupted for rain shall
 restart during daylight as soon as pavement is dry. Provide temporary
 painting on all roadways and stress, except where permanent markings can be
 placed within 48 hours after pavement is placed.

PART 2     PRODUCTS

2.1   Traffic Control Devices

 FHWA SA-89-006.

PART 3     EXECUTION

 Not Used.

         -- End of Section --




                                SECTION 01 13 00   Page 2
Design MET Facility                                                        5490419




                                    SECTION 01 14 00

                                   WORK RESTRICTIONS

                                         01/07



PART 1        GENERAL

1.1     SPECIAL SCHEDULING REQUIREMENTS

         a.    Permission to interrrupt any Station roads, railroads, and/or
               utility service shall be requested in writing a minimum of 15
               calendar days prior to the desired date of interruption.

1.2     CONTRACTOR ACCESS AND USE OF PREMISES

1.2.1     Station Regulations

 Ensure that Contractor personnel employed on the Station become familiar
 with and obey Station regulations. Keep within the limits of the work and
 avenues of ingress and egress as directed. Do not enter restricted areas
 unless required to do so and until cleared for such entry. Wear hard hats
 in designated areas. Do not enter any restricted aras unless required to
 do so and until cleared for such entry. The Contractor's equipment shall
 be conspicuously marked for identification.

1.2.2     Working Hours

 Regular working hours shall consist of an eight and one-half hour period
 established by the Contracting Officer, Monday through Friday, excluding
 Government holidays.

1.2.3     Work Outside Regular Hours

 Work outside regular working hours requires Contracting Officer approval.
 Provide written request at least 15 calendar days prior to such work to
 allow arrangements to be made by the Government for inspecting the work in
 progress. During periods of darkness, the different parts of the work
 shall be lighted in a manner approved by the Contracting Officer.

1.2.4     Occupied and Existing Buildings

 The Contractor shall be working around existing buildings which are
 occupied. Do not enter the buildings without prior approval of the
 Contracting Officer.

 The existing buildings and their contents shall be kept secure at all
 times. Provide temporary closures as required to maintain security as
 directed by the Contracting Officer.

 Provide dust covers or protective enclosures to protect existing work that
 remains and Government material located in the work area during the
 construction period.

 The Government will remove and relocate other Government property in the


                                SECTION 01 14 00   Page 1
Design MET Facility                                                       5490419


 areas of the buildings scheduled to receive work.

1.2.5     Utility Cutovers and Interruptions

        a.   Make utility cutovers and interruptions after normal working hours
             or on Saturdays, Sundays, and Government holidays. Conform to
             procedures required in the paragraph "Work Outside Regular Hours."

        b.   Ensure that new utility lines are complete, except for the
             connection, before interrupting existing service.

        c.   Interruption to water, sanitary sewer, storm sewer, telephone
             service, electric service, air conditioning, heating, fire alarm,
             and compressed air, shall be considered utility cutovers pursuant
             to the paragraph entitled "Work Outside Regular Hours." Such
             interruption shall be further limited to 4 hours. This time limit
             includes time for deactivation and reactivation.

        d.   Operation of Station Utilities: The Contractor shall not operate
             nor disturb the setting of control devices in the station
             utilities system, including water, sewer, electrical, and steam
             services. The Government will operate the control devices as
             required for normal conduct of the work. The Contractor shall
             notify the Contracting Officer giving reasonable advance notice
             when such operation is required.

1.3     SECURITY REQUIREMENTS

1.3.1     Station Regulations

 No employee or representative of the contractor will be admitted to the
 work site without an Identification Badge or is specifically authorized
 admittance to the work site by the OIC, NAVFAC Contracts.

1.3.2     Contractor Access to MCAS Cherry Point and Outlying Areas

DOCUMENTATION REQUIRED TO GRANT ACCESS TO COMMERCIAL AND CONTRACT EMPLOYEES
(THIS DOCUMENT IS AN AID IN MEETING AIR STATION ORDER 5500.14B REQUIREMENTS
AND IS NOT A SUBSTITUTE FOR THE ORDER)

1.     The initial approved contract letter from the authorized military
contracting agency. The letter must contain the following before being sent
to Pass & ID:

A) The employer's company/business name
B) Contract number and work location
C) Contract expiration/termination date
D) Flightline access: Vehicle gate access (must be gate specific) and/or
   turnstile access (Normal contractor access is turnstiles only.)
E) FRC-East access (if required)

2. Employers must provide a letter (on company letterhead) to the Pass & ID
office. This may be by e-mailed to chpt_pass-id_omb@usmc.mil, or fax
(252-466-2626) or it may be hand carried, listing all employees (to include
date and place of birth) who will be requiring access to the installation.
Contractors hired for more than 30 days will be issued a contractor's badge
after the conditions outlined in this document are met. The badge must be
carried or readily accessible at all times while on Station. All badges will
be issued for a period NOT TO EXCEED ONE YEAR regardless of the length of the


                                SECTION 01 14 00   Page 2
Design MET Facility                                                     5490419


contract. Upon the expiration of the badge, the company/employee will
provide a new 50 state/national criminal record check prior to being
re-badged.

3. Any access from 1 day to less than 30 days, employers will provide the
same documentation as stated above. In place of a badge, a copy of this
letter with the worker's name highlighted, stamped with the "Pass & ID"
stamp, "Criminal Records Check (CRC) Sighted", and we will also annotate
below the stamps the following statement: "Valid until (expiration date)
then date and initial it." This document will be issued to each worker and
IS their authorization to be aboard the installation. This letter must be
carried on their person or readily accessible at all times while on Station.

4. All employers/employees must provide a CRC from any internet
investigative service or any other investigative service company that
provides a 50 state/national criminal records check and a check of the Sexual
Offenders List.   (Local county/state checks are not authorized and will not
be accepted.) This record check must be a "complete" check covering the
period from at the minimum their 18th birthday to present. The CRC must also
contain a statement that this is a "national records check" or the
terminology the agency uses to indicate such. Please be sure of what you are
requesting. If it is anything less then a national check, it will be
rejected. The CRC can not be more than 30 days old at the time it is
presented to Pass & ID personnel. CRCs may be obtained from, but not limited
to the following sources (*):


     A)   WWW.INTEGRASCAN.COM
     B)   WWW.SENTRYLINK.COM
     C)   WWW.CRIMINALWATCHDOG.COM
     D)   WWW.CASTLEBRANCH.COM
     E)   WWW.PEOPLESCANNER.COM
     F)   WWW.KROLLBACKGROUNDSCREENING.COM
     G)   WWW.BACKGROUNDCHECKS.COM
     H)   WWW.INSTANTPEOPLECHECK.COM
     I)   WWW.AMERICANBACKGROUND.COM
     J)   WWW.LEXISNEXIS.COM

Cost of a background check can vary anywhere from $19 to $60 based on the
type or amount of services requested. Minimum information required for a
background check is the individual's Last Name, First Name, Middle name
(optional) and Date of Birth.    A social security number verification is also
available at an additional cost.

5. In accordance with ASO 5500.14B (not an all inclusive list), access will
be denied if the individual:

A)    Is on the National Terrorist Watch List.
B)    Is illegally present in the United States.
C)    Is currently debarred or banned from military installations.
D)    Is a registered sex offender or been convicted of any child abuse or
      related offense(s).
E)    Is a convicted felon within the past 5 years.
F)    Convicted of any drug offense within the past 5 years.
G)    Is subject to an outstanding warrant or is currently pending trial.
H)    Has knowingly submitted a false/fraudulent employment questionnaire.
I)    Any reason the Installation Commander deems reasonable for good order &
      discipline.
J)    Individuals convicted of a DUI/DWI within the past year will be allowed


                              SECTION 01 14 00   Page 3
Design MET Facility                                                    5490419


     aboard but not be permitted to drive.

6.  Picture ID from a state or federal agency (i.e., valid driver's license
    or state identification card).
7. Social Security Card or any official document listing the SSN (letter
    from Social Security Administration listing the SSN, W-2 (tax form),
    DD-214, pay stub listing complete SSN).   An additional source may be
    through the internet with E-Verify
8. Birth certificates and passports are used when necessary to verify
    citizenship and are never used as a means to verify social security
    numbers.
9. If the employee is not a U.S. Citizen, PROOF OF IMMIGRATION STATUS must
    be provided and carried on their person or be readily accessible at all
    times while on station. Proof must also be provided if an individual is
    a naturalized U.S. citizen.
10. Due to recent changes with Privacy laws, please do not include social
     security numbers or DOBs in the company letters being faxed or emailed
     to this office. Additionally, all criminal record checks must be hand
     carried by the individual worker or brought in by the supervisor.
11. As of 19 Dec 07 security clearances are no longer valid as a means for
     requesting access to the installation. All personnel hired as
     commercial or contractor employees to work for a company aboard the
     installation will be required to provide a 50 state/national criminal
     check.
12. The changes in this document are effective as of 1 June 2010.

Note: Until further notice, ID cards and vehicle passes issued to
contractors at Camp Lejeune and New River are currently not valid at Cherry
Point without a 50 state/national CRC in their possession at the time they
are requesting access at MCAS Cherry Point.

(*) The United States Government and the United States Marine Corps does not
endorse nor are they affiliated with any of the screening services provided
above. We must be able to verify/validate the information contained in the
CRC via telephone. If we are unable to validate the CRC the clearance
information will not be accepted.

(**) Due to recent developments concerning the screening services of
Criminal CBS and Net Detective, they are no longer authorized as a means for
entry at MCAS Cherry Point.PART 2   PRODUCTS

 Not used.

PART 3     EXECUTION

 Not used.



         -- End of Section --




                                SECTION 01 14 00   Page 4
Design MET Facility                                                        5490419



                                 SECTION 01 20 00.00 20

                              PRICE AND PAYMENT PROCEDURES
                                          07/06

PART 1     GENERAL

1.1     REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to within the text by the
 basic designation only.

             U.S. ARMY CORPS OF ENGINEERS (USACE)

 EP-1110-1-8                           (2003) Construction Equipment Ownership
                                       and Operating Expense Schedule, Vol 1-12

1.2     SUBMITTALS

 Government approval is required for submittals with a "G" designation;
 submittals not having a "G" designation are for information only.    The
 following shall be submitted in accordance with Section 01 33 00 SUBMITTAL
 PROCEDURES:

         SD-01 Preconstruction Submittals

             Schedule of prices; G

1.3     SCHEDULE OF PRICES

1.3.1     Data Required

 Within 15 calendar days of notice of award, prepare and deliver to the
 Contracting Officer a schedule of prices (construction contract) on the
 forms furnished by the Government. Provide a detailed breakdown of the
 contract price, giving quantities for each of the various kinds of work,
 unit prices, and extended prices therefore.

1.3.2     Schedule Instructions

 Payments will not be made until the Schedule of Prices has been submitted
 to and accepted by the Contracting Officer. Identify the cost for site
 work, and include incidental work to the 5 foot line. Identify costs for
 the building(s), and include work out to the 5 foot line. Work out to the
 5 foot line shall include construction encompassed within a theoretical line
  5 feet from the face of exterior walls and shall include attendant
 construction, such as cooling towers, placed beyond the 5 foot line.

1.4     CONTRACT MODIFICATIONS

 In conjunction with the Contract Clause "DFARS 252.236-7000, Modification
 Proposals-Price Breakdown," and where actual ownership and operating costs
 of construction equipment cannot be determined from Contractor accounting
 records, equipment use rates shall be based upon the applicable provisions
 of the EP-1110-1-8.




                             SECTION 01 20 00.00 20   Page 1
Design MET Facility                                                      5490419


1.5     CONTRACTOR'S INVOICE

1.5.1     Content of Invoice

 Requests for payment in accordance with the terms of the contract shall
 consist of the following:

        a.   Contractor's Invoice on NAVFAC Form 7300/30, which shall show, in
             summary form, the basis for arriving at the amount of the invoice.

        b.   Contractor's Monthly Estimate for Voucher (LANTNAVFACENGCOM Form
             4-4330/110 (New 7/84)), with subcontractor and supplier payment
             certification.

        c.   Affidavit to accompany invoice (LANTDIV NORVA Form 4-4235/4 (Rev.
             5/81)).

        d.   Updated copy of submittal register.

        e.   Updated copy of progress schedule. Furnish as specified in "FAR
             52.236-15, Schedules for Construction Contracts."

1.5.2     Monthly Invoices and Supporting Forms

 Forms will be furnished by the Contracting Officer. Requests for payment
 shall be processed in accordance with "FAR 52.232-5, Payments Under
 Fixed-Price Construction Contracts." Monthly invoices and supporting forms
 for work performed through the anniversary award date of the contract shall
 be submitted to the Contracting Officer between the 1st - 7th if contract's
 last digit is 0, 1, 2; 8th - 14th if contract's last digit is 3 or 4; 15th
 - 21st if contract's last digit is 5, 6, or 7; 22nd and last if the
 contract's last digit is 8th or 9th day of the month. Payments will be
 using Wide Area Workflow (WAWF). Submit the following documents with
 invoice WAWF:

        a.   Contractor's invoice

        b.   Contractor's monthly estimate for voucher

        c.   Affidavit

        d.   Updated submittal register

        e.   Progress schedule

        f.   Certificate of Progess Payments

        g.   Contractor Safety Self Evaluation Checklist

1.6     PAYMENTS TO THE CONTRACTOR

 Payments will be made on submission of itemized requests by the Contractor
 which comply with the requirements of this section, and will be subject to
 reduction for overpayments or increase for underpayments made on previous
 payments to the Contractor.

1.6.1     Obligation of Government Payments

 The obligation of the Government to make payments required under the


                          SECTION 01 20 00.00 20   Page 2
Design MET Facility                                                        5490419


 provisions of this contract will, at the discretion of the Contracting
 Officer, be subject to reductions and/or suspensions permitted under the
 FAR and agency regulations including the following in accordance with "FAR
 32.503-6:

         a.    Reasonable deductions due to defects in material or workmanship;

         b.    Claims which the Government may have against the Contractor under
               or in connection with this contract;

         c.    Unless otherwise adjusted, repayment to the Government upon demand
               for overpayments made to the Contractor; and

         d.    Failure to provide up to date record drawings not current as
               stated in Contract Clause "FAC 5252.236-9310, Record Drawings."

PART 2        PRODUCTS

 Not used.

PART 3        EXECUTION

 Not used.
      -- End of Section --




                            SECTION 01 20 00.00 20   Page 3
Design MET Facility                                                         5490419




                                    SECTION 01 30 00
                              ADMINISTRATIVE REQUIREMENTS
                                          04/06


PART 1        GENERAL

1.1     SUBMITTALS

 Government approval is required for submittals with a "G" designation;
 submittals not having a "G" designation are for information only or as
 otherwise designated. When used, a designation following the "G"
 designation identifies the office that will review the submittal for the
 Government. The following shall be submitted per Section 01 33 00
 SUBMITTAL PROCEDURES:

         SD-01 Preconstruction Submittals

               List of contact personnel

1.2     MINIMUM INSURANCE REQUIREMENTS

 Procure and maintain during the entire period of performance under this
 contract the following minimum insurance coverage:

         a.    Comprehensive general liability:   $500,000 per occurrence

         b.    Automobile liability: $200,000 per person, $500,000 per
               occurrence for bodily injury, $20,000 per occurrence for property
               damage

         c.    Workmen's compensation as required by Federal and State workers'
               compensation and occupational disease laws.

         d.    Employer's liability coverage of $100,000, except in States where
               workers compensation may not be written by private carriers,

         e.    Others as required by North Carolina State law.

         f.    The Cancellation clause on the insurance certificate should read:

               "Cancellation or any material change in the policies adversely
               affecting the interest of the Government in such insurance shall
               not be effective for such period as may be prescribed by the laws
               of the State in which this contract is to be performed and in no
               event less than thirty (30) days after written notice thereof to
               the Contracting Officer."

1.3     CONTRACTOR PERSONNEL REQUIREMENTS

1.3.1     Subcontractors and Personnel

 Furnish a list of contact personnel of the Contractor and subcontractors
 including addresses and telephone numbers for use in the event of an
 emergency. As changes occur and additional information becomes available,
 correct and change the information contained in previous lists.


                               SECTION 01 30 00   Page 1
Design MET Facility                                                      5490419



1.3.2     Identification Badges

 Identification badges will be furnished without charge. Application for and
 use of badges will be as directed. Immediately report instances of lost or
 stolen badges to the Contracting Officer.

 Commercial and contract employees will be issued a contractor's badge good
 for one year. Commercial and contract employees are required to resubmit a
 complete 50 state criminal records check in order to renew their
 contractor's badge.

 If an employee is terminated prior to end of the contract, the contractor
 shall return the base identification card to the Contracting Officer. This
 requirement also applies to all sub-contract employees.

 In no event will a contractor employee be permitted access to the US Marine
 Corps Air Station for the purpose of on-site performance without the
 documentation.

1.3.3     Subcontractor Special Requirements

1.3.3.1     Asbestos Containing Material

 All contract requirements assigned to the Private Qualified Person (PQP)
 shall be accomplished directly by a first tier subcontractor.

1.3.4     Contractor Personnel Requirements

 Follow Security requirements addressed in 01 14 00 WORK RESTRICTIONS.

1.4     SUPERVISION

 Have at least one qualified supervisor capable of reading, writing, and
 conversing fluently in the English language on the job site during working
 hours. In addition, if a Quality Control (QC) representative is required
 on the contract, then that individual shall also have fluent English
 communication skills.

1.5     PRECONSTRUCTION CONFERENCE

 After award of the contract but prior to commencement of any work at the
 site, meet with the Contracting Officer to discuss and develop a mutual
 understanding relative to the administration of the value engineering and
 safety program, preparation of the schedule prices, shop drawings, and
 other submittals, scheduling programming, and prosecution of the work.
 Major subcontractors who will engage in the work shall also attend.

1.6     LEVEL "C" PARTNERING

 To most effectively accomplish the contract, the Government requires the
 formation of a cohesive partnership with the contractor and its
 subcontractors. The partnering relationship is based upon trust,
 dedication to common goals, an understanding of each other's expectations
 and values, and a commitment to success. The goals of the partnering
 process are improved communication, efficiency and cost effectiveness,
 increased opportunity for innovation, and the continuous improvement of
 product quality. The partnership will strive to draw in the strength of
 each organization in an effort to achieve a quality project done right the


                               SECTION 01 30 00   Page 2
Design MET Facility                                                   5490419


 first time, within budget, on schedule, and without any safety mishaps,
 thereby providing the opportunity for the contractor to make a reasonable
 profit. This level of partnering is an introduction to partnering concepts
 and benefits and should become a part of the preconstruction conference.
 The senior ROICC and contract persons present will jointly host the initial
 session. The partners will determine the frequency of the follow-on
 sessions. Partnering sessions should be held at or near the location of
 the ROICC office.

1.7   ELECTRONIC MAIL (E-MAIL) ADDRESS

 The Contractor shall establish and maintain electronic mail (e-mail)
 capability along with the capability to open various electronic attachments
 in Microsoft, Adobe Acrobat, and other similar formats. Within 10 days
 after contractor award, the Contractor shall provide the Contracting
 Officer a single (only one) e-mail address for electronic communications
 from the Contracting Officer related to this contract including, but not
 limited to contract documents, invoice information, request for proposals,
 and other correspondence. The Contracting Officer may also use e-mail to
 notify the Contractor of base access conditions when emergency conditions
 warrant, such as hurricanes, terrorist threats, etc. Multiple e-mail
 addresses will not be allowed.

 It is the Contractor's responsibility to make timely distribution of all
 Contracting Officer initiated e-mail with its own organization including
 the field office(s). The Contractor shall promptly notify the Contracting
 Officer, in writing, of any changes to this e-mail address.

PART 2     PRODUCTS

 Not used.


PART 3     EXECUTION

 Not used.


         -- End of Section --




                                SECTION 01 30 00   Page 3
Design MET Facility                                                      5490419



                                     SECTION 01 31 50

                 TRANSFER AND ACCEPTANCE OF MILITARY REAL PROPERTY

                                          01/07


PART 1     GENERAL

1.1   SUBMITTALS

 The following shall be submitted in accordance with Section 01 33 00
 SUBMITTAL PROCEDURES:

         SD-11 Closeout Submittals

             Interim DD-1354, Transfer & Acceptance of Military Real Property

1.2   Interim DD-1354, Transfer & Acceptance of Military Real Property

 Submit Interim DD-1354 thirty (30) days prior to beneficial occupancy date
 (draft copy attached).

PART 2     PRODUCTS

 Not Used.

PART 3     EXECUTION

 Not Used.

         -- End of Section --




                                SECTION 01 31 50   Page 1
Design MET Facility                                                           5490419




                                    SECTION 01 32 16

                          CONSTRUCTION PROGRESS DOCUMENTATION

                                            01/07



PART 1        GENERAL

1.1     SUBMITTALS

 Submit the following in accordance with Section 01 33 00, "Submittal
 Procedures."

         SD-01 Preconstruction Submittals

               Construction schedule

               Equipment delivery schedule

1.2     CONSTRUCTION SCHEDULE

 Within 21 days after receipt of the Notice of Award, prepare and submit to
 the Contracting Officer for approval a Critical Path Method (CPM), Network
 Schedule in accordance with the terms in Contract Clause "FAR 52.236-15,
 Schedules for Construction Contracts," except as modified in this
 contract. Primavera Suretrak 3.0 will be utilized to produce and update
 all progress schedules.

1.3     EQUIPMENT DELIVERY SCHEDULE

1.3.1     Initial Schedule

 Within 30 calendar days after approval of the proposed construction
 schedule, submit for Contracting Officer approval a schedule showing
 procurement plans for materials, plant, and equipment. Submit in the
 format and content as prescribed by the Contracting Officer, and include as
 a minimum the following information:

         a.    Description.

         b.    Date of the purchase order.

         c.    Promised shipping date.

         d.    Name of the manufacturer or supplier.

         e.    Date delivery is expected.

         f.    Date the material or equipment is required, according to the
               current construction schedule.

1.4     NETWORK ANALYSIS SYSTEM (NAS)

 The Contractor shall use the critical path method (CPM) to schedule and
 control construction activities. The Network shall have a minimum of 25


                                SECTION 01 32 16    Page 1
Design MET Facility                                                         5490419


 activities and a maximum of 50 activities.        The schedule shall identify as
 a minimum:

         a.    Construction time for all major systems and components;

         b.    Manpower requirements for each activity;

         c.    Major submittals and submittal processing time; and

         d.    Major equipment lead time.

1.4.1     CPM Submittals and Procedures

 Submit all network analysis and updates in hard copy. The network analysis
 system shall be kept current, with changes made to reflect the actual
 progress and status of the construction.

1.5     UPDATED SCHEDULES

 Update the construction schedule and equipment delivery schedule at monthly
 intervals or when schedule has been revised. Reflect any changes occurring
 since the last update. Submit copies of the purchase orders and
 confirmation of the delivery dates as directed.

PART 2        PRODUCTS

 Not used.

PART 3        EXECUTION

 Not used.



         -- End of Section --




                                SECTION 01 32 16   Page 2
Design MET Facility                                                         5490419



                                  SECTION 01 33 00

                                SUBMITTAL PROCEDURES
                                        06/10

PART 1     GENERAL

1.1   DEFINITIONS
1.1.1   Submittal

 Contract Clauses "FAR 52.236-5, Material and Workmanship," paragraph (b)
 and "FAR 52.236-21, Specifications and Drawings for Construction,"
 paragraphs (d), (e), and (f) apply to all "submittals."

1.1.2     Submittal Descriptions (SD)

 Submittals requirements are specified in the technical sections.
 Submittals are identified by SD numbers and titles as follows.

 SD-01 Preconstruction Submittals

         Certificates of insurance.
         Surety bonds.
         List of proposed subcontractors.
         List of proposed products.
         Construction Progress Schedule.
         Submittal register.
         Schedule of prices.
         Health and safety plan.
         Work plan.
         Quality control plan.
         Environmental protection plan.

 SD-02 Shop Drawings

         Drawings, diagrams and schedules specifically prepared to illustrate
         some portion of the work.

         Diagrams and instructions from a manufacturer or fabricator for use in
         producing the product and as aids to the Contractor for integrating the
         product or system into the project.

         Drawings prepared by or for the Contractor to show how multiple systems
         and interdisciplinary work will be coordinated.

 SD-03 Product Data

         Catalog cuts, illustrations, schedules, diagrams, performance charts,
         instructions and brochures illustrating size, physical appearance and
         other characteristics of materials, systems or equipment for some
         portion of the work.

         Samples of warranty language when the contract requires extended
         product warranties.

 SD-04 Samples

         Fabricated or unfabricated physical examples of materials, equipment or


                              SECTION 01 33 00   Page 1
Design MET Facility                                                    5490419


      workmanship that illustrate functional and aesthetic characteristics of
      a material or product and establish standards by which the work can be
      judged.

      Color samples from the manufacturer's standard line (or custom color
      samples if specified) to be used in selecting or approving colors for
      the project.

      Field samples and mock-ups constructed on the project site establish
      standards by which the ensuring work can be judged. Includes
      assemblies or portions of assemblies which are to be incorporated into
      the project and those which will be removed at conclusion of the work.

 SD-05 Design Data

      Design calculations, mix designs, analyses or other data pertaining to
      a part of work.

 SD-06 Test Reports

      Report signed by authorized official of testing laboratory that a
      material, product or system identical to the material, product or
      system to be provided has been tested in accord with specified
      requirements. (Testing must have been within three years of date of
      contract award for the project.)

      Report which includes findings of a test required to be performed by
      the Contractor on an actual portion of the work or prototype prepared
      for the project before shipment to job site.

      Report which includes finding of a test made at the job site or on
      sample taken from the job site, on portion of work during or after
      installation.

      Investigation reports.

      Daily logs and checklists.

      Final acceptance test and operational test procedure.

 SD-07 Certificates

      Statements printed on the manufacturer's letterhead and signed by
      responsible officials of manufacturer of product, system or material
      attesting that product, system or material meets specification
      requirements. Must be dated after award of project contract and
      clearly name the project.

      Document required of Contractor, or of a manufacturer, supplier,
      installer or subcontractor through Contractor, the purpose of which is
      to further quality of orderly progression of a portion of the work by
      documenting procedures, acceptability of methods or personnel
      qualifications.

      Confined space entry permits.

      Text of posted operating instructions.

 SD-08 Manufacturer's Instructions


                           SECTION 01 33 00    Page 2
Design MET Facility                                                      5490419



        Preprinted material describing installation of a product, system or
        material, including special notices and Material Safety Data sheets
        concerning impedances, hazards and safety precautions.

 SD-09 Manufacturer's Field Reports

        Documentation of the testing and verification actions taken by
        manufacturer's representative at the job site, in the vicinity of the
        job site, or on a sample taken from the job site, on a portion of the
        work, during or after installation, to confirm compliance with
        manufacturer's standards or instructions. The documentation must be
        signed by an authorized official of a testing laboratory or agency and
        must state the test results; and indicate whether the material,
        product, or system has passed or failed the test.

        Factory test reports.

 SD-10 Operation and Maintenance Data

        Data that is furnished by the manufacturer, or the system provider, to
        the equipment operating and maintenance personnel. This data is needed
        by operating and maintenance personnel for the safe and efficient
        operation, maintenance and repair of the item.

        This Data is intended to be incorporated in an operations and
        maintenance manual or control system.

 SD-11 Closeout Submittals

        A collection of documents representing materials and systems installed
        or provided to the Government during the course of completing all
        contract requirements. Closeout submittals must include all approved
        material submittals and other requirements that describe the finished
        product provided to the Government. Operational and maintenance
        manuals, if required, are included in these submittals. As-built
        drawings must actually describe any deviations that were approved by
        the Contracting Officer. Refer to the specific closeout procedures
        required by specification section 01 77 00.00 20, "Closeout Procedures".

1.1.3     Approving Authority

 Office or designated person authorized to approve submittal.

1.1.4     Work

 As used in this section, on- and off-site construction required by contract
 documents, including labor necessary to produce submittals, construction,
 materials, products, equipment, and systems incorporated or to be
 incorporated in such construction.

1.2     SUBMITTALS

1.2.1     Submittal information applying to the entire contract

 The Contractor is cautioned that symbols used in the "SUBMITTALS" paragraph
 of each Section may not always be consistent from one Section to another.
 For example, in one Section a "G" symbol may indicate that the submittal
 should go to the Engineer Of Record; whereas in another Section the single


                                SECTION 01 33 00   Page 3
Design MET Facility                                                         5490419


 letter "G" may indicate that the submittal should go directly to the
 Government, with a "GA" or "A" symbol used for submittals intended for the
 Engineer of Record. In the event of any such inconsistency, the provisions
 of the particular Section shall govern submittals required by that Section.

1.2.2   Submittal information applying only to this Section (Section 01 33
00, SUBMITTAL PROCEDURES)

 Government   approval is required for submittals with a "G" designation;
 submittals   not having a "G" designation are for Contractor Quality Control
 review and   certification prior to being sent to the Architect-Engineer of
 Record for   approval.   The following shall be submitted in accordance with
 Section 01   33 00 SUBMITTAL PROCEDURES:

        SD-01 Preconstruction Submittals

            Submittal register; G

1.3     USE OF SUBMITTAL REGISTER

 Submittal register will be delivered to the Contractor. will have the
 following fields completed, to the extent that will be required by the
 Government during subsequent usage.

        Column (c): Lists specification section in which submittal is
            required.

        Column (d): Lists each submittal description (SD No. and type, e.g.
            SD-04 Drawings) required in each specification section.

        Column (e): Lists one principal paragraph in specification section
            where a material or product is specified. This listing is only to
            facilitate locating submitted requirements. Do not consider
            entries in column (e) as limiting project requirements.

        Column (f): Indicate approving authority for each submittal. A "G"
            indicates approval by Contracting Officer; a blank indicates
            approval by QC manager.

 Prepare and maintain submittal register, as the work progresses. Do not
 change data which is output in columns (c), (d), (e), and (f) as delivered
 by Government; retain data which is output in columns (a), (g), (h), and
 (i) as approved.

1.3.1     Submittal Register

 Submit submittal register. Submit with quality control plan and project
 schedule required by Section 01 45 10 QUALITY CONTROL. Verify that all
 submittals required for project are listed and add missing submittals.
 Complete the following on the register:

        Column (a) Activity Number:    Activity number from the project schedule.

        Column (g) Contractor Submit Date: Scheduled date for approving
            authority to receive submittals.

        Column (h) Contractor Approval Date:      Date Contractor needs approval
            of submittal.



                               SECTION 01 33 00   Page 4
Design MET Facility                                                    5490419


        Column (i) Contractor Material: Date that Contractor needs material
            delivered to Contractor control.

1.3.2     Contractor Use of Submittal Register

 Update the following fields in the Government-furnished submittal register
 program. .

        Column (b) Transmittal Number:   Contractor assigned list of
            consecutive numbers.

        Column (j) Action Code (k): Date of action used to record
            Contractor's review when forwarding submittals to QC.

        Column (l) List date of submittal transmission.

        Column (q) List date approval received.

1.3.3     Approving Authority Use of Submittal Register

 Update the following fields in the Government-furnished submittal register
 program. .

        Column (b).

        Column (l) List date of submittal receipt.

        Column (m) through (p).

        Column (q) List date returned to Contractor.

1.3.4     Contractor Action Code and Action Code

 Entries used shall be as follows (others may be prescribed by Transmittal
 Form):

        NR - Not Received

        AN - Approved as noted

        A - Approved

        RR - Disapproved, Revise, and Resubmit

1.3.5     Copies Delivered to the Government

 Deliver one copy of submittal register updated by Contractor to Government
 with each invoice request. Deliver in electronic format, unless a paper
 copy is requested by Contracting Officer.

1.4     PROCEDURES FOR SUBMITTALS

1.4.1     Reviewing, Certifying, Approving Authority

 QC organization shall be responsible for reviewing and certifying that
 submittals are in compliance with contract requirements.   At each
 "Submittal" paragraph in individual specification sections, a notation "G,"
 following a submittal item, indicates Contracting Officer is approving
 authority for that submittal item. a blank indicates the


                             SECTION 01 33 00    Page 5
Design MET Facility                                                      5490419


 Architect-Engineer of Record is the approving authority.

1.4.2     Constraints

        a.   Submittals listed or specified in this contract shall conform to
             provisions of this section, unless explicitly stated otherwise.

        b.   Submittals shall be complete for each definable feature of work;
             components of definable feature interrelated as a system shall be
             submitted at same time.

        c.   When acceptability of a submittal is dependent on conditions,
             items, or materials included in separate subsequent submittals,
             submittal will be returned without review.

        d.   Approval of a separate material, product, or component does not
             imply approval of assembly in which item functions.

1.4.3     Scheduling

        a.   Coordinate scheduling, sequencing, preparing and processing of
             submittals with performance of work so that work will not be
             delayed by submittal processing. Allow for potential requirements
             to resubmit.

        b.   Except as specified otherwise, allow review period, beginning with
             receipt by approving authority, that includes at least 15 working
             days for submittals for QC Manager approval and 20 working days
             for submittals for Contracting Officer approval. Period of review
             for submittals with Contracting Officer approval begins when
             Government receives submittal from QC organization. Period of
             review for each resubmittal is the same as for initial submittal.

        c.   For submittals requiring review by fire protection engineer, allow
             review period, beginning when Government receives submittal from
             QC organization, of 30 working days for return of submittal to the
             Contractor. Period of review for each resubmittal is the same as
             for initial submittal.

1.4.4     Variations

 Variations from contract requirements require Government approval pursuant
 to contract Clause entitled "FAR 52.236-21, Specifications and Drawings for
 Construction" and will be considered where advantageous to Government.

1.4.4.1      Considering Variations

 Discussion with Contracting Officer prior to submission, will help ensure
 functional and quality requirements are met and minimize rejections and
 resubmittals. When contemplating a variation which results in lower cost,
 consider submission of the variation as a Value Engineering Change Proposal
 (VECP).

1.4.4.2      Proposing Variations

 When proposing variation, deliver written request to the Contracting
 Officer, with documentation of the nature and features of the variation and
 why the variation is desirable and beneficial to Government. If lower cost
 is a benefit, also include an estimate of the cost saving. In addition to


                              SECTION 01 33 00   Page 6
Design MET Facility                                                        5490419


 documentation required for variation, include the submittals required for
 the item. Clearly mark the proposed variation in all documentation.

1.4.4.3      Warranting That Variations Are Compatible

 When delivering a variation for approval, Contractor warrants that this
 contract has been reviewed to establish that the variation, if
 incorporated, will be compatible with other elements of work.

1.4.4.4      Review Schedule Is Modified

 In addition to normal submittal review period, a period of 10working days
 will be allowed for consideration by the Government of submittals with
 variations.

1.4.5     Contractor's Responsibilities

        a.   Determine and verify field measurements, materials, field
             construction criteria; review each submittal; and check and
             coordinate each submittal with requirements of the work and
             contract documents.

        b.   Transmit submittals to QC organization in accordance with schedule
             on approved Submittal Register, and to prevent delays in the work,
             delays to Government, or delays to separate Contractors.

        c.   Advise Contracting Officer of variation, as required by paragraph
             entitled "Variations."

        d.   Correct and resubmit submittal as directed by approving
             authority. When resubmitting disapproved transmittals or
             transmittals noted for resubmittal, the Contractor shall provide
             copy of that previously submitted transmittal including all
             reviewer comments for use by approving authority. Direct specific
             attention in writing or on resubmitted submittal, to revisions not
             requested by approving authority on previous submissions.

        e.   Furnish additional copies of submittal when requested by
             Contracting Officer, to a limit of 20 copies per submittal.

        f.   Complete work which must be accomplished as basis of a submittal
             in time to allow submittal to occur as scheduled.

        g.   Ensure no work has begun until submittals for that work have been
             returned as "approved," or "approved as noted", except to the
             extent that a portion of work must be accomplished as basis of
             submittal.

1.4.6     QC Organization Responsibilities

        a.   Note date on which submittal was received from Contractor on each
             submittal.

        b.   Review each submittal; and check and coordinate each submittal
             with requirements of work and contract documents.

        c.   Review submittals for conformance with project design concepts and
             compliance with contract documents.



                              SECTION 01 33 00   Page 7
Design MET Facility                                                      5490419


        d.   Act on submittals, determining appropriate action based on QC
             organization's review of submittal.

             (1) When Architect-Engineer of Record is approving authority,
             forward the submittal to the A&E with the certifying statement or
             return submittal marked "not reviewed" or "revise and resubmit" as
             appropriate.

             (2) When Contracting Officer is approving authority or when
             variation has been proposed, forward submittal to Government with
             certifying statement or return submittal marked "not reviewed" or
             "revise and resubmit" as appropriate. T

        e.   Ensure that material is clearly legible.

        f.   Stamp each sheet of each submittal with QC certifying statement or
             approving statement, except that data submitted in bound volume or
             on one sheet printed on two sides may be stamped on the front of
             the first sheet only.

             (1) When approving authority is Contracting Officer, QC
             organization will certify submittals forwarded to Contracting
             Officer with the following certifying statement:

        "I hereby certify that the (equipment) (material) (article) shown and
            marked in this submittal is that proposed to be incorporated with
            contract Number WO #5490419, is in compliance with the contract
            drawings and specification, can be installed in the allocated
            spaces, and is submitted for Government approval.

        Certified by Submittal Reviewer _____________________, Date _______
        (Signature when applicable)

        Certified by QC Manager _____________________________, Date ______"
        (Signature)


        g.   Sign certifying statement or approval statement. The person
             signing certifying statements shall be QC organization member
             designated in the approved QC plan. The signatures shall be in
             original ink. Stamped signatures are not acceptable.

        h.   Update submittal register as submittal actions occur and maintain
             the submittal register at project site until final acceptance of
             all work by Contracting Officer.

        i.   Retain a copy of approved submittals at project site, including
             Contractor's copy of approved samples.

1.4.7    Government's Responsibilities

 When approving authority is Contracting Officer or Architect-Engineer, ,
 the approving authority will:

        a.   Note date on which submittal was received from QC manager, on each
             submittal for which the Contracting Officer is approving authority.

        b.   Review submittals for approval within scheduling period specified
             and only for conformance with project design concepts and


                             SECTION 01 33 00   Page 8
Design MET Facility                                                      5490419


             compliance with contract documents.

        c.   Identify returned submittals with one of the actions defined in
             paragraph entitled "Actions Possible" and with markings
             appropriate for action indicated.

1.4.8     Actions Possible

 Submittals will be returned with one of the following notations:

        a.   Submittals marked "not reviewed" will indicate submittal has been
             previously reviewed and approved, is not required , does not have
             evidence of being reviewed and approved by Contractor, or is not
             complete. A submittal marked "not reviewed" will be returned with
             an explanation of the reason it is not reviewed. Resubmit
             submittals returned for lack of review by Contractor or for being
             incomplete, with appropriate action, coordination, or change.

        b.   Submittals marked "approved" "approved as submitted" authorize
             Contractor to proceed with work covered.

        c.   Submittals marked "approved as noted" or "approval except as
             noted; resubmission not required" authorize Contractor to proceed
             with work as noted provided Contractor takes no exception to the
             notations.

        d.   Submittals marked "revise and resubmit" or "disapproved" indicate
             submittal is incomplete or does not comply with design concept or
             requirements of the contract documents and shall be resubmitted
             with appropriate changes. No work shall proceed for this item
             until resubmittal is approved.

1.5     FORMAT OF SUBMITTALS

1.5.1     Transmittal Form

 Transmit each submittal, except sample installations and sample panels, to
 office of approving authority. Transmit submittals with transmittal form
 prescribed by Contracting Officer and standard for project. The
 transmittal form shall identify Contractor, indicate date of submittal, and
 include information prescribed by transmittal form and required in
 paragraph entitled "Identifying Submittals." Process transmittal forms to
 record actions regarding sample panels and sample installations.

1.5.2     Identifying Submittals

 Identify submittals, except sample panel and sample installation, with the
 following information permanently adhered to or noted on each separate
 component of each submittal and noted on transmittal form. Mark each copy
 of each submittal identically, with the following:

        a.   Project title and location.

        b.   Construction contract number.

        c.   Section number of the specification section by which submittal is
             required.

        d.   Submittal description (SD) number of each component of submittal.


                               SECTION 01 33 00   Page 9
Design MET Facility                                                        5490419



        e.   When a resubmission, add alphabetic suffix on submittal
             description, for example, SD-10A, to indicate resubmission.

        f.   Name, address, and telephone number of subcontractor, supplier,
             manufacturer and any other second tier Contractor associated with
             submittal.

        g.   Product identification and location in project.

1.5.3    Format for SD-02 Shop Drawings

        a.   Shop drawings shall not be less than 8 1/2 by 11 inches nor more
             than 30 by 42 inches.

        b.   Present 8 1/2 by 11 inches sized shop drawings as part of the
             bound volume for submittals required by section. Present larger
             drawings in sets.

        c.   Include on each drawing the drawing title, number, date, and
             revision numbers and dates, in addition to information required in
             paragraph entitled "Identifying Submittals."

        d.   Dimension drawings, except diagrams and schematic drawings;
             prepare drawings demonstrating interface with other trades to
             scale. Shop drawing dimensions shall be the same unit of measure
             as indicated on the contract drawings. Identify materials and
             products for work shown.

        e.   Drawings shall include the nameplate data, size and capacity.
             Also include applicable federal, military, industry and technical
             society publication references.

1.5.4    Format of SD-03 Product Data and SD-08 Manufacturer's Instruction

        a.   Present product data submittals for each section as a complete,
             bound volume. Include table of contents, listing page and catalog
             item numbers for product data.

        b.   Indicate, by prominent notation, each product which is being
             submitted; indicate specification section number and paragraph
             number to which it pertains.

        c.   Supplement product data with material prepared for project to
             satisfy submittal requirements for which product data does not
             exist. Identify this material as developed specifically for
             project.

        e.   Product data shall include the manufacturer's name, trade name,
             place of manufacture, and catalog model or number. Submittals
             shall also include applicable federal, military, industry and
             technical society publication references. Should manufacturer's
             data require supplemental information for clarification, the
             supplemental information shall be submitted as specified for SD-07
             Certificates.

        f.   Where equipment or materials are specified to conform to industry
             and technical society reference standards of the organizations
             such as American National Standards Institute (ANSI), ASTM


                             SECTION 01 33 00   Page 10
Design MET Facility                                                          5490419


             International (ASTM), National Electrical Manufacturer's
             Association (NEMA), Underwriters Laboratories (UL), and
             Association of Edison Illuminating Companies (AEIC), submit proof
             of such compliance. The label or listing by the specified
             organization will be acceptable evidence of compliance. In lieu
             of the label or listing, submit a certificate from an independent
             testing organization, competent to perform testing, and approved
             by the Contracting Officer. The certificate shall state that the
             item has been tested in accordance with the specified
             organization's test methods and that the item complies with the
             specified organization's reference standard.

        g.   Submit manufacturer's instruction prior to installation.

1.5.5    Format of SD-04 Samples

        a.   Furnish samples in sizes below, unless otherwise specified or
             unless the manufacturer has prepackaged samples of approximately
             same size as specified:

             (1)   Sample of Equipment or Device:   Full size.

             (2) Sample of Materials Less Than 2 by 3 inches:       Built up to 8
             1/2 by 11 inches.

             (3) Sample of Materials Exceeding 8 1/2 by 11 inches: Cut down to
              8 1/2 by 11 inches and adequate to indicate color, texture, and
             material variations.

             (4) Sample of Linear Devices or Materials: 10 inch length or
             length to be supplied, if less than 10 inches. Examples of linear
             devices or materials are conduit and handrails.

             (5) Sample of Non-Solid Materials:     Pint.    Examples of non-solid
             materials are sand and paint.

             (6)   Color Selection Samples:   2 by 4 inches.

             (7)   Sample Panel:   4 by 4 feet.

             (8)   Sample Installation:   100 square feet.

        b.   Samples Showing Range of Variation: Where variations are
             unavoidable due to nature of the materials, submit sets of samples
             of not less than three units showing extremes and middle of range.

        c.   Reusable Samples: Incorporate returned samples into work only if
             so specified or indicated. Incorporated samples shall be in
             undamaged condition at time of use.

        d.   Recording of Sample Installation: Note and preserve the notation
             of area constituting sample installation but remove notation at
             final clean up of project.

        e.   When color, texture or pattern is specified by naming a particular
             manufacturer and style, include one sample of that manufacturer
             and style, for comparison.




                              SECTION 01 33 00    Page 11
Design MET Facility                                                       5490419


1.5.6     Format of SD-05 Design Data and SD-07 Certificates

        a.   Provide design data and certificates on 8 1/2 by 11 inches
             paper. Provide a bound volume for submittals containing numerous
             pages.

1.5.7     Format of SD-06 Test Reports and SD-09 Manufacturer's Field Reports

        a.   Provide reports on   8 1/2 by 11 inches paper in a complete bound
             volume.

        b.   Indicate by prominent notation, each report in the submittal.
             Indicate specification number and paragraph number to which it
             pertains.

1.5.8     Format of SD-10 Operation and Maintenance Data (O&M)

        a.   O&M Data format shall comply with the requirements specified in
             Section 01 78 23 OPERATION AND MAINTENANCE DATA

1.5.9     Format of SD-01 Preconstruction Submittals and SD-11 Closeout
          Submittals

        a.   When submittal includes a document which is to be used in project
             or become part of project record, other than as a submittal, do
             not apply Contractor's approval stamp to document, but to a
             separate sheet accompanying document.

1.6     QUANTITY OF SUBMITTALS

1.6.1     Number of Copies of SD-02 Shop Drawings

        a.   Submit six copies of submittals of shop drawings requiring review
             and approval only by QC organization and seven copies of shop
             drawings requiring review and approval by Contracting Officer.

1.6.2   Number of Copies of SD-03 Product Data and SD-08 Manufacturer's
Instructions

 Submit in compliance with quantity requirements specified for shop drawings.

1.6.3     Number of Samples SD-04 Samples

        a.   Submit one sampleshowing range of variation, of each required
             item. One approved sample or set of samples will be retained by
             approving authority and one will be returned to Contractor.

        b.   Submit one sample panel.   Include components listed in technical
             section or as directed.

        c.   Submit one sample installation, where directed.

        d.   Submit one sample of non-solid materials.

1.6.4     Number of Copies SD-05 Design Data and SD-07 Certificates

        a.   Submit in compliance with quantity requirements specified for shop
             drawings.



                             SECTION 01 33 00   Page 12
Design MET Facility                                                         5490419


1.6.5     Number of Copies SD-06 Test Reports and SD-09 Manufacturer's Field
          Reports

        b.   Submit in compliance with quantity with quality requirements
             specified for shop drawings.

1.6.6     Number of Copies of SD-10 Operation and Maintenance Data

 Submit Fivecopies of O&M Data to the Contracting Officer for review and
 approval.

1.6.7     Number of Copies of SD-01 Preconstruction Submittals and SD-11
          Closeout Submittals

        a.   Unless otherwise specified, submit administrative submittals
             compliance with quantity requirements specified for shop drawings.

1.7     FORWARDING SUBMITTALS

1.7.1     Submittals Required from the Contractor

 As soon as practicable after award of contract, and before procurement of
 fabrication, forward to the Architect-Engineer: Avolis Engineering, P.A.,
 submittals required in the technical sections of this specification,
 including shop drawings, product data and samples. One copy of the
 transmittal form for all submittals shall be forwarded to the Resident
 Officer in Charge of Construction, NAVFAC MIDLANT, PSC Box 8006, Cherry
 Point, North Carolina 28533-0006. Submit to the Resident Officer in Charge
 of Construction, NAVFAC MIDLANT Contracts, at the above address, for review
 and approval, the following:.

 As an exception to the standard submittal procedure specified above, submit
 to the Resident Officer In Charge of Construction, NAVFAC MIDLANT
 Contracts, at the above address, for reiview and approval, the following:

             All submittals required by Division 01 - General Requirements.
             All Submittals with "G" designations.

1.7.1.1      O&M Data

 The Architect-Engineer for this project will review and approve for the
 Contracting Officer O&M Data to verify the submittals comply with the
 contract requirements; submit data specified for a given item within 30
 calendar days after the item is delivered to the contract site.

        a.   In the event the Contractor fails to deliver O&M Data within the
             time limits specified, the Contracting Officer may withhold from
             progress payments 50 percent of the price of the item with which
             such O&M Data are applicable.

1.8     SUBMITTAL CLASSIFICATION

 Submittals are classified as follows:

1.9     Government Approved

 Government approval is required for extensions of design, critical
 materials, deviations, equipment whose compatibility with the entire system
 must be checked, and other items as designated by the Contracting Officer.


                              SECTION 01 33 00   Page 13
Design MET Facility                                                   5490419


 Within the terms of the Contract Clause entitled "Specifications and
 Drawings for Construction," they are considered to be "shop drawings."

1.10     Information Only

 All submittals not requiring Government or Architect-Engineer of Record
 approval will be for information only. They are not considered to be "shop
 drawings" within the terms of the Contract Clause referred to above.

1.10.1     APPROVED SUBMITTALS

 The Contracting Officer's and Architect-Engineer's approval of submittals
 shall not be construed as a complete check, but will indicate only that the
 general method of construction, materials, detailing and other information
 are satisfactory. Approval will not relieve the Contractor of the
 responsibility for any error which may exist, as the Contractor under the
 Contractor Quality Control (CQC) requirements of this contract is
 responsible for dimensions, the design of adequate connections and details,
 and the satisfactory construction of all work. After submittals have been
 approved by the approving authority, no resubmittal for the purpose of
 substituting materials or equipment will be considered unless accompanied
 by an explanation of why a substitution is necessary.

1.10.1.1     DISAPPROVED SUBMITTALS

 The Contractor shall make all corrections required by the Contracting
 Officer and promptly furnish a corrected submittal in the form and number
 of copies specified for the initial submittal. If the Contractor considers
 any correction indicated on the submittals to constitute a change to the
 contract, a notice in accordance with the Contract Clause "Changes" shall
 be given promptly to the Contracting Officer.


1.11     WITHHOLDING OF PAYMENT

 Payment for materials incorporated in the work will not be made if required
 approvals have not been obtained.

1.12     GENERAL

 The contractor shall make submittals as required by the specifications.
 The Contracting Officer may request submittals in addition to those
 specified when deemed necessary to adequately describe the work covered in
 the respective sections. Units of weights and measures used on all
 submittals shall be the same as those used in the contract drawings. Each
 submittal shall be complete and in sufficient details to allow ready
 determination of compliance with contract requirements. Prior to
 submittal, all items shall be checked and approved by the contractor's
 Quality Control (CQC) System Manager and each item shall be stamped,
 signed, and dated by the CQC System Manager indicating action taken.
 Proposed deviations from the contract requirements shall be clearly
 identified. Submittals shall include items such as: Contractor's
 manufacturer's, or fabricator's drawings; descriptive literature including
 (but not limited to) catalog cuts, diagrams, operating charts or curves;
 test report; test cylinders; samples; O&M manuals (including parts list);
 certifications; warranties; and other such required submittals. Submittals
 requiring Government approval shall be scheduled and made prior to the
 acquisition of the material or equipment covered thereby. Samples
 remaining upon completion of the work shall be picked up and disposed of in


                            SECTION 01 33 00   Page 14
Design MET Facility                                                    5490419


 accordance with manufacturer's Material Safety Data Sheets (MSDS) and in
 compliance with existing laws and regulations.

1.13     SUBMITTAL REGISTER

 At the end of this section is a submittal register showing items of
 equipment and materials for which submittals are required by the
 specifications; this list may not be all inclusive and additional
 submittals may be required. The Government will provide the initial
 submittal register. Thereafter, the Contractor shall maintain a complete
 list of all submittals, including completion of all data columns. Dates on
 which submittals are received and returned by the Government will be
 included in its export file to the Contractor. The Contractor shall track
 all submittals.

1.14     SCHEDULING

 Submittals covering component items forming a system or items that are
 interrelated shall be scheduled to be coordinated and submitted
 concurrently. Certifications to be submitted with the pertinent drawings
 shall be so scheduled. Adequate time (a minimum of 14 calendar days
 exclusive of mailing time) shall be allowed and shown on the register for
 review and approval. No delay damages or time extensions will be allowed
 for time lost in late submittals.

1.15     TRANSMITTAL FORM (ENG FORM 4025)

 The sample transmittal form (ENG Form 4025) attached to this section shall
 be used for submitting both Government approved and information only
 submittals in accordance with the instructions on the reverse side of the
 form. These forms will be furnished to the Contractor. This form shall be
 properly completed by filling out all the heading blank spaces and
 identifying each time submitted. Special care shall be exercised to ensure
 proper listing of the specification paragraph and/or sheet number of the
 contract drawings pertinent to the data submitted for each item.

1.16     SUBMITTAL PROCEDURES

 Submittals shall be made as follows:

1.16.1     Procedures

 The Government will further discuss detailed submittal procedures with the
 contractor at the Preconstruction Conference.

1.16.1.1     Deviations

 For submittals which include proposed deviations requested by the
 Contractor, the column "variation" of ENG form 4025 shall be checked. The
 Contractor shall set forth in writing the reason for any deviations and
 annotate such deviations on the submittal. The Government reserves the
 right to rescind inadvertent approval of submittals containing unnoted
 deviations.

1.17     CONTROL OF SUBMITTALS

The Contractor shall carefully control his procurement operations to ensure
that each individual submittal is made on or before the Contractor scheduled
submittal date shown on the approved "Submittal Register".


                              SECTION 01 33 00   Page 15
Design MET Facility                                                     5490419



1.18     GOVERNMENT AND ARCHITECT-ENGINEER

Upon completion of review of submittals requiring Government approval, the
submittal will be identified as having received approval by being so stamped
and dated. One copy of the submittal will be retained by the
Architect-Engineer, three copies will be retained by the Contracting Officer
and three copies will be returned to the Contractor.

1.19     INFORMATION ONLY

  Normally submittals for information only will not be returned. Approval of
  the Contracting Officer is not required on information only submittals.
  The Government reserves the right to require the Contractor to resubmit any
  item found not to comply with the contract. This does not relieve the
  Contactor from the obligation to furnish material conforming to the plans
  and specifications; will not prevent the Contracting Officer from requiring
  removal and replacement of nonconforming material incorporate in the work;
  and does not relieve the Contractor of the requirement to furnish samples
  for testing by the Government laboratory or for check testing by the
  Government in those instances where the technical specifications so
  prescribe.
1.20   STAMPS

 Stamps used by the Contractor on the submittal data to certify that the
 submittal meets contract requirements shall be similar to the following:


    ________________________________________________________________________
  |                                CONTRACTOR                                |
  |                                                                          |
  |                                (Firm Name)                               |
  |                                                                          |
  |                                                                          |
  |                                                                          |
  | _____ Approved                                                           |
  |                                                                          |
  |                                                                          |
  | _____ Approved with corrections as noted on submittal data and/or        |
  | attached sheets(s).                                                      |
  |                                                                          |
  |                                                                          |
  |                                                                          |
  | SIGNATURE: __________________________________________________________ |
  |                                                                          |
  | TITLE: ______________________________________________________________ |
  |                                                                          |
  | DATE: _______________________________________________________________ |
  |                                                                          |
  |________________________________________________________________________|

PART 2     PRODUCTS

 Not Used

PART 3     EXECUTION

 Not Used



                            SECTION 01 33 00   Page 16
                                                                                                                                                       CONTRACT NO.
                                                     SUBMITTAL REGISTER
TITLE AND LOCATION                                                                           CONTRACTOR
Design MET Facility
                                                                                                       CONTRACTOR:           CONTRACTOR                        APPROVING AUTHORITY
                                                                                                      SCHEDULE DATES           ACTION
                                                                                        G
                                                                                        O
                                                                                        V
      T                                                                       C         T
      R                                                                       L
      A                                                                       A         O
 A    N                                                                       S         R                                    A                                              A
 C    S                                                                       S                                              C                                              C
 T    M           S                                             P             I         A                                    T                                              T
 I    I           P                                             A             F         /                                    I                                              I
 V    T           E                                             R             I         E                                    O              DATE FWD                        O              MAILED
 I    T           C                                             A             C                                              N               TO APPR                        N                TO
 T    A                                                         G#            A         R                                                     AUTH/                                        CONTR/
 Y    L           S                                             R             T         E                                    C                                              C
                  E                   DESCRIPTION               A             I         V               APPROVAL MATERIAL    O      DATE    DATE RCD DATE FWD DATE RCD      O      DATE    DATE RCD
 N    N           C                                             P             O         W                NEEDED  NEEDED      D       OF       FROM   TO OTHER FROM OTH      D       OF     FRM APPR
 O    O           T                 ITEM SUBMITTED              H             N         R     SUBMIT       BY       BY       E     ACTION    CONTR REVIEWER REVIEWER        E     ACTION     AUTH        REMARKS


(a)   (b)        (c)                      (d)                       (e)           (f)           (g)         (h)        (i)   (j)     (k)       (l)       (m)          (n)   (o)      (p)      (q)            (r)

            01 20 00.00 20 SD-01 Preconstruction Submittals
                            Schedule of prices                1.3         G
            01 30 00       SD-01 Preconstruction Submittals
                            List of contact personnel         1.3.1
            01 31 50       SD-11 Closeout Submittals
                            Interim DD-1354, Transfer &       1.2
                             Acceptance of Military Real
                             Property
            01 32 16       SD-01 Preconstruction Submittals
                            Construction schedule             1.2
                            Equipment delivery schedule       1.3
            01 33 00       SD-01 Preconstruction Submittals
                            Submittal register                1.3.1       G
            01 35 29       SD-01 Preconstruction Submittals
                            Accident Prevention Plan (APP)    1.9
                            Activity Hazard Analysis (AHA)    1.10
                           SD-06 Test Reports
                            Reports                           1.14
                            Accident Reports                  1.14.1
                            Monthly Exposure Reports          1.14.3
                            Regulatory Citations and          1.14.4
                             Violations
                           SD-07 Certificates
                            Confined Space Entry Permit       1.11
            01 45 10       SD-11 Closeout Submittals
                            QC PLAN                           1.6

SUBMITTAL FORM,Jan 96                                                                       PREVIOUS EDITION IS OBSOLETE                                                                            PAGE 1 OF 15 PAGES
                                                                                                                                                  CONTRACT NO.
                                                     SUBMITTAL REGISTER
TITLE AND LOCATION                                                                      CONTRACTOR
Design MET Facility
                                                                                                  CONTRACTOR:           CONTRACTOR                        APPROVING AUTHORITY
                                                                                                 SCHEDULE DATES           ACTION
                                                                                   G
                                                                                   O
                                                                                   V
      T                                                                  C         T
      R                                                                  L
      A                                                                  A         O
 A    N                                                                  S         R                                    A                                              A
 C    S                                                                  S                                              C                                              C
 T    M           S                                           P          I         A                                    T                                              T
 I    I           P                                           A          F         /                                    I                                              I
 V    T           E                                           R          I         E                                    O              DATE FWD                        O              MAILED
 I    T           C                                           A          C                                              N               TO APPR                        N                TO
 T    A                                                       G#         A         R                                                     AUTH/                                        CONTR/
 Y    L           S                                           R          T         E                                    C                                              C
                  E                  DESCRIPTION              A          I         V               APPROVAL MATERIAL    O      DATE    DATE RCD DATE FWD DATE RCD      O      DATE    DATE RCD
 N    N           C                                           P          O         W                NEEDED  NEEDED      D       OF       FROM   TO OTHER FROM OTH      D       OF     FRM APPR
 O    O           T                 ITEM SUBMITTED            H          N         R     SUBMIT       BY       BY       E     ACTION    CONTR REVIEWER REVIEWER        E     ACTION     AUTH        REMARKS


(a)   (b)        (c)                      (d)                  (e)           (f)           (g)         (h)        (i)   (j)     (k)       (l)       (m)          (n)   (o)      (p)      (q)            (r)

            01 50 00.00 20 SD-01 Preconstruction Submittals
                            Traffic control plan            1.8      G
                           SD-06 Test Reports
                            Backflow Preventer Tests        3.3      G
                           SD-07 Certificates
                            Backflow Tester                 1.6      G
                            Backflow Preventers             1.3
            01 57 19.00 20 SD-01 Preconstruction Submittals
                            Preconstruction Survey          1.5.1    G
                            Solid Waste Management Plan     3.4      G
                             and Permit
                            Regulatory Notification         1.5.2    G
                            Environmental Protection Plan   3.1      G
                           SD-06 Test Reports
                            Laboratory Analysis             3.5.2
                            Disposal Requirements           3.15.2
                           SD-11 Closeout Submittals
                            Waste Determination             3.5
                             Documentation
                            Disposal Documentation for      3.6.1
                             Hazardous and Regulated Waste
                            Contractor 40 CFR Employee      1.5.5
                             Training Records
                            Solid Waste Management Report 3.4.1
                            Contractor Hazardous Material   3.5.1    G
                             Inventory Log

SUBMITTAL FORM,Jan 96                                                                  PREVIOUS EDITION IS OBSOLETE                                                                            PAGE 2 OF 15 PAGES
                                                                                                                                                       CONTRACT NO.
                                                     SUBMITTAL REGISTER
TITLE AND LOCATION                                                                           CONTRACTOR
Design MET Facility
                                                                                                       CONTRACTOR:           CONTRACTOR                        APPROVING AUTHORITY
                                                                                                      SCHEDULE DATES           ACTION
                                                                                        G
                                                                                        O
                                                                                        V
      T                                                                       C         T
      R                                                                       L
      A                                                                       A         O
 A    N                                                                       S         R                                    A                                              A
 C    S                                                                       S                                              C                                              C
 T    M           S                                             P             I         A                                    T                                              T
 I    I           P                                             A             F         /                                    I                                              I
 V    T           E                                             R             I         E                                    O              DATE FWD                        O              MAILED
 I    T           C                                             A             C                                              N               TO APPR                        N                TO
 T    A                                                         G#            A         R                                                     AUTH/                                        CONTR/
 Y    L           S                                             R             T         E                                    C                                              C
                  E                  DESCRIPTION                A             I         V               APPROVAL MATERIAL    O      DATE    DATE RCD DATE FWD DATE RCD      O      DATE    DATE RCD
 N    N           C                                             P             O         W                NEEDED  NEEDED      D       OF       FROM   TO OTHER FROM OTH      D       OF     FRM APPR
 O    O           T                 ITEM SUBMITTED              H             N         R     SUBMIT       BY       BY       E     ACTION    CONTR REVIEWER REVIEWER        E     ACTION     AUTH        REMARKS


(a)   (b)        (c)                      (d)                       (e)           (f)           (g)         (h)        (i)   (j)     (k)       (l)       (m)          (n)   (o)      (p)      (q)            (r)

            01 57 19.00 20 Contractor Hazardous Material      3.6         G
                             Inventory Log
                            Hazardous Waste/Debris            3.13.1
                             Management
            01 77 00.00 20 SD-10 Operation and Maintenance
                            Data
                            Equipment/Product Warranty List   1.4.1       G
                           SD-11 Closeout Submittals
                            As-Built Drawings                 1.3.1       G
                            Record Of Materials               1.3.3       G
                            Utility As-Built Drawings         1.3.2       G
                            Equipment/Product Warranty Tag    1.4.2       G
                            Certification of EPA Designated   1.2         G
                             Items
            02 41 00       SD-07 Certificates
                            Demolition plan                   1.9         G
                           SD-11 Closeout Submittals
                            Receipts                          1.4.2
            03 30 00       SD-02 Shop Drawings
                            Reinforcing steel                 1.6.1.1
                           SD-03 Product Data
                            Materials for curing concrete     2.4.7
                            Joint Sealants                    2.4.9
                            Portland Cement                   2.4.1.3
                            Ready-Mix Concrete                2.3.2
                            Concrete Curing Materials         2.3.3

SUBMITTAL FORM,Jan 96                                                                       PREVIOUS EDITION IS OBSOLETE                                                                            PAGE 3 OF 15 PAGES
                                                                                                                                                CONTRACT NO.
                                                   SUBMITTAL REGISTER
TITLE AND LOCATION                                                                    CONTRACTOR
Design MET Facility
                                                                                                CONTRACTOR:           CONTRACTOR                        APPROVING AUTHORITY
                                                                                               SCHEDULE DATES           ACTION
                                                                                 G
                                                                                 O
                                                                                 V
      T                                                                C         T
      R                                                                L
      A                                                                A         O
 A    N                                                                S         R                                    A                                              A
 C    S                                                                S                                              C                                              C
 T    M           S                                           P        I         A                                    T                                              T
 I    I           P                                           A        F         /                                    I                                              I
 V    T           E                                           R        I         E                                    O              DATE FWD                        O              MAILED
 I    T           C                                           A        C                                              N               TO APPR                        N                TO
 T    A                                                       G#       A         R                                                     AUTH/                                        CONTR/
 Y    L           S                                           R        T         E                                    C                                              C
                  E                DESCRIPTION                A        I         V               APPROVAL MATERIAL    O      DATE    DATE RCD DATE FWD DATE RCD      O      DATE    DATE RCD
 N    N           C                                           P        O         W                NEEDED  NEEDED      D       OF       FROM   TO OTHER FROM OTH      D       OF     FRM APPR
 O    O           T               ITEM SUBMITTED              H        N         R     SUBMIT       BY       BY       E     ACTION    CONTR REVIEWER REVIEWER        E     ACTION     AUTH        REMARKS


(a)   (b)        (c)                    (d)                    (e)         (f)           (g)         (h)        (i)   (j)     (k)       (l)       (m)          (n)   (o)      (p)      (q)            (r)

            03 30 00     Reinforcement                      2.5
                         Vapor retarder                     2.4.6
                         Local/Regional Materials           1.8.1
                        SD-05 Design Data
                         mix design                         2.3.1
                        SD-06 Test Reports
                         Concrete mix design                1.6.3.1
                         Fly ash                            1.6.3.2
                         Pozzolan                           1.6.3.2
                         Ground granulated blast-furnace    1.6.3.3
                          slag
                         Compressive strength tests         3.11.2.3
                         Air Content                        3.11.2.4
                         Slump                              3.11.2.1
                        SD-07 Certificates
                         Curing concrete elements           1.6.2.1
                         Pumping concrete                   1.6.2.2
                         VOC Content for form release       1.6.2.3
                          agents, curing compounds, and
                          concrete penetrating sealers
                         Material Safety Data Sheets        1.6.2.4
                        SD-08 Manufacturer’s Instructions
                         Fly ash                            1.6.3.2
                         Ground granulated blast-furnace    1.6.3.3
                          slag
                         Steel Bar                          2.5.4

SUBMITTAL FORM,Jan 96                                                                PREVIOUS EDITION IS OBSOLETE                                                                            PAGE 4 OF 15 PAGES
                                                                                                                                                 CONTRACT NO.
                                                   SUBMITTAL REGISTER
TITLE AND LOCATION                                                                     CONTRACTOR
Design MET Facility
                                                                                                 CONTRACTOR:           CONTRACTOR                        APPROVING AUTHORITY
                                                                                                SCHEDULE DATES           ACTION
                                                                                  G
                                                                                  O
                                                                                  V
      T                                                                 C         T
      R                                                                 L
      A                                                                 A         O
 A    N                                                                 S         R                                    A                                              A
 C    S                                                                 S                                              C                                              C
 T    M           S                                           P         I         A                                    T                                              T
 I    I           P                                           A         F         /                                    I                                              I
 V    T           E                                           R         I         E                                    O              DATE FWD                        O              MAILED
 I    T           C                                           A         C                                              N               TO APPR                        N                TO
 T    A                                                       G#        A         R                                                     AUTH/                                        CONTR/
 Y    L           S                                           R         T         E                                    C                                              C
                  E                DESCRIPTION                A         I         V               APPROVAL MATERIAL    O      DATE    DATE RCD DATE FWD DATE RCD      O      DATE    DATE RCD
 N    N           C                                           P         O         W                NEEDED  NEEDED      D       OF       FROM   TO OTHER FROM OTH      D       OF     FRM APPR
 O    O           T               ITEM SUBMITTED              H         N         R     SUBMIT       BY       BY       E     ACTION    CONTR REVIEWER REVIEWER        E     ACTION     AUTH        REMARKS


(a)   (b)        (c)                    (d)                       (e)       (f)           (g)         (h)        (i)   (j)     (k)       (l)       (m)          (n)   (o)      (p)      (q)            (r)

            05 40 00    SD-02 Shop Drawings
                         Framing Components                 1.6.1
                        SD-03 Product Data
                         studs,joists                       2.1
                        SD-07 Certificates
                         Load-bearing cold-formed metal     1.4
                          framing
                         Welds                              3.1.1
            07 21 16    SD-03 Product Data
                         Blanket insulation                 2.1
                         Accessories                        2.3
                        SD-08 Manufacturer’s Instructions
                         Insulation                         3.3.1
            07 92 00    SD-03 Product Data
                         Sealants                           2.1
                         Primers                            2.2
                         Bond breakers                      2.3
                         Backstops                          2.4
                        SD-07 Certificates
                         Sealant                            3.3.6
            08 11 13    SD-02 Shop Drawings
                         Doors                              2.1
                         Doors                              2.1
                         Frames                             2.5
                         Frames                             2.5
                         Accessories                        2.3

SUBMITTAL FORM,Jan 96                                                                 PREVIOUS EDITION IS OBSOLETE                                                                            PAGE 5 OF 15 PAGES
                                                                                                                                             CONTRACT NO.
                                                  SUBMITTAL REGISTER
TITLE AND LOCATION                                                                 CONTRACTOR
Design MET Facility
                                                                                             CONTRACTOR:           CONTRACTOR                        APPROVING AUTHORITY
                                                                                            SCHEDULE DATES           ACTION
                                                                              G
                                                                              O
                                                                              V
      T                                                             C         T
      R                                                             L
      A                                                             A         O
 A    N                                                             S         R                                    A                                              A
 C    S                                                             S                                              C                                              C
 T    M           S                                       P         I         A                                    T                                              T
 I    I           P                                       A         F         /                                    I                                              I
 V    T           E                                       R         I         E                                    O              DATE FWD                        O              MAILED
 I    T           C                                       A         C                                              N               TO APPR                        N                TO
 T    A                                                   G#        A         R                                                     AUTH/                                        CONTR/
 Y    L           S                                       R         T         E                                    C                                              C
                  E               DESCRIPTION             A         I         V               APPROVAL MATERIAL    O      DATE    DATE RCD DATE FWD DATE RCD      O      DATE    DATE RCD
 N    N           C                                       P         O         W                NEEDED  NEEDED      D       OF       FROM   TO OTHER FROM OTH      D       OF     FRM APPR
 O    O           T              ITEM SUBMITTED           H         N         R     SUBMIT       BY       BY       E     ACTION    CONTR REVIEWER REVIEWER        E     ACTION     AUTH        REMARKS


(a)   (b)        (c)                   (d)                    (e)       (f)           (g)         (h)        (i)   (j)     (k)       (l)       (m)          (n)   (o)      (p)      (q)            (r)

            08 11 13    SD-03 Product Data
                         Doors                          2.1
                         Frames                         2.5
                         Accessories                    2.3
            08 33 23    SD-02 Shop Drawings
                         Overhead Coiling Doors         2.1
                         Counterbalancing Mechanism     1.6
                         Counterbalancing Mechanism     2.3
                         Manual Door Operators          1.6
                         Manual Door Operators          2.4
                         Bottom Bar                     2.1.3
                         Guides                         1.5
                         Mounting Brackets              2.3.1
                         Overhead Drum                  2.1.8
                         Painting                       1.6
                         Installation Drawings          1.5
                        SD-03 Product Data
                         Overhead Coiling Doors         2.1
                         Hardware                       2.2
                         Counterbalancing Mechanism     1.6
                         Counterbalancing Mechanism     2.3
                         Manual Door Operators          1.6
                         Manual Door Operators          2.4
                        SD-05 Design Data
                         Overhead Coiling Doors         2.1
                         Hardware                       2.2

SUBMITTAL FORM,Jan 96                                                             PREVIOUS EDITION IS OBSOLETE                                                                            PAGE 6 OF 15 PAGES
                                                                                                                                                 CONTRACT NO.
                                                   SUBMITTAL REGISTER
TITLE AND LOCATION                                                                     CONTRACTOR
Design MET Facility
                                                                                                 CONTRACTOR:           CONTRACTOR                        APPROVING AUTHORITY
                                                                                                SCHEDULE DATES           ACTION
                                                                                  G
                                                                                  O
                                                                                  V
      T                                                                 C         T
      R                                                                 L
      A                                                                 A         O
 A    N                                                                 S         R                                    A                                              A
 C    S                                                                 S                                              C                                              C
 T    M           S                                           P         I         A                                    T                                              T
 I    I           P                                           A         F         /                                    I                                              I
 V    T           E                                           R         I         E                                    O              DATE FWD                        O              MAILED
 I    T           C                                           A         C                                              N               TO APPR                        N                TO
 T    A                                                       G#        A         R                                                     AUTH/                                        CONTR/
 Y    L           S                                           R         T         E                                    C                                              C
                  E                DESCRIPTION                A         I         V               APPROVAL MATERIAL    O      DATE    DATE RCD DATE FWD DATE RCD      O      DATE    DATE RCD
 N    N           C                                           P         O         W                NEEDED  NEEDED      D       OF       FROM   TO OTHER FROM OTH      D       OF     FRM APPR
 O    O           T               ITEM SUBMITTED              H         N         R     SUBMIT       BY       BY       E     ACTION    CONTR REVIEWER REVIEWER        E     ACTION     AUTH        REMARKS


(a)   (b)        (c)                    (d)                       (e)       (f)           (g)         (h)        (i)   (j)     (k)       (l)       (m)          (n)   (o)      (p)      (q)            (r)

            08 33 23     Counterbalancing Mechanism         1.6
                         Counterbalancing Mechanism         2.3
                         Manual Door Operators              1.6
                         Manual Door Operators              2.4
                        SD-10 Operation and Maintenance
                         Data
                         Operation and Maintenance          1.5
                          Manuals
                         Overhead Coiling Door              1.6
                          Assemblies
                         Materials                          1.6
                         Devices                            1.6
                         Procedures                         1.6
                         Manufacture's Brochures            1.6
                         Parts Lists                        1.6
                         Cleaning                           3.3.2
            08 71 00    SD-02 Shop Drawings
                         Hardware schedule                  1.3
                        SD-03 Product Data
                         Hardware items                     2.3
                        SD-08 Manufacturer’s Instructions
                         Installation                       3.1
                        SD-10 Operation and Maintenance
                         Data
                         Hardware Schedule                  1.3
                        SD-11 Closeout Submittals

SUBMITTAL FORM,Jan 96                                                                 PREVIOUS EDITION IS OBSOLETE                                                                            PAGE 7 OF 15 PAGES
                                                                                                                                                 CONTRACT NO.
                                                   SUBMITTAL REGISTER
TITLE AND LOCATION                                                                     CONTRACTOR
Design MET Facility
                                                                                                 CONTRACTOR:           CONTRACTOR                        APPROVING AUTHORITY
                                                                                                SCHEDULE DATES           ACTION
                                                                                  G
                                                                                  O
                                                                                  V
      T                                                                 C         T
      R                                                                 L
      A                                                                 A         O
 A    N                                                                 S         R                                    A                                              A
 C    S                                                                 S                                              C                                              C
 T    M           S                                           P         I         A                                    T                                              T
 I    I           P                                           A         F         /                                    I                                              I
 V    T           E                                           R         I         E                                    O              DATE FWD                        O              MAILED
 I    T           C                                           A         C                                              N               TO APPR                        N                TO
 T    A                                                       G#        A         R                                                     AUTH/                                        CONTR/
 Y    L           S                                           R         T         E                                    C                                              C
                  E                DESCRIPTION                A         I         V               APPROVAL MATERIAL    O      DATE    DATE RCD DATE FWD DATE RCD      O      DATE    DATE RCD
 N    N           C                                           P         O         W                NEEDED  NEEDED      D       OF       FROM   TO OTHER FROM OTH      D       OF     FRM APPR
 O    O           T               ITEM SUBMITTED              H         N         R     SUBMIT       BY       BY       E     ACTION    CONTR REVIEWER REVIEWER        E     ACTION     AUTH        REMARKS


(a)   (b)        (c)                    (d)                       (e)       (f)           (g)         (h)        (i)   (j)     (k)       (l)       (m)          (n)   (o)      (p)      (q)            (r)

            08 71 00     Key Bitting                        1.4
            09 90 00    SD-03 Product Data
                         Coating                            2.1
                         Manufacturer's Technical Data      2.1
                          Sheets
                        SD-04 Samples
                         Color                              1.8
                        SD-07 Certificates
                         Applicator's qualifications        1.3
                        SD-08 Manufacturer’s Instructions
                         Application instructions           3.2.1
                         Mixing                             3.5.2
                         Manufacturer's Material Safety     1.6.2
                          Data Sheets
                        SD-10 Operation and Maintenance
                         Data
                         Coatings:                          2.1
            10 44 16    SD-01 Preconstruction Submittals
                         Manufacturer's Data                2.1
                        SD-02 Shop Drawings
                         Fire Extinguishers                 2.1
                         Accessories                        2.4
                         Wall Brackets                      2.5
                        SD-03 Product Data
                         Fire Extinguishers                 2.1
                         Accessories                        2.4

SUBMITTAL FORM,Jan 96                                                                 PREVIOUS EDITION IS OBSOLETE                                                                            PAGE 8 OF 15 PAGES
                                                                                                                                                CONTRACT NO.
                                                  SUBMITTAL REGISTER
TITLE AND LOCATION                                                                    CONTRACTOR
Design MET Facility
                                                                                                CONTRACTOR:           CONTRACTOR                        APPROVING AUTHORITY
                                                                                               SCHEDULE DATES           ACTION
                                                                                 G
                                                                                 O
                                                                                 V
      T                                                                C         T
      R                                                                L
      A                                                                A         O
 A    N                                                                S         R                                    A                                              A
 C    S                                                                S                                              C                                              C
 T    M           S                                          P         I         A                                    T                                              T
 I    I           P                                          A         F         /                                    I                                              I
 V    T           E                                          R         I         E                                    O              DATE FWD                        O              MAILED
 I    T           C                                          A         C                                              N               TO APPR                        N                TO
 T    A                                                      G#        A         R                                                     AUTH/                                        CONTR/
 Y    L           S                                          R         T         E                                    C                                              C
                  E                DESCRIPTION               A         I         V               APPROVAL MATERIAL    O      DATE    DATE RCD DATE FWD DATE RCD      O      DATE    DATE RCD
 N    N           C                                          P         O         W                NEEDED  NEEDED      D       OF       FROM   TO OTHER FROM OTH      D       OF     FRM APPR
 O    O           T              ITEM SUBMITTED              H         N         R     SUBMIT       BY       BY       E     ACTION    CONTR REVIEWER REVIEWER        E     ACTION     AUTH        REMARKS


(a)   (b)        (c)                   (d)                       (e)       (f)           (g)         (h)        (i)   (j)     (k)       (l)       (m)          (n)   (o)      (p)      (q)            (r)

            10 44 16     Wall Brackets                     2.5
                         Replacement Parts                 3.2.1
                        SD-04 Samples
                         Fire Extinguisher                 2.1
                         Wall Brackets                     2.5
                         Accessories                       2.4
                        SD-07 Certificates
                         Fire Extinguishers                2.1
                         Manufacturer's Warranty with      2.1
                          Inspection Tag
            13 12 50    SD-02 Shop Drawings
                         Angle Frame Bleachers             2.2
                        SD-03 Product Data
                         Angle Frame Bleachers             2.2
                        SD-05 Design Data
                         Angle Frame Bleachers             2.2
            13 34 19    SD-01 Preconstruction Submittals
                         Manufacturer's Qualifications     1.6.3
                        SD-02 Shop Drawings
                         Detail Drawings                   1.2.1.7
                         Detail Drawings                   1.6.1
                        SD-03 Product Data
                         sustainable acquisition           2.4.3
                          compliance
                         Manufacturer's catalog data       1.6.1
                        SD-04 Samples

SUBMITTAL FORM,Jan 96                                                                PREVIOUS EDITION IS OBSOLETE                                                                            PAGE 9 OF 15 PAGES
                                                                                                                                               CONTRACT NO.
                                                  SUBMITTAL REGISTER
TITLE AND LOCATION                                                                   CONTRACTOR
Design MET Facility
                                                                                               CONTRACTOR:           CONTRACTOR                        APPROVING AUTHORITY
                                                                                              SCHEDULE DATES           ACTION
                                                                                G
                                                                                O
                                                                                V
      T                                                               C         T
      R                                                               L
      A                                                               A         O
 A    N                                                               S         R                                    A                                              A
 C    S                                                               S                                              C                                              C
 T    M           S                                           P       I         A                                    T                                              T
 I    I           P                                           A       F         /                                    I                                              I
 V    T           E                                           R       I         E                                    O              DATE FWD                        O              MAILED
 I    T           C                                           A       C                                              N               TO APPR                        N                TO
 T    A                                                       G#      A         R                                                     AUTH/                                        CONTR/
 Y    L           S                                           R       T         E                                    C                                              C
                  E                DESCRIPTION                A       I         V               APPROVAL MATERIAL    O      DATE    DATE RCD DATE FWD DATE RCD      O      DATE    DATE RCD
 N    N           C                                           P       O         W                NEEDED  NEEDED      D       OF       FROM   TO OTHER FROM OTH      D       OF     FRM APPR
 O    O           T              ITEM SUBMITTED               H       N         R     SUBMIT       BY       BY       E     ACTION    CONTR REVIEWER REVIEWER        E     ACTION     AUTH         REMARKS


(a)   (b)        (c)                   (d)                     (e)        (f)           (g)         (h)        (i)   (j)     (k)       (l)       (m)          (n)   (o)      (p)      (q)             (r)

            13 34 19     Coil Stock                         1.6.1
                         Coil Stock                         2.1.8
                         Roof Panels                        1.2.1.9
                         Wall Panels                        1.2.1.9
                         Fasteners                          2.5.2
                         Metal Closure Strips               2.8.1
                         Insulation                         1.4.7
                         Vapor Barrier                      1.6.10
                         Manufacturer's color charts and    2.4.4
                          chips
                        SD-05 Design Data
                         descriptive and technical          1.6.1
                          literature
                         building design analysis           1.6.1
                        SD-06 Test Reports
                         test reports                       1.6.1
                         Coatings and base metals           1.6.1
                         Factory Color Finish Performance   1.6.1
                          Requirements
                        SD-07 Certificates
                         system components                  1.6.1
                         Coil Stock                         1.6.1
                         Coil Stock                         2.1.8
                         Aluminized Steel Repair Paint      1.6.1
                         Galvanizing Repair Paint           1.6.1
                         Enamel Repair Paint                1.6.1

SUBMITTAL FORM,Jan 96                                                               PREVIOUS EDITION IS OBSOLETE                                                                            PAGE 10 OF 15 PAGES
                                                                                                                                                 CONTRACT NO.
                                                   SUBMITTAL REGISTER
TITLE AND LOCATION                                                                     CONTRACTOR
Design MET Facility
                                                                                                 CONTRACTOR:           CONTRACTOR                        APPROVING AUTHORITY
                                                                                                SCHEDULE DATES           ACTION
                                                                                  G
                                                                                  O
                                                                                  V
      T                                                                 C         T
      R                                                                 L
      A                                                                 A         O
 A    N                                                                 S         R                                    A                                              A
 C    S                                                                 S                                              C                                              C
 T    M           S                                           P         I         A                                    T                                              T
 I    I           P                                           A         F         /                                    I                                              I
 V    T           E                                           R         I         E                                    O              DATE FWD                        O              MAILED
 I    T           C                                           A         C                                              N               TO APPR                        N                TO
 T    A                                                       G#        A         R                                                     AUTH/                                        CONTR/
 Y    L           S                                           R         T         E                                    C                                              C
                  E                DESCRIPTION                A         I         V               APPROVAL MATERIAL    O      DATE    DATE RCD DATE FWD DATE RCD      O      DATE    DATE RCD
 N    N           C                                           P         O         W                NEEDED  NEEDED      D       OF       FROM   TO OTHER FROM OTH      D       OF     FRM APPR
 O    O           T               ITEM SUBMITTED              H         N         R     SUBMIT       BY       BY       E     ACTION    CONTR REVIEWER REVIEWER        E     ACTION     AUTH         REMARKS


(a)   (b)        (c)                    (d)                       (e)       (f)           (g)         (h)        (i)   (j)     (k)       (l)       (m)          (n)   (o)      (p)      (q)             (r)

            13 34 19     Qualification of Manufacturer      1.6.1
                         Qualification of Erector           1.6.1
                        SD-08 Manufacturer’s Instructions
                         Installation of Roof and Wall      1.6.2
                          panels
                         shipping, handling, and storage    1.7
                        SD-11 Closeout Submittals
                         Manufacturer's Warranty            3.12.1
                         Contractor's Warranty for          3.12.2
                          Installation
            26 20 00    SD-02 Shop Drawings
                         Panelboards                        2.10
                        SD-03 Product Data
                         Receptacles                        2.9
                         Circuit breakers                   2.10.2
                         Switches                           2.8
                        SD-06 Test Reports
                         600-volt wiring test               3.2.2
                         Grounding system test              3.2.4
                         Ground-fault receptacle test       3.2.3
                        SD-07 Certificates
                         Fuses                              2.12
                        SD-10 Operation and Maintenance
                         Data
                         Electrical Systems                 1.5.1
            26 51 00    SD-03 Product Data

SUBMITTAL FORM,Jan 96                                                                 PREVIOUS EDITION IS OBSOLETE                                                                            PAGE 11 OF 15 PAGES
                                                                                                                                                CONTRACT NO.
                                                   SUBMITTAL REGISTER
TITLE AND LOCATION                                                                    CONTRACTOR
Design MET Facility
                                                                                                CONTRACTOR:           CONTRACTOR                        APPROVING AUTHORITY
                                                                                               SCHEDULE DATES           ACTION
                                                                                 G
                                                                                 O
                                                                                 V
      T                                                                C         T
      R                                                                L
      A                                                                A         O
 A    N                                                                S         R                                    A                                              A
 C    S                                                                S                                              C                                              C
 T    M           S                                          P         I         A                                    T                                              T
 I    I           P                                          A         F         /                                    I                                              I
 V    T           E                                          R         I         E                                    O              DATE FWD                        O              MAILED
 I    T           C                                          A         C                                              N               TO APPR                        N                TO
 T    A                                                      G#        A         R                                                     AUTH/                                        CONTR/
 Y    L           S                                          R         T         E                                    C                                              C
                  E                 DESCRIPTION              A         I         V               APPROVAL MATERIAL    O      DATE    DATE RCD DATE FWD DATE RCD      O      DATE    DATE RCD
 N    N           C                                          P         O         W                NEEDED  NEEDED      D       OF       FROM   TO OTHER FROM OTH      D       OF     FRM APPR
 O    O           T               ITEM SUBMITTED             H         N         R     SUBMIT       BY       BY       E     ACTION    CONTR REVIEWER REVIEWER        E     ACTION     AUTH         REMARKS


(a)   (b)        (c)                    (d)                      (e)       (f)           (g)         (h)        (i)   (j)     (k)       (l)       (m)          (n)   (o)      (p)      (q)             (r)

            26 51 00     Fluorescent lighting fixtures     2.1
                         Fluorescent electronic ballasts   1.6.1
                         Fluorescent lamps                 2.1.3
                         High-intensity-discharge (HID)    2.2
                          lighting fixtures
                         HID ballasts                      2.2.1
                         High-pressure sodium (HPS)        2.2.2
                          lamps
                         Metal-halide lamps                2.2.3
                         Exit signs                        2.6
                         Emergency lighting equipment      2.7
                        SD-06 Test Reports
                         Operating test                    3.3
            26 56 00    SD-02 Shop Drawings
                         Luminaire drawings                1.4.1.1
                        SD-03 Product Data
                         Luminaires                        2.2
                         Lamps                             2.2.1
                         Ballasts                          2.2.2
                         Lighting contactor                2.3
                         Time switch                       2.4
                         Photocell switch                  2.5
            27 10 00    SD-02 Shop Drawings
                         Distribution frames               2.4
                        SD-03 Product Data
                         Telecommunications cabling        2.3.1

SUBMITTAL FORM,Jan 96                                                                PREVIOUS EDITION IS OBSOLETE                                                                            PAGE 12 OF 15 PAGES
                                                                                                                                                       CONTRACT NO.
                                                     SUBMITTAL REGISTER
TITLE AND LOCATION                                                                           CONTRACTOR
Design MET Facility
                                                                                                       CONTRACTOR:           CONTRACTOR                        APPROVING AUTHORITY
                                                                                                      SCHEDULE DATES           ACTION
                                                                                        G
                                                                                        O
                                                                                        V
      T                                                                       C         T
      R                                                                       L
      A                                                                       A         O
 A    N                                                                       S         R                                    A                                              A
 C    S                                                                       S                                              C                                              C
 T    M           S                                             P             I         A                                    T                                              T
 I    I           P                                             A             F         /                                    I                                              I
 V    T           E                                             R             I         E                                    O              DATE FWD                        O              MAILED
 I    T           C                                             A             C                                              N               TO APPR                        N                TO
 T    A                                                         G#            A         R                                                     AUTH/                                        CONTR/
 Y    L           S                                             R             T         E                                    C                                              C
                  E                  DESCRIPTION                A             I         V               APPROVAL MATERIAL    O      DATE    DATE RCD DATE FWD DATE RCD      O      DATE    DATE RCD
 N    N           C                                             P             O         W                NEEDED  NEEDED      D       OF       FROM   TO OTHER FROM OTH      D       OF     FRM APPR
 O    O           T                 ITEM SUBMITTED              H             N         R     SUBMIT       BY       BY       E     ACTION    CONTR REVIEWER REVIEWER        E     ACTION     AUTH         REMARKS


(a)   (b)        (c)                      (d)                       (e)           (f)           (g)         (h)        (i)   (j)     (k)       (l)       (m)          (n)   (o)      (p)      (q)             (r)

            27 10 00        Patch panels                      2.4.4
                            Telecommunications                2.6
                             outlet/connector assemblies
                            Equipment support frame           2.4.1
                            Building protector assemblies     2.4.2
                            Connector blocks                  2.4.3
                            Protector modules                 2.4.2.1
                           SD-06 Test Reports
                            Telecommunications cabling        3.3.1
                             testing
                           SD-07 Certificates
                            Contractor Qualifications         1.7.1.1
                            Manufacturer Qualifications       1.7.1.2
                            Test plan                         1.7.2
                           SD-10 Operation and Maintenance
                            Data
                            Telecommunications cabling and    3.1.1
                             pathway system
            31 11 00       SD-03 Product Data
                            Nonsaleable Materials             3.6.2       G
                           SD-04 Samples
                            Tree wound paint                  2.1
                            Herbicide                         2.2
            31 23 00.00 20 SD-01 Preconstruction Submittals
                            Earthwork Inspections             1.7.1
                            Dewatering work plan              1.7.2

SUBMITTAL FORM,Jan 96                                                                       PREVIOUS EDITION IS OBSOLETE                                                                            PAGE 13 OF 15 PAGES
                                                                                                                                                   CONTRACT NO.
                                                      SUBMITTAL REGISTER
TITLE AND LOCATION                                                                       CONTRACTOR
Design MET Facility
                                                                                                   CONTRACTOR:           CONTRACTOR                        APPROVING AUTHORITY
                                                                                                  SCHEDULE DATES           ACTION
                                                                                    G
                                                                                    O
                                                                                    V
      T                                                                   C         T
      R                                                                   L
      A                                                                   A         O
 A    N                                                                   S         R                                    A                                              A
 C    S                                                                   S                                              C                                              C
 T    M           S                                              P        I         A                                    T                                              T
 I    I           P                                              A        F         /                                    I                                              I
 V    T           E                                              R        I         E                                    O              DATE FWD                        O              MAILED
 I    T           C                                              A        C                                              N               TO APPR                        N                TO
 T    A                                                          G#       A         R                                                     AUTH/                                        CONTR/
 Y    L           S                                              R        T         E                                    C                                              C
                  E                   DESCRIPTION                A        I         V               APPROVAL MATERIAL    O      DATE    DATE RCD DATE FWD DATE RCD      O      DATE    DATE RCD
 N    N           C                                              P        O         W                NEEDED  NEEDED      D       OF       FROM   TO OTHER FROM OTH      D       OF     FRM APPR
 O    O           T                  ITEM SUBMITTED              H        N         R     SUBMIT       BY       BY       E     ACTION    CONTR REVIEWER REVIEWER        E     ACTION     AUTH         REMARKS


(a)   (b)         (c)                      (d)                    (e)         (f)           (g)         (h)        (i)   (j)     (k)       (l)       (m)          (n)   (o)      (p)      (q)             (r)

            31 23 00.00 20 SD-06 Test Reports
                            Fill and backfill                  3.13.2.1
                            Density tests                      3.13.2.2
            33 82 00       SD-02 Shop Drawings
                            Telecommunications Outside         1.6.1.1
                             Plant
                            Telecommunications Entrance        1.6.1.2
                             Facility Drawings
                           SD-03 Product Data
                            Wire and cable                     2.7
                            Cable splices, and connectors      2.4
                            Closures                           2.3
                            Building protector assemblies      2.2.1
                            Protector modules                  2.2.2
                            Spare Parts                        1.8.2
                           SD-06 Test Reports
                            Pre-installation tests             3.5.1
                            Acceptance tests                   3.5.2
                            Outside Plant Test Plan            1.6.3
                           SD-07 Certificates
                            Telecommunications Contractor      1.6.2.1
                             Qualifications
                            Key Personnel Qualifications       1.6.2.2
                           SD-08 Manufacturer’s Instructions
                            Building protector assembly        2.2.1
                             installation

SUBMITTAL FORM,Jan 96                                                                   PREVIOUS EDITION IS OBSOLETE                                                                            PAGE 14 OF 15 PAGES
                                                                                                                                           CONTRACT NO.
                                                  SUBMITTAL REGISTER
TITLE AND LOCATION                                                               CONTRACTOR
Design MET Facility
                                                                                           CONTRACTOR:           CONTRACTOR                        APPROVING AUTHORITY
                                                                                          SCHEDULE DATES           ACTION
                                                                            G
                                                                            O
                                                                            V
      T                                                           C         T
      R                                                           L
      A                                                           A         O
 A    N                                                           S         R                                    A                                              A
 C    S                                                           S                                              C                                              C
 T    M           S                                        P      I         A                                    T                                              T
 I    I           P                                        A      F         /                                    I                                              I
 V    T           E                                        R      I         E                                    O              DATE FWD                        O              MAILED
 I    T           C                                        A      C                                              N               TO APPR                        N                TO
 T    A                                                    G#     A         R                                                     AUTH/                                        CONTR/
 Y    L           S                                        R      T         E                                    C                                              C
                  E               DESCRIPTION              A      I         V               APPROVAL MATERIAL    O      DATE    DATE RCD DATE FWD DATE RCD      O      DATE    DATE RCD
 N    N           C                                        P      O         W                NEEDED  NEEDED      D       OF       FROM   TO OTHER FROM OTH      D       OF     FRM APPR
 O    O           T              ITEM SUBMITTED            H      N         R     SUBMIT       BY       BY       E     ACTION    CONTR REVIEWER REVIEWER        E     ACTION     AUTH         REMARKS


(a)   (b)        (c)                   (d)                 (e)        (f)           (g)         (h)        (i)   (j)     (k)       (l)       (m)          (n)   (o)      (p)      (q)             (r)

            33 82 00     Cable tensions                 3.1.8.1
                        SD-10 Operation and Maintenance
                         Data
                         Telecommunications outside     1.6.1.1
                          plant (OSP)
                        SD-11 Closeout Submittals
                         Record Documentation           1.8.1




SUBMITTAL FORM,Jan 96                                                           PREVIOUS EDITION IS OBSOLETE                                                                            PAGE 15 OF 15 PAGES
Design MET Facility                                    5490419


        -- End of Section --




                          SECTION 01 33 00   Page 17
Design MET Facility                                                      5490419




                                  SECTION 01 35 29

                     SAFETY AND OCCUPATIONAL HEALTH REQUIREMENTS

                                        10/08



PART 1     GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to within the text by the
 basic designation only.

            AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)

 ANSI Z359.1                         (1992; R 1999) Safety Requirements for
                                     Personal Fall Arrest Systems, Subsystems
                                     and Components

            NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

 NFPA 241                            (2004) Safeguarding Construction,
                                     Alteration, and Demolition Operations

 NFPA 51B                            (2003) Fire Prevention During Welding,
                                     Cutting, and Other Hot Work

 NFPA 70                             (2008; AMD 1 2008) National Electrical
                                     Code - 2008 Edition

 NFPA 70E                            (2004) Electrical Safety in the Workplace

            U.S. ARMY CORPS OF ENGINEERS (USACE)

 EM 385-1-1                          (2008) Safety and Health Requirements
                                     Manual

            U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

 29 CFR 1910                         Occupational Safety and Health Standards

 29 CFR 1910.146                     Permit-required Confined Spaces

 29 CFR 1910.94                      Ventilation

 29 CFR 1915                         Confined and Enclosed Spaces and Other
                                     Dangerous Atmospheres in Shipyard
                                     Employment

 29 CFR 1926                         Safety and Health Regulations for
                                     Construction

 29 CFR 1926.500                     Fall Protection



                              SECTION 01 35 29   Page 1
Design MET Facility                                                      5490419


1.2   SUBMITTALS

 The following shall be submitted in accordance with Section 01 33 00
 SUBMITTAL PROCEDURES:

      SD-01 Preconstruction Submittals

          Accident Prevention Plan (APP)

          Activity Hazard Analysis (AHA)

      SD-06 Test Reports

          Reports

          Submit reports as their incidence occurs, in accordance with the
          requirements of the paragraph entitled, "Reports."

          Accident Reports

          Monthly Exposure Reports

          Regulatory Citations and Violations

      SD-07 Certificates

          Confined Space Entry Permit

          Submit one copy of each permit/certificate attached to each Daily
          Report.

1.3   DEFINITIONS

      a. Associate Safety Professional (ASP). An individual who is currently
      certified by the Board of Certified Safety Professionals.

      b. Certified Construction Health & Safety Technician (CHST). An
      individual who is currently certified as a CHST by the Board of
      Certified Safety Professionals.

      c. Certified Industrial Hygienist (CIH). An individual who is currently
      certified as a CIH by the American Board of Industrial Hygiene.

      d. Certified Safety Professional (CSP). An individual who is currently
      certified as a CSP by the Board of Certified Safety Professionals.

      e. Certified Safety Trained Supervisor (STS). An individual who is
      currently certified as an STS by the Board of Certified Safety
      Professionals.

      f. Competent Person for Fall Protection. A person who is cabable of
      identifying hazardous or dangerous conditions in the personal fall
      arrest system or any component thereof, as well as their application
      and use with related equipment, and has the authority to take prompt
      corrective measures to eliminate the hazards of falling.

      g.   High Visibility Accident.    Any mishap which may generate publicity
      and/or high visibility.



                             SECTION 01 35 29   Page 2
Design MET Facility                                                         5490419


      h. Low-slope roof. A roof having a slope less than or equal to 4 in
      12 (vertical to horizontal).

      i. Medical Treatment. Treatment administered by a physician or by
      registered professional personnel under the standing orders of a
      physician. Medical treatment does not include first aid treatment even
      through provided by a physician or registered personnel.

      j. Multi-Employer Work Site (MEWS). A multi-employer work site, as
      defined by OSHA, is one in which many employers occupy the same site.
      The Government considers the Prime Contractor to be the "controlling
      authority" for all work site safety and health of the subcontractors.

      k. Operating Envelope. The area surrounding any crane. Inside this
      "envelope" is the crane, the operator, riggers, rigging gear between
      the hook and the load, the load and the crane's supporting structure
      (ground, rail, etc.).

      l. Qualified Person for Fall Protection. A person with a recognized
      degree or professional certifictae, extensive knowledge, training and
      experience in the field of fall protection who is capable of performing
      design, analysis, and evaluation of fall protection systems and
      equipment.

      m. Recordable Injuries or Illnesses.     Any work-related injury or
      illness that results in:

          (1)   Death, regardless of the time between the injury and death,
          or the length of the illness;

          (2)   Days away from work;

          (3)   Restricted work;

          (4)   Transfer to another job;

          (5)   Medical treatment beyond first aid;

          (6)   Loss of consciousness; or

          (7)   A significant injury or illness diagnosed by a physician or
          other licensed health care professional, even if it did not result
          in (1) through (6) above.

      n.   Site Safety and Health Officer (SSHO). The superintendent or
      other qualified or competent person who is responsible for the on-site
      safety and health required for the project. The Contractor quality
      control (QC) person cannot be the SSHO, even though the QC has safety
      inspection responsibilities as part of the QC duties.

      o. Steep roof.    A roof having a slope greater than 4 in 12 (vertical
      to horizontal).

      p.   "USACE" property and equipment specified in USACE EM 385-1-1
      should be interpreted as Government property and equipment.

      q.   Weight Handling Equipment (WHE) Accident. A WHE accident occurs
      when any one or more of the six elements in the operating envelope
      fails to perform correctly during operation, including operation during


                            SECTION 01 35 29   Page 3
Design MET Facility                                                      5490419


        maintenance or testing resulting in personnel injury or death; material
        or equipment damage; dropped load; derailment; two-blocking; overload;
        and collision, including unplanned contact between the load, crane,
        and/or other objects. A dropped load, derailment, two-blocking,
        overload and collision are considered accidents even though no material
        damage or injury occurs. A component failure (e.g., motor burnout,
        gear tooth failure, bearing failure) is not considered an accident
        solely due to material or equipment damage unless the component failure
        results in damage to other components (e.g., dropped boom, dropped
        load, roll over, etc.).

1.4     CONTRACTOR SAFETY SELF-EVALUATION CHECKLIST

 Contracting Officer will provide a "Contractor Safety Self-Evaluation
 checklist" to the Contractor at the pre-construction conference. The
 checklist will be completed monthly by the Contractor and submitted with
 each request for payment voucher. An acceptable score of 90 or greater is
 required. Failure to submit the completed safety self-evaluation checklist
 or achieve a score of at least 90, will result in a retention of up to 10
 percent of the voucher.

1.5     REGULATORY REQUIREMENTS

 In addition to the detailed requirements included in the provisions of this
 contract, work performed shall comply with USACE EM 385-1-1, and the
 following laws, ordinances, criteria, rules and regulations. Submit
 matters of interpretation of standards to the appropriate administrative
 agency for resolution before starting work. Where the requirements of this
 specification, applicable laws, criteria, ordinances, regulations, and
 referenced documents vary, the most stringent requirements shall apply.

1.6     DRUG PREVENTION PROGRAM

 Conduct a proactive drug and alcohol use prevention program for all
 workers, prime and subcontractor, on the site. Ensure that no employee
 uses illegal drugs or consumes alcohol during work hours. Ensure there are
 no employees under the influence of drugs or alcohol during work hours.
 After accidents, collect blood, urine, or saliva specimens and test the
 injured and involved employees for the influence of drugs and alcohol. A
 copy of the test shall be made available to the Contracting Officer upon
 request.

1.7     SITE QUALIFICATIONS, DUTIES AND MEETINGS

1.7.1     Personnel Qualifications

 Work performed under this contract shall meet Level 2.

1.7.1.1     Site Safety and Health Officer (SSHO)

 Site Safety and Health Officer (SSHO) shall be provided at the work site at
 all times to perform safety and occupational health management,
 surveillance, inspections, and safety enforcement for the Contractor. The
 SSHO shall meet the following requirements:


        Level 2:
            A minimum of 3 years safety work on similar project.
            30-hour OSHA construction safety class or equivalent within last 3


                             SECTION 01 35 29   Page 4
Design MET Facility                                                    5490419


           years.
           Competent person training as needed.


1.7.1.2   Certified Safety Professional (CSP) and/or Certified Industrial
hygienist (CIH)

 Provide a Certified Safety Professional (CSP) and/or Certified Industrial
 Hygienist (CIH) at the work site to perform safety and occupational health
 management, surveillance, inspections, and safety enforcement for the
 Contractor. The CSP and/or CIH shall be the safety and occupational health
 "competent person" as defined by USACE EM 385-1-1. The CSP and/or CIH
 shall have no other duties than safety and occupational health management,
 inspections, and/or industrial hygiene.

1.7.1.3   Associate Safety professional (ASP), Certified Safety Trained
Supervisor (STS) and/or Construction Health and Safety Technician (CHST).

 Provide an Associate Safety Professional (ASP); Certified Safety Trained
 Supervisor (STS); and/or Construction Health & Safety Technician (CHST) at
 the work site to perform safety management, surveillance, inspections, and
 safety enforcement for the Contractor to meet the designated safety level
 in paragraph 1.6.1. The ASP, STS, and/or CHST shall be the safety and
 occupational health "competent person" as defined by USACE EM 385-1-1. The
 ASP, STS, and/or CHST shall be at the work site at all times whenever work
 or testing is being performed and shall conduct and document daily safety
 inspections. The ASP, STS, and/or CHST shall have no other duties other
 than safety and occupational health management, inspections, and
 enforcement on this contract.

1.7.1.4    Competent Person for Confined Space Entry

 Provide a competent person meeting the requirements of EM 385-1-1 who is
 assigned in writing by the Designated Authority to assess confined spaces
 and who possesses demonstrated knowledge, skill and ability to:

      a.   Identify the structure, location, and designation of confined and
      permit-required confined spaces where work is done;

      b.   Calibrate and use testing equipment including but not limited to,
      oxygen indicators, combustible gas indicators, carbon monoxide
      indicators, and carbon dioxide indicators, and to interpret accurately
      the test results of that equipment;

      c.   Perform all required tests and inspections specified in
      29 CFR 1910.146 and 29 CFR 1915 Subpart B;

      d.   Assess hazardous conditions including atmospheric hazards in
      confined space and adjacent spaces and specify the necessary protection
      and precautions to be taken;

      e.   Determine ventilation requirements for confined space entries and
      operations;

      f.   Assess hazards associated with hot work in confined and adjacent
      space and determine fire watch requirements; and,

      g.    Maintain records required.



                            SECTION 01 35 29   Page 5
Design MET Facility                                                       5490419


 When the work involves marine operations that handle combustible or
 hazardous materials, this qualified person shall be a NFPA certified marine
 chemist.

1.7.1.5   Competent Person for the Health Hazard Control and Respiratory
Protection Program

 Provide a competent person meeting the requirements of EM 385-1-1 who is:

        a.   Capable by education, specialized training and/or experience of
        anticipating, recognizing, and evaluating employee exposure to
        hazardous chemical, physical and biological agents in accordance with
        USACE EM 385-1-1, Section 6.

        b.   Capable of spe cifying necessary controls and protective actions
        to ensure worker health.

1.7.2     Personnel Duties

1.7.2.1      Site Safety and Health Officer (SSHO)/Superintendent

        a. Conduct daily safety and health inspections and maintain a written
        log which includes area/operation inspected, date of inspection,
        identified hazards, recommended corrective actions, estimated and
        actual dates of corrections. Safety inspection logs shall be attached
        to the Contractors' daily report.

        b. Conduct mishap investigations and complete required reports.
        Maintain the OSHA Form 300 and Daily Production reports for prime and
        sub-contractors.

        c.   Maintain applicable safety reference material on the job site.

        d. Attend the pre-construction conference, pre-work meetings including
        preparatory inspection meeting, and periodic in-progress meetings.

        e.    Implement and enforce accepted APPS and AHAs.

        f.   Maintain a safety and health deficiency tracking system that
        monitors outstanding deficiencies until resolution. A list of
        unresolved safety and health deficiencies shall be posted on the safety
        bulletin board.

        g.   Ensure sub-contractor compliance with safety and health
        requirements.

        h. Ensure an approved "Special Permission Energized Electrical Work
        Permit" prior to starting any activity on energized electrical systems.

 Failure to perform the above duties will result in dismissal of the
 superintendent and/or SSHO, and a project work stoppage. The project work
 stoppage will remain in effect pending approval of a suitable replacement.

1.7.2.2   Certified Safety Professional (CSP), Certified Industrial Hygienist
(CIH), Associate Safety Professional (ASP), Certified Safety Trained
Supervisor (STS), and/or Certified Construction Health & Safety Technician
(CHST)

        a.    Perform safety and occupational health management, surveillance,


                              SECTION 01 35 29   Page 6
Design MET Facility                                                      5490419


        inspections, and safety enforcement for the project.

        b.   Perform as the safety and occupational health "competent person"
        as defined by USACE EM 385-1-1.

        c.    Be on site whenever work or testing is being performed.

        d.    Conduct and document safety inspections.

        e.   Shall have no other duties other than safety and occupational
        health management, inspections, and enforcement on this contract.

 If the CSP, CIH, ASP, STS, CHST is appointed as the SSHO all duties of that
 position shall also be performed.

1.7.3     Meetings

1.7.3.1      Preconstruction Conference

        a. The Contractor will be informed, in writing, of the date of the
        preconstruction conference. The purpose of the preconstruction
        conference is for the Contractor and the Contracting Officer's
        representatives to become acquainted and explain the functions and
        operating procedures of their respective organizations and to reach
        mutual understanding relative to the administration of the overall
        project's Accident Prevention Plan (APP) before the initiation of work.

        b. Contractor representatives who have a responsibility or significant
        role in accident prevention on the project shall attend the
        preconstruction conference. This includes the project superintendent,
        site safety and health officer, quality control supervisor, or any
        other assigned safety and health professionals who participated in the
        development of the APP (including the Activity Hazard Analyses (AHAs)
        and special plans, program and procedures associated with it).

        c. The Contractor shall discuss the details of the submitted APP to
        include incorporated plans, programs, procedures and a listing of
        anticipated AHAs that will be developed and implemented during the
        performance of the contract. This list of proposed AHAs will be
        reviewed at the conference and an agreement will be reached between the
        Contractor and the Contracting Officer's representative as to which
        phases will require an analysis. In addition, a schedule for the
        preparation, submittal, review, and acceptance of AHAs shall be
        established to preclude project delays.

        d. Deficiencies in the submitted APP will be brought to the attention
        of the Contractor at the preconstruction conference, and the Contractor
        shall revise the plan to correct deficiencies and re-submit it for
        acceptance. Work shall not begin until there is an accepted APP.

        e. The functions of a Preconstruction conference may take place at the
        Post-Awqrd Kickoff meeting for Design Build Contracts.

1.7.3.2      Weekly Safety Meetings

 Conduct weekly safety meetings at the project site for all employees.       The
 Contracting Officer will be informed of the meeting in advance and be
 allowed attendance. Minutes showing contract title, signatures of
 attendees and a list of topics discussed shall be attached to the


                              SECTION 01 35 29   Page 7
Design MET Facility                                                   5490419


 Contractors' daily report.

1.7.3.3     Work Phase Meetings

 The appropriate AHA shall be reviewed and attendance documented by the
 Contractor at the preparatory, initial, and follow-up phases of quality
 control inspection. The analysis should be used during daily inspections to
 ensure the implementation and effectiveness of safety and health controls.

1.8     TRAINING

1.8.1     New Employee Indoctrination

 New employees (prime and sub-contractor) will be informed of specific site
 hazards before they begin work. Documentation of this orientation shall be
 kept on file at the project site.

1.8.2     Periodic Training

 Provide Safety and Health Training in accordance with USACE EM 385-1-1 and
 the accepted APP. Ensure all required training has been accomplished for
 all onsite employees.

1.8.3     Training on Activity Hazard Analysis (AHA)

 Prior to beginning a new phase, training will be provided to all affected
 employees to include a review of the AHA to be implemented.

1.9     ACCIDENT PREVENTION PLAN (APP)

 The Contractor shall use a qualified person to prepare the written
 site-specific APP. Prepare the APP in accordance with the format and
 requirements of USACE EM 385-1-1 and as supplemented herein. Cover all
 paragraph and subparagraph elements in USACE EM 385-1-1, Appendix A,
 "Minimum Basic Outline for Preparation of Accident Prevention Plan". Where
 a paragraph or subparagraph element is not applicable to the work to be
 performed indicate "Not Applicable" next to the heading. Specific
 requirements for some of the APP elements are described below at paragraph
 1.8.1. The APP shall be job-specific and shall address any unusual or
 unique aspects of the project or activity for which it is written. The APP
 shall interface with the Contractor's overall safety and health program.
 Any portions of the Contractor's overall safety and health program
 referenced in the APP shall be included in the applicable APP element and
 made site-specific. The Government considers the Prime Contractor to be the
 "controlling authority" for all work site safety and health of the
 subcontractors. Contractors are responsible for informing their
 subcontractors of the safety provisions under the terms of the contract and
 the penalties for noncompliance, coordinating the work to prevent one craft
 from interfering with or creating hazardous working conditions for other
 crafts, and inspecting subcontractor operations to ensure that accident
 prevention responsibilities are being carried out. The APP shall be signed
 by the person and firm (senior person) preparing the APP, the Contractor,
 the on-site superintendent, the designated site safety and health officer
 and any designated CSP and/or CIH.

 Submit the APP to the Contracting Officer 15 calendar days prior to the
 date of the preconstruction conference for acceptance. Work cannot proceed
 without an accepted APP. The Contracting Officer reviews and comments on
 the Contractor's submitted APP and accepts it when it meets the


                              SECTION 01 35 29   Page 8
Design MET Facility                                                      5490419


 requirements of the contract provisions.

 Once accepted by the Contracting Officer, the APP and attachments will be
 enforced as part of the contract. Disregarding the provisions of this
 contract or the accepted APP will be cause for stopping of work, at the
 discretion of the Contracting Officer, until the matter has been rectified.

 Once work begins, changes to the accepted APP shall be made with the
 knowledge and concurrence of the Contracting Officer, project
 superintendent, SSHO and quality control manager. Should any unforeseen
 hazard become evident during the performance of work, the project
 superintendent shall inform the Contracting Officer, both verbally and in
 writing, for resolution as soon as possible. In the interim, all necessary
 action shall be taken by the Contractor to restore and maintain safe
 working conditions in order to safeguard onsite personnel, visitors, the
 public, and the environment.

 Copies of the accepted plan will be maintained at the resident engineer's
 office and at the job site. The APP shall be continuously reviewed and
 amended, as necessary, throughout the life of the contract. Unusual or
 high-hazard activities not identified in the original APP shall be
 incorporated in the plan as they are discovered.

1.9.1    EM 385-1-1 Contents

 In addition to the requirements outlines in Appendix A of USACE EM 385-1-1,
 the following is required:

        a. Names and qualifications (resumes including education, training,
        experience and certifications) of all site safety and health personnel
        designated to perform work on this project to include the designated
        site safety and health officer and other competent and qualified
        personnel to be used such as CSPs, CIHs, STSs, CHSTs. The duties of
        each position shall be specified.

        b. Qualifications of competent and of qualified persons. As a
        minimum, competent persons shall be designated and qualifications
        submitted for each of the following major areas: excavation;
        scaffolding; fall protection; hazardous energy; confined space; health
        hazard recognition, evaluation and control of chemical, physical and
        biological agents; personal protective equipment and clothing to
        include selection, use and maintenance.

        c. Confined Space Entry Plan. Develop a confined space entry plan in
        accordance with USACE EM 385-1-1, applicable OSHA standards 29 CFR 1910,
        29 CFR 1915, and 29 CFR 1926, and any other federal, state and local
        regulatory requirements identified in this contract. Identify the
        qualified person's name and qualifications, training, and experience.
        Delineate the qualified person's authority to direct work stoppage in
        the event of hazardous conditions. Include procedure for rescue by
        contractor personnel and the coordination with emergency responders.
        (If there is no confined space work, include a statement that no
        confined space work exists and none will be created.)

        d. Health Hazard Control Program. The Contractor shall designate a
        competent and qualified person to establish and oversee a Health Hazard
        Control Program in accordance with USACE EM 385-1-1, Section 6. The
        program shall ensure that employees, on-site Government
        representatives, and others, are not adversely exposed to chemical,


                               SECTION 01 35 29   Page 9
Design MET Facility                                                       5490419


       physical and biological agents and that necessary controls and
       protective actions are instituted to ensure health.

       e.   Alcohol and Drug Abuse Plan

            (1) Describe plan for random checks and testing with
            pre-employment screening in accordance with the DFAR Clause
            subpart 252.223-7004, "Drug Free Work Force."

            (2)   Description of the on-site prevention program

       f. Fall Protection and Prevention (FP&P) Plan. The plan shall be site
       specific and address all fall hazards in the work place and during
       different phases of construction. It shall address how to protect and
       prevent workers from falling to lower levels when they are exposed to
       fall hazards above 1.8 m (6 feet). A qualified person for fall
       protection shall prepare and sign the plan. The plan shall include
       fall protection and prevention systems, equipment and methods employed
       for every phase of work, responsibilities, assisted rescue self-rescue
       and evacuation procedures, training requirements, and monitoring
       methods. Fall Protection and Prevention Plan shall be revised every
       six months for lengthy projects, reflecting any changes during the
       course of construction due to changes in personnel, equipment, systems
       or work habits. The accepted Fall Protection and Prevention Plan shall
       be kept and maintained at the job site for the duration of the
       project. The Fall Protection Plan shall be included in the Accident
       Prevention Plan (APP)

       g. Training Records and Requirements. List of mandatory training and
       certifications which are applicable to this project (e.g. explosive
       actuated tools, confined space entry, fall protection, crane operation,
       vehicle operator, forklift operators, personal protective equipment);
       list of requiremetns for periodic retraining/certification; outline
       requirements for supervisory and employee safety meetings.

       h. Site Safety and Health Plan. The safety and health aspects prepared
       in accordance with Section 01 35 30 Safety Health and Emergency
       Response (HTRW/UST).

       i. Excavation Plan. The safety and health aspects prepared in
       accordance with Section 31 23 00.00 20, Excavation and Fill.

1.10   ACTIVITY HAZARD ANALYSIS (AHA)

 The Activity Hazard Analysis (AHA) format shall be in accordance with USACE
 EM 385-1-1. Submit the AHA for review at least 15 calendar days prior to
 the start of each phase. Format subsequent AHA as amendments to the APP.
 An AHA will be developed by the Contractor for every operation involving a
 type of work presenting hazards not experienced in previous project
 operations or where a new work crew or subcontractor is to perform work.
 The analysis must identify and evaluate hazards and outline the proposed
 methods and techniques for the safe completion of each phase of work. At a
 minimum, define activity being performed, sequence of work, specific safety
 and health hazards anticipated, control measures (to include personal
 protective equipment) to eliminate or reduce each hazard to acceptable
 levels, equipment to be used, inspection requirements, training
 requirements for all involved, and the competent person in charge of that
 phase of work. For work with fall hazards, including fall hazards
 associated with scaffold erection and removal, identify the appropriate


                             SECTION 01 35 29   Page 10
Design MET Facility                                                      5490419


 fall protection methods used. For work with materials handling equipment,
 address safeguarding measures related to materials handling equipment. For
 work requiring excavations, include requirements for safeguarding
 excavations. An activity requiring an AHA shall not proceed until the AHA
 has been accepted by the Contracting Officer's representative and a meeting
 has been conducted by the Contractor to discuss its contents with everyone
 engaged in the activity, including on-site Government representatives. The
 Contractor shall document meeting attendance at the preparatory, initial,
 and follow-up phases of quality control inspection. The AHA shall be
 continuously reviewed and, when appropriate, modified to address changing
 site conditions or operations. The analysis should be used during daily
 inspections to ensure the implementation and effectiveness of the
 activity's safety and health controls.

 The AHA list will be reviewed periodically (at least monthly) at the
 Contractor supervisory safety meeting and updated as necessary when
 procedures, scheduling, or hazards change.

 Activity hazard analyses shall be updated as necessary to provide an
 effective response to changing work conditions and activities. The on-site
 superintendent, site safety and health officer and competent persons used
 to develop the AHAs, including updates, shall sign and date the AHAs before
 they are implemented.

 The activity hazard analyses shall be developed using the project schedule
 as the basis for the activities performed. Any activities listed on the
 project schedule will require an AHA. The AHAs will be developed by the
 contractor, supplier or subcontractor and provided t othe prime contractor
 for submittal to the Contracting Offficer.

1.11   DISPLAY OF SAFETY INFORMATION

 Within 1 calendar days after commencement of work, erect a safety bulletin
 board at the job site. The following information shall be displayed on the
 safety bulletin board in clear view of the on-site construction personnel,
 maintained current, and protected against the elements and unauthorized
 removal:

       a.   Map denoting the route to the nearest emergency care facility.

       b.   Emergency phone numbers.

       c.   Copy of the most up-to-date APP.

       d.   Current AHA(s).

       e.   OSHA 300A Form.

       f.   OSHA Safety and Health Protection-On-The-Job Poster.

       g.   Confined space entry permit.

       h.   Hot work permit.

       i. A sign indicating the number of hours worked since last lost
       workday accident.

       j.   Safety and Health Warning Posters.



                               SECTION 01 35 29   Page 11
Design MET Facility                                                       5490419


1.12     SITE SAFETY REFERENCE MATERIALS

 Maintain safety-related references applicable to the project, including
 those listed in the article "References." Maintain applicable equipment
 manufacturer's manuals.

1.13     EMERGENCY MEDICAL TREATMENT

 Contractors will arrange for their own emergency medical treatment.
 Government has no responsibility to provide emergency medical treatment.

1.14     REPORTS

1.14.1     Accident Reports

         a. For recordable injuries and illnesses, and property damage
         accidents resulting in at least $2,000 in damages, the Prime Contractor
         shall conduct an accident investigation to establish the root cause(s)
         of the accident, complete the Navy Contractor Significant Incident
         Report (CSIR) form or USACE Accident Report Form 3394 and provide the
         report to the Contracting Officer within 1 calendar day(s) of the
         accident. The Contracting Officer will provide copies of any required
         or special forms.

         b. For a weight handling equipment accident (including rigging gear
         accidents) the Prime Contractor shall conduct an accident investigation
         to establish the root cause(s) of the accident, complete the WHE
         Accident Report (Crane and Rigging Gear) form and provide the report to
         the Contracting Officer within 30 calendar days of the accident. Crane
         operations shall not proceed until cause is determined and corrective
         actions have been implemented to the satisfaction of the Contracting
         Officer. The Contracting Officer will provide a blank copy of the
         accident report form.

1.14.2     Accident Notification

 Notify the Contracting Officer as soon as practical, but not later than
 four hours, after any accident meeting the definition of Recordable
 Injuries or Illnesses or High Visibility Accidents, property damage equal
 to or greater than $2,000, or any weight handling equipment accident.
 Information shall include contractor name; contract title; type of
 contract; name of activity, installation or location where accident
 occurred; date and time of accident; names of personnel injured; extent of
 property damage, if any; extent of injury, if known, and brief description
 of accident (to include type of construction equipment used, PPE used,
 etc.). Preserve the conditions and evidence on the accident site until the
 Government investigation team arrives on site and Government investigation
 is conducted.

1.14.3     Monthly Exposure Reports

 Monthly exposure reporting to the Contracting Officer is required to be
 attached to the monthly billing request. This report is a compilation of
 employee-hours worked each month for all site workers, both prime and
 subcontractor. The Contracting Officer will provide copies of any special
 forms.




                              SECTION 01 35 29   Page 12
Design MET Facility                                                       5490419


1.14.4     Regulatory Citations and Violations

 Contact the Contracting Officer immediately of any OSHA or other regulatory
 agency inspection or visit, and provide the Contracting Officer with a copy
 of each citation, report, and contractor response. Correct violations and
 citations promptly and provide written corrective actions to the
 Contracting Officer.

1.15     HOT WORK

 Prior to performing "Hot Work" (welding, cutting, etc.) or operating other
 flame-producing/spark producing devices, a written permit shall be
 requested from the Fire Division. CONTRACTORS ARE REQUIRED TO MEET ALL
 CRITERIA BEFORE A PERMIT IS ISSUED. The Contractor will provide at least
 two (2) twenty (20) pound 4A:20 BC rated extinguishers for normal "Hot
 Work". All extinguishers shall be current inspection tagged, approved
 safety pin and tamper resistant seal. It is also mandatory to have a
 designated FIRE WATCH for any "Hot Work" done at this activity. The Fire
 Watch shall be trained in accordance with NFPA 51B and remain on-site for a
 minimum of 30 minutes after completion of the task or as specified on the
 hot work permit.

         a. Oil painting materials (paint, brushes, empty paint cans, etc.),
         and all flammable liquids shall be removed from the facility at
         quitting time. All painting materials and flammable liquids shall be
         stored outside in a suitable metal locker or box and will require
         re-submittal with non-hazardous materials.

         b. Accumulation of trays, paper, shavings, sawdust, boxes and other
         packing materials shall be removed from the facility at the close of
         each workday and such material disposed of in the proper containers
         located away from the facility.

         c. The storage of combustible supplies shall be a safe distance from
         structures.

         d. Area outside the facility undergoing work shall be cleaned of
         trash, paper, or other discarded combustibles at the close of each
         workday.

         e. All portable electric devices (saws, sanders, compressors,
         extension chord, lights, etc.) shall be disconnected at the close of
         each workday. When possible, the main electric switch in the facility
         shall be deactivated.

         f. When starting work in the facility, Contractors shall require their
         personnel to familiarize themselves with the location of the nearest
         fire alarm boxes and place in memory the emergency phone number 911.
         ANY FIRE, NO MATTER HOW SMALL, SHALL BE REPORTED IMMEDIATELY.

         g. Obtain services from th FIRE DIVISION for "HOT WORK" within or
         around flammable materials (such as fuel systems, welding/cutting on
         fuel pipes) or confined spaces (such as sewer wet wells, manholes,
         vaults, etc.) that have the potential for flammable or explosive
         atmospheres.




                             SECTION 01 35 29    Page 13
Design MET Facility                                                   5490419


PART 2     PRODUCTS

2.1     CONFINED SPACE SIGNAGE

 The Contractor shall provide permanent signs integral to or securely
 attached to access covers for all required confined spaces. Signs
 wording: "DANGER--PERMIT-REQUIRED CONFINED SPACE - DO NOT ENTER -" in bold
 letters a minimum of 25 mm(one inch) in height and constructed to be
 clearly legible with all paint removed. The signal word "DANGER" shall be
 red and readable from 1.52 m(5 feet).

2.2     FALL PROTECTION ANCHORAGE

 Fall protection anchorage, conforming to ANSI Z359.1, installed under the
 supervision of a qualified person in fall protection, shall be left in
 place for continued customer use and so identified by signage stating the
 capacity of the anchorage (strength and number of persons who may be
 tied-off to it at any one time).

PART 3     EXECUTION

3.1     CONSTRUCTION AND/OR OTHER WORK

 The Contractor shall comply with USACE EM 385-1-1, NFPA 241, the APP, the
 AHA, Federal and/or State OSHA regulations, and other related submittals
 and activity fire and safety regulations. The most stringent standard
 shall prevail.

3.1.1     Hazardous Material Use

 Each hazardous material must receive approval prior to being brought onto
 the job site or prior to any other use in connection with this contract.
 Allow a minimum of 10 working days for processing of the request for use of
 a hazardous material. Any work or storage involving hazardous chemicals or
 materials must be done in a manner that will not expose Government or
 Contractor employees to any unsafe or unhealthful conditions. Adequate
 protective measures must be taken to prevent Government or Contractor
 employees from being exposed to any hazardous condition that could result
 from the work or storage. The Prime Contractor shall keep a complete
 inventory of hazardous materials brought onto the work-site. Approval by
 the Contracting Officer of protective measures and storage area is required
 prior to the start of the work.

3.1.2     Hazardous Material Exclusions

 Notwithstanding any other hazardous material used in this contract,
 radioactive materials or instruments capable of producing
 ionizing/non-ionizing radiation (with the exception of radioactive material
 and devices used in accordance with USACE EM 385-1-1 such as nuclear
 density meters for compaction testing and laboratory equipment with
 radioactive sources) as well as materials which contain asbestos, mercury
 or polychlorinated biphenyls, di-isocynates, lead-based paint are
 prohibited. The Contracting Officer, upon written request by the
 Contractor, may consider exceptions to the use of any of the above excluded
 materials.

3.1.3     Unforeseen Hazardous Material

 The design should have identified materials such as PCB, lead paint, and


                            SECTION 01 35 29   Page 14
Design MET Facility                                                   5490419


 friable and non-friable asbestos. If additional material, not indicated,
 that may be hazardous to human health upon disturbance during construction
 operations is encountered, stop that portion of work and notify the
 Contracting Officer immediately. Within 14 calendar days the Government
 will determine if the material is hazardous. If material is not hazardous
 or poses no danger, the Government will direct the Contractor to proceed
 without change. If material is hazardous and handling of the material is
 necessary to accomplish the work, the Government will issue a modification
 pursuant to "FAR 52.243-4, Changes" and "FAR 52.236-2, Differing Site
 Conditions."

3.2     PRE-OUTAGE COORDINATION MEETING

 Contractors are required to apply for utility outages at least 15 days in
 advance. As a minimum, the request should include the location of the
 outage, utilities being affected, duration of outage and any necessary
 sketches. Special requirements for electrical outage requests are
 contained elsewhere in this specification section. Once approved, and
 prior to beginning work on the utility system requiring shut down, the
 Contractor shall attend a pre-outage coordination meeting with the
 Contracting Officer to review the scope of work and the lock-out/tag-out
 procedures for worker protection. No work will be performed on energized
 electrical circuits unless proof is provided that no other means exist.

3.3     FALL HAZARD PROTECTION AND PREVENTION

 The Contractor shall establish a fall protection and prevention program,
 for the protection of all employees exposed to fall hazards. The program
 shall include company policy, identify responsibilities, education and
 training requirements, fall hazard identification, prevention and control
 measures, inspection, storage, care and maintenance of fall protection
 equipment and rescue and escape procedures.

3.3.1     Training

 The Contractor shall institute a fall protection training program. As part
 of the Fall Hazard Protection and Prevention Program, the Contractor shall
 provide training for each employee who might be exposed to fall hazards. A
 competent person for fall protection shall provide the training. Training
 requirements shall be in accordance with USACE EM 385-1-1, section 21.A.16.

3.3.2     Fall Protection Equipment

 The Contractor shall enforce use of the fall protection equipment
 designated for each specific work activity in the Fall Protection and
 Prevention Plan and/or AHA at all times when an employee is on a surface
 1.8 m(6 feet) or more above lower levels. Fall protection systems such as
 guardrails, personnel fall arrest system, safety nets, etc., are required
 when working within 1.8m (6 feet) of any leading edge. In addition to the
 required fall protection systems, safety skiff, personal floatation
 devices, life rings etc., are required when working above or next to water
 in accordance with USACE EM 385-1-1, paragraphs 05.I. and 05.J. Personal
 fall arrest systems are required when working from an articulating or
 extendible boom, swing stages, or suspended platform. In addition,
 personal fall arrest systems may be required when operating other equipment
 such as scissor lifts if the work platform is capable of being positioned
 outside the wheelbase. The need for tying-off in such equipment is to
 prevent ejection of the employee from the equipment during raising,
 lowering, or travel. Fall protection must comply with 29 CFR 1926.500,


                            SECTION 01 35 29    Page 15
Design MET Facility                                                      5490419


 Subpart M and USACE EM 385-1-1.

3.3.2.1      Personal Fall Arrest Equipment

 Personal fall arrest equipment, systems, subsystems, and components shall
 meet ANSI Z359.1. Only a full-body harness with a shock-absorbing lanyard
 or self-retracting lanyard is an acceptable personal fall arrest device.
 Body belts may only be used as a positioning device system (for uses such
 as steel reinforcing assembly and in addition to an approved fall arrest
 system). Harnesses shall have a fall arrest attachment affixed to the body
 support (usually a Dorsal D-ring) and specifically designated for
 attachment to the rest of the system. Only locking snap hooks and
 carabiners shall be used. Webbing, straps, and ropes shall be made of
 synthetic fiber. The maximum free fall distance when using fall arrest
 equipment shall not exceed 1.8 m (6 feet). The total fall distance and any
 swinging of the worker (pendulum-like motion) that can occur during a fall
 shall always be taken into consideration when attaching a person to a fall
 arrest system.

3.3.3     Fall Protection for Roofing Work

 Fall protection controls shall be implemented based on the type of roof
 being constructed and work being performed. The roof area to be accessed
 shall be evaluated for its structural integrity including weight-bearing
 capabilities for the projected loading.

        a.   Low Sloped Roofs:

             (1) For work within 1.8 m (6 feet) of an edge, on low-slope
             roofs, personnel shall be protected from falling by use of
             personal fall arrest systems, guardrails, or safety nets. A
             safety monitoring system is not adequate fall protection and is
             not authorized.

             (2) For work greater than 1.8 m (6 feet) from an edge, warning
             lines shall be erected and installed in accordance with
             29 CFR 1926.500 and USACE EM 385-1-1.

        b. Steep Roofs: Work on steep roofs requires a personal fall arrest
        system, guardrails with toe-boards, or safety nets. This requirement
        also includes residential or housing type construction.

3.3.4     Safety Nets

 If safety nets are used as the selected fall protection system on the
 project, they shall be provided at unguarded workplaces, leading edge work
 or when working over water, machinery, dangerous operations and or other
 surfaces where the use of ladders, scaffolds, catch platforms, temporary
 floors, fall arrest systems or restraint/positioning systems are
 impractical. Safety nets shall be tested immediately after installation
 with a drop test of 181.4 kg (400 pounds) dropped from the same elevation a
 person might fall, and every six months thereafter.

3.3.5     Existing Anchorage

 Existing anchorages, to be used for attachment of personal fall arrest
 equipment, shall be certified (or re-certified) by a qualified person for
 fall protection in accordance with ANSI Z359.1. Exiting horizontal
 lifeline achorages shall be certified (or re-certified) by a registered


                               SECTION 01 35 29   Page 16
Design MET Facility                                                   5490419


 professional engineer with experience in designing horizontal lifeline
 systems.

3.3.6     Horizontal Lifelines

 Horizontal lifelines shall be designed, installed, certified and used under
 the supervision of a qualified person for fall protection as part of a
 complete fall arrest system which maintains a safety factor of 2 (
 29 CFR 1926.500).

3.3.7     Guardrail Systems

 Guardrails shall consist of top and mid-rails, post and toe boards. The
 top edge height of standard railing must be 42 inches plus or minus 3
 inches above the walking/working level. When mid-rails are used, they must
 be installed at a height midway between the top edge of the guardrail
 system and the walking/working level. Posts shall be placed no more than 8
 feet apart (29 CFR 1926.500 and USACE EM 385-1-1).

3.3.8     Rescue and Evacuation Procedures

 When personal fall arrest systems are used, the contracator must ensure
 that the mishap victim can self-rescue or can be rescued promptly should a
 fall occur. A Rescue and Evacuation Plan shall be prepared by the
 contractor and include a detailed discussion of the following: methods of
 rescue; methods of self-rescue; equipment used; training requirement;
 specialized training for the rescuers; procedures for requesting rescue and
 medical assistance; and transportation routes to a medical facility. The
 Rescue and Evaluation Plan shall be included in the Activity Hazard
 Analysis (AHA) for the phase of work, in the Fall Protection and Prevention
 (FP&P) Plan, and the Accident Prevention Plan (APP).

3.4     PERSONAL PROTECTIVE EQUIPMENT

 All personnel who enter a construction site area shall wear Personal
 Protective Equipment (PPE) at all times as outlined in the EM 385 1-1. In
 addition to the requirements of the EM 385 1-1, Safety Glasses (ANSI Z87.1)
 and High-Visibility Apparel (ANSI 107-2004 Performance Class II, Shirt or
 Vest) will be worn at all times on construction sites. Hearing protection
 is required in noise hazard areas or when performing noise hazard tasks.
 Mandatory PPE on all construction sites includes:

        a.   Hard Hats

        b.   Safety Glasses

        c.   High-Visibility Shirt or Vest

        d.   Safety-Toed Shoes or Boots

3.5     SCAFFOLDING

 Employees shall be provided with a safe means of access to the work area on
 the scaffold. Climbing of any scaffold braces or supports not specifically
 designed for access is prohibited. Access to scaffold platforms greater
 than 6 m (20 feet) in height shall be accessed by use of a scaffold stair
 system. Vertical ladders commonly provided by scaffold system
 manufacturers shall not be used for accessing scaffold platforms greater
 than 6 m (20 feet) in height. The use of an adequate gate is required.


                              SECTION 01 35 29   Page 17
Design MET Facility                                                       5490419


 Contractor shall ensure that employees are qualified to perform scaffold
 erection and dismantling. Do not use scaffold without the capability of
 supporting at least four times the maximum intended load or without
 appropriate fall protection as delineated in the accepted fall protection
 and prevention plan. Stationary scaffolds must be attached to structural
 building components to safeguard against tipping forward or backward.
 Special care shall be given to ensure scaffold systems are not overloaded.
 Side brackets used to extend scaffold platforms on self-supported scaffold
 systems for the storage of material is prohibited. The first tie-in shall
 be at the height equal to 4 times the width of the smallest dimension of
 the scaffold base. Work platforms shall be placed on mud sills. Scaffold
 or work platform erectors shall have fall protection during the erection
 and dismantling of scaffolding or work platforms that are more than six
 feet. Delineate fall protection requirements when working above six feet
 or above dangerous operations in the Fall Protection and Prevention (FP&P)
 Plan and Activity Hazard Analysis (AHA) for the phase of work.

3.5.1     Stilts

 The use of stilts for gaining additional height in construction,
 renovation, repair or maintenance work is prohibited.

3.6     EQUIPMENT

3.6.1     Material Handling Equipment

        a. Material handling equipment such as forklifts shall not be modified
        with work platform attachments for supporting employees unless
        specifically delineated in the manufacturer's printed operating
        instructions.

        b. The use of hooks on equipment for lifting of material must be in
        accordance with manufacturer's printed instructions.

        c.   Operators of forklifts or power industrial trucks shall be
        licensed in accordance with OSHA.

3.7     EXCAVATIONS

 The competent person for excavations performed as a result of contract work
 shall be on-site when excavation work is being performed, and shall
 inspect, and document the excavations daily prior to entry by workers. The
 competent person must evaluate all hazards, including atmospheric, that may
 be associated with the work, and shall have the resources necessary to
 correct hazards promptly. The competent person shall perform soil
 classification in accordance with 29 CFR 1926.

3.7.1     Utility Locations

 Prior to digging, the appropriate digging permit must be obtained. All
 underground utilities in the work area must be positively identified by a
 private utility locating service in addition to any station locating
 service and coordinated with the station utility department. Any markings
 made during the utility investigation must be maintained throughout the
 contract.

3.7.2     Utility Location Verification

 The Contractor must physically verify underground utility locations by hand


                              SECTION 01 35 29   Page 18
Design MET Facility                                                   5490419


 digging using wood or fiberglass handled tools when any adjacent
 construction work is expected to come within three feet of the underground
 system. Digging within .061 m (2 feet) of a known utility must not be
 performed by means of mechanical equipment; hand digging shall be used. If
 construction is parallel to an existing utility the utility shall be
 exposed by hand digging every 30.5 m (100 feet) if parallel within 1.5 m (5
 feet) of the excavation.

3.7.3     Utilities with Concrete Slabs

 Utilities located within concrete slabs or pier decks, bridges, and the
 like are extremely difficult to identify. The location must be coordinated
 with station utility departments in addition to a private locating
 service. Outages on system utilities shall be used in circumstances where
 concrete chipping, saw cutting, or core drilling is required and utilities
 are unable to be completely identified.

3.7.4     Shoring Systems

 Trench and shoring systems must be identified in the accepted safety plan
 and AHA. Manufacture tabulated data and specifications or registered
 engineer tabulated data for shoring or benching systems shall be readily
 available on site for review. Job-made shoring or shielding shall have the
 registered professional engineer stamp, specifications, and tabulated
 data. Extreme care must be used when excavating near direct burial
 electric underground cables.

3.7.5     Trenching Machinery

 Trenching machines with digging chain drives shall be operated only when
 the spotters/laborers are in plain view of the operator. Operator and
 spotters/laborers shall be provided training on the hazards of the digging
 chain drives with emphasis on the distance that needs to be maintained when
 the digging chain is operating. Documentation of the training shall be kept
 on file at the project site.

3.8     ELECTRICAL

3.8.1     Conduct of Electrical Work

 Underground electrical spaces must be certified safe for entry before
 entering to conduct work. Cables that will be cut must be positively
 identified and de-energized prior to performing each cut. Positive cable
 identification must be made prior to submitting any outage request for
 electrical systems. Arrangements are to be coordinated with the
 Contracting Officer and Station Utilities for identification. The
 Contracting Officer will not accept an outage request until the Contractor
 satisfactorily documents that the circuits have been clearly identified.
 Perform all high voltage cable cutting remotely using hydraulic cutting
 tool. When racking in or live switching of circuit breakers, no additional
 person other than the switch operator will be allowed in the space during
 the actual operation. Plan so that work near energized parts is minimized
 to the fullest extent possible. Use of electrical outages clear of any
 energized electrical sources is the preferred method. When working in
 energized substations, only qualified electrical workers shall be permitted
 to enter. When work requires Contractor to work near energized circuits as
 defined by the NFPA 70, high voltage personnel must use personal protective
 equipment that includes, as a minimum, electrical hard hat, safety shoes,
 insulating gloves with leather protective sleeves, fire retarding shirts,


                            SECTION 01 35 29   Page 19
Design MET Facility                                                        5490419


 coveralls, face shields, and safety glasses. In addition, provide
 electrical arc flash protection for personnel as required. Insulating
 blankets, hearing protection, and switching suits may be required,
 depending on the specific job and as delineated in the Contractor's AHA.

3.8.2     Portable Extension Cords

 Portable extension cords shall be sized in accordance with manufacturer
 ratings for the tool to be powered and protected from damage. All damaged
 extension cords shall be immediately removed from service. Portable
 extension cords shall meet the requirements of NFPA 70.

3.8.3     Special Permission Energized Electrical Work Permit

 All work on energized electrical systems, including high voltage, must have
 an approved "Special Permission Energized Electrical Work Permit." The
 results of a Arc Flash risk/Hazard Analysis, per NFPA 70E, shall be
 included in the "Special Permission Energized Electrical Work Permit"
 request.

 Flame-resistant (FR) clothing and personel protective equipment (PPE) shall
 be rated for a minimum of 8 calories per square centimeter even if the
 flash hazard analysis indicates a lower value. A blank copy of the permit
 request is attached. An editable version may be obtained from the
 Contracting Officer.

3.9     WORK IN CONFINED SPACES

 The Contractor shall comply with the requirements in Section 06.I of USACE
 EM 385-1-1 and OSHA 29 CFR 1910.146. Any potential for a hazard in the
 confined space requires a permit system to be used.

        a. Entry Procedures. Prohibit entry into a confined space by
        personnel for any purpose, including hot work, until the qualified
        person has conducted appropriate tests to ensure the confined or
        enclosed space is safe for the work intended and that all potential
        hazards are controlled or eliminated and documented. (See Section
        06.I.05 of USACE EM 385-1-1 for entry procedures.) All hazards
        pertaining to the space shall be reviewed with each employee during
        review of the AHA.

        b. Forced air ventilation is required for all confined space entry
        operations and the minimum air exchange requirements must be maintained
        to ensure exposure to any hazardous atmosphere is kept below its'
        action level.

        c. Ensure the use of rescue and retrieval devices in confined spaces
        greater than 1.5 m (5 feet) in depth. Conform to Sections 06.I.09,
        06.I.10 and 06.I.11 of USACE EM 385-1-1.

        d. Sewer wet wells require continuous atmosphere monitoring with
        audible alarm for toxic gas detection.

        e. Include training information for employees who will be involved as
        entrants and attendants for the work. Conform to Section 06.I.06 of
        USACE EM 385-1-1.

        f. Daily Entry Permit. Post the permit in a conspicuous place close
        to the confined space entrance.


                            SECTION 01 35 29   Page 20
Design MET Facility                                                   5490419



3.10     CRYSTALLINE SILICA

 Grinding, abrasive blasting, and foundry operations of construction
 materials containing crystalline silica, shall comply with OSHA
 regulations, such as 29 CFR 1910.94, and USACE EM 385-1-1, Appendix C. The
 Contractor shall develop and implement effective exposure control and
 elimination procedures to include dust control systems, engineering
 controls, and establishment of work area boundaries, as well as medical
 surveillance, training, air monitoring, and personal protective equipment.

3.11     HOUSEKEEPING

3.11.1     Clean-Up

 All debris in work areas shall be cleaned up daily or more frequently if
 necessary. Construction debris may be temporarily located in an approved
 location, however garbage accumulation must be removed each day.

3.11.2     Falling Object Protection

 All areas must be barricaded to safeguard employees. When working
 overhead, barricade the area below to prevent entry by unauthorized
 employees. Construction warning tape and signs shall be posted so they are
 clearly visible from all possible access points. When employees are
 working overhead all tools and equipment shall be secured so that they will
 not fall. When using guardrail as falling object protection, all openings
 shall be small enough to prevent passage of potential falling objects.

         -- End of Section --




                              SECTION 01 35 29   Page 21
Design MET Facility                                                   5490419




                                 SECTION 01 42 00

                      SOURCES FOR REFERENCE PUBLICATIONS

                                      01/07


PART 1   GENERAL

1.1   REFERENCES

 Various publications are referenced in other sections of the specifications
 to establish requirements for the work. These references are identified in
 each section by document number, date and title. The document number used
 in the citation is the number assigned by the standards producing
 organization, (e.g.   ASTM B 564 Nickel Alloy Forgings). However, when the
 standards producing organization has not assigned a number to a document,
 an identifying number has been assigned for reference purposes.

1.2   ORDERING INFORMATION

 The addresses of the standards publishing organizations whose documents are
 referenced in other sections of these specifications are listed below, and
 if the source of the publications is different from the address of the
 sponsoring organization, that information is also provided. Documents
 listed in the specifications with numbers which were not assigned by the
 standards producing organization should be ordered from the source by title
 rather than by number. The designations "AOK" and "LOK" are for
 administrative purposes and should not be used when ordering publications.

          ACI INTERNATIONAL (ACI)
          P.O. Box 9094
          Farmington Hills, MI 48333-9094
          Ph:   248-848-3700
          Fax: 248-848-3701
          Internet: http://www.aci-int.org
          AOK 5/01
          LOK 2/01

          ALUMINUM ASSOCIATION (AA)
          900 19th Street N.W.
          Washington, DC 20006
          Ph:   202-862-5100
          Fax: 202-862-5164
          Internet: http://www.aluminum.org
          AOK 5/01
          LOK 2/01

          AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
          1827 Walden Ofc. Sq.
          Suite 104
          Schaumburg, IL 60173-4268
          Ph:   847-303-5664
          Fax: 847-303-5774
          Internet: http://www.aamanet.org
          AOK 5/01
          LOK 2/01


                             SECTION 01 42 00   Page 1
Design MET Facility                                                   5490419



          AMERICAN ASSOCIATION OF STATE HIGHWAY AND TRANSPORTATION OFFICIALS
          (AASHTO)
          444 N. Capital St., NW, Suite 249
          Washington, DC 20001
          Ph:   800-231-3475 202-624-5800
          Fax: 800-525-5562 202-624-5806
          Internet: http://www.transportation.org
          AOK 5/01
          LOK 2/01

          AMERICAN CONFERENCE OF GOVERNMENTAL INDUSTRIAL HYGIENISTS (ACGIH)
          1330 Kemper Meadow Dr.
          Suite 600
          Cincinnati, OH 45240
          Ph:   513-742-2020
          Fax: 513-742-3355
          Internet: http://www.acgih.org
          E-mail: pubs@acgih.org
          AOK 5/01
          LOK 2/01

          AMERICAN HARDBOARD ASSOCIATION (AHA)
          c/o Composite Panel Association
          18922 Premiere Court
          Gaithersburg, MD 20879-1574
          Ph:   301-670-0604
          Fax: 301-840-1252
          Internet: http://www.pbmdf.org

          AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
          One East Wacker Dr., Suite 3100
          Chicago, IL 60601-2001
          Ph:   312-670-2400
          Publications: 800-644-2400
          Fax: 312-670-5403
          Internet: http://www.aisc.org
          AOK 5/01
          LOK 3/01

          AMERICAN IRON AND STEEL INSTITUTE (AISI)
          1101 17th St., NW Suite 1300
          Washington, DC 20036
          Ph: 202-452-7100
          Internet: http://www.steel.org
          AOK 5/01
          LOK 3/01

          AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
          1819 L Street, NW, 6th Floor
          Washington, DC 20036
          Ph:   202-293-8020
          Fax: 202-293-9287
          Internet: http://www.ansi.org/

          Note --- Documents beginning with the letter "S" can be ordered
          from:

          Acoustical Society of America


                          SECTION 01 42 00   Page 2
Design MET Facility                                       5490419


          Standards and Publications Fulfillment Center
          P. O. Box 1020
          Sewickley, PA 15143-9998
          Ph:   412-741-1979
          Fax: 412-741-0609
          Internet: http://asa.aip.org
          General e-mail: asa@aip.org
          Publications e-mail: asapubs@abdintl.com
          AOK 5/01
          LOK 6/00

          ASTM INTERNATIONAL (ASTM)
          100 Barr Harbor Drive, P.O. Box C700
          West Conshohocken, PA 19428-2959
          Ph:   610-832-9585
          Fax: 610-832-9555
          Internet: http://www.astm.org
          E-mail: service@astm.org
          AOK 5/01
          LOK 3/01

          AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
          1801 Alexander Bell Drive
          Reston, VA 20191-4400
          Ph:   703-295-6300 - 800-548-2723
          Fax: 703-295-6222
          Internet: http://www.asce.org
          e-mail: marketing@asce.org
          AOK 5/01
          LOK 3/01

          AMERICAN WATER WORKS ASSOCIATION(AWWA)
          6666 West Quincy
          Denver, CO 80235
          Ph: 800-926-7337 - 303-794-7711
          Fax: 303-794-7310
          Internet: http://www.awwa.org
          AOK 5/01
          LOK 3/01

          AMERICAN WELDING SOCIETY (AWS)
          550 N.W. LeJeune Road
          Miami, FL 33126
          Ph:   800-443-9353 - 305-443-9353
          Fax: 305-443-7559
          Internet: http://www.amweld.org
          AOK 5/01
          LOK 3/01

          ASME INTERNATIONAL (ASME)
          Three Park Avenue
          New York, NY 10016-5990
          Ph:   212-591-7722
          Fax: 212-591-7674
          Internet: http://www.asme.org
          AOK 5/01
          LOK 6/00




                          SECTION 01 42 00    Page 3
Design MET Facility                                                   5490419


          BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)
          355 Lexington Ave.
          17th floor
          New York, NY 10017-6603
          Ph: 212-297-2122
          Fax: 212-370-9047
          Internet: http://www.buildershardware.com
          AOK 5/01
          LOK 6/00

          CONCRETE REINFORCING STEEL INSTITUTE (CRSI)
          933 N. Plum Grove Rd.
          Schaumburg, IL 60173-4758
          Ph:   847-517-1200
          Fax: 847-517-1206
          Internet: http://www.crsi.org/
          AOK 5/01
          LOK 6/00

          ELECTRONIC INDUSTRIES ALLIANCE (EIA)
          2500 Wilson Blvd.
          Arlington, VA 22201-3834
          Ph: 703-907-7500
          Fax: 703-907-7501
          Internet: http://www.eia.org
          AOK 5/01
          LOK 6/00

          FOUNDATION FOR CROSS-CONNECTION CONTROL AND HYDRAULIC RESEARCH
          (FCCCHR)
          University of South California
          Kaprielian Hall 200
          Los Angeles, CA 90089-2531
          Ph:   213-740-2032
          Fax: 213-740-8399
          Internet: http://www.usc.edu/dept/fccchr
          AOK 5/01
          LOK 6/00

          ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA (IESNA)
          120 Wall St., 17th Floor
          New York, NY 10005-4001
          Ph:   212-248-5000
          Fax: 212-248-5017
          Internet: http://www.iesna.org
          AOK 5/01
          LOK 6/00

          INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
          445 Hoes Ln, P. O. Box 1331
          Piscataway, NJ 08855-1331
          Ph:   732-981-0060 OR 800-701-4333
          Fax: 732-981-9667
          Internet: http://www.ieee.org
          E-mail: customer.services@ieee.org
          AOK 5/01
          LOK 6/00




                          SECTION 01 42 00   Page 4
Design MET Facility                                                   5490419


          INSULATED CABLE ENGINEERS ASSOCIATION (ICEA)
          P.O. Box 440
          South Yarmouth, MA 02664
          Ph:   508-394-4424
          Fax: 508-394-1194
          E-mail:
          Internet: http://www.icea.net
          AOK 5/01
          LOK 6/00

          INTERNATIONAL CODE COUNCIL (ICC)
          5203 Leesburg Pike, Suite 600
          Falls Church, VA 22041
          Ph:   703-931-4533
          Fax: 703-379-1546
          Internet: http://www.intlcode.org
          AOK 5/01
          LOK 6/00

          MASTER PAINTERS INSTITUTE (MPI)
          4090 Graveley Street
          Burnaby, BC CANADA V5C 3T6
          PH: 888-674-8937
          Fx: 888-211-8708
          Internet: http://www.paintinfo.com/mpi
          AOK 9/01
          LOK 0/00

          METAL BUILDING MANUFACTURERS ASSOCIATION (MBMA)
          1300 Sumner Ave.
          Cleveland, OH 44115-2851
          Ph:    216-241-7333
          Fax: 216-241-0105
          Internet: http://www.mbma.com
          e-mail: mbma@mbma.com
          AOK 5/01
          LOK 6/00

          NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)
          8 S. Michigan Ave, Suite 1000
          Chicago, IL 60603
          Ph:   312-782-4951
          Fax: 312-332-0405
          Internet: http://www.naamm.org
          e-mail: naamm@gss.net
          AOK 5/01
          LOK 6/00

          NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
          1300 N. 17th St., Suite 1847
          Rosslyn, VA 22209
          Ph:   703-841-3200
          Fax: 703-841-3300
          Internet: http://www.nema.org/
          AOK 5/01
          LOK 6/00

          NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
          1 Batterymarch Park


                          SECTION 01 42 00    Page 5
Design MET Facility                                                   5490419


          P.O. Box 9101
          Quincy, MA 02269-9101
          Ph:   617-770-3000
          Fax: 617-770-0700
          Internet: http://www.nfpa.org
          AOK 5/01
          LOK 8/00

          NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY (NIST)
          100 Bureau Drive
          Stop 3460
          Gaithersburg, MD 20899-3460
          Ph: 301-975-NIST
          Internet: http://www.nist.gov
          Order Publications From:
          Superintendent of Documents
          U.S. Government Printing Office
          732 North Capitol Street, NW
          Mailstop: SDE
          Washington, DC 20401
          Ph: 202-512-1530
          Fax: 202-512-1262
          Internet: http://www.gpo.gov
          or
          National Technical Information Services (NTIS)
          5285 Port Royal Rd.
          Springfield, VA 22161
          Ph: 703-605-6000
          Fax: 703-605-6900
          Internet: http://www.ntis.gov
          AOK 5/01
          LOK 6/00

          NATIONAL ROOFING CONTRACTORS ASSOCIATION (NRCA)
          10255 W. higgins Rd., Suite 600
          Rosemont, IL 60018
          Ph:   847-299-9070
          Fax: 847-299-1183
          Internet: http://www.nrca.net
          AOK 5/01
          LOK 6/00

          SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION
          (SMACNA)
          4201 Lafayette Center Drive
          Chantilly, VA 20151-1209
          Ph:   703-803-2980
          Fax: 703-803-3732
          E-mail: info@smacna.org
          Internet: http://www.smacna.org

          SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)
          400 Commonwealth Dr.
          Warrendale, PA 15096-0001
          Ph:   724-776-4841
          Fax: 724-776-5760
          Internet: http://www.sae.org
          e-mail: custsvc@sae.org
          AOK 5/01


                          SECTION 01 42 00   Page 6
Design MET Facility                                                      5490419


          LOK 6/00

          STATE OF NORTH CAROLINA DEPARTMENT OF TRANSPORTATION (NCDOT)
          No. 1 South Wilmington Street
          P.O. Box 25201
          Raleigh, NC 27611
          phone:    919-733-2520
          fax:      919-733-9150
          Internet:

          STEEL DOOR INSTITUTE (SDI/DOOR)
          30200 Detroit Rd.
          Cleveland, OH 44145-1967
          Ph:   440-899-0010
          Fax: 440-892-1404
          Internet: http://www.steeldoor.org
          AOK 5/01
          LOK 6/00

          THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)
          40 24th Street, 6th Floor
          Pittsburgh, PA 15222-4656
          Ph: 412-281-2331
          Fax: 412-281-9992
          Internet: http://www.sspc.org
          AOK 5/01
          LOK 6/00

          UNDERWRITERS LABORATORIES (UL)
          333 Pfingsten Rd.
          Northbrook, IL 60062-2096
          Ph: 847-272-8800
          Fax: 847-272-8129
          Internet: http://www.ul.com/
          e-mail: northbrook@us.ul.com
          AOK 5/01
          LOK 6/00

          U.S. ARMY CORPS OF ENGINEERS (USACE)
          Order CRD-C DOCUMENTS from:
          U.S. Army Engineer Waterways Experiment Station
          ATTN: Technical Report Distribution Section, Services
          Branch, TIC
          3909 Halls Ferry Rd.
          Vicksburg, MS 39180-6199
          Ph:   601-634-2664
          Fax: 601-634-2388
          Internet: http://www.wes.army.mil/SL/MTC/handbook/handbook.htm

          Order Other Documents from:
          USACE Publications Depot
          Attn: CEIM-SP-D
          2803 52nd Avenue
          Hyattsville, MD 20781-1102
          Ph: 301-394-0081
          Fax: 301-394-0084
          Internet: http://www.usace.army.mil/publications
               or   http://www.hnd.usace.army.mil/techinfo/index.htm
          AOK 5/01


                          SECTION 01 42 00   Page 7
Design MET Facility                                          5490419


          LOK 6/00

          U.S. DEPARTMENT OF AGRICULTURE (USDA)
          Order AMS Publications from:
          AGRICULTURAL MARKETING SERVICE (AMS)
          Seed Regulatory and Testing Branch
          USDA, AMS, LS Div.
          Room 209, Bldg. 306, BARC-East
          Beltsville, MD 20705-2325
          Ph:   301-504-9430
          Fax: 301-504-8098
          Internet: http://www.ams.usda.gov/nop/
          e-mail: jeri.irwin@usda.gov

          Order Other Publications from:
          U.S. Department of Agriculture
          14th and Independence Ave., SW, Room 4028-S
          Washington, DC 20250
          Ph:   202-720-2791
          Fax: 202-720-2166
          Internet: http://www.usda.gov
          AOK 5/01
          LOK 6/00

          U.S. DEPARTMENT OF COMMERCE (DOC)
          Order Publications From:
          National Technical Information Service
          5285 Port Royal Road
          Springfield, VA 22161
          Ph:   703-605-6000
          Fax: 703-605-6900
          Internet: http://www.ntis.gov
          AOK 5/01
          LOK 6/00

          U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)
          Ariel Rios Building
          1200 Pennsylvania Avenue, N.W.
          Washington, DC 20460
          Ph:   202-260-2090
          FAX: 202-260-6257
          Internet: http://www.epa.gov

          NOTE --- Some documents are available only from:
          National Technical Information Services (NTIS)
          5285 Port Royal Rd.
          Springfield, VA 22161
          Ph: 703-605-6000
          Fax: 703-605-6900
          Internet: http://www.ntis.gov
          AOK 5/01
          LOK 6/00

          U.S. FEDERAL HIGHWAY ADMINISTRATION (FHWA)
          Office of Highway Safety (HHS-31)
          400 Seventh St., SW
          Washington, DC 20590-0001
          Ph:   202-366-0411
          Fax: 202-366-2249


                          SECTION 01 42 00   Page 8
Design MET Facility                                                  5490419


          Internet: http://www.fhwa.dot.gov
          Order from:

          Superintendant of Documents
          U. S. Government Printing Office
          732 North Capitol Street, NW
          Mailstop: SDE
          Washington, DC 20401
          Ph: 202-512-1530
          Fax: 202-512-1262
          Internet: http://www.gpo.gov
          AOK 5/01
          LOK 6/00

          U.S. GENERAL SERVICES ADMINISTRATION (GSA)
          Order from:
          General Services Administration
          Federal Supply Service Bureau
          470 E L'Enfant Plaza, S.W., Suite 8100
          Washington, DC 20407
          Ph: 202-619-8925
          Fx: 202-619-8978
          Internet: http://www.fss.gsa.gov/pub/fed-specs.cfm
          AOK 5/01
          LOK 6/00

          U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
          700 Pennsylvania Avenue, N.W.
          Washington, D.C. 20408
          Phone: 800-234-8861
          Internet: http://www.nara.gov

          Order documents from:
          Superintendent of Documents
          U.S.Government Printing Office
          732 North Capitol Street, NW
          Washington, DC 20401
          Mailstop: SDE
          Ph: 202-512-1530
          Fax: 202-512-1262
          Internet: http://www.gpo.gov
          E-mail:    gpoaccess@gpo.gov
          AOK 5/01

        -- End of Section --




                           SECTION 01 42 00   Page 9
Design MET Facility                                                         5490419




                                     SECTION 01 45 10

                                     QUALITY CONTROL

                                           09/01

PART 1        GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to in the text by the
 basic designation only.

               ASTM INTERNATIONAL (ASTM)

 ASTM A 880                             (1996) Criteria for Use in Evaluation of
                                        Testing Laboratories and Organizations for
                                        Examination and Inspection of Steel,
                                        Stainless Steel, and Related Alloys

 ASTM C 1077                            (2005a) Laboratories Testing Concrete and
                                        Concrete Aggregates for Use in
                                        Construction and Criteria for Laboratory
                                        Evaluation

 ASTM D 3666                            (2000) Minimum Requirements for Agencies
                                        Testing and Inspecting Bituminous Paving
                                        Materials

 ASTM D 3740                            (1999c) Agencies Engaged in the Testing
                                        and/or Inspection of Soil and Rock as Used
                                        in Engineering Design and Construction

 ASTM E 329                             (2008) Standard Specification for Agencies
                                        Engaged in the Testing and/or Inspection
                                        of Materials Used in Construction

 ASTM E 543                             (1999) Evaluating Agencies that Perform
                                        Nondestructive Testing

1.2   SUBMITTALS

 Submit the following in accordance with Section 01 33 00, "Submittal
 Procedures."

         SD-11 Closeout Submittals

               Quality Control Plan (QC PLAN)

 Submit a QC plan within 15 calendar days after receipt of Notice of Award.

1.3   INFORMATION FOR THE CONTRACTING OFFICER

 Deliver the following to the Contracting Officer:

         a.    Combined Contractor Production Report/Contractor Quality Control


                               SECTION 01 45 10    Page 1
Design MET Facility                                                        5490419


             Report (1 sheet): Original and 1 copy, by 10:00 AM the next work
             ing day after each day that work is performed;

        b.   QC Specialist Reports and Test Results: Originals and 1 copy, by
             10:00 AM the next working day after each day that work is per
             formed;

        c.   Testing Plan and Log, 1 copy, at the end of each month;

        d.   QC Meeting Minutes:    1 copy, within 2 calendar days of the meeting;

        e.   Rework Items List:    1 copy, by the last working day of the month
             and;

        f.   QC Certifications:    As required by the paragraph entitled "QC
             Certifications".

1.4     QC PROGRAM REQUIREMENTS

 Establish and maintain a QC program as described in this section. The QC
 program consists of a QC Organization, a QC Plan, attending a QC Plan meet
 ing, attending a Coordination and Mutual Understanding Meeting, conducting
 QC meetings, performing three phases of control, performing submittal
 review, ensuring testing is performed, and preparing QC certifications and
 documentation necessary to provide materials, equipment, workmanship,
 fabrication, construction and operations which comply with the requirements
 of this Contract. The QC program shall cover construction operations on-
 site and off-site and shall be keyed to the proposed construction sequence.

1.5     QC ORGANIZATION

1.5.1     QC Manager

1.5.1.1      Duties

 Provide a QC Manager at the work site to manage and implement the QC
 program. The QC Manager is required to attend the QC Plan meeting, attend
 the Coordination and Mutual Understanding Meeting, conduct the QC meetings,
 perform the three phases of control, perform submittal review, ensure
 testing is performed and prepare QC certifications and documentation
 required in this Contract. The QC Manager is responsible for managing and
 coordinating the three phases of control and documentation performed by the
 QC specialists. In addition to managing and implementing the QC program,
 the QC Manager may perform the duties of project superintendent.

1.5.1.2      Qualifications

 An individual with a minimum of five years experience as a foreman, super
 intendent, inspector, QC Manager, project manager, or construction manager
 on similar size construction contracts which included the major trades that
 are part of this Contract.

1.5.1.3      Construction Quality Management Training

 In addition to the above experience and education requirements, the QC
 Manager shall have completed the course entitled "Construction Quality
 Management for Contractors." This course is periodically offered by the
 Navy and the Corps of Engineers. However, it is sponsered by both the AGC
 and the ABC of Charlotte, North Carolina. Call one of the following to


                              SECTION 01 45 10   Page 2
Design MET Facility                                                          5490419


 sign up for the next available class:

 The Army Corps of Engineers, Baltimore District;
 (Offered in Baltimore, MD)
 Contact: Corps of Engineers, Baltimore District
 10 South Howard Street
 Baltimore, MD 21201
 Phone: 410-962-2323

 The Associated General Contractors (AGC), Virginia Chapter
 in Cooperation with the Army Corps of Engineers, Norfolk District, and
 the Naval Facilities Engineering Command, Atlantic Division.
 (Offered at rotating locations in Norfolk, Williamsburg, and Richmond)
 Contact: AGC of Virginia
 8631 Maylan Drive, Parham Park
 Richmond, VA 23294
 Phone: 804-346-3383

 Carolinas Associated General Contractors (CACG)
 Contact: CACG
 1100 Euclid Avenue
 Charlotte, NC 28203
 Phone: 704-372-1450 (ext. 5248)

 Associated Builders and Contractors (ABC), Carolinas Chapter
 Contact: ABC, Carolinas Chapter
 3705 Latrobe Drive
 Charlotte, NC 28211
 Phone: 704-367-1331
    or: 877-470-4819

1.5.2     Alternate QC Manager Duties and Qualifications

 Designate an alternate for the QC Manager at the work site to serve in the
 event of the designated QC Manager's absence. The period of absence may
 not exceed two weeks at one time, and not more than 30 workdays during a
 calendar year. The qualification requirements for the Alternate QC Manager
 shall be three years of experience in one of the specified positions.

1.6     QC PLAN

1.6.1     Requirements

 Provide for approval by the Contracting Officer, a QC plan submitted in a
 3-ring binder with pages numbered sequentially that covers, both on-site
 and off-site work and includes, the following:

        a.    A table of contents listing the major sections identified with
              tabs in the following order:

             I.       QC ORGANIZATION
             II.      NAMES AND QUALIFICATIONS
             III.     DUTIES, RESPONSIBILITY AND AUTHORITY OF QC PERSONNEL
             IV.      OUTSIDE ORGANIZATIONS
             V.       APPOINTMENT LETTERS
             VI.      SUBMITTAL PROCEDURES AND INITIAL SUBMITTAL REGISTER
             VII.     TESTING LABORATORY INFORMATION
             VIII.    TESTING PLAN AND LOG
             IX.      PROCEDURES TO COMPLETE REWORK ITEMS


                              SECTION 01 45 10   Page 3
Design MET Facility                                                        5490419


           X.       DOCUMENTATION PROCEDURES
           XI.      LIST OF DEFINABLE FEATURES
           XII.     PROCEDURES FOR PERFORMING THE THREE PHASES OF CONTROL
           XIII.    PERSONNEL MATRIX
           XIV.     PROCEDURES FOR COMPLETION INSPECTION

      b.    A chart showing the QC organizational structure and its
            relationship to the production side of the organization.

      c.    Names and qualifications, in resume format, for each person in the
            QC organization.

      d.    Duties, responsibilities and authorities of each person in the QC
            organization.

      e.    A listing of outside organizations such as, architectural and
            consulting engineering firms that will be employed by the
            Contractor and a description of the services these firms will
            provide.

      f.    A letter signed by an officer of the firm appointing the QC
            Manager and stating that he/she is responsible for managing and
            implementing the QC program as described in this contract.
            Include in this letter the QC Manager's authority to direct the
            removal and replacement of non-conforming work.

      g.    Procedures for reviewing, approving and managing submittals.
            Provide the names of the persons in the QC organization authorized
            to review and certify submittals prior to approval.

      h.    Testing laboratory information required by the paragraphs entitled
            "Accredited Laboratories" or "Testing Laboratory Requirements", as
            applicable.

      i.    A Testing Plan and Log that includes the tests required,
            referenced by the specification paragraph number requiring the
            test, the frequency, and the person responsible for each test.

      j.    Procedures to identify, record, track and complete rework items.

      k.    Documentation procedures, including proposed report formats.

      l.    A list of the definable features of work. A definable feature of
            work is a task which is separate and distinct from other tasks and
            requires separate control requirements. As a minimum, if approved
            by the Contracting Officer, consider each Section of the
            Specifications as a definable feature of work. However, at times,
            there may be more than one definable feature of work in each
            Section of the Specifications.

      m.    A personnel matrix showing, for each section of the specification,
            who will perform and document the three phases of control, and who
            will perform and document the testing.

      o.    Procedures for Identifying and Documenting the Completion
            Inspection process. Include in these procedures the responsible
            party for punch out inspection, prefinal inspection, and final
            acceptance inspection.



                            SECTION 01 45 10   Page 4
Design MET Facility                                                   5490419


1.6.2     Preliminary Work Authorized Prior to Approval

 The only work that is authorized to proceed prior to the approval of the QC
 plan is mobilization of storage and office trailers and surveying.

1.6.3     Approval

 Approval of the QC plan is required prior to the start of construction.
 The Contracting Officer reserves the right to require changes in the QC
 plan and operations as necessary to ensure the specified quality of work.
 The Contracting Officer reserves the right to interview any member of the
 QC organization at any time in order to verify his/her submitted
 qualifications.

1.6.4     Notification of Changes

 Notify the Contracting Officer, in writing, of any proposed change,
 including changes in the QC organization personnel, a minimum of seven
 calendar days prior to a proposed change. Proposed changes must be
 approved by the Contracting Officer.

1.7     QC PLAN MEETING

 Prior to submission of the QC plan, meet with the Contracting Officer to
 discuss the QC plan requirements of this Contract. The purpose of this
 meeting is to develop a mutual understanding of the QC plan requirements
 prior to plan development and submission.

1.8     COORDINATION AND MUTUAL UNDERSTANDING MEETING

 After submission of the QC Plan, but prior to the start of construction,
 meet with the Contracting Officer to discuss the QC program required by
 this Contract. The purpose of this meeting is to develop a mutual
 understanding of the QC details, including forms to be used for
 documentation, administration for on-site and off-site work, and the
 coordination of the Contractor's management, production and QC personnel
 with the Contracting Officer. As a minimum, the Contractor's personnel
 required to attend shall include the project manager, project
 superintendent, and QC Manager. Minutes of the meeting shall be prepared
 by the QC Manager and signed by both the Contractor and the Contracting
 Officer.

1.9     QC MEETINGS

 After the start of construction, the QC Manager shall conduct weekly QC
 meetings at the work site with the project superintendent and QC
 specialists. The QC Manager shall prepare the minutes of the meeting and
 provide a copy to the Contracting Officer within 2 working days after the
 meeting. The Contracting Officer may attend these meetings. The QC
 Manager shall notify the Contracting Officer at least 48 hours in advance
 of each meet ing. As a minimum, the following shall be accomplished at
 each meeting:

        a.   Review the minutes of the previous meeting;

        b.   Review the schedule and the status of work:

             - Work or testing accomplished since last meeting
             - Rework items identified since last meeting


                              SECTION 01 45 10   Page 5
Design MET Facility                                                       5490419


             - Rework items completed since last meeting;

        c.    Review the status of submittals:

             - Submittals reviewed and approved since last meeting
             - Submittals required in the near future;

        d.    Review the work to be accomplished in the next 2 weeks and documen
              tation required. Schedule the three phases of control and testing:

             -   Establish completion dates for rework items
             -   Preparatory phases required
             -   Initial phases required
             -   Follow-up phases required
             -   Testing required
             -   Status of off-site work or testing
             -   Documentation required;

        e.    Resolve QC and production problems; and

        f.    Address items that may require revising the QC plan:

             - Changes in QC organization personnel
             - Changes in procedures.

1.9.1    THREE PHASES OF CONTROL

 The QC Manager shall perform the three phases of control to ensure that
 work complies with Contract requirements. The Three Phases of Control
 shall adequately cover both on-site and off-site work and shall include the
 following for each definable features of work: A definable feature of work
 is a task which is separate and distinct from other tasks and requires
 separate control requirements.

1.9.2    Preparatory Phase

 Notify the Contracting Officer at least 48 hours in advance of each
 preparatory phase. Conduct the preparatory phase with the superintendent,
 and the foreman responsible for the definable feature. Document the
 results of the preparatory phase actions in the daily Contractor Quality
 Control Report. Perform the following prior to beginning work on each
 definable feature of work:

        a.    Review each paragraph of the applicable specification sections;

        b.    Review the Contract drawings;

        c.    Verify that appropriate shop drawings and submittals for materials
              and equipment have been submitted and approved. Verify receipt of
              approved factory test results, when required;

        d.    Review the testing plan and ensure that provisions have been made
              to provide the required QC testing;

        e.    Examine the work area to ensure that the required preliminary work
              has been completed;

        f.    Examine the required materials, equipment and sample work to
              ensure that they are on hand and conform to the approved shop


                                SECTION 01 45 10   Page 6
Design MET Facility                                                         5490419


             drawings and submitted data;

        g.   Review the safety plan and appropriate activity hazard analysis to
             ensure that applicable safety requirements are met, and that
             required Material Safety Data Sheets (MSDS) are submitted; and

        h.   Discuss construction methods

1.9.3    Initial Phase

 Notify the Contracting Officer at least 48 hours in advance of each initial
 phase. When construction crews are ready to start work on a definable
 feature of work, conduct the initial phase with the QC Specialists, the
 super intendent, and the foreman responsible for that definable feature of
 work. Observe the initial segment of the definable feature of work to
 ensure that the work complies with Contract requirements. Document the
 results of the initial phase in the daily Contractor Quality Control
 Report. Repeat the initial phase for each new crew to work on-site, or
 when acceptable levels of specified quality are not being met. Perform the
 following for each definable feature of work:

        a.   Establish the quality of workmanship required;

        b.   Resolve conflicts;

        c.   Review the Safety Plan and the appropriate activity hazard
             analysis to ensure that applicable safety requirements are met; and

        d.   Ensure that testing is performed by an approved laboratory.

1.9.4    Follow-Up Phase

 Perform the following for on-going work daily, or more frequently as
 necessary until the completion of each definable feature of work and
 document in the daily Contractor Quality Control Report:

        a.   Ensure the work is in compliance with Contract requirements;

        b.   Maintain the quality of workmanship required;

        c.   Ensure that testing is performed by an approved laboratory; and

        d.   Ensure that rework items are being corrected.

1.9.5    Notification of Three Phases of Control for Off-Site Work

 Notify the Contracting Officer at least two weeks prior to the start of the
 preparatory and initial phases.

1.10    SUBMITTAL REVIEW

 Procedures for submittals are as described in Section entitled "Submittal
 Procedures."

1.11    TESTING

 Except as stated otherwise in the specification sections, perform sampling
 and testing required under this Contract.



                             SECTION 01 45 10   Page 7
Design MET Facility                                                        5490419


1.11.1        Testing Laboratory Requirements

 Provide an independent testing laboratory or establish a laboratory quali
 fied to perform sampling and tests required by this Contract. When the
 proposed testing laboratory is not accredited by an acceptable
 accreditation program as described by the paragraph entitled "Accredited
 Laboratories", submit to the Contracting Officer for approval, certified
 statements signed by an official of the testing laboratory attesting that
 the proposed laboratory meets or conforms to the following requirements:

         a.    Sampling and testing shall be under the technical direction of a
               Registered Professional Engineer (P.E) with at least 5 years of
               experience in construction material testing.

         b.    Laboratories engaged in testing of concrete and concrete
               aggregates shall meet the requirements of ASTM C 1077.

         c.    Laboratories engaged in testing of bituminous paving materials
               shall meet the requirements of ASTM D 3666.

         d.    Laboratories engaged in testing of soil and rock, as used in
               engineering design and construction, shall meet the requirements
               of ASTM D 3740.

         e.    Laboratories engaged in inspection and testing of steel, stainless
               steel, and related alloys will be evaluated according to ASTM A 880.
               Laboratories shall meet the requirements of ASTM E 329.

         f.    Laboratories engaged in nondestructive testing (NDT) shall meet
               the requirements of ASTM E 543.

         g.    Laboratories engaged in hazardous materials testing shall meet the
               requirements of OSHA and EPA.

1.11.2        Accredited Laboratories

 Acceptable accreditation programs are the National Institute of Standards
 and Technology (NIST) National Voluntary Laboratory Accreditation Program
 (NVLAP), the American Association of State Highway and Transportation
 Officials (AASHTO) program and the American Association for Laboratory
 Accreditation (A2LA) program. Furnish to the Contracting Officer, a copy
 of the Certificate of Accreditation, Scope of Accreditation and latest
 directory of the accrediting organization for accredited laboratories. The
 scope of the laboratory's accreditation shall include the test methods
 required by the Contract.

1.11.3        Inspection of Testing Laboratories

 Prior to approval of non-accredited laboratories, the proposed testing
 laboratory facilities and records shall be subject to inspection by the
 Contracting Officer. Records subject to inspection include equipment
 inventory, equipment calibration dates and procedures, library of test
 procedures, audit and inspection reports by agencies conducting laboratory
 evaluations and certifications, testing and management personnel
 qualifications, test report forms, and the internal QC procedures.

1.11.4        Capability Check

 The Contracting Officer retains the right to check laboratory equipment in


                                 SECTION 01 45 10   Page 8
Design MET Facility                                                        5490419


 the proposed laboratory and the laboratory technician's testing procedures,
 techniques, and other items pertinent to testing, for compliance with the
 standards set forth in this Contract.

1.11.5        Test Results

 Cite applicable Contract requirements, tests or analytical procedures
 used. Provide actual results and include a statement that the item tested
 or analyzed conforms or fails to conform to specified requirements.
 Conspicuously stamp the cover sheet for each report in large red letters
 "CONFORMS" or "DOES NOT CONFORM" to the specification requirements,
 whichever is applicable. Test results shall be signed by a testing
 laboratory representative authorized to sign certified test reports.
 Furnish the signed reports, certifications, and other documentation to the
 Contracting Officer via the QC Manager. Furnish a summary report of field
 tests at the end of each month. Attach a copy of the summary report to the
 last daily Contractor Quality Control Report of each month.

1.12     QC CERTIFICATIONS

1.12.1        Contractor Quality Control Report Certification

 Each Contractor Quality Control Report shall contain the following
 statement: "On behalf of the Contractor, I certify that this report is
 complete and correct and equipment and material used and work performed
 during this reporting period is in compliance with the contract drawings
 and specifications to the best of my knowledge, except as noted in this
 report".

1.12.2        Invoice Certification

 Furnish a      certificate to the Contracting Officer with each payment request,
 signed by      the QC Manager, attesting that as-built drawings are current and
 attesting      that the work for which payment is requested, including stored
 material,      is in compliance with contract requirements.

1.12.3        Completion Certification

 Upon completion of work under this Contract, the QC Manager shall furnish a
 certificate to the Contracting Officer attesting that "the work has been
 completed, inspected, tested and is in compliance with the Contract".

1.13     DOCUMENTATION

 Maintain current and complete records of on-site and off-site QC program
 operations and activities.

1.13.1        Contractor Production Report

 Reports are required for each day that work is performed and shall be
 attached to the Contractor Quality Control Report prepared for the same
 day. Account for each calendar day throughout the life of the Contract.
 The reporting of work shall be identified by terminology consistent with
 the construction schedule. Contractor Production Reports are to be
 prepared, signed and dated by the project superintendent and shall contain
 the following information:

         a.    Date of report, report number, name of contractor, contract
               number, title and location of Contract and superintendent present.


                                SECTION 01 45 10   Page 9
Design MET Facility                                                          5490419



         b.    Weather conditions in the morning and in the afternoon including
               maximum and minimum temperatures.

         c.    A list of Contractor and subcontractor personnel on the work site,
               their trades, employer, work location, description of work
               performed and hours worked.

         e.    A list of job safety actions taken and safety inspections
               conducted. Indicate that safety requirements have been met
               including the results on the following:

               (1) Was a job safety meeting held this date? (If YES, attach a
               copy of the meeting minutes.)

               (2) Were there any lost time accidents this date? (If YES, attach
               a copy of the completed OSHA report.)

               (3) Was crane/manlift/trenching/scaffold/hv electrical/high
               work/hazmat work done? (If YES, attach a statement or checklist
               showing inspection performed.)

               (4) Was hazardous material/waste released into the environment?
               (If YES, attach a description of incident and proposed action.)

         f.    A list of safety actions taken today and safety inspections
               conducted.

         g.    A list of equipment/material received each day that is
               incorporated into the job.

         h.    A list of construction and plant equipment on the work site
               including the number of hours used, idle and down for repair.

         i.    Include a "remarks" section in this report which will contain
               pertinent information including directions received, problems
               encountered during construction, work progress and delays,
               conflicts or errors in the drawings or specifications, field
               changes, safety hazards encountered, instructions given and
               corrective actions taken, delays encountered and a record of
               visitors to the work site.

1.13.2        Contractor Quality Control Report

 Reports are required for each day that work is performed and for every
 seven consecutive calendar days of no-work and on the last day of a no-work
 period. Account for each calendar day throughout the life of the
 Contract. The reporting of work shall be identified by terminology
 consistent with the construction schedule. Contractor Quality Control
 Reports are to be prepared, signed and dated by the QC Manager and shall
 contain the following information:

         a.    Identify the control phase and the definable feature of work.

         b.    Results of the Preparatory Phase meetings held including the
               location of the definable feature of work and a list of personnel
               present at the meeting. Indicate in the report that for this
               definable feature of work, the drawings and specifications have
               been reviewed, submittals have been approved, materials comply


                               SECTION 01 45 10   Page 10
Design MET Facility                                                           5490419


               with approved submittals, materials are stored properly,
               preliminary work was done correctly, the testing plan has been
               reviewed, and work methods and schedule have been discussed.

         c.    Results of the Initial Phase meetings held including the location
               of the definable feature of work and a list of personnel present
               at the meeting. Indicate in the report that for this definable
               feature of work the preliminary work was done correctly, samples
               have been prepared and approved, the workmanship is satisfactory,
               test results are acceptable, work is in compliance with the
               Contract, and the required testing has been performed and include
               a list of who performed the tests.

         d.    Results of the Follow-up Phase inspections held including the
               location of the definable feature of work. Indicate in the report
               for this definable feature of work that the work complies with the
               Contract as approved in the Initial Phase, and that required
               testing has been performed and include a list of who performed the
               tests.

         e.    Results of the three phases of control for off-site work, if
               applicable, including actions taken.

         f.    List the rework items identified, but not corrected by close of
               business.

         g.    List the rework items corrected from the rework items list along
               with the corrective action taken.

         h.    Include a "remarks" section in this report which will contain
               pertinent information including directions received, quality
               control problem areas, deviations from the QC plan, construction
               deficiencies encountered, QC meetings held, acknowledgement that
               as-built drawings have been updated, corrective direction given by
               the QC Organization and corrective action taken by the Contractor.

         i.    Contractor Quality Control Report certification.

1.13.3        Testing Plan and Log

 As tests are performed, the QC Manager shall record on the "Testing Plan
 and Log" the date the test was conducted, the date the test results were
 forwarded to the Contracting Officer, remarks and acknowledgement that an
 accredited or Contracting Officer approved testing laboratory was used.
 Attach a copy of the updated "Testing Plan and Log" to the last daily
 Contractor Quality Control Report of each month.

1.13.4        Rework Items List

 The QC Manager shall maintain a list of work that does not comply with the
 Contract, identifying what items need to be reworked, the date the item was
 originally discovered, and the date the item was corrected. There is no
 requirement to report a rework item that is corrected the same day it is
 discovered. Attach a copy of the "Contractor Rework Items List" to the
 last daily Contractor Quality Control Report of each month. The Contractor
 shall be responsible for including on this list items needing rework
 including those identified by the Contracting Officer.




                                  SECTION 01 45 10   Page 11
Design MET Facility                                                           5490419


1.13.5        As-Built Drawings

 The QC Manager is required to review the as-built drawings required by
 Section 01 11 00, "Summary of Work", to ensure that as-built drawings are
 kept current on a daily basis and marked to show deviations which have been
 made from the Contract drawings. The QC Manager shall initial each
 deviation and each revision. Upon completion of work, the QC Manager shall
 furnish a certificate attesting to the accuracy of the as-built drawings
 prior to submission to the Contracting Officer.

1.13.6        Report Forms

 The following forms, which are attached at the end of this section, are
 acceptable for providing the information required by the paragraph entitled
 "Documentation". While use of these specific formats are not required, any
 other format used shall contain the same information:

         a.    Combined Contractor Production Report and Contractor Quality
               Control Report (1 sheet), with separate continuation sheet

         b.    Testing Plan and Log

         c.    Rework Items List

PART 2        PRODUCTS

 Not used.

PART 3        EXECUTION

 Not used.




                                  SECTION 01 45 10   Page 12
Design MET Facility                                                         5490419



                                  SECTION 01 50 00.00 20

                         TEMPORARY FACILITIES AND CONTROLS
                                       05/10

PART 1     GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to within the text by the
 basic designation only.

             AMERICAN WATER WORKS ASSOCIATION(AWWA)

 AWWA C511                              (1997) Reduced-Pressure Principle Backflow
                                        Prevention Assembly

             FOUNDATION FOR CROSS-CONNECTION CONTROL AND HYDRAULIC RESEARCH
             (FCCCHR)

 FCCCHR List                            (continuously updated) List of Approved
                                        Backflow Prevention Assemblies

 FCCCHR Manual                          (1988e9) Manual of Cross-Connection Control

             NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

 NFPA 241                               (2004) Safeguarding Construction,
                                        Alteration, and Demolition Operations

 NFPA 70                                (2008; AMD 1 2008) National Electrical
                                        Code - 2008 Edition

             U.S. FEDERAL HIGHWAY ADMINISTRATION (FHWA)

 FHWA SA-89-006                         (2009) Manual on Uniform Traffic Control
                                        Devices for Streets and Highways

1.2   SUBMITTALS

   The following shall be submitted in accordance with Section 01 33 00
 SUBMITTAL PROCEDURES:

         SD-01 Preconstruction Submittals

             Traffic control plan; G

         SD-06 Test Reports

             Backflow Preventer Tests; G

         SD-07 Certificates

             Backflow Tester Certification; G

             Backflow Preventers Certificate of Full Approval



                              SECTION 01 50 00.00 20   Page 1
Design MET Facility                                                   5490419


1.3     BACKFLOW PREVENTERS CERTIFICATE

 Certificate of Full Approval from FCCCHR List, University of Southern
 California, attesting that the design, size and make of each backflow
 preventer has satisfactorily passed the complete sequence of performance
 testing and evaluation for the respective level of approval. Certificate
 of Provisional Approval will not be acceptable.

1.3.1     Backflow Prevention Training Certificate

 The Contractor shall submit a certificate recognized by the State or local
 authority that states the Contractor has completed at least 10 hours of
 training in backflow preventer installations. The certificate must be
 current.

1.4     Contractor Utilities

 The Contractor shall provide his own utilities.

1.5     Utilities at Special Locations

 Reasonable amounts of utilities will be made available to the Contractor at
 the prevailing Government rates. These rates may be obtained upon
 application to the Commanding Officer, by way of the Contracting Officer.
 The Contractor will be responsible for making connections, providing
 transformers and meters, (THE CONTRACTOR MUST CERTIFY THAT ALL
 TRANSFORMERS INSTALLED ARE TEMPORARY POWER DURING THIS CONTRACT ARE PCB
 FREE), and making disconnections; and for providing backflow preventer
 devices on connections to domestic water lines. Under no circumstances
 will taps to base fire hydrants be allowed for obtaining domestic water.
 Neither potable water nor sanitary facilities will be available at the main
 Contractor laydown area at Marine Corps Air Station (MCAS), Cherry Point,
 NC.


1.6     BACKFLOW TESTER CERTIFICATION

 Prior to testing, submit to the Contracting Officer certification issued by
 the State or local regulatory agency attesting that the backflow tester has
 successfully completed a certification course sponsored by the regulatory
 agency. Tester shall not be affiliated with any company participating in
 any other phase of this Contract.

1.7     WEATHER PROTECTION

 Take necessary precautions to ensure that roof openings and other critical
 openings in the building are monitored carefully. Take immediate actions
 required to seal off such openings when rain or other detrimental weather
 is imminent, and at the end of each workday. Ensure that the openings are
 completely sealed off to protect materials and equipment in the building
 from damage.

1.7.1     Building and Site Storm Protection

 When a warning of gale force winds is issued, take precautions to minimize
 danger to persons, and protect the work and nearby Government property.
 Precautions shall include, but are not limited to, closing openings;
 removing loose materials, tools and equipment from exposed locations; and
 removing or securing scaffolding and other temporary work. Close openings


                             SECTION 01 50 00.00 20   Page 2
Design MET Facility                                                    5490419


 in the work when storms of lesser intensity pose a threat to the work or
 any nearby Government property.

1.7.1.1    Hurricane Condition of Readiness

 Unless directed otherwise, comply with:

      a.   Condition FOUR (Sustained winds of 50 knots or greater expected
           within 72 hours): Normal daily jobsite cleanup and good
           housekeeping practices. Collect and store in piles or containers
           scrap lumber, waste material, and rubbish for removal and disposal
           at the close of each work day. Maintain the construction site
           including storage areas, free of accumulation of debris. Stack
           form lumber in neat piles less than 4 feet high. Remove all
           debris, trash, or objects that could become missile hazards.
           Contact Contracting Officer for Condition of Readiness (COR)
           updates and completion of required actions.

      b.   Condition THREE (Sustained winds of 50 knots or greater expected
           within 48 hours): Maintain "Condition FOUR" requirements and
           commence securing operations necessary for "Condition ONE" which
           cannot be completed within 18 hours. Cease all routine activities
           which might interfere with securing operations. Commence securing
           and stow all gear and portable equipment. Make preparations for
           securing buildings. Review requirements pertaining to "Condition
           TWO" and continue action as necessary to attain "Condition THREE"
           readiness. Contact Contracting Officer for weather and COR
           updates and completion of required actions.

      c.   Condition TWO (Sustained winds of 50 knots or greater expected
           within 24 hours): Curtail or cease routine activities until
           securing operation is complete. Reinforce or remove form work and
           scaffolding. Secure machinery, tools, equipment, materials, or
           remove from the jobsite. Expend every effort to clear all missile
           hazards and loose equipment from general base areas. Contact
           Contracting Officer for weather and Condition of Readiness (COR)
           updates and completion of required actions.

      d.   Condition ONE. (Sustained winds of 50 knots or greater expected
           within 12 hours): Secure the jobsite, and leave Government
           premises.

1.8   Interruption of Vehicular Traffic

 If during the performance of work, it becomes necessary to modify vehicular
 traffic patterns at any locations, notify the Contracting Officer at least
 15 calendar days prior to the proposed modification date, and provide a
 Traffic Control Plan detailing the proposed controls to traffic movement
 for approval. The plan shall be in accordance with State and local
 regulations and the FHWA SA-89-006, Part VI. Make all notifications and
 obtain any permits required for modification to traffic movements outside
 Station's jurisdiction. Provide cones, signs, barricades, lights, or other
 traffic control devices and personnel required to control traffic. Do not
 use foil-backed material for temporary pavement marking because of its
 potential to conduct electricity during accidents involving downed power
 lines.




                         SECTION 01 50 00.00 20   Page 3
Design MET Facility                                                       5490419


1.9    TEMPORARY SANITARY FACILITIES

 Provide adequate sanitary conveniences of a type approved for the use of
 persons employed on the work, properly secluded from public observation,
 and maintained in such a manner as required and approved by the Contracting
 Officer. Maintain these conveniences at all times without nuisance. Upon
 completion of the work, remove the conveniences from the premises, leaving
 the premises clean and free from nuisance. Dispose of sewage through
 connection to a municipal, district sanitary sewage system. Where such
 systems are not available, use chemical toilets or comparably effective
 units, and periodically empty wastes into a municipal, district sanitary
 sewage system, or remove waste to a commercial facility. Obtain approval
 from the system owner prior to discharge into any municipal, district, or
 commercial sanitary sewer system. Any penalties and / or fines associated
 with improper discharge shall be the responsibility of the Contractor.
 Include provisions for pest control and elimination of odors.

1.10     TEMPORARY BUILDINGS

 Trailers or storage buildings will be permitted, where space is available,
 subject to the approval of the Contracting Officer. The trailers or
 buildings shall be in good condition, free from visible damage rust and
 deterioration, and meet all applicable safety requirements. Trailers shall
 be roadworthy and comply with all appropriate state and local vehicle
 requirements. Failure to maintain storage trailers or buildings to these
 standards shall result in the removal of non-complying units at the
 Contractor's expense. A sign not smaller than 24 x 24 inches shall be
 conspicuously placed on the trailer depicting the company name, business
 phone number, and emergency phone number. Trailers shall be anchored to
 resist high winds and must meet applicable state and local standards for
 anchoring mobile trailers. A laydown site will be provided as indicated
 for trailers, storage buildings, and/or bulk storage within five miles of
 the construction site. As this contract involves multiple construction
 sites, a small staging area in the vicinity of each site will be permitted
 where space is available, subject to the approval of the Contracting
 Officer. All trailers or storage buildings shall be suitably painted, kept
 in a good state of repairs, and clearly identified with the Contractor's
 name and telephone number. All laydown sites, staging areas, and
 construction sites shall be kept free of debris and trash, fences properly
 maintained, and all vegetation trimmed. Failure of the Contractor to
 maintain his trailers or storage buildings in good condition will be
 considered sufficient reason to require their removal from the job site.
 Trailers shall be anchored to resist high winds and must meet applicable
 state or local standards for anchoring mobile trailers.

1.10.1     Maintenance of Temporary Facilities

 Suitably paint and maintain the temporary facilities.      Failure to do so
 will be sufficient reason to require their removal.

PART 2     PRODUCTS

2.1    Backflow Preventers

 Reduced pressure principle type conforming to the applicable requirements
 AWWA C511. Provide backflow preventers complete with 150 pound flanged
 mounted gate valve The particular make, model/design, and size of backflow
 preventers to be installed shall be included in the latest edition of the
 List of Approved Backflow Prevention Assemblies issued by the FCCCHR List


                          SECTION 01 50 00.00 20   Page 4
Design MET Facility                                                   5490419


 and shall be accompanied by a Certificate of Full Approval from FCCCHR List.

PART 3     EXECUTION

3.1     TEMPORARY PHYSICAL CONTROLS

3.1.1     Access Controls

3.1.1.1     Temporary Barricades

 Contractor shall provide for barricading around all work areas to prevent
 public access.

3.1.1.2     Fencing

 Fencing shall be provided along the construction site for each road segment
 and isolated area of work to prevent access by unauthorized people (special
 emphasis shall be placed on preventing access by children). Fencing shall
 be a four feet high orange plastic grid supported at intervals sufficient
 to resist at least 250 pounds of force applied against the fence. Fencing
 shall be moved as work progresses. Place fencing on the side opposite the
 street side of the walkway to allow adequate work space for the
 Contractor's activities.

3.1.1.3     Signs

 Place warning signs at the construction area perimeter designating the
 presence of construction hazards requiring unauthorized persons to keep
 out. Signs must be placed on all sides of the project, with at least one
 sign every 300 feet. All points of entry shall have signs designating the
 construction site as a hard hat area.

3.1.1.4     Traffic Work

 All work around/involving roadways, to include roadway excavations and
 utility crossings, will be conducted in accordance with Manual of Traffic
 Control Devices. Contractors shall provide and ensure appropriate road
 closure and detour signs are established as necessary for motor traffic
 management. All road closures shall be coordinated with the Contracting
 Officer in advance. Self-illuminated (lighted) barricades shall be
 provided during hours of darkness. Brightly-colored (orange) vests are
 required for all personnel working in roadways. Road closures shall
 require a road closure plan showing the location of signage.

3.2     TEMPORARY WIRING

 Provide temporary wiring in accordance with NFPA 241 and NFPA 70, Article
 305-6(b), Assured Equipment Grounding Conductor Program. Program shall
 include frequent inspection of all equipment and apparatus.

3.3     REDUCED PRESSURE BACKFLOW PREVENTERS

 Provide an approved reduced pressure backflow prevention assembly at each
 location where the Contractor taps into the Government potable water supply.

 A certified tester(s) shall perform testing of backflow preventer(s) for
 proper installation and operation and provide subsequent tagging. Backflow
 preventer tests shall be performed using test equipment, procedures, and
 certification forms conforming to those outlined in the latest edition of


                            SECTION 01 50 00.00 20   Page 5
Design MET Facility                                                   5490419


 the Manual of Cross-Connection Control published by the FCCCHR Manual.
 Test and tag each reduced pressure backflow preventer upon initial
 installation (prior to continued water use) thereafter. Tag shall contain
 the following information: make, model, serial number, dates of tests,
 results, maintenance performed, and signature of tester. Record test
 results on certification forms conforming to requirements cited earlier in
 this paragraph.

3.4   GRASS CUTTING

 Cut grass (or annual weeds) within construction and storage sites to a
 maximum 4 inch height at least once a week during the growing season unless
 the grass area is not visible to the public. Trim the grass around fences
 at time of grass cutting. Maintain grass or weeds on stockpiled earth as
 described above.
      -- End of Section --




                       SECTION 01 50 00.00 20   Page 6
Design MET Facility                                                   5490419



                           SECTION 01 57 19.00 20

                      TEMPORARY ENVIRONMENTAL CONTROLS
                                    07/10

PART 1   GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to within the text by the
 basic designation only.

          U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

 29 CFR 1910                      Occupational Safety and Health Standards

 29 CFR 1910.120                  Hazardous Waste Operations and Emergency
                                  Response

 40 CFR 112                       Oil Pollution Prevention

 40 CFR 241                       Guidelines for Disposal of Solid Waste

 40 CFR 243                       Guidelines for the Storage and Collection
                                  of Residential, Commercial, and
                                  Institutional Solid Waste

 40 CFR 258                       Subtitle D Landfill Requirements

 40 CFR 261                       Identification and Listing of Hazardous
                                  Waste

 40 CFR 262                       Standards Applicable to Generators of
                                  Hazardous Waste

 40 CFR 263                       Standards Applicable to Transporters of
                                  Hazardous Waste

 40 CFR 264                       Standards for Owners and Operators of
                                  Hazardous Waste Treatment, Storage, and
                                  Disposal Facilities

 40 CFR 265                       Interim Status Standards for Owners and
                                  Operators of Hazardous Waste Treatment,
                                  Storage, and Disposal Facilities

 40 CFR 266                       Standards for the Management of Specific
                                  Hazardous Wastes and Specific Types of
                                  Hazardous Waste Management Facilities

 40 CFR 268                       Land Disposal Restrictions

 40 CFR 279                       Standards for the Management of Used Oil

 40 CFR 300                       National Oil and Hazardous Substances
                                  Pollution Contingency Plan



                       SECTION 01 57 19.00 20   Page 1
Design MET Facility                                                         5490419


 40 CFR 355                           Emergency Planning and Notification

 40 CFR 372-SUBPART D                 Specific Toxic Chemical Listings

 49 CFR 173                           Shippers - General Requirements for
                                      Shipments and Packaging

 49 CFR 178                           Specifications for Packaging

1.2     DEFINITIONS

1.2.1     Sediment

 Soil and other debris that have eroded and have been transported by runoff
 water or wind.

1.2.2     Solid Waste

 Garbage, refuse, debris, sludge, or other discharged material, including
 solid, liquid, semisolid, or contained gaseous materials resulting from
 domestic, industrial, commercial, mining, or agricultural operations.
 Types of solid waste typically generated at construction sites may include:

        a.   Green waste: The vegetative matter from landscaping, land
             clearing and grubbing, including, but not limited to, grass,
             bushes, scrubs, small trees and saplings, tree stumps and plant
             roots. Marketable trees, grasses and plants that are indicated to
             remain, be re-located, or be re-used are not included.

        b.   Surplus soil: Existing soil that is in excess of what is required
             for this work, including aggregates intended, but not used, for
             on-site mixing of concrete, mortars and paving. Contaminated soil
             meeting the definition of hazardous material or hazardous waste is
             not included.

        c.   Debris: Non-hazardous solid material generated during the
             construction, demolition, or renovation of a structure which
             exceeds 2.5 inch particle size that is: a manufactured object;
             plant or animal matter; or natural geologic material (e.g. cobbles
             and boulders), broken or removed concrete, masonry, and rock
             asphalt paving; ceramics; roofing paper and shingles. Inert
             materials may not be reinforced with or contain ferrous wire,
             rods, accessories and weldments. A mixture of debris and other
             material such as soil or sludge is also subject to regulation as
             debris if the mixture is comprised primarily of debris by volume,
             based on visual inspection..

        d.   Wood: Dimension and non-dimension lumber, plywood, chipboard,
             hardboard. Treated and/or painted wood that meets the definition
             of lead contaminated or lead based contaminated paint is not
             included.

        e.   Scrap metal: Scrap and excess ferrous and non-ferrous metals such
             as reinforcing steel, structural shapes, pipe and wire that are
             recovered or collected and disposed of as scrap. Scrap metal
             meeting the definition of hazardous material or hazardous waste is
             not included.

        f.   Paint cans:   Metal cans that are empty of paints, solvents,


                           SECTION 01 57 19.00 20   Page 2
Design MET Facility                                                      5490419


             thinners and adhesives. If permitted by the paint can label, a
             thin dry film may remain in the can.

        g.   Recyclables: Materials, equipment and assemblies such as doors,
             windows, door and window frames, plumbing fixtures, glazing and
             mirrors that are recovered and sold as recyclable. Metal meeting
             the definition of lead contaminated or lead based paint
             contaminated may not be included as recyclable if sold to a scrap
             metal company. Paint cans may not be included as recyclable if
             sold to a scrap metal company.

        h.   Hazardous Waste: By definition, to be a hazardous waste a
             material must first meet the definition of a solid waste.
             Hazardous waste and hazardous debris are special cases of solid
             waste. They have additional regulatory controls and must be
             handled separately. They are thus defined separately in this
             document.

             Material not regulated as solid waste are: nuclear source or
             byproduct materials regulated under the Federal Atomic Energy Act
             of 1954 as amended; suspended or dissolved materials in domestic
             sewage effluent or irrigation return flows, or other regulated
             point source discharges; regulated air emissions; and fluids or
             wastes associated with natural gas or crude oil exploration or
             production.

1.2.3    Hazardous Debris

 As defined in Solid Waste paragraph, debris that contains listed hazardous
 waste (either on the debris surface, or in its interstices, such as pore
 structure) per 40 CFR 261; or debris that exhibits a characteristic of
 hazardous waste per 40 CFR 261.

1.2.4    Chemical Wastes

 This includes salts, acids, alkalizes, herbicides, pesticides, and organic
 chemicals.

1.2.5    Garbage

 Refuse and scraps resulting from preparation, cooking, dispensing, and
 consumption of food.

1.2.6    Hazardous Waste (Including Universal Hazardous Waste)

 Hazardous Wastes are defined by the Resource Conservation and Recovery Act
 (RCRA - Subtitle C) as wastes which first meet the definition of "solid"
 wastes and are then further defined in 40CFR Parts 261.21, 261.22, 261.23,
 261.24, 261.31, 261.32, 261.33(e), and 261.33(f) with regard to their
 hazardous waste properties and / or characteristics (to include U.S. EPA's
 lists of Hazardous Wastes. These regulations cover a wide range of process
 and product generated wastes, and discarded (including materials intended
 to be discarded) or unusable materials in solid, liquid, and gaseous forms.

 Universal (Hazardous) Wastes are a subset of Hazardous Waste, and are
 defined in 40CFR Part 273.2, 273.3. 273.4, and 273.5 and include batteries,
 pesticides, mercury containing equipment, and lamps.

 Contractors must be intimately familiar with the above-detailed Hazardous


                            SECTION 01 57 19.00 20   Page 3
Design MET Facility                                                      5490419


 Waste regulations to ensure compliance with section 1.4.1.

1.2.7   Hazardous Materials

 Hazardous material is any material that:

          a.   Is regulated as a hazardous material per 49 CFR 173, or

          b. Requires a Material Safety Data Sheet (MSDS) per
          29 CFR 1910.120, or

          c. During end use, treatment, handling, packaging, storage,
          transpiration, or disposal meets or has components that meet or
          have potential to meet the definition of a hazardous waste as
          defined by 40 CFR 261 Subparts A, B, C, or D.

 Designation of a material by this definition, when separately regulated or
 controlled by other instructions or directives, does not eliminate the need
 for adherence to that hazard-specific guidance which takes precedence over
 this instruction for "control" purposes. Such material include ammunition,
 weapons, explosive actuated devices, propellants, pyrotechnics, chemical
 and biological warfare materials, medical and pharmaceutical supplies,
 medical waste and infectious materials, bulk fuels, radioactive materials,
 and other materials such as asbestos, mercury, and polychlorinated
 biphenyls (PCBs). Nonetheless, the exposure may occur incident to
 manufacture, storage, use and demilitarization of these items.

1.2.8   Waste Hazardous Material and Substances

 Waste hazardous materials and substances are those materials which do not
 meet any of the regulatory definitions of either Hazardous Waste or
 Universal (Hazardous) Waste, but which still may pose a threat to human
 health or the environment or cause significant legal liabilities under
 CERCLA if not properly managed. In general, such materials may be defined
 as those which pose a threat to human health and / or the environment due
 to their quantity, concentration, or their physical, chemical, or
 infectious characteristics and which have been so designated by federal,
 state, or local agencies.

1.2.9   Used Oil and Oily Wastes

 Used Oil is defined in 40CFR Part 279 to include a wide variety of oils and
 fuels and how they must be properly managed to ensure proper disposal,
 reclamation, and / or recycling. Animal and vegetable oils do not fall
 under this regulatory classification. Grease does not fall under this
 regulatory classification

 Those materials which are, or were, mixed with used oil and have become
 separated from that used oil. Oily wastes also means materials, including
 wastewaters, centrifuge solids, filter residues or sludges, bottom
 sediments, tank bottoms, and sorbents which have come into contact with and
 have been contaminated by, used oil and may be appropriately tested and
 discarded in a manner which is in compliance with other State and local
 requirements.

 This definition includes materials such as oily rags, "kitty litter"
 sorbent clay and organic sorbent material. These materials may be land
 filled provided that:



                        SECTION 01 57 19.00 20    Page 4
Design MET Facility                                                           5490419


             a. It is not prohibited in other State regulations or local
             ordinances

             b. The amount generated is "de minimus" (a small amount)

             c. It is the result of minor leaks or spills resulting from normal
             process operations

             d. All free-flowing oil has been removed to the practical extent
             possible

 Large quantities of this material, generated as a result of a major spill
 or in lieu of proper maintenance of the processing equipment, are a solid
 waste. As a solid waste, a hazardous waste determination must be performed
 prior to disposal. As this can be an expensive process, it is recommended
 that this type of waste be minimized through good housekeeping practices
 and employee education.

1.2.10     Regulated Waste

 Those solid waste that have specific additional Federal, state, or local
 controls for handling, storage, or disposal.

1.2.11     Class I Ozone Depleting Substance (ODS)

 Class I ODS is defined in Section 602(a) of The Clean Air Act and includes
 the following chemicals:

 chlorofluorocarbon-11 (CFC-11)                chlorofluorocarbon-213   (CFC-213)
 chlorofluorocarbon-12 (CFC-12)                chlorofluorocarbon-214   (CFC-214)
 chlorofluorocarbon-13 (CFC-13)                chlorofluorocarbon-215   (CFC-215)
 chlorofluorocarbon-111 (CFC-111)              chlorofluorocarbon-216   (CFC-216)
 chlorofluorocarbon-112 (CFC-112)              chlorofluorocarbon-217   (CFC-217)
 chlorofluorocarbon-113 (CFC-113)              halon-1211
 chlorofluorocarbon-114 (CFC-114)              halon-1301
 chlorofluorocarbon-115 (CFC-115)              halon-2402
 chlorofluorocarbon-211 (CFC-211)              carbon tetrachloride
 chlorofluorocarbon-212 (CFC-212)              methyl chloroform

1.3   SUBMITTALS

 Government approval is required for submittals with a "G" designation;
 submittals not having a "G" designation are for Contractor Quality Control
 approval. The following shall be submitted in accordance with Section
 01 33 00 SUBMITTAL PROCEDURES:

         SD-01 Preconstruction Submittals

             Preconstruction Survey; G

             Solid Waste Management Plan and Permit;      G

             Regulatory Notification; G

             Environmental Protection Plan; G

             Construction Dewatering Plan; G

         SD-06 Test Reports


                              SECTION 01 57 19.00 20   Page 5
Design MET Facility                                                     5490419



            Laboratory Analysis

            Disposal Requirements

            Erosion and Sediment Control Inspection Reports

            Storm Water Inspection Reports for General Permit

        SD-11 Closeout Submittals

              Some of the records listed below are also required as part of
            other submittals. For the "Records" submittal, maintain on-site a
            separate three-ring Environmental Records binder and submit at the
            completion of the project. Make separate parts to the binder
            corresponding to each of the applicable sub items listed below.

            Waste Determination Documentation

            Disposal Documentation for Hazardous and Regulated Waste

            Contractor 40 CFR Employee Training Records

            Solid Waste Management Report

            Contractor Hazardous Material Inventory Log; G

            Hazardous Waste/Debris Management

1.4     ENVIRONMENTAL PROTECTION REQUIREMENTS

 Provide and maintain, during the life of the contract, environmental
 protection as defined. Plan for and provide environmental protective
 measures to control pollution that develops during normal construction
 practice. Plan for and provide environmental protective measures required
 to correct conditions that develop during the construction of permanent or
 temporary environmental features associated with the project. Comply with
 Federal, State, and local regulations pertaining to the environment,
 including water, air, solid waste, hazardous waste and substances, oily
 substances, and noise pollution.

 Marine Corps Air Station, Cherry Point is listed on the National Priorities
 List pursuant to the Comprehensive Environmental Response, Compensation and
 Liabilities Act 42 USCA, Section 9601.et seq. as amended April 15, 1996
 (CERCLA). Bogue Field, Oakgrove, BT-11 and Atlantic Field are not listed
 on the National Priorities List. The Contractor shall immediately bring to
 the Contracting Officer's attention any unanticipated site condition which
 may involve hazardous materials or hazardous waste and the Contractor shall
 not disturb such conditions without the Contracting Officer's prior written
 documentation as to whether such conditions are outside the contract
 requirements.

1.4.1     Facility Hazardous Waste Generator Status

 Marine Corps Air Station Cherry Point is designated as a Large Quantity
 Generator (LQG) of Hazardous Waste, a Large Quantity Handler of Universal
 (Hazardous) Waste, and maintains a Treatment, Storage, and Disposal
 facility. Accordingly, MCAS Cherry Point is required to actively maintain
 and comply with a RCRA Part "B" operating permit issued by the State of


                          SECTION 01 57 19.00 20   Page 6
Design MET Facility                                                   5490419


 North Carolina. All work conducted within the boundaries of this activity
 must be in compliance with the Part B permit, and the generator's various
 designations and operational requirements. Contractors will comply with
 all federal, state, and local regulatory requirements governing the proper
 training of personnel, and proper identification, generation, management,
 storage, handling, manifesting, transportation, and disposal of any
 Hazardous Waste(s) which they may cause to be generated in the course of
 the execution of their contract(s).

1.5     QUALITY ASSURANCE

1.5.1     Preconstruction Survey

 Perform a Preconstruction Survey of the project site with the Contracting
 Officer, and take photographs showing existing environmental conditions in
 and adjacent to the site. Submit a report for the record.

1.5.2     Regulatory Notification

 The Contractor is responsible for all Regulatory Notification requirements
 in accordance with Federal, State and local regulations. In cases where
 the Navy must also provide public notification (such as stormwater
 permitting), the Contractor must coordinate with the Contracting Officer.
 The Contractor shall submit copies of all regulatory notifications to the
 Contracting Officer prior to commencement of work activities. Typically,
 regulatory notifications must be provided for the following (this listing
 is not all inclusive): demolition, renovation, NPDES defined site work,
 remediation of controlled substances (asbestos, hazardous waste, lead
 paint).

1.5.3     Environmental Brief

 Attend an environmental brief to be included in the preconstruction
 meeting. Provide the following information: types, quantities, and use of
 hazardous materials that will be brought onto the activity; types and
 quantities of wastes/wastewater that may be generated during the contract.
 Discuss the results of the Preconstruction Survey at this time.

 Prior to initiating any work on site, meet with the Contracting Officer and
 activity environmental staff to discuss the proposed Environmental
 Protection Plan. Develop a mutual understanding relative to the details of
 environmental protection, including measures for protecting natural
 resources, required reports, required permits, permit requirements, and
 other measures to be taken.

1.5.4     Environmental Manager

 Appoint in writing an Environmental Manager for the project site. The
 Environmental Manager will be directly responsible for coordinating
 contractor compliance with Federal, State, local, and station
 requirements. The Environmental Manager will ensure compliance with
 Hazardous Waste Program requirements (including hazardous waste handling,
 storage, manifesting, and disposal); implement the Environmental Protection
 Plan; ensure that all environmental permits are obtained, maintained, and
 closed out; ensure compliance with Storm Water Program Management
 requirements; ensure compliance with Hazardous Materials (storage,
 handling, and reporting) requirements; and coordinate any remediation of
 regulated substances (lead, asbestos, PCB transformers). This can be a
 collateral position; however the person in this position must be trained to


                            SECTION 01 57 19.00 20   Page 7
Design MET Facility                                                      5490419


 adequately accomplish the following duties: ensure waste segregation and
 storage compatibility requirements are met; inspect and manage Satellite
 Accumulation areas; ensure only authorized personnel add wastes to
 containers; ensure all Contractor personnel are trained in 40 CFR
 requirements in accordance with their position requirements; coordinate
 removal of waste containers; and maintain the Environmental Records binder
 and required documentation, including environmental permits compliance and
 close-out.

1.5.5    Contractor 40 CFR Employee Training Records

 Prepare and maintain employee training records throughout the term of the
 contract meeting applicable 40 CFR requirements. The Contractor will
 ensure every employee completes a program of classroom instruction or
 on-the-job training that teaches them to perform their duties in a way that
 ensures compliance with Federal, State and local regulatory requirements
 for RCRA Large Quantity Generator. The Contractor will provide a Position
 Description for each employee, by subcontractor, based on the Davis-Bacon
 Wage Rate designation or other equivalent method, evaluating the employee's
 association with hazardous and regulated wastes. This Position Description
 will include training requirements as defined in 40 CFR 265 for a Large
 Quantity Generator facility. Submit these training records to the
 Contracting Officer at the conclusion of the project, unless otherwise
 directed.

1.5.6    Contractor Environmental Management System (EMS) Requirements

 The Contractor shall perform work under this contract consistent with the
 policy, objectives, and targets identified in Marine Corps Air Station
 Cherry Point's Environmental Management System (EMS). Executive Order
 13423, Strengthening Federal Environmental, Energy, and Transportation
 Management and Marine Corps Order P5090.2A, Environmental Compliance and
 Protection Manual require that all Federal agencies implement, utilize, and
 maintain an EMS. The Contractor shall perform work in a manner that does
 not circumvent objectives and targets, environmental programs goals, and
 operational controls identified by the EMS. The Contractor is also required
 not to impede compliance with the provisions of Executive Order 13423. The
 work performed under this contract affects practices that have been
 identified as significant, and requires more stringent requirements to
 adhere to the objectives and targets identified for MCAS Cherry Point.

 The Contractor shall assume liability for nonconformances and
 noncompliances resulting from the Contractor's activities and work with Air
 Station personnel to conduct corrective and preventive actions. The
 Contractor is responsible for ensuring that their employees receive
 applicable environmental training, along with any applicable environmental
 management systems training, and are knowledgeable of current regulatory
 required specific training for the type of work to be conducted on-site.
 The Contractor personnel and their subcontractor personnel shall have the
 appropriate education, training, and experience in order to perform the
 work specified under this contract. Upon contract award, the Contractor
 shall review the Contractor Environmental Training Binder and Training
 Presentation and sign the Contractor/Vendor Environmental Service Agreement.
 Training and Service Agreement Documents are located on-line at
 http://www.marines.mil/unit/mcascherrypoint/Pages/EA/EA.aspx

PART 2    PRODUCTS

 Not used.


                         SECTION 01 57 19.00 20   Page 8
Design MET Facility                                                        5490419



PART 3        EXECUTION

3.1   ENVIRONMENTAL PROTECTION PLAN

 Prior to initiating any work on site, the Contractor will meet with the
 Contracting Officer to discuss the proposed Environmental Protection Plan
 and develop a mutual understanding relative to the details of environmental
 protection, including measures for protecting natural resources, required
 reports, and other measures to be taken. The Environmental Protection Plan
 will be submitted in the following format and will, at a minimum, address
 the following elements:

         a.    Description of the Environmental Protection Plan

               (1)    General overview and purpose

               (2)    General site information

               (3) A letter signed by an officer of the firm appointing the
               Environmental Manager and stating that he/she is responsible for
               managing and implementing the Environmental Program as described
               in this contract. Include in this letter the Environmental
               Manager's authority to direct the removal and replacement of
               non-conforming work.

         b.    Protection of Natural Resources

               (1)    Land resources

               (2)    Tree protection

               (3)    Replacement of damaged landscape features

               (4)    Temporary construction

               (5)    Stream crossings

               (6)    Fish and wildlife resources

               (7)    Wetland areas

         c.    Protection of Historical and Archaeological Resources

               (1)    Objectives

               (2)    Methods

         d.    Storm Water Management and Control

               (1)    Ground cover

               (2)    Erodible soils

               (3)    Temporary measures

                     (a)   Mechanical retardation and control of runoff

                     (b)   Vegetation and mulch


                                SECTION 01 57 19.00 20   Page 9
Design MET Facility                                                       5490419



      e.   Protection of the Environment from Waste Derived from Contractor
           Operations

           (1)    Control and disposal of solid and sanitary waste

           (2) Control and disposal of hazardous waste (Hazardous Waste
           Management Section)

           This item will consist of the management procedures for all
           hazardous waste to be generated. The elements of those procedures
           will coincide with the Activity Hazardous Waste Management Plan.
           A copy of the Activity Hazardous Waste Management Plan will be
           provided by the Contracting Officer. As a minimum, include the
           following:

               (a) Procedures to be employed to ensure a written waste
           determination is made for appropriate wastes which are to be
           generated;

                 (b)   Sampling/analysis plan;

               (c) Methods of hazardous waste accumulation/storage (i.e., in
           tanks and/or containers);

               (d) Management procedures for storage, labeling,
           transportation, and disposal of waste (treatment of waste is not
           allowed unless specifically noted);

               (e) Management procedures and regulatory documentation
           ensuring disposal of hazardous waste complies with Land Disposal
           Restrictions (40 CFR 268);

               (f) Management procedures for recyclable hazardous materials
           such as lead-acid batteries, used oil, and the like;

               (g) Used oil management procedures in accordance with
           40 CFR 279;

               (h) Pollution prevention\hazardous waste minimization
           procedures;

               (i) Plans for the disposal of hazardous waste by permitted
           facilities;

               (j) Procedures to be employed to ensure all required employee
           training records are maintained.

      f.   Prevention of Releases to the Environment

           (1)    Procedures to prevent releases to the environment

           (2)    Notifications in the event of a release to the environment

      g.   Regulatory Notification and Permits

           (1) List what notifications and permit applications must be
           made. Include copies of all applicable, environmental permits.



                           SECTION 01 57 19.00 20   Page 10
Design MET Facility                                                   5490419


3.1.1     Environmental Protection Plan Review

 Fourteen days after the environmental protection meeting, submit the
 proposed Environmental Protection Plan for further discussion, review, and
 approval. Commencement of work will not begin until the environmental
 protection plan has been approved.

3.1.2     Licenses and Permits

 Obtain licenses and permits pursuant to the "Permits and Responsibilities"
 FAR Clause.

 No permits will be obtained by the Contracting Officer.

 Where required by the State regulatory authority, the inspections and
 certifications will be provided through the services of a Professional
 Engineer (PE), registered in the State where the work is being performed.
 Where a PE is not required, the individual must be otherwise qualified by
 other current State licensure, specific training and prior experience
 (minimum 5 years). As a part of the quality control plan, which is
 required to be submitted for approval by the quality control section,
 provide a sub item containing the name, appropriate professional
 registration or licence number, address, and telephone number of the
 professionals or other qualified persons who will be performing the
 inspections and certifications for each permit.

3.1.2.1     Construction Dewatering Plan

 Dewatering using well points is considered a well contractor activity, and
 must be performed or personally supervised by a North Carolina Certified
 Well Driller. Construction and abandonment must be performed per 15A NCAC
 2C, Titled 15A, Subchapter 2C. Well construction and abandonment records
 are required, and the original copies shall be submitted to the Contracting
 Officer for review and submittal to the state. Submittal must also include
 the name(s) of NC Certified Well Driller and a copy of their certification.

3.2     PROTECTION OF NATURAL RESOURCES

 Preserve the natural resources within the project boundaries and outside
 the limits of permanent work. Restore to an equivalent or improved
 condition upon completion of work. Confine construction activities to
 within the limits of the work indicated or specified. Conform to the
 national permitting requirements of the Clean Water Act.

 Do not disturb fish and wildlife. Do not alter water flows or otherwise
 significantly disturb the native habitat adjacent to the project and
 critical to the survival of fish and wildlife, except as indicated or
 specified.

 Except in areas to be cleared, do not remove, cut, deface, injure, or
 destroy trees or shrubs without the Contracting Officer's permission. Do
 not fasten or attach ropes, cables, or guys to existing nearby trees for
 anchorages unless authorized by the Contracting Officer. Where such use of
 attached ropes, cables, or guys is authorized, the Contractor will be
 responsible for any resultant damage.

 Protect existing trees which are to remain and which may be injured,
 bruised, defaced, or otherwise damaged by construction operations. Remove
 displaced rocks from uncleared areas. By approved excavation, remove trees


                         SECTION 01 57 19.00 20   Page 11
Design MET Facility                                                        5490419


 with 30 percent or more of their root systems destroyed. Remove trees and
 other landscape features scarred or damaged by equipment operations, and
 replace with equivalent, undamaged trees and landscape features. Obtain
 Contracting Officer's approval before replacement.

 The Contracting Officer's approval is required before any equipment will be
 permitted to ford live streams. In areas where frequent crossings are
 required, install temporary culverts or bridges. Obtain Contracting
 Officer's approval prior to installation. Remove temporary culverts or
 bridges upon completion of work, and repair the area to its original
 condition or as indicated.

3.2.1     Erosion and Sediment Control Measures

3.2.1.1      Burnoff

 Burnoff of the ground cover is not permitted.

3.2.1.2      Protection of Erodible Soils

 Immediately finish the earthwork brought to a final grade, as indicated or
 specified. Immediately protect the side slopes and back slopes upon
 completion of rough grading. Plan and conduct earthwork to minimize the
 duration of exposure of unprotected soils.

3.2.1.3      Temporary Protection of Erodible Soils

 Use the following methods to prevent erosion and control sedimentation:

        a.   Mechanical Retardation and Control of Runoff

             (1) Mechanically retard    and control the rate of runoff from the
             construction site. This    includes construction of diversion
             ditches, benches, berms,   and use of silt fences and straw bales to
             retard and divert runoff   to protected drainage courses.

        b.   Sediment Basins

             (1) Trap sediment in temporary sediment basins. Select a basin
             size to accommodate the runoff of a local 10-year storm. Pump dry
             and remove the accumulated sediment, after each storm. Use a
             paved weir or vertical overflow pipe for overflow. Remove
             collected sediment from the site. Institute effluent quality
             monitoring programs.

             (2) Install, inspect, and maintain best management practices
             (BMPs) as required by the general permit. Prepare BMP Inspection
             Reports as required by the general permit. If required by the
             permit, include those inspection reports.

        c.   Vegetation and Mulch

             (1) Provide temporary protection on sides and back slopes as soon
             as rough grading is completed or sufficient soil is exposed to
             require erosion protection. Protect slopes by accelerated growth
             of permanent vegetation, temporary vegetation, mulching, or
             netting. Stabilize slopes by hydroseeding, anchoring mulch in
             place, covering with anchored netting, sodding, or such
             combination of these and other methods necessary for effective


                          SECTION 01 57 19.00 20    Page 12
Design MET Facility                                                         5490419


              erosion control.

              (2) Seeding: Provide new seeding where ground is disturbed.
              Include topsoil or nutriment during the seeding operation
              necessary to establish a suitable stand of grass. The seeding
              operation will be as specified in Section02 82 30,
              "Re-Establishing Vegetation".

3.2.2     Erosion, Sediment and Stormwater Control

 Submit "Erosion and Sediment Control Reports" (E&S) (form provided at the
 pre-construction conference) and "Stormwater Inspections for General Permit
 NCG010000 - Land Disturbing Activities" (form provided at
 http://h2o.enr.state.nc.us/su/PDF_Files/SW_General_Permits/NCG01_Inspect_log.pdf)
 to the Contracting Officer once every 7 days and within 24 hours of a storm
 event that produces 0.5 inch or more of rain.

 Comply with NCG010000, North Carolina Permit to Discharge Storm Water under
 the National Pollutant Discharge Elimination System. The existing permit
 may be obtained from:
 http://h20.enr.state.nc.us/su/PDF_Files/SW_General_Permits/NCG01_Inspect_log.pdf.

3.2.2.1       Storm Water Notice of Intent for Construction Activities

 The Contractor shall submit a Storm Water Pollution Prevention Plan (SWPPP)
 for the project to the Contracting Officer prior and gain approval prior to
 the commencement of work. The SWPPP will meet the requirements of the
 State of North Carolina general permit for storm water discharges from
 construction sites. Submit the SWPPP to the Contracting Officer a minimum
 of 14 calendar days prior to the start of any land disturbing activities.
 The Contractor shall maintain an approved copy of the SWPPP at the
 construction on-site office, and continually update as regulations require,
 to reflect current site conditions.

        (1)    The SWPPP shall:

              a.   Identify potential sources of pollution which may be
              reasonably expected to affect the quality of storm water discharge
              from the site.

              b.    Describe and ensure implementation of practices which will be
              used to reduce the pollutants in storm water discharge from the
              site.

              c.   Select applicable best management practices from EPA
              832-R-92-005.

              f. The Contractor shall install, inspect, and maintain best
              management practices (BMPs.

3.3     HISTORICAL AND ARCHAEOLOGICAL RESOURCES

 Carefully protect in-place and report immediately to the Contracting
 Officer historical and archaeological items or human skeletal remains
 discovered in the course of work. Upon discovery, notify the Contracting
 Officer. Stop work in the immediate area of the discovery until directed
 by the Contracting Officer to resume work. The Government retains
 ownership and control over historical and archaeological resources.



                           SECTION 01 57 19.00 20   Page 13
Design MET Facility                                                   5490419


3.4     SOLID WASTE MANAGEMENT PLAN and PERMIT

 Provide to the contracting officer written notification of the quantity of
 solid waste/debris that is anticipated to be generated by construction.
 Include in the report the locations where various types of waste will be
 disposed or recycled. Include letters of acceptance or as applicable,
 submit one copy of a State and local permit or license showing such agency's
  approval of the disposal plan before transporting wastes off Government
 property.

3.4.1     Solid Waste management Report

 Monthly, submit a solid waste disposal report to the Contracting Officer.
 For each waste, the report will state the classification (using the
 definitions provided in this section), amount, location, and name of the
 business receiving the solid waste. Include copies of the waste handling
 facilities' weight tickets, receipts, bills of sale, and other sales
 documentation. In lieu of sales documentation, the Contractor may submit a
 statement indicating the disposal location for the solid waste which is
 signed by an officer of the Contractor firm authorized to legally obligate
 or bind the firm. The sales documentation or Contractor certification will
 include the receiver's tax identification number and business, EPA or State
 registration number, along with the receiver's delivery and business
 addresses and telephone numbers. For each solid waste retained by the
 Contractor for his own use, the Contractor will submit on the solid waste
 disposal report the information previously described in this paragraph.
 Prices paid or received will not be reported to the Contracting Officer
 unless required by other provisions or specifications of this Contract or
 public law.

3.4.2     Control and Disposal of Solid Wastes

 Pick up solid wastes, and place in covered containers which are regularly
 emptied. Do not prepare or cook food on the project site. Prevent
 contamination of the site or other areas when handling and disposing of
 wastes. At project completion, leave the areas clean. Recycling is
 encouraged and can be coordinated with the Contracting Officer and the
 activity recycling coordinator. Remove all solid waste (including
 non-hazardous debris) from Government property and dispose off-site at an
 approved landfill. Solid waste disposal off-site must comply with most
 stringent local, State, and Federal requirements including 40 CFR 241,
 40 CFR 243, and 40 CFR 258.

3.5     WASTE DETERMINATION DOCUMENTATION

 Complete a Waste Determination form (provided at the pre-construction
 conference) for all contractor derived wastes to be generated. Base the
 waste determination upon either a constituent listing from the manufacturer
 used in conjunction with consideration of the process by which the waste
 was generated, EPA approved analytical data, or laboratory analysis
 (Material Safety Data Sheets (MSDS) by themselves are not adequate).
 Attach all support documentation to the Waste Determination form. As a
 minimum, a Waste Determination form must be provided for the following
 wastes (this listing is not all inclusive): oil and latex based painting
 and caulking products, solvents, adhesives, aerosols, petroleum products,
 and all containers of the original materials.




                         SECTION 01 57 19.00 20   Page 14
Design MET Facility                                                   5490419


3.5.1     Contractor Hazardous Material Inventory Log

 Submit the Contractor Hazardous Material Inventory Log (found at:
 http://www.wbdg.org/ccb/NAVGRAPH/01575n.pdf), which provides information
 required by (EPCRA Sections 312 and 313) along with corresponding Material
 Safety Data Sheets (MSDS) to the Contracting Officer at the start and at
 the end of construction (30 days from final acceptance), and update no
 later than January 31 of each calendar year during the life of the
 contract. Documentation for any spills/releases, environmental reports or
 off-site transfers may be requested by the Contracting Officer.

3.5.2     Laboratory Analysis

 Submit a copy of a Laboratory Analysis of solid waste and debris with the
 potential of becoming classified as a hazardous waste (i.e., abrasive/sand
 blasting debris, etc.). Waste stream determinations are required at the
 point of generation and must sufficiently document whether the waste will
 be a solid waste, hazardous waste, or Resource Conservation and Recovery
 Act (RCRA) exempt waste. Determinations must use EPA approved methods and
 provide written rational for whether the waste is classified as hazardous
 or non-hazardous. The Contractor will bear the cost of the waste stream
 determinations, and the Contracting Officer reserves the right to request
 waste stream determinations on questionable waste streams.

3.6     CONTRACTOR HAZARDOUS MATERIAL INVENTORY LOG

 Submit the "Contractor Hazardous Material Inventory Log"(found at:
 http://www.lantdiv.navfac.navy.mil/pls/lantdiv/docs/FOLDER/EICO/UFGS/GRAPHICS/01575.pdf
 ), which provides information required by (EPCRA Sections 312 and 313)
 along with corresponding Material Safety Data Sheets (MSDS) to the
 Contracting Officer at the start and at the end of construction (30 days
 from final acceptance), and update no later than January 31 of each
 calendar year during the life of the contract. Documentation for any
 spills/releases, environmental reports or off-site transfers may be
 requested by the Contracting Officer.

3.6.1     Disposal Documentation for Hazardous and Regulated Waste

 Manifest, pack, ship and dispose of hazardous or toxic waste and universal
 waste that is generated as a result of construction in accordance with the
 generating facilities generator status under the Recourse Conservation and
 Recovery Act. Contact the Contracting Officer for the facility RCRA
 identification number that is to be used on each manifest.

 Submit a copy of the applicable EPA and State permit(s), manifest(s), or
 license(s) for transportation, treatment, storage, and disposal of
 hazardous and regulated waste by permitted facilities. Hazardous or toxic
 waste manifest must be reviewed, signed, and approved by the Navy before
 the Contractor may ship waste. To obtain specific disposal instructions
 the Contractor must coordinate with the Activity environmental office.

 3.7     POLLUTION PREVENTION/HAZARDOUS WASTE MINIMIZATION

 minimize the use of hazardous materials and the generation of hazardous
 waste. Include procedures for pollution prevention/ hazardous waste
 minimization in the Hazardous Waste Management Section of the Environmental
 Protection Plan. Consult with the activity Environmental Office for
 suggestions and to obtain a copy of the installation's pollution
 prevention/hazardous waste minimization plan for reference material when


                         SECTION 01 57 19.00 20   Page 15
Design MET Facility                                                   5490419


 preparing this part of the plan. If no written plan exists, obtain
 information by contacting the Contracting Officer. Describe the types of
 the hazardous materials expected to be used in the construction when
 requesting information.

3.8    WHM/HW MATERIALS PROHIBITION

 No waste hazardous material or hazardous waste shall be disposed of on
 government property. No hazardous material shall be brought onto
 government property that does not directly relate to requirements for the
 performance of this contract. The government is not responsible for
 disposal of Contractor's waste material brought on the job site and not
 required in the performance of this contract. The intent of this provision
 is to dispose of that waste identified as waste hazardous
 material/hazardous waste as defined herein that was generated as part of
 this contract and existed within the boundary of the Contract limits and
 not brought in from offsite by the Contractor. Incidental materials used
 to support the contract including, but not limited to aerosol cans, waste
 paint, cleaning solvents, contaminated brushes, rags, clothing, etc. are
 the responsibility of the Contractor. The list is illustrative rather than
 inclusive. The Contractor is not authorized to discharge any materials to
 sanitary sewer, storm drain, or to the river or conduct waste treatment or
 disposal on government property without written approval of the Contracting
 Officer.

3.9    HAZARDOUS MATERIAL CONTROL

 Include hazardous material control procedures in the Safety Plan. Address
 procedures and proper handling of hazardous materials, including the
 appropriate transportation requirements. Submit a MSDS and estimated
 quantities to be used for each hazardous material to the Contracting
 Officer prior to bringing the material on base. Typical materials
 requiring MSDS and quantity reporting include, but are not limited to, oil
 and latex based painting and caulking products, solvents, adhesives,
 aerosol, and petroleum products. At the end of the project, provide the
 Contracting Officer with the maximum quantity of each material that was
 present at the site at any one time, the dates the material was present,
 the amount of each material that was used during the project, and how the
 material was used. Ensure that hazardous materials are utilized in a
 manner that will minimize the amount of hazardous waste that is generated.
 Ensure that all containers of hazardous materials have NFPA labels or their
 equivalent. Keep copies of the MSDS for hazardous materials on site at all
 times and provide them to the Contracting Officer at the end of the
 project. Certify that all hazardous materials removed from the site are
 hazardous materials and do not meet the definition of hazardous waste per
 40 CFR 261.

3.10    PETROLEUM PRODUCTS

 Conduct the fueling and lubricating of equipment and motor vehicles in a
 manner that protects against spills and evaporation. Manage all used oil
 generated on site in accordance with 40 CFR 279. Determine if any used oil
 generated while on-site exhibits a characteristic of hazardous waste. Used
 oil containing 1000 parts per million of solvents will be considered a
 hazardous waste and disposed of at Contractor's expense. Used oil mixed
 with a hazardous waste will also be considered a hazardous waste.




                        SECTION 01 57 19.00 20   Page 16
Design MET Facility                                                    5490419


3.10.1     Oily and Hazardous Substances

 Prevent oil or hazardous substances from entering the ground, drainage
 areas, or navigable waters. In accordance with 40 CFR 112, surround all
 temporary fuel oil or petroleum storage tanks with a temporary berm or
 containment of sufficient size and strength to contain the contents of the
 tanks, plus 10 percent freeboard for precipitation. The berm will be
 impervious to oil for 72 hours and be constructed so that any discharge
 will not permeate, drain, infiltrate, or otherwise escape before cleanup
 occurs.

3.11     FUEL TANKS

 Petroleum products and lubricants required to sustain up to 30 days of
 construction activity may be kept on site. Storage and refilling practices
 shall comply with 40 CFR Part 112. Secondary containment shall be provided
 and be no less than 110 percent of the tank volume plus five inches of
 free-board. If a secondary berm is used for containment then the berm
 shall be impervious to oil for 72 hours and be constructed so that any
 discharge will not permeate, drain, infiltrate, or otherwise escape before
 cleanup occurs. Drips pans are required and the tanks must be covered
 during inclement weather.


3.12     RELEASES/SPILLS OF OIL AND HAZARDOUS SUBSTANCES

 Exercise due diligence to prevent, contain, and respond to spills of
 hazardous material, hazardous substances, hazardous waste, sewage,
 regulated gas, petroleum, lubrication oil, and other substances regulated
 by environmental law. Maintain spill cleanup equipment and materials at
 the work site. In the event of a spill, take prompt, effective action to
 stop, contain, curtail, or otherwise limit the amount, duration, and
 severity of the spill/release. In the event of any releases of oil and
 hazardous substances, chemicals, or gases; immediately (within 15 minutes)
 notify the Base or Activity Fire Department, the activity's Command Duty
 Officer, and the Contracting Officer. If the contractor's response is
 inadequate, the Navy may respond. If this should occur, the contractor
 will be required to reimburse the government for spill response assistance
 and analysis.

 The Contractor is responsible for verbal and written notifications as
 required by the federal 40 CFR 355, State, local regulations and Navy
 Instructions. Spill response will be in accordance with 40 CFR 300 and
 applicable State and local regulations. Contain and clean up these spills
 without cost to the Government. If Government assistance is requested or
 required, the Contractor will reimburse the Government for such
 assistance. Provide copies of the written notification and documentation
 that a verbal notification was made within 20 days.

 Maintain spill cleanup equipment and materials at the work site. Clean up
 all hazardous and non-hazardous (WHM) waste spills. The Contractor shall
 reimburse the government for all material, equipment, and clothing
 generated during any spill cleanup. The Contractor shall reimburse the
 government for all costs incurred including sample analysis materials,
 equipment, and labor if the government must initiate its own spill cleanup
 procedures, for Contractor responsible spills, when:

            a. The Contractor has not begun spill cleanup procedure within
            one hour of spill discovery/occurrence, or


                         SECTION 01 57 19.00 20   Page 17
Design MET Facility                                                         5490419



            b. If, in the government's judgment, the Contractor's spill
            cleanup is not adequately abating life threatening situation
            and/or is a threat to any body of water or environmentally
            sensitive areas.

3.13     CONTROL AND DISPOSAL OF HAZARDOUS WASTES

3.13.1     Hazardous Waste/Debris Management

 Identify all construction activities which will generate hazardous
 waste/debris. Provide a documented waste determination for all resultant
 waste streams. Hazardous waste/debris will be identified, labeled,
 handled, stored, and disposed of in accordance with all Federal, State, and
 local regulations including 40 CFR 261, 40 CFR 262, 40 CFR 263, 40 CFR 264,
 40 CFR 265, 40 CFR 266, and 40 CFR 268. Hazardous waste will also be
 managed in accordance with the approved Hazardous Waste Management Section
 of the Environmental Protection Plan. Store hazardous wastes in approved
 containers in accordance with 49 CFR 173 and 49 CFR 178. Hazardous waste
 generated within the confines of Government facilities will be identified
 as being generated by the Government. Prior to removal of any hazardous
 waste from Government property, all hazardous waste manifests must be
 signed by activity personnel from the Station Environmental Office. No
 hazardous waste will be brought onto Government property. Provide to the
 Contracting Officer a copy of waste determination documentation for any
 solid waste streams that have any potential to be hazardous waste or
 contain any chemical constituents listed in 40 CFR 372-SUBPART D. For
 hazardous wastes spills, verbally notify the Contracting Officer
 immediately.

3.13.1.1     Regulated Waste Storage/Satellite Accumulation/90 Day Storage Areas

 If the work requires the temporary storage/collection of regulated or
 hazardous wastes, the Contractor will request the establishment of a
 Regulated Waste Storage Area, a Satellite Accumulation Area, or a 90 Day
 Storage Area at the point of generation. The Contractor must submit a
 request in writing to the Contracting Officer providing the following
 information:

 Contract Number           ____________      Contractor        ______________

 Haz/Waste or
 Regulated Waste POC       ____________      Phone Number      ______________

 Type of Waste             ____________      Source of Waste   ______________

 Emergency POC             ____________      Phone Number      ______________

 Location of the Site: ____________
 (Attach Site Plan to the Request)

 Attach a waste determination form.       Allow ten working days for processing
 this request.

3.13.2     Class I   ODS Prohibition

 Class I ODS as defined and identified herein will not be used in the
 performance of this contract, nor be provided as part of the equipment.
 This prohibition will be considered to prevail over any other provision,


                          SECTION 01 57 19.00 20    Page 18
Design MET Facility                                                   5490419


 specification, drawing, or referenced documents.

3.14     DUST CONTROL

 Keep dust down at all times, including during nonworking periods. Sprinkle
 or treat, with dust suppressants, the soil at the site, haul roads, and
 other areas disturbed by operations. Dry power brooming will not be
 permitted. Instead, use vacuuming, wet mopping, wet sweeping, or wet power
 brooming. Air blowing will be permitted only for cleaning nonparticulate
 debris such as steel reinforcing bars. Only wet cutting will be permitted
 for cutting concrete blocks, concrete, and bituminous concrete. Do not
 unnecessarily shake bags of cement, concrete mortar, or plaster.

3.14.1     Dirt and Dust Control Plan

 Submit truck and material haul routes along with a plan for controlling
 dirt, debris, and dust on base roadways. As a minimum, identify in the
 plan the subcontractor and equipment for cleaning along the haul route and
 measures to reduce dirt, dust, and debris from roadways.

3.15     ABRASIVE BLASTING

3.15.1     Blasting Operations

 The use of silica sand is prohibited in sandblasting.

 Provide tarpaulin drop cloths and windscreens to enclose abrasive blasting
 operations to confine and collect dust, abrasive, agent, paint chips, and
 other debris. Perform work involving removal of hazardous material in
 accordance with 29 CFR 1910.

3.15.2     Disposal Requirements

 Submit analytical results of the debris generated from abrasive blasting
 operations per paragraph entitled Laboratory Analysis of this section.
 Hazardous waste generated from blasting operations will be managed in
 accordance with paragraph entitled "Hazardous Waste\Debris Management" of
 this section and with the approved HWMP.

3.16     NOISE

 Make the maximum use of low-noise emission products, as certified by the
 EPA. Blasting or use of explosives will not be permitted without written
 permission from the Contracting Officer, and then only during the
 designated times.

3.17     MERCURY MATERIALS

 Mercury is prohibited in the construction of this facility, unless
 specified otherwise, and with the exception of mercury vapor lamps and
 fluorescent lamps. Dumping of mercury-containing materials and devices
 such as mercury vapor lamps, fluorescent lamps, and mercury switches, in
 rubbish containers is prohibited. Remove without breaking, pack to prevent
 breakage, and transport out of the activity in an unbroken condition for
 disposal as directed. Immediately report to the Contracting Officer
 instances of breakage or mercury spillage. Clean mercury spill area to the
 satisfaction of the Contracting Officer.




                         SECTION 01 57 19.00 20   Page 19
Design MET Facility                                                        5490419


3.18     Soil

 Soils encountered during project activities shall be managed per Air
 Station soil management polices in affect for the duration of the project.
 If soil is encountered during construction operations that may be
 contaiminated (as indicated by odor, color, or unusual appearance) that was
 not previously indicated as contaminated, stop the portion of work
 immediately and notify the Contracting Officer immediately.

3.18.1        Quarantne for Imported Fire Ants

 Onslow, Jones, and Carteret Counties and portions of Duplin and Craven
 Counties have been declared a generally infested area by the United States
 Department of Agriculture (USDA) for the imported fire ant. Compliance
 with the quarantine regulations established by this authority as set forth
 is USDA Publication 301.81 of 31 December 1992, is required for operations
 hereunder. Pertinent requirements of quarantine for materials originating
 on the Camp Lejeune reservation, the Marine Corps Air Station (Helicopter),
 New River and the Marine Corps Air Station, Cherry Point, which are to be
 transported outside Onslow County or adjacent suppression areas, include
 the following:

               a. Certification is required for the following articles and they
               shall not be moved from the reservation to any point outside
               Onslow County and adjacent designated areas unless accompanied by
               a valid inspection certificate issued by an Officer of the Plant
               Protection and AQuarantine Program (PPQ) of the U.S. Department of
               Agriculture.

               (1)   Bulk soil

               (2) Used Mechanized soil-moving equipment. (Used mechanized
               soil-moving equipment is exempt if cleaned of loose non compacted
               soil).

               (3) Other products, articles, or means of conveyances, if it is
               determined by an inspector that they present a hazard of
               transporting spread of the imported fire ant and the person in
               possession therof has been so notified.

         b.    Authorization for movement of equipment outside the imported fire
               and regulated area shall be obtained from USDA, APHIS, PPQ, Attn:
               JB Perry, C/o NCSPA, 113 Arendell St. Room 216, Morehead City, NC
               28557, telephone (252) 726-4358, fax (252) 726-5713. Requests for
               inspection shall be made sufficiently in advance of the date of
               movement to permit arrangement for the services of authorized
               inspectors. The equipment shall be prepared and assembled so that
               it may be readily inspected. Soil on or attached to equipment,
               supplies, and materials shall be removed by washing with water or
               such other means as necessary to accomplish complete removal.
               Resulting spoil shall be wasted as necessary and as directed.

    -- End of Section --




                             SECTION 01 57 19.00 20   Page 20
Design MET Facility                                                        5490419



                               SECTION 01 77 00.00 20

                                CLOSEOUT PROCEDURES
                                       07/06

PART 1     GENERAL

1.1     SUBMITTALS

 Government approval is required for submittals with a "G" designation;
 submittals not having a "G" designation are for information only. The
 following shall be submitted in accordance with Section 01 33 00 SUBMITTAL
 PROCEDURES:

         SD-10 Operation and Maintenance Data

             Equipment/Product Warranty List; G

               Submit Data Package 1 in accordance with Section 01 78 23
             OPERATION AND MAINTENANCE DATA.

         SD-11 Closeout Submittals

             As-Built Drawings; G

             Record Of Materials; G

             Utility As-Built Drawings; G

             Equipment/Product Warranty Tag; G

             Monthly Project Waste Summary Report; G

             Hazardous Material Reporting; G

             Certification of EPA Designated Items; G

             Form DD1354; G

             Checklist for Form DD1354; G

1.2     CERTIFICATION OF EPA DESIGNATED ITEMS

 Submit the Certification of EPA Designated Items as required by FAR
 52.223-9, "Certification and Estimate of Percentage of Recovered Material
 Content for EPA Designated Items". The certification form shall include
 the following information: project name, project number, Contractor name,
 license number, Contractor address, and certification. The certification
 shall read as follows and shall be signed and dated by the Contractor.
 Recycled and biobased content values may be determined by weight or volume
 percent, but must be consistent throughout.

1.3     PROJECT RECORD DOCUMENTS

1.3.1     As-Built Drawings

 "NFAS 5252.236-9310, Record Drawings."



                           SECTION 01 77 00.00 20   Page 1
Design MET Facility                                                            5490419


1.3.2     Utility As-Built Drawings

 In addition to record drawings provide for each exterior utility system a
 set of reproducible utility drawings, stamped and signed by a registered
 professional civil engineer or professional land surveyor, and two copies.
 Submit within ten working days after each system is in place, but no later
 than five working days before final inspection. Indicate exterior
 utilities from a point five feet from a building to the termination point
 or point of connection to existing system. Include the following:

        a.   Horizontal and vertical controls for new utilities and existing
             utilities exposed during construction. Reference to station's
             horizontal and vertical control system.

        b.   Sufficient dimensional control for all important features such as
             beginning and termination points, points of connection, inverts
             for sewer lines and drainage collection systems, top of pipe or
             conduit runs, manholes, cathodic protection appurtenances, valves,
             valve stem tops, backflow preventers, and other significant
             features.

        c.   Indicate type and size of all materials used in the construction
             of the system.

        d.   Indicate bearing and distance on tangent lines. On curves,
             indicate delta and radius of the curve, also provide X, Y, and Z
             coordinates at all BC and EC angle points. Indicate horizontal
             and vertical control for all intersecting and tangent points where
             utility alignment changes. Indicate X, Y, and Z coordinates at
             building line and point of connection for straight building
             laterals or services under 40 feet.

        e.   Tolerances: Horizontal and vertical control dimensions, plus or
             minus 0.10 foot. Angular control, plus or minus 0 degrees 01
             minute.

1.3.3     As-Built Record of Materials

 Furnish a record of materials.

 Where several manufacturers' brands, types, or classes of the item listed
 have been used in the project, designate specific areas where each item was
 used. Designations shall be keyed to the areas and spaces depicted on the
 contract drawing. Furnish the record of materials used in the following
 format:

  MATERIALS       SPECIFICATION    MANUFACTURER     MATERIALS USED     WHERE
  DESIGNATION                                       (MANUFACTURER'S    USED
                                                    DESIGNATION)


  Roofing          _____          _____              _____            _____


1.4     EQUIPMENT/PRODUCT WARRANTIES

1.4.1     Equipment/Product Warranty List

 Furnish to the Contracting Officer a bound and indexed notebook containing


                           SECTION 01 77 00.00 20    Page 2
Design MET Facility                                                      5490419


 written warranties for equipment/products furnished under the contract, and
 prepare a complete listing of such equipment/products. The
 equipment/products list shall state the specification section applicable to
 the equipment/product, duration of the warranty therefore, start date of
 the warranty, ending date of the warranty, and the point of contact for
 fulfillment of the warranty. The warranty period shall begin on the same
 date as project acceptance and shall continue for the full product warranty
 period. Execute the full list and deliver to the Contracting Officer prior
 to final acceptance of the facility.

1.4.2     Equipment Warranty Tags and Guarantor's Local Representative

 Furnish with each warranty the name, address, and telephone number of the
 guarantor's representative nearest to the location where the equipment and
 appliances are installed. The guarantor's representative, upon request of
 the station representative, shall honor the warranty during the warranty
 period, and shall provide the services prescribed by the terms of the
 warranty. At the time of installation, tag each item of warranted
 equipment with a durable, oil- and water-resistant tag approved by the
 Contracting Officer. Attach tag with copper wire and spray with a clear
 silicone waterproof coating. Leave the date of acceptance and QC's
 signature blank until project is accepted for beneficial occupancy. Tag
 shall show the following information:

                          EQUIPMENT/PRODUCT WARRANTY TAG

         Type of Equipment/Product ____________________
         Warranty Period __________ From __________ To __________
         Contract No. ____________________
         Inspector's Signature _____________________ Date Accepted ____________

         Construction Contractor:
         Name: ____________________
         Address: _______________________
         Telephone: _______________________

         Warranty Contact: __________________
         Name: ____________________
         Address: ________________________
         Telephone: ________________________

         STATION PERSONNEL TO PERFORM ONLY OPERATIONAL MAINTENANCE

1.5     CLEANUP

 Leave premises "broom clean." Clean interior and exterior glass surfaces
 exposed to view; remove temporary labels, stains and foreign substances;
 polish transparent and glossy surfaces; vacuum carpeted and soft surfaces.
 Clean equipment and fixtures to a sanitary condition. Replacefilters of
 operating equipment. Clean debris from roofs, gutters, downspouts and
 drainage systems. Sweep paved areas and rake clean landscaped areas.
 Remove waste and surplus materials, rubbish and construction facilities
 from the site.

PART 2     PRODUCTS

 Not used.




                          SECTION 01 77 00.00 20   Page 3
Design MET Facility                                         5490419


PART 3     EXECUTION

 Not used.

         -- End of Section --




                          SECTION 01 77 00.00 20   Page 4
Design MET Facility                                                   5490419



                                    SECTION 01 78 23

                            OPERATION AND MAINTENANCE DATA
                                         07/10

PART 1     GENERAL

1.1     SUBMISSION OF OPERATION AND MAINTENANCE DATA

 Submit Operation and Maintenance (O&M) Data specifically applicable to this
 contract and a complete and concise depiction of the provided equipment,
 product, or system, stressing and enhancing the importance of system
 interactions, troubleshooting, and long-term preventative maintenance and
 operation. The subcontractors shall compile and prepare data and deliver
 to the Contractor prior to the training of Government personnel. The
 Contractor shall compile and prepare aggregate O&M data including
 clarifying and updating the original sequences of operation to as-built
 conditions. Organize and present information in sufficient detail to
 clearly explain O&M requirements at the system, equipment, component, and
 subassembly level. Include an index preceding each submittal. Submit in
 accordance with this section and Section 01 33 00 SUBMITTAL PROCEDURES.

1.1.1     Package Quality

 Documents must be fully legible. Poor quality copies and material with
 hole punches obliterating the text or drawings will not be accepted.

1.1.2     Package Content

 Data package content shall be as shown in the paragraph titled "Schedule of
 Operation and Maintenance Data Packages." Comply with the data package
 requirements specified in the individual technical sections, including the
 content of the packages and addressing each product, component, and system
 designated for data package submission, except as follows. Commissioned
 items without a specified data package requirement in the individual
 technical sections shall use Data Package 3.

1.1.3     Changes to Submittals

 Manufacturer-originated changes or revisions to submitted data shall be
 furnished by the Contractor if a component of an item is so affected
 subsequent to acceptance of the O&M Data. Changes, additions, or revisions
 required by the Contracting Officer for final acceptance of submitted data,
 shall be submitted by the Contractor within 30 calendar days of the
 notification of this change requirement.

1.1.4     Review and Approval

 The Contractor's Commissioning Authority (CA) shall review the commissioned
 systems and equipment submittals for completeness and applicability. The
 CA shall verify that the systems and equipment provided meet the
 requirements of the Contract documents and design intent, particularly as
 they relate to functionality, energy performance, water performance,
 maintainability, sustainability, system cost, indoor environmental
 quality, and local environmental impacts. The CA shall communicate
 deficiencies to the Contracting Officer. Upon a successful review of the
 corrections, the CA shall recommend approval and acceptance of these O&M
 manuals to the Contracting Officer. This work shall be in addition to the


                                SECTION 01 78 23   Page 1
Design MET Facility                                                      5490419


 normal review procedures for O&M data.

1.1.5     O&M Database

 Develop a database from the O&M manuals that contains the information
 required to start a preventative maintenance program.

1.2     TYPES OF INFORMATION REQUIRED IN O&M DATA PACKAGES

1.2.1     Operating Instructions

 Include specific instructions, procedures, and illustrations for the
 following phases of operation for the installed model and features of each
 system:

1.2.1.1     Safety Precautions

 List personnel hazards and equipment or product safety precautions for all
 operating conditions.

1.2.1.2     Operator Prestart

 Include procedures required to install, set up, and prepare each system for
 use.

1.2.1.3     Startup, Shutdown, and Post-Shutdown Procedures

 Provide narrative description for Startup, Shutdown and Post-shutdown
 operating procedures including the control sequence for each procedure.

1.2.1.4     Normal Operations

 Provide narrative description of Normal Operating Procedures. Include
 Control Diagrams with data to explain operation and control of systems and
 specific equipment.

1.2.1.5     Emergency Operations

 Include Emergency Procedures for equipment malfunctions to permit a short
 period of continued operation or to shut down the equipment to prevent
 further damage to systems and equipment. Include Emergency Shutdown
 Instructions for fire, explosion, spills, or other foreseeable
 contingencies. Provide guidance and procedures for emergency operation of
 all utility systems including required valve positions, valve locations and
 zones or portions of systems controlled.

1.2.1.6     Operator Service Requirements

 Include instructions for services to be performed by the operator such as
 lubrication, adjustment, inspection, and recording gage readings.

1.2.1.7     Environmental Conditions

 Include a list of Environmental Conditions (temperature, humidity, and
 other relevant data) that are best suited for the operation of each
 product, component or system. Describe conditions under which the item
 equipment should not be allowed to run.




                                SECTION 01 78 23   Page 2
Design MET Facility                                                       5490419


1.2.2     Preventive Maintenance

 Include the following information for preventive and scheduled maintenance
 to minimize corrective maintenance and repair for the installed model and
 features of each system. Include potential environmental and indoor air
 quality impacts of recommended maintenance procedures and materials.

1.2.2.1      Lubrication Data

 Include preventative maintenance lubrication data, in addition to
 instructions for lubrication provided under paragraph titled "Operator
 Service Requirements":

        a.   A table showing recommended lubricants for specific temperature
             ranges and applications.

        b.   Charts with a schematic diagram of the equipment showing
             lubrication points, recommended types and grades of lubricants,
             and capacities.

        c.   A Lubrication Schedule showing service interval frequency.

1.2.2.2      Preventive Maintenance Plan and Schedule

 Include manufacturer's schedule for routine preventive maintenance,
 inspections, tests and adjustments required to ensure proper and economical
 operation and to minimize corrective maintenance. Provide manufacturer's
 projection of preventive maintenance work-hours on a daily, weekly,
 monthly, and annual basis including craft requirements by type of craft.
 For periodic calibrations, provide manufacturer's specified frequency and
 procedures for each separate operation.

1.2.3     Corrective Maintenance (Repair)

 Include manufacturer's recommended procedures and instructions for
 correcting problems and making repairs.

1.2.3.1      Troubleshooting Guides and Diagnostic Techniques

 Include step-by-step procedures to promptly isolate the cause of typical
 malfunctions. Describe clearly why the checkout is performed and what
 conditions are to be sought. Identify tests or inspections and test
 equipment required to determine whether parts and equipment may be reused
 or require replacement.

1.2.3.2      Wiring Diagrams and Control Diagrams

 Wiring diagrams and control diagrams shall be point-to-point drawings of
 wiring and control circuits including factory-field interfaces. Provide a
 complete and accurate depiction of the actual job specific wiring and
 control work. On diagrams, number electrical and electronic wiring and
 pneumatic control tubing and the terminals for each type, identically to
 actual installation configuration and numbering.

1.2.3.3      Maintenance and Repair Procedures

 Include instructions and a list of tools required to repair or restore the
 product or equipment to proper condition or operating standards.



                                SECTION 01 78 23   Page 3
Design MET Facility                                                        5490419


1.2.3.4     Removal and Replacement Instructions

 Include step-by-step procedures and a list required tools and supplies for
 removal, replacement, disassembly, and assembly of components, assemblies,
 subassemblies, accessories, and attachments. Provide tolerances,
 dimensions, settings and adjustments required. Instructions shall include
 a combination of text and illustrations.

1.2.3.5     Spare Parts and Supply Lists

 Include lists of      spare parts and supplies required for maintenance and
 repair to ensure      continued service or operation without unreasonable
 delays. Special       consideration is required for facilities at remote
 locations. List       spare parts and supplies that have a long lead-time to
 obtain.

1.2.4     Corrective Maintenance Work-Hours

 Include manufacturer's projection of corrective maintenance work-hours
 including requirements by type of craft. Corrective maintenance that
 requires completion or participation of the equipment manufacturer shall be
 identified and tabulated separately.

1.2.5     Appendices

 Provide information required below and information not specified in the
 preceding paragraphs but pertinent to the maintenance or operation of the
 product or equipment. Include the following:

1.2.5.1     Product Submittal Data

 Provide a copy of all SD-03 Product Data submittals required in the
 applicable technical sections.

1.2.5.2     Manufacturer's Instructions

 Provide a copy of all SD-08 Manufacturer's Instructions submittals required
 in the applicable technical sections.

1.2.5.3     O&M Submittal Data

 Provide a copy of all SD-10 Operation and Maintenance Data submittals
 required in the applicable technical sections.

1.2.5.4     Parts Identification

 Provide identification and coverage for all parts of each component,
 assembly, subassembly, and accessory of the end items subject to
 replacement. Include special hardware requirements, such as requirement to
 use high-strength bolts and nuts. Identify parts by make, model, serial
 number, and source of supply to allow reordering without further
 identification. Provide clear and legible illustrations, drawings, and
 exploded views to enable easy identification of the items. When
 illustrations omit the part numbers and description, both the illustrations
 and separate listing shall show the index, reference, or key number that
 will cross-reference the illustrated part to the listed part. Parts shown
 in the listings shall be grouped by components, assemblies, and
 subassemblies in accordance with the manufacturer's standard practice.
 Parts data may cover more than one model or series of equipment,


                               SECTION 01 78 23   Page 4
Design MET Facility                                                    5490419


 components, assemblies, subassemblies, attachments, or accessories, such as
 typically shown in a master parts catalog

1.2.5.5    Warranty Information

 List and explain the various warranties and clearly identify the servicing
 and technical precautions prescribed by the manufacturers or contract
 documents in order to keep warranties in force. Include warranty
 information for primary components such as the compressor of air
 conditioning system.

1.2.5.6    Personnel Training Requirements

 Provide information available from the manufacturers that is needed for
 use in training designated personnel to properly operate and maintain the
 equipment and systems.

1.2.5.7    Testing Equipment and Special Tool Information

 Include information on test equipment required to perform specified tests
 and on special tools needed for the operation, maintenance, and repair of
 components.

1.2.5.8    Testing and Performance Data

 Include completed prefunctional checklists, functional performance test
 forms, and monitoring reports. Include recommended schedule for retesting
 and blank test forms.

1.2.5.9    Contractor Information

 Provide a list that includes the name, address, and telephone number of the
 General Contractor and each Subcontractor who installed the product or
 equipment, or system. For each item, also provide the name address and
 telephone number of the manufacturer's representative and service
 organization that can provide replacements most convenient to the project
 site. Provide the name, address, and telephone number of the product,
 equipment, and system manufacturers.

1.3   TYPES OF INFORMATION REQUIRED IN CONTROLS O&M DATA PACKAGES

 Include Data Package 5 and the following for control systems:

      a. Narrative description on how to perform and apply all functions,
      features, modes, and other operations, including unoccupied operation,
      seasonal changeover, manual operation, and alarms. Include detailed
      technical manual for programming and customizing control loops and
      algorithms.

      b.   Full as-built sequence of operations.

      c. Copies of all checkout tests and calibrations performed by the
      Contractor (not Cx tests).

1.4   SCHEDULE OF OPERATION AND MAINTENANCE DATA PACKAGES

 Furnish the O&M data packages specified in individual technical sections.
 The required information for each O&M data package is as follows:



                            SECTION 01 78 23   Page 5
Design MET Facility                                            5490419


1.4.1    Data Package 1

        a.   Safety precautions

        b.   Cleaning recommendations

        c.   Maintenance and repair procedures

        d.   Warranty information

        e.   Contractor information

        f.   Spare parts and supply list

1.4.2    Data Package 2

        a.   Safety precautions

        b.   Normal operations

        c.   Environmental conditions

        d.   Lubrication data

        e.   Preventive maintenance plan and schedule

        f.   Cleaning recommendations

        g.   Maintenance and repair procedures

        h.   Removal and replacement instructions

        i.   Spare parts and supply list

        j.   Parts identification

        k.   Warranty information

        l.   Contractor information

1.4.3    Data Package 3

        a.   Safety precautions

        b.   Operator prestart

        c.   Startup, shutdown, and post-shutdown procedures

        d.   Normal operations

        e.   Emergency operations

        f.   Environmental conditions

        g.   Lubrication data

        h.   Preventive maintenance plan and schedule

        i.   Cleaning recommendations


                                SECTION 01 78 23   Page 6
Design MET Facility                                             5490419



        j.   Troubleshooting guides and diagnostic techniques

        k.   Wiring diagrams and control diagrams

        l.   Maintenance and repair procedures

        m.   Removal and replacement instructions

        n.   Spare parts and supply list

        o.   Product submittal data

        p.   O&M submittal data

        q.   Parts identification

        r.   Warranty information

        s.   Testing equipment and special tool information

        t.   Testing and performance data

        u.   Contractor information

1.4.4    Data Package 4

        a.   Safety precautions

        b.   Operator prestart

        c.   Startup, shutdown, and post-shutdown procedures

        d.   Normal operations

        e.   Emergency operations

        f.   Operator service requirements

        g.   Environmental conditions

        h.   Lubrication data

        i.   Preventive maintenance plan and schedule

        j.   Cleaning recommendations

        k.   Troubleshooting guides and diagnostic techniques

        l.   Wiring diagrams and control diagrams

        m.   Maintenance and repair procedures

        n.   Removal and replacement instructions

        o.   Spare parts and supply list

        p.   Corrective maintenance man-hours



                                SECTION 01 78 23   Page 7
Design MET Facility                                               5490419


         q.    Product submittal data

         r.    O&M submittal data

         s.    Parts identification

         t.    Warranty information

         u.    Personnel training requirements

         v.    Testing equipment and special tool information

         w.    Testing and performance data

         x.    Contractor information

1.4.5     Data Package 5

         a.    Safety precautions

         b.    Operator prestart

         c.    Start-up, shutdown, and post-shutdown procedures

         d.    Normal operations

         e.    Environmental conditions

         f.    Preventive maintenance plan and schedule

         g.    Troubleshooting guides and diagnostic techniques

         h.    Wiring and control diagrams

         i.    Maintenance and repair procedures

         j.    Removal and replacement instructions

         k.    Spare parts and supply list

         l.    Product submittal data

         m.    Manufacturer's instructions

         n.    O&M submittal data

         o.    Parts identification

         p.    Testing equipment and special tool information

         q.    Warranty information

         r.    Testing and performance data

         s.    Contractor information

PART 2        PRODUCTS

 Not used.


                               SECTION 01 78 23    Page 8
Design MET Facility                                         5490419



PART 3     EXECUTION

 Not used.

         -- End of Section --




                                SECTION 01 78 23   Page 9
Design MET Facility                                                       5490419



                                    SECTION 01 80 00

                                        REPORTS
                                         07/06

PART 1     GENERAL

1.1     REPORTS INCLUDED

1.1.1     Geotechnical Report

         Report of Subsurface Exploration and Geotechnical Engineering Analysis,
         MRAP Trainer Facility, MCAs Cherry Point, Craven County, North
         Carolina, Dated June 30, 2010.

1.2     USE OF INFORMATION

1.2.1     Warranty

 The information disclosed in the referenced reports is based on data
 obtained in specific locations and is assumed to be representative of
 conditions throughout the site. This information is furnished without
 warranty and is only for general information to be used by the contractor
 in the preparation of his bid and work schedule. It is not intended as a
 replacement for personal investigation and judgment, or interpretation of
 the information furnished, as required of the contractor in the performance
 of this contract.

1.2.2     Site Visit

 Bidders should visit the site and acquaint themselves with all existing
 conditions prior to preparing their bid. This will include a review of the
 conditions contained in the enclosed report as they relate to the site.
 The contractor is responsible for including in his bid and work schedule,
 procedures for handling existing site conditions delineated in the included
 reports in accord with applicable laws and regulations as those conditions
 may effect the work.

1.2.3     Application of Information

 Recommendations contained in the reports are to be used by the contractor
 only to the extent that these recommendations comply with applicable laws,
 regulations, and other sections of the these specifications.

PART 2     PRODUCTS

 Not used.

PART 3     EXECUTION

3.1     VARYING CONDITIONS

 If during the course of the work, conditions are encountered which are not
 covered in the included reports or are different from conditions that would
 be reasonably anticipated from the included reports, the contractor shall
 immediately notify the Officer in Charge of Construction. If such
 conditions are hazardous or the continuation of work would cause a
 hazardous condition to develop, he shall stop work and proceed as directed


                                SECTION 01 80 00   Page 1
Design MET Facility                                                   5490419


 by the Officer in Charge of Construction as directed by provisions
 contained in other sections of this specification. This may include
 modifications to, or the development of a new, Health and Safety Plan for
 this project, and alternate or additional appropriate abatement procedures.

3.2   CHANGES TO THE CONTRACT

 Any changes to the contract made as a result of site conditions which
 differ from those delineated in the report may result in an adjustment of
 the contract amount. The adjustment will be an increase or decrease
 depending on the scope and nature of the change and will be in accord with
 other provisions of these specifications.

       -- End of Section --




                              SECTION 01 80 00   Page 2
Design MET Facility                                                         5490419




                                     SECTION 02 41 00

                                        DEMOLITION
                                           04/06

PART 1     GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to within the text by the
 basic designation only.

             AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)

 ANSI A10.6                             (1990; R 1998) Safety Requirements for
                                        Demolition Operations

             U.S. ARMY CORPS OF ENGINEERS (USACE)

 EM 385-1-1                             (2008) Safety and Health Requirements
                                        Manual

             U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

 40 CFR 61-SUBPART M                    National Emission Standard for Asbestos

1.2   GENERAL REQUIREMENTS

 Do not begin demolition until authorization is received from the
 Contracting Officer. Remove rubbish and debris from the station daily; do
 not allow accumulations inside or outside the buildings. The work includes
 demolition, salvage of identified items and materials, and removal of
 resulting rubbish and debris. Remove rubbish and debris from Government
 property daily, unless otherwise directed. Materials that cannot be
 removed daily shall be stored in areas specified by the Contracting Officer.
   In the interest of occupational safety and health, perform the work in
 accordance with EM 385-1-1, Section 23, Demolition, and other applicable
 Sections.

1.3   SUBMITTALS

 Government approval is required for submittals with a "G" designation;
 submittals not having a "G" designation are for Contractor Quality Control
 approval. The following shall be submitted in accordance with Section
 01 33 00 SUBMITTAL PROCEDURES:

         SD-07 Certificates

             Demolition plan; G

               Proposed demolition and removal procedures for approval before
             work is started.

         SD-11 Closeout Submittals

             Receipts


                              SECTION 02 41 00       Page 1
Design MET Facility                                                   5490419



              Receipts or bills of laden, as specified.

1.4     REGULATORY AND SAFETY REQUIREMENTS

 Comply with federal, state, and local hauling and disposal regulations.   In
 addition to the requirements of the "Contract Clauses," conform to the
 safety requirements contained in ANSI A10.6.

1.4.1     Notifications

1.4.1.1     General Requirements

 Furnish timely notification of demolition and renovation projects to
 Federal, State, regional, and local authorities in accordance with
 40 CFR 61-SUBPART M. Notify the State's environmental protection agency
 and the Contracting Officer in writing 10 working days prior to the
 commencement of work in accordance with 40 CFR 61-SUBPART M.

1.4.2     Receipts

 Submit a shipping receipt or bill of lading for all containers of ozone
 depleting substance (ODS) shipped to the Defense Depot, Richmond, Virginia.

1.5     DUST AND DEBRIS CONTROL

 Prevent the spread of dust and debris to occupied portions of the building
 and avoid the creation of a nuisance or hazard in the surrounding area. Do
 not use water if it results in hazardous or objectionable conditions such
 as, but not limited to, ice, flooding, or pollution. Sweep pavements as
 often as necessary to control the spread of debris that may result in
 foreign object damage potential to aircraft.

1.6     PROTECTION

1.6.1     Traffic Control Signs

 Where pedestrian and driver safety is endangered in the area of removal
 work, use traffic barricades with flashing lights. Notify the Contracting
 Officer prior to beginning such work.

1.6.2     Existing Work

 Before beginning any demolition work, survey the site and examine the
 drawings and specifications to determine the extent of the work. Record
 existing work in the presence of the Contracting Officer showing the
 condition of structures and other facilities adjacent to areas of
 alteration or removal. Photographs sized 4 inch will be acceptable as a
 record of existing conditions. Include in the record the elevation of the
 top of foundation walls, the location and extent of cracks and other damage
 and description of surface conditions that exist prior to before starting
 work.

1.6.3     Items to Remain in Place

 Take necessary precautions to avoid damage to existing items to remain in
 place, to be reused, or to remain the property of the Government. Repair
 or replace damaged items as approved by the Contracting Officer.
 Coordinate the work of this section with all other work indicated.


                             SECTION 02 41 00   Page 2
Design MET Facility                                                   5490419


 Construct and maintain shoring, bracing, and supports as required. Ensure
 that structural elements are not overloaded. Increase structural supports
 or add new supports as may be required as a result of any cutting, removal,
 or demolition work performed under this contract. Do not overload
 pavements to remain. Provide new supports and reinforcement for existing
 construction weakened by demolition or removal work. Repairs,
 reinforcement, or structural replacement require approval by the
 Contracting Officer prior to performing such work.

1.6.4   Existing Construction

 Do not disturb existing construction beyond the extent indicated or
 necessary for installation of new construction. Provide temporary shoring
 and bracing for support of building components to prevent settlement or
 other movement. Provide protective measures to control accumulation and
 migration of dust and dirt in all work areas. Remove dust, dirt, and
 debris from work areas daily.

1.6.5   Weather Protection

 For portions of the building to remain, protect building interior and
 materials and equipment from the weather at all times. Where removal of
 existing roofing is necessary to accomplish work, have materials and
 workmen ready to provide adequate and temporary covering of exposed areas.

1.6.6   Trees

 Protect trees within the project site which might be damaged during
 demolition, and which are indicated to be left in place, by a 6 foot high
 fence. Erect and secure fence a minimum of 5 feet from the trunk of
 individual trees or follow the outer perimeter of branches or clumps of
 trees. Replace any tree designated to remain that is damaged during the
 work under this contract with like-kind or as approved by the Contracting
 Officer.

1.6.7   Utility Service

 Maintain existing utilities indicated to stay in service and protect
 against damage during demolition operations. Prior to start of work,
 utilities serving each area of alteration or removal will be shut off by
 the Government and disconnected and sealed by the Contractor.

1.6.8   Facilities

 Protect electrical and mechanical services and utilities. Where removal of
 existing utilities and pavement is specified or indicated, provide approved
 barricades, temporary covering of exposed areas, and temporary services or
 connections for electrical and mechanical utilities. Floors, roofs, walls,
 columns, pilasters, and other structural components that are designed and
 constructed to stand without lateral support or shoring, and are determined
 to be in stable condition, must remain standing without additional bracing,
 shoring, or lateral support until demolished, unless directed otherwise by
 the Contracting Officer. Ensure that no elements determined to be unstable
 are left unsupported and place and secure bracing, shoring, or lateral
 supports as may be required as a result of any cutting, removal, or
 demolition work performed under this contract.




                             SECTION 02 41 00   Page 3
Design MET Facility                                                      5490419


1.6.9     Protection of Personnel

 Before, during and after the demolition work the Contractor shall
 continuously evaluate the condition of the structure being demolished and
 take immediate action to protect all personnel working in and around the
 demolition site. No area, section, or component of floors, roofs, walls,
 columns, pilasters, or other structural element will be allowed to be left
 standing without sufficient bracing, shoring, or lateral support to prevent
 collapse or failure while workmen remove debris or perform other work in
 the immediate area.

1.7     BURNING

 The use of burning at the project site for the disposal of refuse and
 debris will not be permitted. Where burning is permitted, adhere to
 federal, state, and local regulations.

1.8     RELOCATIONS

 Perform the removal and reinstallation of relocated items as indicated with
 workmen skilled in the trades involved. Items to be relocated which are
 damaged by the Contractor shall be repaired or replaced with new undamaged
 items as approved by the Contracting Officer.

1.9     REQUIRED DATA

 The Demolition plan shall include procedures for careful removal and
 disposition of materials specified to be salvaged, coordination with other
 work in progress, a disconnection schedule of utility services, a detailed
 description of methods and equipment to be used for each operation and of
 the sequence of operations. Provide procedures for safe conduct of the
 work in accordance with EM 385-1-1.

1.10     ENVIRONMENTAL PROTECTION

 Comply with the Environmental Protection Agency requirements specified.

1.11     USE OF EXPLOSIVES

 Use of explosives will not be permitted.

PART 2     PRODUCTS

2.1     FILL MATERIAL

 Comply with excavating, backfilling, and compacting procedures for soils
 used as backfill material to fill basements, voids, depressions or
 excavations resulting from demolition of structures.

PART 3     EXECUTION

3.1     EXISTING FACILITIES TO BE REMOVED

3.1.1     Structures

         a. Remove existing structures indicated to be removed to two feet
         below grade. Interior walls, other than retaining walls and
         partitions, shall be removed to two feet below grade or to top of
         concrete slab on ground. Basement slabs shall be broken up to permit


                             SECTION 02 41 00   Page 4
Design MET Facility                                                     5490419


        drainage. Sidewalks, curbs, gutters and street light bases shall be
        removed as indicated.

        b. Demolish structures in a systematic manner from the top of the
        structure to the ground. Complete demolition work above each tier or
        floor before the supporting members on the lower level are disturbed.
        Demolish concrete and masonry walls in small sections. Remove
        structural framing members and lower to ground by means of derricks,
        platforms hoists, or other suitable methods as approved by the
        Contracting Officer.

        c. Locate demolition equipment throughout the structure and remove
        materials so as to not impose excessive loads to supporting walls,
        floors, or framing.

        d. Building, or the remaining portions thereof, not exceeding 80 feet
        in height may be demolished by the mechanical method of demolition.

3.1.2     Utilities and Related Equipment

3.1.2.1     General Requirements

 Do not interrupt existing utilities serving occupied or used facilities,
 except when authorized in writing by the Contracting Officer. Do not
 interrupt existing utilities serving facilities occupied and used by the
 Government except when approved in writing and then only after temporary
 utility services have been approved and provided. Do not begin demolition
 work until all utility disconnections have been made. Shut off and cap
 utilities for future use, as indicated.

3.1.2.2     Disconnecting Existing Utilities

 Remove existing utilities, as indicated and terminate in a manner
 conforming to the nationally recognized code covering the specific utility
 and approved by the Contracting Officer. When utility lines are
 encountered that are not indicated on the drawings, the Contracting Officer
 shall be notified prior to further work in that area. Remove meters and
 related equipment and deliver to a location in accordance with instructions
 of the Contracting Officer.

3.1.3     Chain Link Fencing

 Remove chain link fencing, gates and other related salvaged items scheduled
 for removal and transport to designated areas. Remove gates as whole
 units. Cut chain link fabric to 25 foot lengths and store in rolls off
 the groung.

3.1.4     Paving and Slabs

 Remove concrete and asphaltic concrete paving and slabs including aggregate
 base as indicated to a depth of 16 inches below new finish grade. Provide
 neat sawcuts at limits of pavement removal as indicated.

3.1.5     Concrete

 Saw concrete along straight lines to a depth of a minimum 2 inch. Make
 each cut in walls perpendicular to the face and in alignment with the cut
 in the opposite face. Break out the remainder of the concrete provided
 that the broken area is concealed in the finished work, and the remaining


                               SECTION 02 41 00   Page 5
Design MET Facility                                                       5490419


 concrete is sound. At locations where the broken face cannot be concealed,
 grind smooth or saw cut entirely through the concrete.

3.1.6     Patching

 Where removals leave holes and damaged surfaces exposed in the finished
 work, patch and repair these holes and damaged surfaces to match adjacent
 finished surfaces. Where new work is to be applied to existing surfaces,
 perform removals and patching in a manner to produce surfaces suitable for
 receiving new work. Finished surfaces of patched area shall be flush with
 the adjacent existing surface and shall match the existing adjacent surface
 as closely as possible as to texture and finish. Patching shall be as
 specified and indicated, and shall include:

        a.   Concrete and Masonry: Completely fill holes and depressions,
             caused by previous physical damage or left as a result of removals
             in existing masonry walls to remain, with an approved masonry
             patching material, applied in accordance with the manufacturer's
             printed instructions.

3.2     CONCURRENT EARTH-MOVING OPERATIONS

 Do not begin excavation, filling, and other earth-moving operations that
 are sequential to demolition work in areas occupied by structures to be
 demolished until all demolition in the area has been completed and debris
 removed. Holes, open basements and other hazardous openings shall be
 filled.

3.3     DISPOSITION OF MATERIAL

3.3.1     Title to Materials

 Except for salvaged items specified in related Sections, and for materials
 or equipment scheduled for salvage, all materials and equipment removed and
 not reused or salvaged, shall become the property of the Contractor and
 shall be removed from Government property. Title to materials resulting
 from demolition, and materials and equipment to be removed, is vested in
 the Contractor upon approval by the Contracting Officer of the Contractor's
 demolition and removal procedures, and authorization by the Contracting
 Officer to begin demolition. The Government will not be responsible for
 the condition or loss of, or damage to, such property after contract
 award. Materials and equipment shall not be viewed by prospective
 purchasers or sold on the site.

3.3.2     Reuse of Materials and Equipment

 Remove and store materials and equipment indicated to be reused or
 relocated to prevent damage, and reinstall as the work progresses.

3.3.3     Salvaged Materials and Equipment

 Remove materials and equipment that are indicated to be removed by the
 Contractor and that are to remain the property of the Government, and
 deliver to a storage site, as directed within 10 miles of the work site.

        a.   Salvage items and material to the maximum extent possible.

        b. Material salvaged for the Contractor shall be stored as approved by
        the Contracting Officer and shall be removed from Government property


                               SECTION 02 41 00   Page 6
Design MET Facility                                                      5490419


        before completion of the contract. Material salvaged for the
        Contractor shall not be sold on the site.

        c. Salvaged items to remain the property of the Government shall be
        removed in a manner to prevent damage, and packed or crated to protect
        the items from damage while in storage or during shipment. Items
        damaged during removal or storage shall be repaired or replaced to
        match existing items. Containers shall be properly identified as to
        contents.

        d. Historical items shall be removed in a manner to prevent damage.
        The following historical items shall be delivered to the Government for
        disposition: Corner stones, contents of corner stones, and document
        boxes wherever located on the site.

3.3.4     Unsalvageable Material

 Concrete, masonry, and other noncombustible material, except concrete
 permitted to remain in place, shall be disposed of in the disposal area
 located as indicated on the project plans. After disposal is completed,
 the disposal area shall be uniformly graded to drain. Dispose of
 combustible material in the sanitary land fill area located as indicated on
 the project plans.

3.4     CLEANUP

 Debris and rubbish shall be removed from basement and similar excavations.
 Debris shall be removed and transported in a manner that prevents spillage
 on streets or adjacent areas. Apply local regulations regarding hauling
 and disposal.

3.5     DISPOSAL OF REMOVED MATERIALS

3.5.1     Sub Title

 Dispose of debris, rubbish, scrap, and other nonsalvageable materials
 resulting rom removal operations with all applicable federal, state and
 local regulations.

3.5.2     Burning on Government Property

 Burning of materials removed from demolished structures will not be
 permitted on Government property.

3.5.3     Removal from Government Property

 Transport waste materials removed from demolished structures, except waste
 soil, from Government property for legal disposal. Dispose of waste soil
 as directed.

3.6     REUSE OF SALVAGED ITEMS

 Recondition salvaged materials and equipment designated for reuse before
 installation. Replace items damaged during removal and salvage operations
 or restore them as necessary to usable condition.

         -- End of Section --




                                SECTION 02 41 00   Page 7
Design MET Facility                                                   5490419



                                  SECTION 02 82 30

                             RE-ESTABLISHING VEGETATION

                                       01/07


PART 1   GENERAL

1.1   GENERAL REQUIREMENTS

 The work covered by this section consists of preparing seedbeds; furnishing
 and placing limestone, fertilizer, and seed; compacting seedbeds;
 furnishing, placing, and securing mulch; mowing; and other operations
 necessary for the permanent establishment of grasses.

 Seeding and mulching shall be performed on all earth areas disturbed by
 construction. The Contractor shall adapt his operations to variations in
 weather or soil conditions as necessary for the successful establishment
 and growth.

 The quantity of mowing to be performed will be affected by the actual
 conditions which occur during the construction of the project. The
 quantity of mowing may be increased, decreased, or eliminated entirely at
 the direction of the Contracting Officer. Such variations in quantity will
 not be considered as alterations in the details of construction or a change
 in the character of the work.

PART 2   PRODUCTS

2.1   FERTILIZER

 The quality of all fertilizer and all operations in connection with the
 furnishing of this material shall comply with the requirements of the North
 Carolina Fertilizer Law and with the rules and regulations, adopted by the
 North Carolina Board of Agriculture in accordance with the provisions of
 said law, in effect at the time of sampling. Fertilizer shall be 10-10-10.
 Dry fertilizer shall have been manufactured from cured stock. Liquid
 fertilizer shall be stored and cared for after manufacture in a manner that
 will prevent loss of plant food values.

2.2   LIMESTONE

 The quality of all limestone and all operations in connection with the
 furnishing of this material shall comply with the requirements of the North
 Carolina Lime Law and with the rules and regulations adopted by the North
 Carolina Board of. Limestone shall be agricultural grade ground Dolomitic
 limestone. All limestone shall contain not less than 90 percent calcium
 carbonate equivalents. Dolomitic limestone shall contain not less than 10
 percent of magnesium. Dolomitic limestone shall be so graded that at least
 90 percent will pass through a U.S. Standard 20 mesh screen, and at least
 35 percent will pass through a U.S. Standard 100 mesh screen.

2.3   SEED

 The quality of all seed and all operations in connection with the
 furnishing of this material shall comply with the requirements of the North
 Carolina Seed Law and with the rules and regulations adopted by the North


                              SECTION 02 82 30   Page 1
Design MET Facility                                                    5490419


 Carolina Board of Agriculture. Seed shall have been approved by the North
 Carolina Department of Agriculture before being sown. No seed will be
 accepted with a date of test more than 8 months prior to the date of
 sowing, excluding the month in which the test was completed. Seed mix by
 weight shall be as specified on the plans.

2.4     MULCH FOR EROSION CONTROL

 Mulch for erosion control shall consist of grain straw or other acceptable
 material, and shall have been approved by the Contracting Officer before
 being used. All mulch shall be reasonably free from mature seed bearing
 stalks, roots, or bulblets. Material for holding mulch in place shall be
 asphalt or other approved binding material.

2.5     MATTING FOR EROSION CONTROL

2.5.1     General

 Matting for erosion control shall be or excelsior matting. Other
 acceptable material manufactured especially for erosion control may be used
 when approved by the Contracting Officer in writing before being used.
 Matting for erosion control shall not be dyed, bleached, or otherwise
 treated in a manner that will result in toxicity to vegetation.

2.5.2     Erosion Control Matting

 Matting shall consist of a machine produced mat of curled wood excelsior a
 minimum of 47 inches in width. The mat shall weigh 1.6 pounds per square
 yard with a tolerance of plus or minus 10 percent. At least 80 percent of
 the individual fibers shall be 6 inches or more in length. The fibers
 shall be evenly distributed over the entire area of the blanket. One side
 of the excelsior matting shall be covered with an extruded plastic mesh.
 The mesh size for the plastic mesh shall be a maximum of 1 inch x 1 inch.

2.6.3     Wire Staples

 Staples shall be machine made of No. 11 gage new steel wire formed into a
 "U" shape. The size when formed shall be not less than 6 inches in length
 with a throat of not less than 1 inch in width.

2.6     WATER

Water used in the planting or care of vegetation shall meet the requirements
of Class C fresh waters as defined in 15 NAC 2B.0200.

PART 3     EXECUTION

3.1     GENERAL REQUIREMENTS

 The work shall be performed immediately upon completion of earthwork
 areas. No exception will be made to this requirement unless otherwise
 permitted in writing by the Contracting Officer. Upon failure or neglect
 on the part of the Contractor to coordinate his grading with seeding and
 mulching operations and diligently pursue the control of erosion and
 siltation, the Contracting Officer may suspend the Contractor's operations
 until such time as the work is coordinated in a manner acceptable to the
 Contracting Officer.




                               SECTION 02 82 30   Page 2
Design MET Facility                                                   5490419


3.2   SEEDBED PREPARATION

 The Contractor shall cut and satisfactorily dispose of weeds or other
 unacceptable growth on the areas to be seeded. The soil shall then be
 scarified or otherwise loosened to a depth of not less than 3 inches except
 as otherwise provided below or otherwise directed by the Contracting
 Officer. Clods shall be broken and the top 2 to 3 inches of soil shall be
 worked into an acceptable seedbed by the use of soil pulverizers, drags, or
 harrows; or by other methods approved by the Contracting Officer. All rock
 and debris 3 inches or larger shall be removed prior to the application of
 seed and fertilizer. On cut slopes that are 2:1 and steeper, both the
 depth of preparation and the degree of smoothness of the seedbed may be
 reduced as permitted by the Contracting Officer, but in all cases the slope
 surface shall be scarified, grooved, trenched, or punctured so as to
 provide pockets, ridges, or trenches in which the seeding materials can
 lodge. On cut slopes that are either 2:1 or steeper, the Contracting
 Officer may permit the preparation of a partial or complete seedbed during
 the initial grading of the slope. If at the time of final seeding and
 mulching operations such initial preparation is still in a condition
 acceptable to the Contracting Officer, additional seedbed preparation may
 be reduced or eliminated. Seedbed preparation within 2 feet of the edge of
 any pavement shall be limited to a depth of 2 to 3 inches. The preparation
 of seedbeds shall not be done when the soil is frozen, extremely wet, or
 when the Contracting Officer determines that it is an otherwise unfavorable
 working condition.

3.3   LIMESTONE AND FERTILIZER

 Limestone may be applied as a part of the seedbed preparation, provided it
 is immediately worked into the soil. If not so applied, limestone and
 fertilizer shall be distributed uniformly over the prepared seedbed and
 then harrowed, raked, or otherwise thoroughly worked into the seedbed.
 Apply fertilizer at the rate as specified on the plans. Apply lime at the
 rate as specified on the plans. Application equipment for liquid
 fertilizer, other than a hydraulic seeder, shall be calibrated to ensure
 that the required rate of fertilizer is applied uniformly.

3.4   SEEDING

 Seed shall be distributed uniformly over the seedbed at the rate as
 specified on the plans. Seed shall be harrowed, dragged, raked, or
 otherwise worked so as to cover the seed with a layer of soil. The depth
 of covering shall be 1/4 inch. When a hydraulic seeder is used for
 application of seed and fertilizer, the seed shall not remain in water
 containing fertilizer for more than 30 minutes prior to application unless
 otherwise permitted by the Contracting Officer. Immediately after seed has
 been properly covered the seedbed shall be compacted in the manner and
 degree approved by the Contracting Officer.

3.5   MULCHING

 All seeded areas shall be mulched. Grain straw or excelsior mat may be
 used as mulch at any time of the year. Mulch shall be applied within 24
 hours after completion of seeding unless otherwise permitted by the
 Contracting Officer. Care shall be exercised to prevent displacement of
 soil or seed or other damage to the seeded area during the mulching
 operations. Mulch shall be uniformly spread by hand or by approved
 mechanical spreaders or blowers which will provide an acceptable
 application. An acceptable application will be that which will allow some


                            SECTION 02 82 30   Page 3
Design MET Facility                                                  5490419


 sunlight to penetrate and air to circulate but also partially shade the
 ground, reduce erosion, and conserve soil moisture. Mulch shall be held in
 place by applying a sufficient amount of asphalt or other approved binding
 material to assure that the mulch is properly held in place. The rate and
 method of application of binding material shall meet the approval of the
 Contracting Officer. Where the binding material is not applied directly
 with the mulch it shall be applied immediately following the mulch
 application. During the application of binding material, adequate
 precautions shall be taken to prevent damage to vehicles, structures,
 guardrails, and devices. Areas where seeding and mulching have been
 performed shall be maintained in a satisfactory condition until final
 acceptance of the project. Maintenance shall include mowing at the
 location and times directed by the Contracting Officer. Areas of damage or
 failure due to any cause shall be corrected by being repaired or by being
 completely redone as may be directed by the Contracting Officer.
 Excelsior matting shall be installed on all seeded slopes greater than 3:1
 (h:v). Install the matting per the manufacturer's printed instructions.

       -- End of Section --




                              SECTION 02 82 30   Page 4
Design MET Facility                                                     5490419



                              SECTION 03 30 00

                           CAST-IN-PLACE CONCRETE
                                    01/08

PART 1   GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to within the text by the
 basic designation only.

          ACI INTERNATIONAL (ACI)

 ACI/MCP-1                          (2007) Manual of Concrete Practice Part 1:
                                    ACI 104-71R-97 to 223-98

 ACI/MCP-2                          (2007) Manual of Concrete Practice Part 2
                                    - ACI 224R-01 to ACI 313R-97

 ACI/MCP-3                          (2007) Manual of Concrete Practice Part 3
                                    - ACI 315-99 to ACI 343R-95

 ACI/MCP-4                          (2006) Manual of Concrete Practice Part 4
                                    - ACI 345R-05 to 355.2R-04

          AMERICAN ASSOCIATION OF STATE HIGHWAY AND TRANSPORTATION OFFICIALS
          (AASHTO)

 AASHTO M 182                       (2005) Standard Specification for Burlap
                                    Cloth Made from Jute or Kenaf and Cotton
                                    Mats

          AMERICAN HARDBOARD ASSOCIATION (AHA)

 AHA A135.4                         (2004) Basic Hardboard

          ASTM INTERNATIONAL (ASTM)

 ASTM A 185/A 185M                  (2007) Standard Specification for Steel
                                    Welded Wire Reinforcement, Plain, for
                                    Concrete

 ASTM A 496/A 496M                  (2007) Standard Specification for Steel
                                    Wire, Deformed, for Concrete Reinforcement

 ASTM A 497/A 497M                  (2007) Standard Specification for Steel
                                    Welded Wire Reinforcement, Deformed, for
                                    Concrete

 ASTM A 615/A 615M                  (2007) Standard Specification for Deformed
                                    and Plain Carbon-Steel Bars for Concrete
                                    Reinforcement

 ASTM A 82/A 82M                    (2007) Standard Specification for Steel
                                    Wire, Plain, for Concrete Reinforcement



                          SECTION 03 30 00    Page 1
Design MET Facility                                                  5490419


 ASTM C 1017/C 1017M          (2007) Standard Specification for Chemical
                              Admixtures for Use in Producing Flowing
                              Concrete

 ASTM C 1107/C 1107M          (2007a) Standard Specification for
                              Packaged Dry, Hydraulic-Cement Grout
                              (Nonshrink)

 ASTM C 143/C 143M            (2005a) Standard Test Method for Slump of
                              Hydraulic-Cement Concrete

 ASTM C 150                   (2007) Standard Specification for Portland
                              Cement

 ASTM C 156                   (2005) Standard Test Method for Water
                              Retention by Concrete Curing Materials

 ASTM C 171                   (2003) Standard Specification for Sheet
                              Materials for Curing Concrete

 ASTM C 172                   (2007) Standard Practice for Sampling
                              Freshly Mixed Concrete

 ASTM C 173/C 173M            (2007) Standard Test Method for Air
                              Content of Freshly Mixed Concrete by the
                              Volumetric Method

 ASTM C 192/C 192M            (2007) Standard Practice for Making and
                              Curing Concrete Test Specimens in the
                              Laboratory

 ASTM C 231                   (2009a) Standard Test Method for Air
                              Content of Freshly Mixed Concrete by the
                              Pressure Method

 ASTM C 233                   (2007) Standard Test Method for
                              Air-Entraining Admixtures for Concrete

 ASTM C 260                   (2006) Standard Specification for
                              Air-Entraining Admixtures for Concrete

 ASTM C 309                   (2007) Standard Specification for Liquid
                              Membrane-Forming Compounds for Curing
                              Concrete

 ASTM C 31/C 31M              (2006) Standard Practice for Making and
                              Curing Concrete Test Specimens in the Field

 ASTM C 311                   (2005) Sampling and Testing Fly Ash or
                              Natural Pozzolans for Use as a Mineral
                              Admixture in Portland-Cement Concrete

 ASTM C 33                    (2003) Standard Specification for Concrete
                              Aggregates

 ASTM C 39/C 39M              (2005e1) Standard Test Method for
                              Compressive Strength of Cylindrical
                              Concrete Specimens



                       SECTION 03 30 00   Page 2
Design MET Facility                                                      5490419


 ASTM C 42/C 42M                    (2004) Standard Test Method for Obtaining
                                    and Testing Drilled Cores and Sawed Beams
                                    of Concrete

 ASTM C 494/C 494M                  (2005a) Standard Specification for
                                    Chemical Admixtures for Concrete

 ASTM C 618                         (2005) Standard Specification for Coal Fly
                                    Ash and Raw or Calcined Natural Pozzolan
                                    for Use in Concrete

 ASTM C 94/C 94M                    (2009) Standard Specification for
                                    Ready-Mixed Concrete

 ASTM C 989                         (2006) Standard Specification for Ground
                                    Granulated Blast-Furnace Slag for Use in
                                    Concrete and Mortars

 ASTM D 1557                        (2007) Standard Test Methods for
                                    Laboratory Compaction Characteristics of
                                    Soil Using Modified Effort (56,000
                                    ft-lbf/ft3) (2700 kN-m/m3)

 ASTM D 4397                        (2002) Standard Specification for
                                    Polyethylene Sheeting for Construction,
                                    Industrial, and Agricultural Applications

 ASTM D 5759                        (1995; R 2005) Characterization of Coal
                                    Fly Ash and Clean Coal Combustion Fly Ash
                                    for Potential Uses

 ASTM E 329                         (2008) Standard Specification for Agencies
                                    Engaged in the Testing and/or Inspection
                                    of Materials Used in Construction

 ASTM E 648                         (2006a) Standard Test Method for Critical
                                    Radiant Flux of Floor-Covering Systems
                                    Using a Radiant Heat Energy Source

            CONCRETE REINFORCING STEEL INSTITUTE (CRSI)

 CRSI MSP-2                         (1998) Manual of Standard Practice

            NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY (NIST)

 NIST PS 1                          (1996) Construction and Industrial Plywood

            U.S. DEPARTMENT OF COMMERCE (DOC)

 PS1                                (1995) Consturction and Industrial Plywood
                                    (APA V995)

1.2    DEFINITIONS

       a.   "Cementitious material" as used herein must include all portland
            cement, pozzolan, fly ash, and ground granulated blast-furnace slag.

       b.   "Exposed to public view" means situated so that it can be seen
            from eye level from a public location after completion of the


                            SECTION 03 30 00    Page 3
Design MET Facility                                                       5490419


           building. A public location is accessible to persons not
           responsible for operation or maintenance of the building.

      c.   "Chemical admixtures" are materials in the form of powder or
           fluids that are added to the concrete to give it certain
           characteristics not obtainable with plain concrete mixes.

      d.   "Workability (or consistence)" is the ability of a fresh (plastic)
           concrete mix to fill the form/mould properly with the desired work
           (vibration) and without reducing the concrete's quality.
           Workability depends on water content, chemical admixtures,
           aggregate (shape and size distribution), cementitious content and
           age (level of hydration).

1.3   SUBMITTALS

   Submit the following in accordance with Section 01 33 00 SUBMITTAL
 PROCEDURES:

      SD-02 Shop Drawings

           Reinforcing steel

             Reproductions of contract drawings are unacceptable.

      SD-03 Product Data

           Materials for curing concrete

             Submit manufacturer's product data, indicating VOC content.
           Manufacturer's catalog data for the following items must include
           printed instructions for admixtures, bonding agents, epoxy-resin
           adhesive binders, and liquid chemical floor hardeners.

           Joint Sealants
           Portland Cement
           Ready-Mix Concrete
           Concrete Curing Materials
           Reinforcement
           Vapor retarder

           Local/Regional Materials

             Submit documentation indicating distance between manufacturing
           facility and the project site. Indicate distance of raw material
           origin from the project site. Indicate relative dollar value of
           local/regional materials to total dollar value of products
           included in project.

      SD-05 Design Data

           Concrete mix design

             Thirty days minimum prior to concrete placement, submit a mix
           design for each strength and type of concrete. Submit a complete
           list of materials including type; brand; source and amount of
           cement, fly ash, pozzolans, ground slag, and admixtures; and
           applicable reference specifications. Provide mix proportion data
           using at least three different water-cement ratios for each type


                            SECTION 03 30 00   Page 4
Design MET Facility                                                    5490419


          of mixture, which produce a range of strength encompassing those
          required for each class and type of concrete required. If source
          material changes, resubmit mix proportion data using revised
          source material. Provide only materials that have been proven by
          trial mix studies to meet the requirements of this specification,
          unless otherwise approved in writing by the Contracting Officer.
          Indicate clearly in the submittal where each mix design is used
          when more than one mix design is submitted. Submit additional
          data regarding concrete aggregates if the source of aggregate
          changes. Submit copies of the fly ash, and pozzolan test results,
          in addition. The approval of fly ash, and pozzolan test results
          must be within 6 months of submittal date. Obtain acknowledgement
          of receipt prior to concrete placement.

      SD-06 Test Reports

          Concrete mix design

          Fly ash

          Pozzolan

          Ground granulated blast-furnace slag

          Compressive strength tests

          Air Content

          Slump

      SD-07 Certificates

          Curing concrete elements

          Pumping concrete

          VOC Content for form release agents, curing compounds, and
          concrete penetrating sealers

          Material Safety Data Sheets

      SD-08 Manufacturer's Instructions

          Fly ash

          Ground granulated blast-furnace slag

            Submit mill certificates for Steel Bar according to the
          paragraph entitled, "Fabrication," of this section.

            Provide certificates for concrete that are in accordance with
          the paragraph entitled, "Classification and Quality of Concrete,"
          of this section. Provide certificates that contain project name
          and number, date, name of Contractor, name of concrete testing
          service, source of concrete aggregates, material manufacturer,
          brand name of manufactured materials, material name, values as
          specified for each material, and test results.

      SD-11 Closeout Submittals


                             SECTION 03 30 00   Page 5
Design MET Facility                                                    5490419



1.4     MODIFICATION OF REFERENCES

 Accomplish work in accordance with ACI publications except as modified
 herein. Consider the advisory or recommended provisions to be mandatory.
 Interpret reference to the "Building Official," the "Structural Engineer,"
 and the "Architect/Engineer" to mean the Contracting Officer.

1.5     DELIVERY, STORAGE, AND HANDLING

 Do not deliver concrete until vapor barrier, forms, reinforcement, embedded
 items, and chamfer strips are in place and ready for concrete placement.
 ACI/MCP-2 for job site storage of materials. Protect materials from
 contaminants such as grease, oil, and dirt. Ensure materials can be
 accurately identified after bundles are broken and tags removed. Do not
 store concrete curing compounds or sealers with materials that have a high
 capacity to adsorb volatile organic compound (VOC) emissions. Do not store
 concrete curing compounds or sealers in occupied spaces.

1.5.1     Reinforcement

 Store reinforcement of different sizes and shapes in separate piles or
 racks raised above the ground to avoid excessive rusting. Protect from
 contaminants such as grease, oil, and dirt. Ensure bar sizes can be
 accurately identified after bundles are broken and tags removed.

1.6     QUALITY ASSURANCE

1.6.1     Drawings

1.6.1.1     Reinforcing Steel

 ACI/MCP-4. Indicate bending diagrams, assembly diagrams, splicing and laps
 of bars, shapes, dimensions, and details of bar reinforcing, accessories,
 and concrete cover. Do not scale dimensions from structural drawings to
 determine lengths of reinforcing bars.

1.6.2     Control Submittals

1.6.2.1     Curing Concrete Elements

 Submit proposed materials and methods for curing concrete elements.

1.6.2.2     Pumping Concrete

 Submit proposed materials and methods for pumping concrete. Submittal must
 include mix designs, pumping equipment including type of pump and size and
 material for pipe, and maximum length and height concrete is to be pumped.

1.6.2.3   VOC Content for form release agents, curing compounds, and concrete
penetrating sealers

 Submit certification for the form release agent, curing compounds, and
 concrete penetrating sealers that indicate the VOC content of each product.

1.6.2.4     Material Safety Data Sheets

 Submit Material Safety Data Sheets (MSDS) for all materials that are
 regulated for hazardous health effects. Prominently post the MSDS at the


                                SECTION 03 30 00   Page 6
Design MET Facility                                                      5490419


 construction site.

1.6.3     Test Reports

1.6.3.1     Concrete Mix Design

 Submit copies of laboratory test reports showing that the mix has been
 successfully tested to produce concrete with the properties specified and
 that mix must be suitable for the job conditions. Include mill test and
 all other test for cement, aggregates, and admixtures in the laboratory
 test reports. Provide maximum nominal aggregate size, gradation analysis,
 percentage retained and passing sieve, and a graph of percentage retained
 verses sieve size. Submit test reports along with the concrete mix
 design. Obtain approval before concrete placement.

1.6.3.2     Fly Ash and Pozzolan

 Submit test results in accordance with ASTM C 618 for fly ash and
 pozzolan. Submit test results performed within 6 months of submittal
 date. Submit manufacturer's policy statement on fly ash use in concrete.

1.6.3.3     Ground Granulated Blast-Furnace Slag

 Submit test results in accordance with ASTM C 989 for ground granulated
 blast-furnace slag. Submit test results performed within 6 months of
 submittal date. Submit manufacturer's policy statement on slag use in
 concrete.

1.7     ENVIRONMENTAL REQUIREMENTS

 Provide space ventilation according to manufacturer recommendations, at a
 minimum, during and following installation of concrete curing compound and
 sealer. Maintain one of the following ventilation conditions during the
 curing compound/sealer curing period or for 72 hours after installation:

  a. Supply 100 percent outside air 24 hours a day.

  b. Supply airflow at a rate of 6 air changes per hour, when outside
      temperatures are between 55 degrees F and 84 degrees F and humidity is
      between 30 percent and 60 percent.

  c. Supply airflow at a rate of 1.5 air changes per hour, when outside air
      conditions are not within the range stipulated above.

1.7.1     Submittals for Environmental Performance

  a. Provide data indication the percentage of post-industrial pozzolan (fly
      ash, blast furnace slag) cement substitution as a percentage of the
      full product composite by weight.

  b. Provide data indicating the percentage of post-industrial and
      post-consumer recycled content aggregate.

  c. Provide product data indicating the percentage of post-consumer recycled
      steel content in each type of steel reinforcement as a percentage of
      the full product composite by weight.

  d. Provide product data stating the location where all products were
      manufactured


                             SECTION 03 30 00   Page 7
Design MET Facility                                                         5490419



  e. For projects using FSC certified formwork, provide chain-of-custody
      documentation for all certified wood products.

  f. For projects using reusable formwork, provide data showing how formwork
      is reused.

  g. Provide MSDS product information data showing that form release agents
      meet any environmental performance goals such as using vegetable and
      soy based products.

  h. Provide MSDS product information data showing that concrete adhesives
      meet any environmental performance goals including low emitting, low
      volatile organic compound products.

1.8     SUSTAINABLE DESIGN REQUIREMENTS

1.8.1     Local/Regional Materials

 Use materials or products extracted, harvested, or recovered, as well as
 manufactured, within a 500 mile radius from the project site, if available
 from a minimum of three sources.

1.9     QUALIFICATIONS FOR CONCRETE TESTING SERVICE

 Perform concrete testing by an approved laboratory and inspection service
 experienced in sampling and testing concrete. Testing agency must meet the
 requirements of ASTM E 329.

1.10     CONCRETE SAMPLING AND TESTING

 Testing by the Contractor must include sampling and testing concrete
 materials proposed for use in the work and testing the design mix for each
 class of concrete. Perform quality control testing during construction.

 Sample and test concrete aggregate materials proposed for use in the work
 in accordance with ASTM C 33.

 Sample and test portland cement in accordance with ASTM C 150.

 Sample and test air-entraining admixtures in accordance with ASTM C 233.

 Testing must be performed by a Grade I Testing Technician.

PART 2     PRODUCTS

2.1     MATERIALS FOR FORMS

 Provide wood, plywood, plastic, carton, or steel.        Use plywood or steel
 forms where a smooth form finish is required.

2.1.1     Wood Forms

 Use lumber as follows. Provide lumber that is square edged or
 tongue-and-groove boards, free of raised grain, knotholes, or other surface
 defects. Provide plywood that complies with PS1, B-B concrete form panels
 or better or AHA A135.4, hardboard for smooth form lining.




                              SECTION 03 30 00   Page 8
Design MET Facility                                                             5490419


2.1.1.1     Concrete Form Plywood (Standard Rough)

 Provide plywood that conforms to NIST PS 1, B-B, concrete form, not less
 than 5/8-inch thick.

2.1.1.2     Overlaid Concrete Form Plywood (Standard Smooth)

 Provide plywood that conforms to NIST PS 1, B-B, high density form overlay,
 not less than 5/8-inch thick.

2.1.2     Steel Forms

 Provide steel form surfaces that do not contain irregularities, dents, or
 sags.

2.2     FORM TIES AND ACCESSORIES

 The use of wire alone is prohibited. Provide form ties and accessories
 that do not reduce the effective cover of the reinforcement.

2.3     CONCRETE

2.3.1     Contractor-Furnished Mix Design

 ACI/MCP-1, ACI/MCP-2, and ACI/MCP-3 except as otherwise specified.
 Indicate the compressive strength (f'c) of the concrete for each portion of
 the structure(s) and as specified below.

                    f'c         ASTM C 33                   Maximum
                    (Min. 28-   Maximum      Range          Water-
                    Day Comp.   Nominal      of             Cement       Air
                    Strength) Aggregate      Slump          Ratio        Entr.
      Location     (psi)      (Size No.)    (inches)       (by weight)   (percent)

  Concrete
  exposed
  to weather       4000          57              2-4         0.45          6

  Interior
  Concrete
  Slab             4000          57              2-4         0.45         (a)


  Concrete         3000          57              2-4         0.58        ----
  Foundations

 Maximum slump shown above may be increased 1 inch for methods of
 consolidation other than vibration. Slump may be increased to 8 inches
 when superplasticizers are used. Provide air entrainment using
 air-entraining admixture. Provide air entrainment within plus or minus 1.5
 percent of the value specified. The water soluble chloride ion
 concentrations in hardened concrete at ages from 28 to 42 days must not
 exceed 0.15. Note (a): Entrapped air must be 3% or less.

2.3.1.1     Mix Proportions for Normal Weight Concrete

 Trial design batches, mixture proportioning studies, and testing
 requirements for various classes and types of concrete specified are the
 responsibility of the Contractor. Base mixture proportions on compressive


                              SECTION 03 30 00    Page 9
Design MET Facility                                                   5490419


 strength as determined by test specimens fabricated in accordance with
 ASTM C 192/C 192M and tested in accordance with ASTM C 39/C 39M. Samples
 of all materials used in mixture proportioning studies must be
 representative of those proposed for use in the project and must be
 accompanied by the manufacturer's or producer's test report indicating
 compliance with these specifications. Base trial mixtures having
 proportions, consistencies, and air content suitable for the work on
 methodology described in ACI/MCP-1. In the trial mixture, use at least
 three different water-cement ratios for each type of mixture, which must
 produce a range of strength encompassing those required for each class and
 type of concrete required on the project. The maximum water-cement ratio
 required must be based on equivalent water-cement ratio calculations as
 determined by the conversion from the weight ratio of water to cement plus
 pozzolan, and ground granulated blast-furnace slag by weight equivalency
 method. Design laboratory trial mixture for maximum permitted slump and
 air content. Each combination of material proposed for use must have
 separate trial mixture, except for accelerator or retarder use can be
 provided without separate trial mixture. Report the temperature of
 concrete in each trial batch. For each water-cement ratio, at least three
 test cylinders for each test age must be made and cured in accordance with
 ASTM C 192/C 192M and tested in accordance with ASTM C 39/C 39M for 7 and
 28 days. From these results, plot a curve showing the relationship between
 water-cement ratio and strength for each set of trial mix studies. In
 addition, plot a curve showing the relationship between 7 and 28 day
 strengths.

2.3.1.2     Required Average Strength of Mix Design

 The selected mixture must produce an average compressive strength exceeding
 the specified strength by the amount indicated in ACI/MCP-2. When a
 concrete production facility has a record of at least 15 consecutive tests,
 the standard deviation must be calculated and the required average
 compressive strength must be determined in accordance with ACI/MCP-2. When
 a concrete production facility does not have a suitable record of tests to
 establish a standard deviation, the required average strength must follow
 ACI/MCP-2 requirements.

2.3.2     Ready-Mix Concrete

 Provide concrete that meets the requirements of ASTM C 94/C 94M.

 Ready-mixed concrete manufacturer must provide duplicate delivery tickets
 with each load of concrete delivered. Provide delivery tickets with the
 following information in addition to that required by ASTM C 94/C 94M:

        Type and brand cement

        Cement content in 95-pound bags per cubic yard of concrete

        Maximum size of aggregate

        Amount and brand name of admixtures

        Total water content expressed by water/cement ratio




                               SECTION 03 30 00   Page 10
Design MET Facility                                                          5490419


2.3.3     Concrete Curing Materials

2.3.3.1     Absorptive Cover

 Provide burlap cloth cover for curing concrete made from jute or kenaf,
 weighing 10 ounces plus or minus 5 percent per square yard when clean and
 dry, conforming to ASTM C 171, Class 3; or cover may be cotton mats as
 approved.

2.3.3.2     Moisture-Retaining Cover

 Provide waterproof paper cover for curing concrete conforming to ASTM C 171,
 regular or white, or polyethylene sheeting conforming to ASTM C 171, or
 polyethylene-coated burlap consisting of a laminate of burlap and a white
 opaque polyethylene film permanently bonded to the burlap; burlap must
 conform to ASTM C 171, Class 3, and polyethylene film must conform to
 ASTM C 171. When tested for water retention in accordance with ASTM C 156,
 weight of water lost 72 hours after application of moisture retaining
 covering material must not exceed 0.039 gram per square centimeter of the
 mortar specimen surface.

2.3.3.3     Membrane-Forming Curing Compound

 Provide liquid type compound conforming to ASTM C 309, Type 1, clear, Type
 1D with fugitive dye for interior work and Type 2, white, pigmented for
 exterior work.

2.4     MATERIALS

2.4.1     Cement

 ASTM C 150, Type I or II.

2.4.1.1     Fly Ash and Pozzolan

 ASTM C 618, Type N, F, or C, except that the maximum allowable loss on
 ignition must be 6 percent for Types N and F. Add with cement. Limit fly
 ash content to be a maximum of 25 percent by weight of cementitious
 material, provided the fly ash does not reduce the amount of cement in the
 concrete mix below the minimum requirements of local building codes. Where
 the use of fly ash cannot meet the minimum level, provide the maximum
 amount of fly ash permittable that meets the code requirements for cement
 content. Report the chemical analysis of the fly ash in accordance with
 ASTM C 311. Evaluate and classify fly ash in accordance with ASTM D 5759.

2.4.1.2     Ground Granulated Blast-Furnace Slag

 ASTM C 989, Grade 100 or 120. Limit slag content to be a maximum of 50
 percent by weight of cementitious material.

2.4.1.3     Portland Cement

 Provide cement that conforms to ASTM C 150, Type I, IA, II, or IIA. Use
 one brand and type of cement for formed concrete having exposed-to-view
 finished surfaces.

2.4.2     Water

 Minimize the amount of water in the mix.         The amount of water must not


                               SECTION 03 30 00   Page 11
Design MET Facility                                                      5490419


 exceed 45 percent by weight of cementitious materials (cement + pozzolans),
 and in general, improve workability by adjusting the grading rather than by
 adding water. Water must be fresh, clean, and potable; free from injurious
 amounts of oils, acids, alkalis, salts, organic materials, or other
 substances deleterious to concrete.

2.4.3     Aggregates

 ASTM C 33, fine aggregate grading with a maximum of 3 percent by weight
 passing ASTM D 1140, No. 200 sieve, or course aggregate size 57, 67, or 7.
 except as modified herein. Furnish aggregates for exposed concrete
 surfaces from one source. Provide aggregates that do not contain any
 substance which may be deleteriously reactive with the alkalies in the
 cement.

2.4.4     Nonshrink Grout

 ASTM C 1107/C 1107M.

2.4.5     Admixtures

 ASTM C 494/C 494M: Type A, water reducing; Type B, retarding; Type C,
 accelerating; Type D, water-reducing and retarding; and Type E,
 water-reducing and accelerating admixture. Do not use calcium chloride
 admixtures.

2.4.5.1     Air-Entraining

 ASTM C 260.

2.4.5.2     High Range Water Reducer (HRWR) (Superplasticizers)

 ASTM C 494/C 494M, Type F and Type G (HRWR retarding admixture) and
 ASTM C 1017/C 1017M.

2.4.5.3     Pozzolan

 Provide fly ash or other pozzolans used as admixtures that conform to
 ASTM C 618.

2.4.6     Vapor Retarder

 ASTM D 4397 polyethylene sheeting, minimum 10 mil thickness.

2.4.7     Materials for Curing Concrete

 Consider the use of water based or vegetable or soy based curing agents in
 lieu of petroleum based products. Consider agents that are not toxic and
 emit low or no Volatile Organic Compounds (VOC). Consider the use of
 admixtures that offer high performance to increase durability of the finish
 product but also have low toxicity and are made from bio-based materials
 such as soy, and emit low levels of Volatile Organic Compounds (VOC).

2.4.7.1     Impervious Sheeting

 ASTM C 171; waterproof paper, clear or white polyethylene sheeting, or
 polyethylene-coated burlap.




                             SECTION 03 30 00   Page 12
Design MET Facility                                                         5490419


2.4.7.2     Pervious Sheeting

 AASHTO M 182.

2.4.7.3     Liquid Membrane-Forming Compound

 ASTM C 309, white-pigmented, Type 2, Class B.

2.4.8     Liquid Chemical Sealer-Hardener Compound

 Provide magnesium fluorosilicate compound which when mixed with water seals
 and hardens the surface of the concrete. Do not use on exterior slabs
 exposed to freezing conditions. Provide compound that does not reduce the
 adhesion of resilient flooring, tile, paint, roofing, waterproofing, or
 other material applied to concrete.

2.4.9     Joint Sealants

 Use 2-part self leveling semi-rigid type.

2.5     REINFORCEMENT

2.5.1     Reinforcing Bars

 ACI/MCP-2 unless otherwise specified.     Use deformed steel.
 ASTM A 615/A 615M , Grade 60

2.5.2     Wire

 ASTM A 82/A 82M or ASTM A 496/A 496M.

2.5.2.1     Welded Wire Fabric

 ASTM A 185/A 185M or ASTM A 497/A 497M.        Provide flat sheets of welded wire
 fabric for slabs and toppings.

2.5.2.2     Steel Wire

 Wire must conform to ASTM A 82/A 82M.

2.5.3     Reinforcing Bar Supports

 Provide bar ties and supports of coated or non corrodible material.

2.5.4     Supports for Reinforcement

 Supports include bolsters, chairs, spacers, and other devices necessary for
 proper spacing, supporting, and fastening reinforcing bars and wire fabric
 in place.

 Provide wire bar type supports conforming to ACI/MCP-3 and CRSI MSP-2.

 Legs of supports in contact with formwork must be hot-dip galvanized, or
 plastic coated after fabrication, or stainless-steel bar supports.




                             SECTION 03 30 00    Page 13
Design MET Facility                                                        5490419


PART 3     EXECUTION

3.1     EXAMINATION

 Do not begin installation until substrates have been properly constructed;
 verify that substrates are plumb and true.

 If substrate preparation is the responsibility of another installer, notify
 Architect/Engineer of unsatisfactory preparation before processing.

 Check field dimensions before beginning installation. If dimensions vary
 too much from design dimensions for proper installation, notify
 Architect/Engineer and wait for instructions before beginning installation.

3.2     PREPARATION

 Determine quantity of concrete needed and minimize the production of excess
 concrete. Designate locations or uses for potential excess concrete before
 the concrete is poured.

3.2.1     General

 Surfaces against which concrete is to be placed must be free of debris,
 loose material, standing water, snow, ice, and other deleterious substances
 before start of concrete placing.

 Remove standing water without washing over freshly deposited concrete.
 Divert flow of water through side drains provided for such purpose.

3.2.2     Subgrade Under Foundations and Footings

 When subgrade material is semiporous and dry, sprinkle subgrade surface
 with water as required to eliminate suction at the time concrete is
 deposited. When subgrade material is porous, seal subgrade surface by
 covering surface with specified water barrier subgrade cover; this may also
 be used over semiporous, dry subgrade material instead of water sprinkling.

3.2.3     Subgrade Under Slabs on Ground

 Before construction of slabs on ground, have underground work on pipes and
 conduits completed and approved.

 Previously constructed subgrade or fill must be cleaned of foreign
 materials and inspected by the Contractor for adequate compaction and
 surface tolerances as specified.

 Actual density of top 12 inches of subgrade soil material-in-place must not
 be less than the following percentages of maximum density of same soil
 material compacted at optimum moisture content in accordance with
 ASTM D 1557.

              SOIL MATERIAL                      PERCENT MAXIMUM DENSITY

              Drainage fill                                 100

              Cohesionless soil material                    100

              Cohesive soil material                         95



                              SECTION 03 30 00    Page 14
Design MET Facility                                                   5490419


 Finish surface of drainage fill under interior slabs on ground must not
 show deviation in excess of 1/4 inch when tested with a 10-foot
 straightedge parallel with and at right angles to building lines.

 Finished surface of subgrade or fill under exterior slabs on ground must
 not be more than 0.02-foot above or 0.10-foot below elevation indicated.

 Cover drainage fill surface under interior slabs on ground with specified
 water-vapor retarder subgrade cover immediately prior to placing
 reinforcement. Install subgrade cover to avoid puncture or tear. Patch
 punctures or tears over 12 inches with separate sheets lapped not less than
 6 inches. Seal all punctures or tears less than 12 inches with
 pressure-sensitive vapor barrier tape not less than 2-inches wide. Seal
 lapped joints with vapor barrier adhesive or pressure-sensitive vapor
 barrier tape not less than 2-inches wide. Lay subgrade cover sheets with
 not less than a 6-inch lap at edges and ends and in direction in which
 concrete is to be placed.

 Prepare subgrade or fill surface under exterior slabs on ground as
 specified for subgrade under foundations and footings.

3.2.4     Formwork

 Complete and approve formwork. Remove debris and foreign material from
 interior of forms before start of concrete placing.

3.2.5     Edge Forms and Screed Strips for Slabs

 Set edge forms or bulkheads and intermediate screed strips for slabs to
 obtain indicated elevations and contours in finished slab surface and must
 be strong enough to support vibrating bridge screeds or roller pipe screeds
 if nature of specified slab finish requires use of such equipment. Align
 concrete surface to elevation of screed strips by use of strike-off
 templates or approved compacting-type screeds.

3.2.6     Reinforcement and Other Embedded Items

 Secure reinforcement, joint materials, and other embedded materials in
 position, inspected, and approved before start of concrete placing.

3.3     FORMS

 ACI/MCP-2. Provide forms, shoring, and scaffolding for concrete
 placement. Set forms mortar-tight and true to line and grade. Chamfer
 above grade exposed joints, edges, and external corners of concrete 0.75
 inch unless otherwise indicated. Provide formwork with clean-out openings
 to permit inspection and removal of debris. Forms submerged in water must
 be watertight.

3.3.1     General

 Construct forms to conform, within the tolerances specified, to shapes
 dimensions, lines, elevations, and positions of cast-in-place concrete
 members as indicated. Forms must be supported, braced, and maintained
 sufficiently rigid to prevent deformation under load.

3.3.2     Design and Construction of Formwork

 Provide formwork design and construction that conforms to and ACI/MCP-2,


                            SECTION 03 30 00    Page 15
Design MET Facility                                                   5490419


 Chapter 4.

 Provide forms that are tight to prevent leakage of cement paste during
 concrete placing.

 Support form facing materials by structural members spaced close to prevent
 deflection of form facing material. Fit forms placed in successive units
 for continuous surfaces to accurate alignment to ensure a smooth completed
 surface within the tolerances specified. Where necessary to maintain the
 tolerances specified, such as long spans where immediate supports are not
 possible, camber formwork for anticipated deflections in formwork due to
 weight and pressure of fresh concrete and to construction loads.

 Chamfer exposed joints, edges, and external corners a minimum of 3/4 inch
 by moldings placed in corners of column, beam, and wall forms.

 Provide shores and struts with a positive means of adjustment capable of
 taking up formwork settlement during concrete placing operations. Obtain
 adjustment with wedges or jacks or a combination thereof. When adequate
 foundations for shores and struts cannot be secured, provide trussed
 supports.

 Provide temporary openings in wall forms, column forms, and at other points
 where necessary to permit inspection and to facilitate cleaning.

 Provide forms that are readily removable without impact, shock, or damage
 to concrete.

3.3.3   Coating

 Before concrete placement, coat the contact surfaces of forms with a
 nonstaining mineral oil, nonstaining form coating compound, or two coats of
 nitrocellulose lacquer. Do not use mineral oil on forms for surfaces to
 which adhesive, paint, or other finish material is to be applied.

3.3.4   Reshoring

 Reshore concrete elements where forms are removed prior to the specified
 time period. Do not permit elements to deflect or accept loads during form
 stripping or reshoring. Forms on columns, walls, or other load-bearing
 members may be stripped after 2 days if loads are not applied to the
 members. Provide reshoring elements with the same load-carrying
 capabilities as original shoring and spaced similar to original shoring.
 Firmly secure and brace reshoring elements to provide solid bearing and
 support.

3.3.5   Reuse

 Reuse forms providing the structural integrity of concrete and the
 aesthetics of exposed concrete are not compromised.

3.3.6   Forms for Standard Rough Form Finish

 Give rough form finish concrete formed surfaces that are to be concealed by
 other construction, unless otherwise specified.

 Form facing material for standard rough form finish must be the specified
 concrete form plywood or other approved form facing material that produces
 concrete surfaces equivalent in smoothness and appearance to that produced


                          SECTION 03 30 00     Page 16
Design MET Facility                                                       5490419


 by new concrete form plywood panels.

 For concrete surfaces exposed only to the ground, undressed, square-edge,
 1-inch nominal thickness lumber may be used. Provide horizontal joints
 that are level and vertical joints that are plumb.

3.3.7     Forms for Standard Smooth Form Finish

 Give smooth form finish concrete formed surfaces that are to be exposed to
 view or that are to be covered with coating material applied directly to
 concrete or with covering material bonded to concrete, such as
 waterproofing, dampproofing, painting, or other similar coating system.

 Form facing material for standard smooth finish must be the specified
 overlaid concrete form plywood or other approved form facing material that
 is nonreactive with concrete and that produce concrete surfaces equivalent
 in smoothness and appearance to that produced by new overlaid concrete form
 plywood panels.

 Maximum deflection of form facing material between supports and maximum
 deflection of form supports such as studs and wales must not exceed 0.0025
 times the span.

 Provide arrangement of form facing sheets that are orderly and symmetrical,
 and sheets that are in sizes as large as practical.

 Arrange panels to make a symmetrical pattern of joints. Horizontal and
 vertical joints must be solidly backed and butted tight to prevent leakage
 and fins.

3.3.8     Form Ties

 Provide ties that are factory fabricated metal, adjustable in length,
 removable or snap-off type that do allow form deflection or do not spall
 concrete upon removal. Portion of form ties remaining within concrete
 after removal of exterior parts must be at least 1-1/2 inches back from
 concrete surface. Provide form ties that are free of devices that leave a
 hole larger than 7/8 inch or less than 1/2 inch in diameter in concrete
 surface. Form ties fabricated at the project site or wire ties of any type
 are not acceptable.

3.3.9     Tolerances for Form Construction

 Construct formwork to ensure that after removal of forms and prior to
 patching and finishing of formed surfaces, provide concrete surfaces in
 accordance with tolerances specified in ACI/MCP-1 and ACI/MCP-2.

3.3.10     Removal of Forms and Supports

 After placing concrete, forms must remain in place for the time periods
 specified in ACI/MCP-4. Do not remove forms and shores (except those used
 for slabs on grade and slip forms) until the client determines that the
 concrete has gained sufficient strength to support its weight and
 superimposed loads. Base such determination on compliance with one of the
 following:

         a. The plans and specifications stipulate conditions for removal of
         forms and shores, and such conditions have been followed, or



                             SECTION 03 30 00   Page 17
Design MET Facility                                                      5490419


        b. The concrete has been properly tested with an appropriate ASTM
        standard test method designed to indicate the concrete compressive
        strength, and the test results indicate that the concrete has gained
        sufficient strength to support its weight and superimposed loads.

 Prevent concrete damage during form removal.     Clean all forms immediately
 after removal.

3.3.10.1     Special Requirements for Reduced Time Period

 Forms may be removed earlier than specified if ASTM C 39/C 39M test results
 of field-cured samples from a representative portion of the structure
 indicate that the concrete has reached a minimum of 85 percent of the
 design strength.

3.4     FORMED SURFACES

3.4.1     Preparation of Form Surfaces

 Coat contact surfaces of forms with form-coating compound before
 reinforcement is placed. Provide a commercial formulation form-coating
 compound that does not bond with, stain, nor adversely affect concrete
 surfaces and impair subsequent treatment of concrete surfaces that entails
 bonding or adhesion nor impede wetting of surfaces to be cured with water
 or curing compounds. Do not allow excess form-coating compound to stand in
 puddles in the forms nor to come in contact with concrete against which
 fresh concrete is placed. Make thinning of form-coating compound with
 thinning agent of the type, in the amount, and under the conditions
 recommended by form-coating compound manufacturer's printed or written
 directions.

3.4.2     Tolerances

 ACI/MCP-4 and as indicated.

3.4.3     As-Cast Form

 Provide form facing material producing a smooth, hard, uniform texture on
 the concrete. Arrange facing material in an orderly and symmetrical manner
 and keep seams to a practical minimum. Support forms as necessary to meet
 required tolerances. Do not use material with raised grain, torn surfaces,
 worn edges, patches, dents, or other defects which can impair the texture
 of the concrete surface.

3.5     PLACING REINFORCEMENT AND MISCELLANEOUS MATERIALS

 ACI/MCP-2. Provide bars, wire fabric, wire ties, supports, and other
 devices necessary to install and secure reinforcement. Reinforcement must
 not have rust, scale, oil, grease, clay, or foreign substances that would
 reduce the bond. Rusting of reinforcement is a basis of rejection if the
 effective cross-sectional area or the nominal weight per unit length has
 been reduced. Remove loose rust prior to placing steel. Tack welding is
 prohibited.

3.5.1     General

 Provide details of reinforcement that are in accordance with, and ACI/MCP-4
 and as specified.



                            SECTION 03 30 00   Page 18
Design MET Facility                                                          5490419


3.5.2    Vapor Retarder

 Provide beneath the on-grade concrete floor slab. Use the greatest widths
 and lengths practicable to eliminate joints wherever possible. Lap joints
 a minimum of 12 inches. Remove torn, punctured, or damaged vapor retarder
 material and provide with new vapor retarder prior to placing concrete.
 Concrete placement must not damage vapor barrier material.

3.5.3    Reinforcement Supports

 Place reinforcement and secure with galvanized or non corrodible chairs,
 spacers, or metal hangers. For supporting reinforcement on the ground, use
 concrete or other non corrodible material, having a compressive strength
 equal to or greater than the concrete being placed.



3.5.4    Splicing

 As indicated. For splices not indicated ACI/MCP-2. Do not splice at
 points of maximum stress. Overlap welded wire fabric the spacing of the
 cross wires, plus 2 inches.

3.5.5    Cover

 ACI/MCP-2 for minimum coverage, unless otherwise indicated.

3.5.6    Setting Miscellaneous Material

 Place and secure anchors and bolts, pipe sleeves, conduits, and other such
 items in position before concrete placement. Plumb anchor bolts and check
 location and elevation. Temporarily fill voids in sleeves with readily
 removable material to prevent the entry of concrete.

3.5.7    Construction Joints

 Locate joints to least impair strength.         Continue reinforcement across
 joints unless otherwise indicated.

3.5.8    Contraction Joints

 Provide contraction joints, either formed or saw cut or cut with a jointing
 tool, to the indicated depth after the surface has been finished. Complete
 saw joints within 4 to 12 hours after concrete placement. Protect joints
 from intrusion of foreign matter.

3.5.9    Fabrication

 Shop fabricate reinforcing bars to conform to shapes and dimensions
 indicated for reinforcement, and as follows:

        Provide fabrication tolerances that are in accordance with ACI/MCP-1,
        ACI/MCP-2 and ACI/MCP-3.

        Provide hooks and bends that are in accordance with and ACI/MCP-3.

 Reinforcement must be bent cold to shapes as indicated. Bending must be
 done in the shop. Rebending of a reinforcing bar that has been bent
 incorrectly is not be permitted. Bending must be in accordance with


                              SECTION 03 30 00    Page 19
Design MET Facility                                                         5490419


 standard approved practice and by approved machine methods.

 Tolerance on nominally square-cut, reinforcing bar ends must be in
 accordance with ACI/MCP-3.

 Deliver reinforcing bars bundled, tagged, and marked. Tags must be metal
 with bar size, length, mark, and other information pressed in by machine.
 Marks must correspond with those used on the placing drawings.

 Do not use reinforcement that has any of the following defects:

         a. Bar lengths, depths, and bends beyond specified fabrication
         tolerances

         b. Bends or kinks not indicated on drawings or approved shop drawings

         c. Bars with reduced cross-section due to rusting or other cause

 Replace defective reinforcement with new reinforcement having required
 shape, form, and cross-section area.

3.5.10     Placing Reinforcement

 Place reinforcement in accordance with ACI/MCP-4.

 For slabs on grade (over earth or over capillary water barrier) and for
 footing reinforcement, support bars or welded wire fabric on precast
 concrete blocks, spaced at intervals required by size of reinforcement, to
 keep reinforcement the minimum height specified above the underside of slab
 or footing.

 For slabs other than on grade, supports for which any portion is less than
 1 inch from concrete surfaces that are exposed to view or to be painted
 must be of precast concrete units, plastic-coated steel, or stainless steel
 protected bar supports. Precast concrete units must be wedge shaped, not
 larger than 3-1/2 by 3-1/2 inches, and of thickness equal to that indicated
 for concrete protection of reinforcement. Provide precast units that have
 cast-in galvanized tie wire hooked for anchorage and blend with concrete
 surfaces after finishing is completed.

 Contractor must cooperate with other trades in setting of anchor bolts,
 inserts, and other embedded items. Where conflicts occur between locating
 reinforcing and embedded items, the Contractor must notify the Contracting
 Officer so that conflicts may be reconciled before placing concrete.
 Anchors and embedded items must be positioned and supported with
 appropriate accessories.
 Provide reinforcement that is supported and secured together to prevent
 displacement by construction loads or by placing of wet concrete, and as
 follows:

             Provide supports for reinforcing bars that are sufficient in
             number and sufficiently heavy to carry the reinforcement they
             support, and in accordance with ACI/MCP-4 and CRSI MSP-2. Do not
             use supports to support runways for concrete conveying equipment
             and similar construction loads.

         Equip supports on ground and similar surfaces with sand-plates.

         Support welded wire fabric as required for reinforcing bars.


                             SECTION 03 30 00   Page 20
Design MET Facility                                                       5490419



         Secure reinforcements to supports by means of tie wire. Wire must be
         black, soft iron wire, not less than 16 gage.

         With the exception of temperature reinforcement, tied to main steel
         approximately 24 inches on center, reinforcement must be accurately
         placed, securely tied at intersections with 18-gage annealed wire, and
         held in position during placing of concrete by spacers, chairs, or
         other approved supports. Point wire-tie ends away from the form.
         Unless otherwise indicated, numbers, type, and spacing of supports must
         conform to ACI/MCP-3.

         Bending of reinforcing bars partially embedded in concrete is permitted
         only as specified inand ACI/MCP-4.

3.5.11     Spacing of Reinforcing Bars

 Spacing must be as indicated.     If not indicated, spacing must be in
 accordance with theACI/MCP-3.

 Reinforcing bars may be relocated to avoid interference with other
 reinforcement, or with conduit, pipe, or other embedded items. If any
 reinforcing bar is moved a distance exceeding one bar diameter or specified
 placing tolerance, resulting rearrangement of reinforcement is subject to
 approval.

3.5.12     Concrete Protection for Reinforcement

 Concrete protection must be in accordance with the ACI/MCP-4, ASTM E 648,and
 ACI/MCP-3.

3.6     BATCHING, MEASURING, MIXING, AND TRANSPORTING CONCRETE

 ASTM C 94/C 94M, and ACI/MCP-2, except as modified herein. Batching
 equipment must be such that the concrete ingredients are consistently
 measured within the following tolerances: 1 percent for cement and water, 2
 percent for aggregate, and 3 percent for admixtures. Furnish mandatory
 batch ticket information for each load of ready mix concrete.

3.6.1     Measuring

 Make measurements at intervals as specified in paragraphs entitled
 "Sampling" and "Testing."

3.6.2     Mixing

 ASTM C 94/C 94M and ACI/MCP-2. Machine mix concrete. Begin mixing within
 30 minutes after the cement has been added to the aggregates. Place
 concrete within 90 minutes of either addition of mixing water to cement and
 aggregates or addition of cement to aggregates if the air temperature is
 less than 84 degrees F. Reduce mixing time and place concrete within 60
 minutes if the air temperature is greater than 84 degrees F except as
 follows: if set retarding admixture is used and slump requirements can be
 met, limit for placing concrete may remain at 90 minutes. Additional water
 may be added, provided that both the specified maximum slump and
 water-cement ratio are not exceeded. When additional water is added, an
 additional 30 revolutions of the mixer at mixing speed is required. If the
 entrained air content falls below the specified limit, add a sufficient
 quantity of admixture to bring the entrained air content within the


                             SECTION 03 30 00   Page 21
Design MET Facility                                                   5490419


 specified limits. Dissolve admixtures in the mixing water and mix in the
 drum to uniformly distribute the admixture throughout the batch.

3.6.3     Transporting

 Transport concrete from the mixer to the forms as rapidly as practicable.
 Prevent segregation or loss of ingredients. Clean transporting equipment
 thoroughly before each batch. Do not use aluminum pipe or chutes. Remove
 concrete which has segregated in transporting and dispose of as directed.

3.7     PLACING CONCRETE

 Place concrete as soon as practicable after the forms and the reinforcement
 have been inspected and approved. Do not place concrete when weather
 conditions prevent proper placement and consolidation; in uncovered areas
 during periods of precipitation; or in standing water. Prior to placing
 concrete, remove dirt, construction debris, water, snow, and ice from
 within the forms. Deposit concrete as close as practicable to the final
 position in the forms. Do not exceed a free vertical drop of 3 feet from
 the point of discharge. Place concrete in one continuous operation from
 one end of the structure towards the other. Position grade stakes on 10
 foot centers maximum in each direction when pouring interior slabs and on
 20 foot centers maximum for exterior slabs.

3.7.1     General Placing Requirements

 Deposit concrete continuously or in layers of such thickness that no
 concrete is placed on concrete which has hardened sufficiently to cause
 formation of seams or planes of weakness within the section. If a section
 cannot be placed continuously, provide construction joints as specified.
 Perform concrete placing at such a rate that concrete which is being
 integrated with fresh concrete is still plastic. Deposit concrete as
 nearly as practical in its final position to avoid segregation due to
 rehandling or flowing. Do not subject concrete to procedures which cause
 segregation.

 Concrete to receive other construction must be screeded to proper level to
 avoid excessive skimming or grouting.

 Do not use concrete which becomes nonplastic and unworkable or does not
 meet quality control limits as specified or has been contaminated by
 foreign materials. Use of retempered concrete is permitted. Remove
 rejected concrete from the site.

3.7.2     Footing Placement

 Concrete for footings may be placed in excavations without forms upon
 inspection and approval by the Contracting Officer. Excavation width must
 be a minimum of 4 inches greater than indicated.

3.7.3     Vibration

 ACI/MCP-2. Furnish a spare, working, vibrator on the job site whenever
 concrete is placed. Consolidate concrete slabs greater than 4 inches in
 depth with high frequency mechanical vibrating equipment supplemented by
 hand spading and tamping. Consolidate concrete slabs 4 inches or less in
 depth by wood tampers, spading, and settling with a heavy leveling
 straightedge. Operate internal vibrators with vibratory element submerged
 in the concrete, with a minimum frequency of not less than 6000 impulses


                              SECTION 03 30 00   Page 22
Design MET Facility                                                      5490419


 per minute when submerged. Do not use vibrators to transport the concrete
 in the forms. Insert and withdraw vibrators approximately 20 inches
 apart. Penetrate the previously placed lift with the vibrator when more
 than one lift is required. Place concrete in 20 inch maximum vertical
 lifts. Use external vibrators on the exterior surface of the forms when
 internal vibrators do not provide adequate consolidation of the concrete.

3.7.4   Pumping

 ACI/MCP-2. Pumping must not result in separation or loss of materials nor
 cause interruptions sufficient to permit loss of plasticity between
 successive increments. Loss of slump in pumping equipment must not exceed
 2 inches. Do not convey concrete through pipe made of aluminum or aluminum
 alloy. Avoid rapid changes in pipe sizes. Limit maximum size of course
 aggregate to 33 percent of the diameter of the pipe. Limit maximum size of
 well rounded aggregate to 40 percent of the pipe diameter. Take samples
 for testing at both the point of delivery to the pump and at the discharge
 end.

3.7.5   Cold Weather

 ACI/MCP-2. Do not allow concrete temperature to decrease below 50 degrees F
 Obtain approval prior to placing concrete when the ambient temperature is
 below 40 degrees F or when concrete is likely to be subjected to freezing
 temperatures within 24 hours. Cover concrete and provide sufficient heat
 to maintain 50 degrees F minimum adjacent to both the formwork and the
 structure while curing. Limit the rate of cooling to 37 degrees F in any 1
 hour and 50 degrees F per 24 hours after heat application.

3.7.6   Hot Weather

 Maintain required concrete temperature using Figure 2.1.5 in ACI/MCP-2 to
 prevent the evaporation rate from exceeding 0.2 pound of water per square
 foot of exposed concrete per hour. Cool ingredients before mixing or use
 other suitable means to control concrete temperature and prevent rapid
 drying of newly placed concrete. Shade the fresh concrete as soon as
 possible after placing. Start curing when the surface of the fresh
 concrete is sufficiently hard to permit curing without damage. Provide
 water hoses, pipes, spraying equipment, and water hauling equipment, where
 job site is remote to water source, to maintain a moist concrete surface
 throughout the curing period. Provide burlap cover or other suitable,
 permeable material with fog spray or continuous wetting of the concrete
 when weather conditions prevent the use of either liquid membrane curing
 compound or impervious sheets. For vertical surfaces, protect forms from
 direct sunlight and add water to top of structure once concrete is set.

3.7.7   Follow-up

 Check concrete within 24 hours of placement for flatness, levelness, and
 other specified tolerances. Adjust formwork and placement techniques on
 subsequent pours to achieve specified tolerances.

3.7.8   Placing Concrete in Forms

 Deposit concrete placed in forms in horizontal layers not exceeding 24
 inches.

 Remove temporary spreaders in forms when concrete placing has reached
 elevation of spreaders.


                          SECTION 03 30 00   Page 23
Design MET Facility                                                       5490419



 Consolidate concrete placed in forms by mechanical vibrating equipment
 supplemented by hand spading, rodding, or tamping. Design vibrators to
 operate with vibratory element submerged in concrete and maintain a speed
 of not less than 9,000 impulses per minute when submerged in concrete.
 Provide vibrating equipment adequate in number of units and power of each
 unit to properly consolidate concrete. Vibration of forms and
 reinforcement is not be permitted. Do not use vibrators to transport
 concrete inside forms. Insert and withdraw vibrators vertically at
 uniformly spaced points not farther apart than visible effectiveness of
 machine. Do not insert vibrator into lower courses of concrete that have
 begun to set. At each insertion, limit duration of vibration to time
 necessary to consolidate concrete and complete embedment of reinforcement
 and other embedded items without causing segregation of concrete mix.

 Do not start placing of concrete in supporting elements until concrete
 previously placed in columns and walls is no longer plastic and has been in
 place a minimum of 2 hours.

3.7.9     Placing Concrete Slabs

 Place and consolidate concrete for slabs in a continuous operation, within
 the limits of approved construction joints until placing of panel or
 section is completed.

 During concrete placing operations, consolidate concrete by mechanical
 vibrating equipment so that concrete is worked around reinforcement and
 other embedded items and into corners. Consolidate concrete placed in
 beams and girders of supported slabs and against bulkheads of slabs on
 ground by mechanical vibrators as specified. Consolidate concrete in
 remainder of slabs by vibrating bridge screeds, roller pipe screeds, or
 other approved method. Limit consolidation operations to time necessary to
 obtain consolidation of concrete without bringing an excess of fine
 aggregate to the surface. Concrete to be consolidated must be as dry as
 practical and surfaces thereof must not be manipulated prior to finishing
 operations. Bring concrete correct level with a straightedge and
 struck-off. Use bull floats or darbies to smooth surface, leaving it free
 of humps or hollows. Sprinkling of water on plastic surface is not
 permitted.

3.7.10     Bonding

 Surfaces of set concrete at joints, except where bonding is obtained by use
 of concrete bonding agent, must be roughened and cleaned of laitance,
 coatings, loose particles, and foreign matter. Roughen surfaces in a
 manner that exposes the aggregate uniformly and does not leave laitance,
 loosened particles of aggregate, nor damaged concrete at the surface.

 Obtain bonding of fresh concrete that has set as follows:

         At joints between footings and walls or columns, between walls or
         columns and the beams or slabs they support, and elsewhere unless
         otherwise specified; roughened and cleaned surface of set concrete must
         be dampened, but not saturated, immediately prior to placing of fresh
         concrete.

         At joints in exposed-to-view work; at vertical joints in walls; at
         joints near midpoint of span in girders, beams, supported slabs, other
         structural members; in work designed to contain liquids; the roughened


                             SECTION 03 30 00   Page 24
Design MET Facility                                                         5490419


        and cleaned surface of set concrete must be dampened but not saturated
        and covered with a cement grout coating.

        Provide cement grout that consists of equal parts of portland cement
        and fine aggregate by weight with not more than 6 gallons of water per
        sack of cement. Apply cement grout with a stiff broom or brush to a
        minimum thickness of 1/16 inch. Deposit fresh concrete before cement
        grout has attained its initial set.

        Bonding of fresh concrete to concrete that has set may be obtained by
        use of a concrete bonding agent. Apply such bonding material to
        cleaned concrete surface in accordance with approved printed
        instructions of bonding material manufacturer.

3.8     SURFACE FINISHES EXCEPT FLOOR, SLAB, AND PAVEMENT FINISHES

3.8.1     Defects

 Repair formed surfaces by removing minor honeycombs, pits greater than 1
 square inch surface area or 0.25 inch maximum depth, or otherwise defective
 areas. Provide edges perpendicular to the surface and patch with nonshrink
 grout. Patch tie holes and defects when the forms are removed. Concrete
 with extensive honeycomb including exposed steel reinforcement, cold
 joints, entrapped debris, separated aggregate, or other defects which
 affect the serviceability or structural strength will be rejected, unless
 correction of defects is approved. Obtain approval of corrective action
 prior to repair. The surface of the concrete must not vary more than the
 allowable tolerances of ACI/MCP-4. Exposed surfaces must be uniform in
 appearance and finished to a smooth form finish unless otherwise specified.

3.8.2     Not Against Forms (Top of Walls)

 Surfaces not otherwise specified must be finished with wood floats to even
 surfaces. Finish must match adjacent finishes.

3.8.3     Formed Surfaces

3.8.3.1     Tolerances

 ACI/MCP-1 and as indicated.

3.8.3.2     As-Cast Rough Form

 Provide for surfaces not exposed to public view. Patch these holes and
 defects and level abrupt irregularities. Remove or rub off fins and other
 projections exceeding 0.25 inch in height.

3.8.3.3     Standard Smooth Finish

 Finish must be as-cast concrete surface as obtained with form facing
 material for standard smooth finish. Repair and patch defective areas as
 specified; and all fins and remove other projections on surface.

3.9     FLOOR, SLAB, AND PAVEMENT FINISHES AND MISCELLANEOUS CONSTRUCTION

 ACI/MCP-2, unless otherwise specified. Slope floors uniformly to drains
 where drains are provided. Steel trowel and fine-broom finish concrete
 slabs that are to receive quarry tile, ceramic tile, or paver tile . Where
 straightedge measurements are specified, Contractor must provide


                            SECTION 03 30 00   Page 25
Design MET Facility                                                   5490419


 straightedge.

3.9.1     Finish

 Place, consolidate, and immediately strike off concrete to obtain proper
 contour, grade, and elevation before bleedwater appears. Permit concrete
 to attain a set sufficient for floating and supporting the weight of the
 finisher and equipment. If bleedwater is present prior to floating the
 surface, drag the excess water off or remove by absorption with porous
 materials. Do not use dry cement to absorb bleedwater.

3.9.1.1     Floated

 Use for exterior slabs where not otherwise specified. After the concrete
 has been placed, consolidated, struck off, and leveled, do not work the
 concrete further, until ready for floating. Whether floating with a wood,
 magnesium, or composite hand float, with a bladed power trowel equipped
 with float shoes, or with a powered disc, float must begin when the surface
 has stiffened sufficiently to permit the operation. During or after the
 first floating, check surface with a 10 foot straightedge applied at no
 less than two different angles, one of which is perpendicular to the
 direction of strike off. Cut down high spots and fill low spots during
 this procedure to produce a surface level within 1/4 inch in 10 feet.

3.9.1.2     Steel Troweled

 Use for floors intended as walking surfaces, and for reception of floor
 coverings. First, provide a floated finish. Next, the finish must be
 power troweled two times, and finally hand troweled. The first troweling
 after floating needs to produce a smooth surface which is relatively free
 of defects but which may still show some trowel marks. Perform additional
 trowelings done by hand after the surface has hardened sufficiently. The
 final troweling is done when a ringing sound is produced as the trowel is
 moved over the surface. Thoroughly consolidate the surface by the hand
 troweling operations. The finished surface must be essentially free of
 trowel marks and uniform in texture and appearance. The finished surface
 must produce a surface level to within 1/4 inch in 10 feet. On surfaces
 intended to support floor coverings, remove any defects of sufficient
 magnitude to show through the floor covering by grinding.

3.9.1.3     Broomed

 Use on surfaces of exterior walks, platforms, patios, and ramps, unless
 otherwise indicated. Perform a floated finish, then draw a broom or burlap
 belt across the surface to produce a coarse scored texture. Permit surface
 to harden sufficiently to retain the scoring or ridges. Broom transverse
 to traffic or at right angles to the slope of the slab.

3.9.1.4     Pavement

 Screed the concrete with a template advanced with a combined longitudinal
 and crosswise motion. Maintain a slight surplus of concrete ahead of the
 template. After screeding, float the concrete longitudinally. Use a
 straightedge to check slope and flatness; correct and refloat as
 necessary. Obtain final finish by a burlap drag. Drag a strip of clean,
 wet burlap from 3 to 10 feet wide and 2 feet longer than the pavement width
 across the slab. Produce a fine, granular, sandy textured surface without
 disfiguring marks. Round edges and joints with an edger having a radius of
 1/8 inch.


                             SECTION 03 30 00   Page 26
Design MET Facility                                                   5490419



3.9.2     Concrete Walks

 Provide 4 inches thick minimum. Provide contraction joints spaced every 5
 linear feet unless otherwise indicated. Cut contraction joints one inch
 deep with a jointing tool after the surface has been finished. Provide 0.5
 inch thick transverse expansion joints at changes in direction where
 sidewalk abuts curb, steps, rigid pavement, or other similar structures;
 space expansion joints every 50 feet maximum. Give walks a broomed
 finish. Unless indicated otherwise, provide a transverse slope of 1/48.
 Limit variation in cross section to 1/4 inch in 5 feet.

3.9.3     Curbs and Gutters

 Provide contraction joints spaced every 10 feet maximum unless otherwise
 indicated. Cut contraction joints 3/4 inch deep with a jointing tool after
 the surface has been finished. Provide expansion joints 1/2 inch thick and
 spaced every 100 feet maximum unless otherwise indicated. Perform pavement
 finish.

3.9.4     Splash Blocks

 Provide at outlets of downspouts emptying at grade. Splash blocks may be
 precast concrete, and must be 24 inches long, 12 inches wide, and 4 inches
 thick, unless otherwise indicated, with smooth-finished countersunk dishes
 sloped to drain away from the building.

3.10     CURING AND PROTECTION

 ACI/MCP-2 unless otherwise specified. Begin curing immediately following
 form removal. Avoid damage to concrete from vibration created by blasting,
 pile driving, movement of equipment in the vicinity, disturbance of
 formwork or protruding reinforcement, and any other activity resulting in
 ground vibrations. Protect concrete from injurious action by sun, rain,
 flowing water, frost, mechanical injury, tire marks, and oil stains. Do
 not allow concrete to dry out from time of placement until the expiration
 of the specified curing period. Do not use membrane-forming compound on
 surfaces where appearance would be objectionable, on any surface to be
 painted, where coverings are to be bonded to the concrete, or on concrete
 to which other concrete is to be bonded. If forms are removed prior to the
 expiration of the curing period, provide another curing procedure specified
 herein for the remaining portion of the curing period. Provide moist
 curing for those areas receiving liquid chemical sealer-hardener or epoxy
 coating.

3.10.1     General

 Protect freshly placed concrete from premature drying and cold or hot
 temperature and maintain without drying at a relatively constant
 temperature for the period of time necessary for hydration of cement and
 proper hardening of concrete.

 Start initial curing as soon as free water has disappeared from surface of
 concrete after placing and finishing. Keep concrete moist for minimum 72
 hours.

 Final curing must immediately follow initial curing and before concrete has
 dried. Continue final curing until cumulative number of hours or fraction
 thereof (not necessarily consecutive) during which temperature of air in


                              SECTION 03 30 00   Page 27
Design MET Facility                                                    5490419


 contact with the concrete is above 50 degrees F has totaled 168 hours.
 Alternatively, if tests are made of cylinders kept adjacent to the
 structure and cured by the same methods, final curing may be terminated
 when the average compressive strength has reached 70 percent of the 28-day
 design compressive strength. Prevent rapid drying at end of final curing
 period.

3.10.2     Moist Curing

 Remove water without erosion or damage to the structure.   Prevent water
 run-off.

3.10.2.1     Ponding or Immersion

 Continually immerse the concrete throughout the curing period. Water must
 not be more than 50 degrees F less than the temperature of the concrete.
 For temperatures between 40 and 50 degrees F, increase the curing period by
 50 percent.

3.10.2.2     Fog Spraying or Sprinkling

 Apply water uniformly and continuously throughout the curing period. For
 temperatures between 40 and 50 degrees F, increase the curing period by 50
 percent.

3.10.2.3     Pervious Sheeting

 Completely cover surface and edges of the concrete with two thicknesses of
 wet sheeting. Overlap sheeting 6 inches over adjacent sheeting. Provide
 sheeting that is at least as long as the width of the surface to be cured.
 During application, do not drag the sheeting over the finished concrete nor
 over sheeting already placed. Wet sheeting thoroughly and keep
 continuously wet throughout the curing period.

3.10.2.4     Impervious Sheeting

 Wet the entire exposed surface of the concrete thoroughly with a fine spray
 of water and cover with impervious sheeting throughout the curing period.
 Lay sheeting directly on the concrete surface and overlap edges 12 inches
 minimum. Provide sheeting not less than 18 inches wider than the concrete
 surface to be cured. Secure edges and transverse laps to form closed
 joints. Repair torn or damaged sheeting or provide new sheeting. Cover or
 wrap columns, walls, and other vertical structural elements from the top
 down with impervious sheeting; overlap and continuously tape sheeting
 joints; and introduce sufficient water to soak the entire surface prior to
 completely enclosing.

3.10.3     Liquid Membrane-Forming Curing Compound

 Seal or cover joint openings prior to application of curing compound.
 Prevent curing compound from entering the joint. Apply in accordance with
 the recommendations of the manufacturer immediately after any water sheen
 which may develop after finishing has disappeared from the concrete
 surface. Provide and maintain compound on the concrete surface throughout
 the curing period. Do not use this method of curing where the use of
 Figure 2.1.5 in ACI/MCP-2 indicates that hot weather conditions cause an
 evaporation rate exceeding 0.2 pound of water per square foot per hour.




                            SECTION 03 30 00   Page 28
Design MET Facility                                                      5490419


3.10.3.1     Application

 Unless the manufacturer recommends otherwise, apply compound immediately
 after the surface loses its water sheen and has a dull appearance, and
 before joints are sawed. Mechanically agitate curing compound thoroughly
 during use. Use approved power-spraying equipment to uniformly apply two
 coats of compound in a continuous operation. The total coverage for the
 two coats must be 200 square feet maximum per gallon of undiluted compound
 unless otherwise recommended by the manufacturer's written instructions.
 The compound must form a uniform, continuous, coherent film that does not
 check, crack, or peel. Immediately apply an additional coat of compound to
 areas where the film is defective. Re-spray concrete surfaces subjected to
 rainfall within 3 hours after the curing compound application.

3.10.3.2     Protection of Treated Surfaces

 Prohibit pedestrian and vehicular traffic and other sources of abrasion at
 least 72 hours after compound application. Maintain continuity of the
 coating for the entire curing period and immediately repair any damage.

3.10.4     Liquid Chemical Sealer-Hardener

 Apply sealer-hardener to interior floors not receiving floor covering.
 Apply the sealer-hardener in accordance with manufacturer's
 recommendations. Seal or cover joints and openings in which joint sealant
 is to be applied as required by the joint sealant manufacturer. Do not
 apply the sealer hardener until the concrete has been moist cured and has
 aged for a minimum of 30 days. Apply a minimum of two coats of
 sealer-hardener.

3.10.5     Curing Periods

 ACI/MCP-2 except 10 days for retaining walls, pavement or chimneys, 21 days
 for concrete that is in full-time or intermittent contact with seawater,
 salt spray, alkali soil or waters. Begin curing immediately after
 placement. Protect concrete from premature drying, excessively hot
 temperatures, and mechanical injury; and maintain minimal moisture loss at
 a relatively constant temperature for the period necessary for hydration of
 the cement and hardening of the concrete. The materials and methods of
 curing are subject to approval by the Contracting Officer.

3.10.6     Curing Methods

 Accomplish curing by moist curing, by moisture-retaining cover curing, by
 membrane curing, and by combinations thereof, as specified.

 Moist curing:

         Accomplish moisture curing by any of the following methods:

             Keeping surface of concrete wet by covering with water

             Continuous water spraying

             Covering concrete surface with specified absorptive cover for
             curing concrete saturated with water and keeping absorptive cover
             wet by water spraying or intermittent hosing. Place absorptive
             cover to provide coverage of concrete surfaces and edges with a
             slight overlap over adjacent absorptive covers.


                             SECTION 03 30 00   Page 29
Design MET Facility                                                       5490419



 Moisture-cover curing:

         Accomplish moisture-retaining cover curing by covering concrete
         surfaces with specified moisture-retaining cover for curing concrete.
         Place cover directly on concrete in widest practical width, with sides
         and ends lapped at least 3 inches. Weight cover to prevent
         displacement; immediately repair tears or holes appearing during curing
         period by patching with pressure-sensitive, waterproof tape or other
         approved method.

 Membrane curing:

         Accomplish membrane curing by applying specified membrane-forming
         curing compound to damp concrete surfaces as soon as moisture film has
         disappeared. Apply curing compound uniformly in a two-coat operation
         by power-spraying equipment using a spray nozzle equipped with a wind
         guard. Apply second coat in a direction at right angles to direction
         of first coat. Total coverage for two coats must be not more than 200
         square feet per gallon of curing compound. Respray concrete surfaces
         which are subjected to heavy rainfall within 3 hours after curing
         compound has been applied by method and at rate specified. Maintain
         continuity of coating for entire curing period and immediately repair
         damage to coating during this period.

         Membrane-curing compounds must not be used on surfaces that are to be
         covered with coating material applied directly to concrete or with a
         covering material bonded to concrete, such as other concrete, liquid
         floor hardener, waterproofing, dampproofing, membrane roofing,
         painting, and other coatings and finish materials.

3.10.7     Curing Formed Surfaces

 Accomplish curing of formed surfaces, including undersurfaces of girders,
 beams, supported slabs, and other similar surfaces by moist curing with
 forms in place for full curing period or until forms are removed. If forms
 are removed before end of curing period, accomplish final curing of formed
 surfaces by any of the curing methods specified above, as applicable.

3.10.8     Curing Unformed Surfaces

 Accomplish initial curing of unformed surfaces, such as monolithic slabs,
 floor topping, and other flat surfaces, by membrane curing.

 Unless otherwise specified, accomplish final curing of unformed surfaces by
 any of curing methods specified above, as applicable.

 Accomplish final curing of concrete surfaces to receive liquid floor
 hardener of finish flooring by moisture-retaining cover curing.

3.10.9     Temperature of Concrete During Curing

 When temperature of atmosphere is 41 degrees F and below, maintain
 temperature of concrete at not less than 55 degrees F throughout concrete
 curing period or 45 degrees F when the curing period is measured by
 maturity. When necessary, make arrangements before start of concrete
 placing for heating, covering, insulation, or housing as required to
 maintain specified temperature and moisture conditions for concrete during
 curing period.


                             SECTION 03 30 00   Page 30
Design MET Facility                                                       5490419



 When the temperature of atmosphere is 80 degrees F and above or during
 other climatic conditions which cause too rapid drying of concrete, make
 arrangements before start of concrete placing for installation of wind
 breaks, of shading, and for fog spraying, wet sprinkling, or
 moisture-retaining covering of light color as required to protect concrete
 during curing period.

 Changes in temperature of concrete must be uniform and not exceed   37
 degrees F in any 1 hour nor 80 degrees F in any 24-hour period.

3.10.10     Protection from Mechanical Injury

 During curing period, protect concrete from damaging mechanical
 disturbances, particularly load stresses, heavy shock, and excessive
 vibration and from damage caused by rain or running water.

3.10.11     Protection After Curing

 Protect finished concrete surfaces from damage by construction operations.

3.11     FIELD QUALITY CONTROL

3.11.1     Sampling

 ASTM C 172. Collect samples of fresh concrete to perform tests specified.
 ASTM C 31/C 31M for making test specimens.

3.11.2     Testing

3.11.2.1     Slump Tests

 ASTM C 143/C 143M. Take concrete samples during concrete placement. The
 maximum slump may be increased as specified with the addition of an
 approved admixture provided that the water-cement ratio is not exceeded.
 Perform tests at commencement of concrete placement, when test cylinders
 are made, and for each batch (minimum) or every 20 cubic yards (maximum) of
 concrete.

3.11.2.2     Temperature Tests

 Test the concrete delivered and the concrete in the forms. Perform tests
 in hot or cold weather conditions (below 50 degrees F and above 80 degrees F
 ) for each batch (minimum) or every 20 cubic yards (maximum) of concrete,
 until the specified temperature is obtained, and whenever test cylinders
 and slump tests are made.

3.11.2.3     Compressive Strength Tests

 ASTM C 39/C 39M. Make five test cylinders for each set of tests in
 accordance with ASTM C 31/C 31M. Take precautions to prevent evaporation
 and loss of water from the specimen. Test two cylinders at 7 days, two
 cylinders at 28 days, and hold one cylinder in reserve. Take samples for
 strength tests of each mix design of and for concrete placed each day not
 less than once a day, nor less than once for each 160 cubic yards of
 concrete, nor less than once for each 5400 square feet of surface area for
 slabs or walls. For the entire project, take no less than five sets of
 samples and perform strength tests for each mix design of concrete placed.
 Each strength test result must be the average of two cylinders from the


                            SECTION 03 30 00    Page 31
Design MET Facility                                                    5490419


 same concrete sample tested at 28 days. If the average of any three
 consecutive strength test results is less than f'c or if any strength test
 result falls below f'c by more than 450 psi, take a minimum of three
 ASTM C 42/C 42M core samples from the in-place work represented by the low
 test cylinder results and test. Concrete represented by core test is
 considered structurally adequate if the average of three cores is equal to
 at least 85 percent of f'c and if no single core is less than 75 percent of
 f'c. Retest locations represented by erratic core strengths. Remove
 concrete not meeting strength criteria and provide new acceptable
 concrete. Repair core holes with nonshrink grout. Match color and finish
 of adjacent concrete.

3.11.2.4   Air Content

 ASTM C 173/C 173M or ASTM C 231 for normal weight concrete. Test
 air-entrained concrete for air content at the same frequency as specified
 for slump tests.

3.11.2.5   Strength of Concrete Structure

 Compliance with the following is considered deficient if it fails to meet
 the requirements which control strength of structure in place, including
 following conditions:

      Failure to meet compressive strength tests as evaluated

      Reinforcement not conforming to requirements specified

      Concrete which differs from required dimensions or location in such a
      manner as to reduce strength

      Concrete curing and protection of concrete against extremes of
      temperature during curing, not conforming to requirements specified

      Concrete subjected to damaging mechanical disturbances, particularly
      load stresses, heavy shock, and excessive vibration

      Poor workmanship likely to result in deficient strength

3.11.2.6   Testing Concrete Structure for Strength

 When there is evidence that strength of concrete structure in place does
 not meet specification requirements, make cores drilled from hardened
 concrete for compressive strength determination in accordance with
 ASTM C 42/C 42M, and as follows:

      Take at least three representative cores from each member or area of
      concrete-in-place that is considered potentially deficient. Location
      of cores will be determined by the Contracting Officer.

      Test cores after moisture conditioning in accordance with
      ASTM C 42/C 42M if concrete they represent is more than superficially
      wet under service.

      Air dry cores, (60 to 80 degrees F with relative humidity less than 60
      percent) for 7 days before test and test dry if concrete they represent
      is dry under service conditions.

      Strength of cores from each member or area are considered satisfactory


                          SECTION 03 30 00   Page 32
Design MET Facility                                                         5490419


         if their average is equal to or greater than 85 percent of the 28-day
         design compressive strength of the class of concrete.

         Core specimens will be taken and tested by the Government. If the
         results of core-boring tests indicate that the concrete as placed does
         not conform to the drawings and specification, the cost of such tests
         and restoration required must be borne by the Contractor.

 Fill core holes solid with patching mortar and finished to match adjacent
 concrete surfaces.

 Correct concrete work that is found inadequate by core tests in a manner
 approved by the Contracting Officer.

3.12     WASTE MANAGEMENT

 As specified in the Waste Management Plan and as follows.

3.12.1     Mixing Equipment

 Before concrete pours, designate Company-owned site meeting environmental
 standards for cleaning out concrete mixing trucks. Minimize water used to
 wash equipment.

3.12.2     Hardened, Cured Waste Concrete

 Crush and reuse hardened, cured waste concrete as fill or as a base course
 for pavement. Use hardened, cured waste concrete as aggregate in concrete
 mix if approved by Contracting Officer.

3.12.3     Reinforcing Steel

 Collect reinforcing steel and place in designated area for recycling.

3.12.4     Other Waste

 Identify concrete manufacturer's or supplier's policy for collection or
 return of construction waste, unused material, deconstruction waste, and/or
 packaging material. Return excess cement to supplier.

3.13     JOINTS

3.13.1     Construction Joints

 Make and locate joints not indicated so as not to impair strength and
 appearance of the structure, as approved. Locate construction joints as
 follows:

         a. In walls at not more than 60 feet in any horizontal direction; at
         top of footing; at top of slabs on ground; at top and bottom of door
         and window openings or where required to conform to architectural
         details; and at underside of deepest beam or girder framing into wall

         b. In slabs on ground, so as to divide slab into areas not in excess of
         1,200 square feet

 Joints must be perpendicular to main reinforcement.        Reinforcement must be
 continued across construction joints.



                               SECTION 03 30 00   Page 33
Design MET Facility                                                   5490419


3.13.2     Isolation Joints in Slabs on Ground

 Provide joints at points of contact between slabs on ground and vertical
 surfaces, such as column pedestals, foundation walls, grade beams, and
 elsewhere as indicated.

 Fill joints with premolded joint filler strips 1/2 inch thick, extending
 full slab depth. Install filler strips at proper level below finish floor
 elevation with a slightly tapered, dress-and-oiled wood strip temporarily
 secured to top of filler strip to form a groove not less than 3/4 inch in
 depth where joint is sealed with sealing compound and not less than 1/4 inch
 in depth where joint sealing is not required. Remove wood strip after
 concrete has set. Contractor must clean groove of foreign matter and loose
 particles after surface has dried.

3.13.3     Control Joints in Slabs on Ground

 Provide joints to form panels as indicated.

 Under and on exact line of each control joint, cut 50 percent of welded
 wire fabric reinforcement before placing concrete.

 Joints must be 1/8-inch wide by 1/5 to 1/4 of slab depth and formed by
 inserting hand-pressed fiberboard strip into fresh concrete until top
 surface of strip is flush with slab surface or by cutting the concrete with
 a saw after the concrete has set. After concrete has cured for at least 7
 days, the Contractor must remove inserts and clean groove of foreign matter
 and loose particles.

 Sawcutting will be limited to within 12 hours after set and at 1/4 slab
 depth.

3.14     INSTALLATION OF ANCHORAGE DEVICES

3.14.1     General

 Anchorage devices and embedded items required for other work that is
 attached to, or supported by, set and build in cast-in-place concrete as
 part of the work of this section, using setting drawings, instructions, and
 directions for work to be attached thereto.

3.14.2     Placing Anchorage Devices

 Anchorage devices and embedded items must be positioned accurately and
 supported against displacement. Fill openings in anchorage devices such as
 slots and threaded holes with an approved, removable material to prevent
 entry of concrete into openings.

3.15     CONCRETE CONVEYING

3.15.1     Transfer of Concrete At Project Site

 Handle concrete from point of delivery and transfer to concrete conveying
 equipment and to locations of final deposit as rapidly as practical by
 methods which prevent segregation and loss of concrete mix materials.

3.15.2     Mechanical Equipment for Conveying Concrete

 Equipment must ensure a continuous flow of concrete at delivery end, as


                              SECTION 03 30 00   Page 34
Design MET Facility                                                   5490419


 approved. Provide runways for wheeled concrete-conveying equipment from
 concrete delivery point to locations of final deposit. Interior surfaces
 of concrete conveying equipment must be free of hardened concrete, debris,
 water, snow, ice, and other deleterious substances.


       -- End of Section --




                          SECTION 03 30 00   Page 35
Design MET Facility                                                     5490419



                                SECTION 05 40 00

                            COLD-FORMED METAL FRAMING
                                      04/06

PART 1     GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to within the text by the
 basic designation only.

            AMERICAN IRON AND STEEL INSTITUTE (AISI)

 AISI SG02-1                        (2001) North American Specification for
                                    the Design of Cold-Formed Steel Structural
                                    Members

 AISI SG03-3                        (2002) Cold-Formed Steel Design Manual Set

            AMERICAN WELDING SOCIETY (AWS)

 AWS D1.3/D1.3M                     (2008; Errata 2008) Structural Welding
                                    Code - Sheet Steel

            ASTM INTERNATIONAL (ASTM)

 ASTM A 123/A 123M                  (2009) Standard Specification for Zinc
                                    (Hot-Dip Galvanized) Coatings on Iron and
                                    Steel Products

 ASTM A 153/A 153M                  (2009) Standard Specification for Zinc
                                    Coating (Hot-Dip) on Iron and Steel
                                    Hardware

 ASTM A 653/A 653M                  (2009) Standard Specification for Steel
                                    Sheet, Zinc-Coated (Galvanized) or
                                    Zinc-Iron Alloy-Coated (Galvannealed) by
                                    the Hot-Dip Process

 ASTM B 633                         (2007) Standard Specification for
                                    Electrodeposited Coatings of Zinc on Iron
                                    and Steel

 ASTM C 955                         (2008a) Load-Bearing (Transverse and
                                    Axial) Steel Studs, Runners (Tracks), and
                                    Bracing or Bridging for Screw Application
                                    of Gypsum Panel Products and Metal Plaster
                                    Bases

            SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)

 SAE J78                            (1998) Steel Self Drilling Tapping Screws

1.2   SUBMITTALS

 The following shall be submitted in accordance with Section 01 33 00


                            SECTION 05 40 00   Page 1
Design MET Facility                                                    5490419


 SUBMITTAL PROCEDURES:

      SD-02 Shop Drawings

           Framing Components

             a. Cross sections, plans, and/or elevations showing component
           types and locations for each framing application; including shop
           coatings and material thicknesses for each framing component.

             b. Connection details showing fastener type, quantity,
           location, and other information to assure proper installation.

             c. Drawings depicting panel configuration, dimensions,
           components, locations, and construction sequence if the Contractor
           elects to install prefabricated/prefinished frames.

      SD-03 Product Data

           Steel studs,joists, tracks, bracing, bridging and accessories

      SD-07 Certificates
          Load-bearing cold-formed metal framing

           Welds

             Certified copies of welder qualifications test records showing
           qualification in accordance with AWS D1.3/D1.3M.

1.3   DELIVERY, STORAGE, AND HANDLING

 Deliver materials to job site and store in adequately ventilated, dry
 locations. Storage area shall permit easy access for inspection and
 handling. If necessary to store materials outside, stack off the ground,
 support on a level platform, and protect from the weather as approved.
 Handle materials to prevent damage. Finish of the framing members shall be
 maintained at all times, using an approved high zinc dust content,
 galvanizing repair paint whenever necessary to prevent the formation of
 rust. Replace damaged items with new, as directed by the Contracting
 Officer.

1.4   LOAD-BEARING COLD-FORMED METAL FRAMING

 Include top and bottom tracks, bracing, fastenings, and other accessories
 necessary for complete installation. Framing members shall have the
 structural properties indicated. Where physical structural properties are
 not indicated, they shall be as necessary to withstand all imposed loads.
 Design framing in accordance with AISI SG03-3.

1.5   MAXIMUM DEFLECTION

  Wall deflections shall be computed on the basis that studs withstand all
lateral forces independent of any composite action from sheathing materials.
Studs abutting windows or louvers shall also be designed not to exceed 1/4
inch maximum deflection.

      a.   Floor Joists:

           L/360 - Live load only


                            SECTION 05 40 00   Page 2
Design MET Facility                                                        5490419


               L/240 - Total load



1.6     QUALITY ASSURANCE

1.6.1     Drawing Requirements

 Submit framing components to show sizes, thicknesses, layout, material
 designations, methods of installation, and accessories.

PART 2        PRODUCTS

2.1     STEEL STUDS, JOISTS, TRACKS, BRACING, BRIDGING AND ACCESSORIES

 Framing components shall comply with ASTM C 955 and the following.

2.1.1     Studs and Joists of 16 Gage (0.0598 Inch) and Heavier

 Galvanized steel, ASTM A 653/A 653M, SS Grade 50, G60 .

2.1.2     Studs and Joists of 18 Gage (0.0478 Inch) and Lighter

 Studs and Joists of 18 Gage (0.0478 Inch) and Lighter, Track, and
 Accessories (All Gages): Galvanized steel, ASTM A 653/A 653M, SS, Grade 50
 33,000 psi G60.

2.1.3     Sizes, Gages, Section Modulus, and Other Structural Properties

 Size and gage as indicated. Steel stud deflection shall be limited to
 L/600 for exterior wall brick veneer construction.

2.2     MARKINGS

 Studs and track shall have product markings stamped on the web of the
 section. The markings shall be repeated throughout the length of the
 member at a maximum spacing of 4 feet on center and shall be legible and
 easily read. The product marking shall include the following:

         a.     An ICBO number.

         b.    Manufacturer's identification.

         c.    Minimum delivered uncoated steel thickness.

         d.    Protective coating designator.

         e.    Minimum yield strength.

2.3     CONNECTIONS

 Screws for steel-to-steel connections shall be self-drilling tapping in
 compliance with SAE J78 of the type, size, and location as shown on the
 drawings. Electroplated screws shall have a Type II coating in accordance
 with ASTM B 633. Screws, bolts, and anchors shall be hot-dipped galvanized
 in accordance with ASTM A 123/A 123M or ASTM A 153/A 153M as appropriate.
 Screws bolts, and anchors shall be hot dipped galvanized in accordance
 with ASTM A 123/A 123M or ASTM A 153/A 153M as appropriate.



                                  SECTION 05 40 00   Page 3
Design MET Facility                                                      5490419


2.4     PLASTIC GROMMETS

 Supply plastic grommets, recommended by stud manufacturer, to protect
 electrical wires. Prevent metal to metal contact for plumbing pipes.

PART 3     EXECUTION

3.1     FASTENING

 Fasten framing members together by welding or by using self-drilling or
 self-tapping screws. Electrodes and screw connections shall be as required
 and indicated in the design calculations.

3.1.1     Welds

 All welding shall be performed in accordance with AWS D1.3/D1.3M, as
 modified by AISI SG02-1. All welders, welding operations, and welding
 procedures shall be qualified according to AWS D1.3/D1.3M. All welds shall
 be cleaned and coated with rust inhibitive galvanizing paint. Do not field
 weld materials lighter than 18 gage.

3.1.2     Screws

 Screws shall be of the self-drilling self-tappingtype, size, and location
 shown on the drawings. Screw penetration through joined materials shall
 not be less than three exposed threads. Minimum spacings and edge
 distances for screws shall be as specified in AISI SG02-1. Screws covered
 by sheathing materials shall have low profile heads.

3.1.3     Anchors

 Anchors shall be of the type, size, and location shown on the drawings.

3.2     INSTALLATION

3.2.1     Tracks

 Provide accurately aligned runners at top and bottom of partitions. Anchor
 tracks as indicated in design calculations. Butt weld joints in tracks or
 splice with stud inserts. Fasteners shall be at least 3 inches from the
 edge of concrete slabs.

3.2.2     Studs

 Cut studs square and set with firm bearing against webs of top and bottom
 tracks. Position studs vertically in tracks and space as indicated in
 design. Do not splice studs. Provide at least two studs at jambs of doors
 and other openings 2 feet wide or larger. Provide jack studs over
 openings, as necessary, to maintain indicated stud spacing. Provide
 tripled studs at corners, positioned to receive interior and exterior
 finishes. Fasten studs to top and bottom tracks by welding or screwing
 both flanges to the tracks. Framed wall openings shall include headers and
 supporting components as shown on the drawings. Headers shall be installed
 in all openings that are larger than the stud spacing in a wall. In
 curtain wall construction, provide for vertical movement where studs
 connect to the structural frame. Provide horizontal bracing in accordance
 with the design calculations and AISI SG03-3, consisting of, as a minimum,
 runner channel cut to fit between and welded to the studs or hot- or
 cold-rolled steel channels inserted through cutouts in web of each stud and


                           SECTION 05 40 00   Page 4
Design MET Facility                                                                 5490419


 secured to studs with welded clip angles. Bracing shall be not less than
 the following:

              LOAD                        HEIGHT                 BRACING

         Wind load only               Up to 10 feet      One row at mid-height
                                      Over 10 feet       Rows 5'-0" o.c. maximum

         Axial load                   Up to 10 feet      Two rows at 1/3 points
                                      Over 10 feet       Rows 3'-4" o.c. maximum

3.2.3    Joists

 Locate each joist directly above a stud. Provide doubled joists under
 parallel partitions wherever partition length exceeds 1/2 of joist span.
 Joists shall have at least 2.50 inches of bearing on steel and shall be
 reinforced over bearings where required to prevent web crippling. Splice
 joists over bearings only. Lap and weld splices as indicated. Provide
 manufacturer's standard bridging which shall not be less than the following:

             CLEAR SPAN                      BRIDGING

              Up   to   14   feet          One row near center
              14   to   20   feet          Two rows at 1/3 points
              20   to   26   feet          Three rows at 1/4 points
              26   to   32   feet          Four rows at 1/5 points

 Temporary bracing shall be provided and remain in place until work is
 permanently stabilized.

3.2.4    Erection Tolerances

        a.   Framing members which will be covered by finishes such as
             wallboard, plaster, or ceramic tile set in a mortar setting bed,
             shall be within the following limits:

             (1) Layout of walls and partitions:           1/4 inch from intended
             position;

             (2)   Plates and runners:       1/4 inch in 8 feet from a straight line;

             (3)   Studs:      1/4 inch in 8 feet out of plumb, not cumulative; and

             (4) Face of framing members:          1/4 inch in 8 feet from a true
             plane.

        b.   Framing members which will be covered by ceramic tile set in
             dry-set mortar, latex-portland cement mortar, or organic adhesive
             shall be within the following limits:

             (1) Layout of walls and partitions:           1/4 inch from intended
             position;

             (2)   Plates and runners:       1/8 inch in 8 feet from a straight line;

             (3)   Studs:      1/8 inch in 8 feet out of plumb, not cumulative; and

             (4) Face of framing members:          1/8 inch in 8 feet from a true
             plane.


                                    SECTION 05 40 00    Page 5
Design MET Facility                                    5490419



        -- End of Section --




                           SECTION 05 40 00   Page 6
Design MET Facility                                                          5490419




                                   SECTION 07 21 16

                           MINERAL FIBER BLANKET INSULATION
                                         04/06

PART 1     GENERAL

1.1     REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to within the text by the
 basic designation only.

             ASTM INTERNATIONAL (ASTM)

 ASTM C 665                           (2006) Mineral-Fiber Blanket Thermal
                                      Insulation for Light Frame Construction
                                      and Manufactured Housing

 ASTM C 930                           (2005) Potential Health and Safety
                                      Concerns Associated with Thermal
                                      Insulation Materials and Accessories

 ASTM E 136                           (2009) Behavior of Materials in a Vertical
                                      Tube Furnace at 750 Degrees C

 ASTM E 84                            (2009) Standard Test Method for Surface
                                      Burning Characteristics of Building
                                      Materials

             U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

 29 CFR 1910.134                      Respiratory Protection

1.2     SUBMITTALS

 The following shall be submitted in accordance with Section 01 33 00
 SUBMITTAL PROCEDURES:

         SD-03 Product Data

             Blanket insulation

             Accessories

         SD-08 Manufacturer's Instructions

             Insulation

1.3     DELIVERY, STORAGE, AND HANDLING

1.3.1     Delivery

 Deliver materials to site in original sealed wrapping bearing
 manufacturer's name and brand designation, specification number, type,
 grade, R-value, and class. Store and handle to protect from damage. Do
 not allow insulation materials to become wet, soiled, crushed, or covered


                               SECTION 07 21 16   Page 1
Design MET Facility                                                   5490419


 with ice or snow. Comply with manufacturer's recommendations for handling,
 storing, and protecting of materials before and during installation.

1.3.2     Storage

 Inspect materials delivered to the site for damage; unload and store out of
 weather in manufacturer's original packaging. Store only in dry locations,
 not subject to open flames or sparks, and easily accessible for inspection
 and handling.

1.4     SAFETY PRECAUTIONS

1.4.1     Respirators

 Provide installers with dust/mist respirators, training in their use, and
 protective clothing, all approved by National Institute for Occupational
 Safety and Health (NIOSH)/Mine Safety and Health Administration (MSHA) in
 accordance with 29 CFR 1910.134.

1.4.2     Smoking

 Do not smoke during installation of blanket thermal insulation.

1.4.3     Other Safety Concerns

 Consider other safety concerns and measures as outlined in ASTM C 930.

PART 2     PRODUCTS

2.1     BLANKET INSULATION

 ASTM C 665, Type I, blankets without membrane coverings ; Class A,
 membrane-faced surface with a flame spread of 25 or less and a smoke
 developed rating of 150 or less when tested in accordance with ASTM E 84.

2.1.1     Thermal Resistance Value (R-VALUE)

 As indicated

2.1.2     Recycled Materials

 Provide Thermal Insulation containing recycled materials to the extent
 practicable, provided the material meets all other requirements of this
 section. The minimum required recycled materials content by weight are:

 Rock Wool:        75 percent slag
 Fiberglass:       20 to 25 percent glass cullet

2.1.3     Prohibited Materials

 Do not provide asbestos-containing materials.

2.2     BLOCKING

 Wood, metal, unfaced mineral fiber blankets in accordance with ASTM C 665,
 Type I, or other approved materials. Use only non-combustible materials
 meeting the requirements of ASTM E 136 for blocking around chimneys and
 heat producing devices.



                               SECTION 07 21 16    Page 2
Design MET Facility                                                   5490419


2.3     ACCESSORIES

2.3.1     Adhesive

 As recommended by the insulation manufacturer.

2.3.2     Mechanical Fasteners

 Corrosion resistant fasteners as recommended by the insulation manufacturer.

2.3.3     Wire Mesh

 Corrosion resistant and as recommended by the insulation manufacturer.

PART 3     EXECUTION

3.1     EXISTING CONDITIONS

 Before installing insulation, ensure that areas that will be in contact
 with the insulation are dry and free of projections which could cause
 voids, compressed insulation, or punctured vapor retarders. If moisture or
 other conditions are found that do not allow the workmanlike installation
 of the insulation, do not proceed but notify Contracting Officer of such
 conditions.

3.2     PREPARATION

3.3     INSTALLATION

3.3.1     Insulation

 Install and handle insulation in accordance with manufacturer's
 instructions. Keep material dry and free of extraneous materials.   Ensure
 personal protective clothing and respiratory equipment is used as
 required. Observe safe work practices.

3.3.1.1     Electrical wiring

 Do not install insulation in a manner that would sandwich electrical wiring
 between two layers of insulation.

3.3.1.2     Continuity of Insulation

 Install blanket insulation to butt tightly against adjoining blankets and
 to studs, rafters, joists, sill plates, headers and any obstructions.
 Provide continuity and integrity of insulation at corners, wall to ceiling
 joints, roof, and floor. Avoid creating thermal bridges.

3.3.1.3     Installation at Bridging and Cross Bracing

 Insulate at bridging and cross bracing by splitting blanket vertically at
 center and packing one half into each opening. Butt insulation at bridging
 and cross bracing; fill in bridged area with loose or scrap insulation.

3.3.1.4     Insulation without Affixed Vapor Retarder

 Provide snug friction fit to hold insulation in place. Stuff pieces of
 insulation into cracks between trusses, joists, studs and other framing,
 such as at attic access doors, door and window heads, jambs, and sills,


                                SECTION 07 21 16   Page 3
Design MET Facility                                                   5490419


 band joists, and headers.

3.3.1.5   Sizing of Blankets

 Provide only full width blankets when insulating between trusses, joists,
 or studs. Size width of blankets for a snug fit where trusses, joists or
 studs are irregularly spaced.

3.3.1.6   Access Panels and Doors

 Affix blanket insulation to access panels greater than one square foot and
 access doors in insulated floors and ceilings. Use insulation with same
 R-Value as that for floor or ceiling.

     -- End of Section --




                             SECTION 07 21 16   Page 4
Design MET Facility                                                         5490419



                                  SECTION 07 92 00

                                   JOINT SEALANTS
                                        01/07

PART 1     GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to within the text by the
 basic designation only.

             ASTM INTERNATIONAL (ASTM)

 ASTM C 734                          (2006) Low-Temperature Flexibility of
                                     Latex Sealants After Artificial Weathering

 ASTM C 834                          (2005) Latex Sealants

 ASTM C 919                          (2008) Use of Sealants in Acoustical
                                     Applications

 ASTM C 920                          (2008) Standard Specification for
                                     Elastomeric Joint Sealants

 ASTM D 217                          (2002; R 2008) Cone Penetration of
                                     Lubricating Grease

 ASTM E 84                           (2009) Standard Test Method for Surface
                                     Burning Characteristics of Building
                                     Materials

1.2   SUBMITTALS

 Submit the following in accordance with Section 01 33 00 SUBMITTAL
 PROCEDURES:

         SD-03 Product Data

             Sealants

             Primers

             Bond breakers

             Backstops

             Manufacturer's descriptive data including storage requirements,
             shelf life, curing time, instructions for mixing and application,
             and primer data (if required). Provide a copy of the Material
             Safety Data Sheet for each solvent, primer or sealant material.

         SD-07 Certificates

             Sealant

             Certificates of compliance stating that the materials conform to


                              SECTION 07 92 00   Page 1
Design MET Facility                                                        5490419


              the specified requirements.

1.3     ENVIRONMENTAL CONDITIONS

 Apply sealant when the ambient temperature is between 40 and 90 degrees F.

1.4     DELIVERY AND STORAGE

 Deliver materials to the job site in unopened manufacturers' external
 shipping containers, with brand names, date of manufacture, color, and
 material designation clearly marked thereon. Label elastomeric sealant
 containers to identify type, class, grade, and use. Carefully handle and
 store materials to prevent inclusion of foreign materials or subjection to
 sustained temperatures exceeding 90 degrees F or less than 0 degrees F.

1.5     QUALITY ASSURANCE

1.5.1     Compatibility with Substrate

 Verify that each of the sealants are compatible for use with joint
 substrates.

1.5.2     Joint Tolerance

 Provide joint tolerances in accordance with manufacturer's printed
 instructions.

1.6     SPECIAL WARRANTY

 Guarantee sealant joint against failure of sealant and against water
 penetration through each sealed joint for five years.

PART 2       PRODUCTS

2.1     SEALANTS

 Provide sealant that has been tested and found suitable for the substrates
 to which it will be applied.

2.1.1     Interior Sealant

 Provide ASTM C 834 .       Location(s) and color(s) of sealant for the following:

                         LOCATION                            COLOR

        a.    Small voids between walls or partitions and    As selected
              shelving, door frames, built-in or
              surface-mounted equipment and fixtures, and
              similar items.

        b.    Perimeter of frames at doors, windows,         As selected
              and access panels which adjoin exposed
              interior concrete surfaces.

        c.    Joints of interior partitions which adjoin     As selected
              columns and exterior walls unless
              otherwise detailed.

        d.    Joints between edge members for acoustical     As selected


                               SECTION 07 92 00   Page 2
Design MET Facility                                                             5490419



                         LOCATION                              COLOR
             tile and adjoining vertical surfaces.

        e.   Interior locations, not otherwise indicated       Match adjacent
             or specified, where small voids exist between     surface color.
             materials specified to be painted.

2.1.2     Exterior Sealant

 For joints in vertical surfaces, provide ASTM C 920, Type S or M, Grade NS,
 Class 25, Use NT. For joints in horizontal surfaces, provide ASTM C 920,
 Type S or M, Grade P, Class 25, Use T. Provide location(s) and color(s) of
 sealant as follows:

                         LOCATION                              COLOR

        a.   Joints and recesses formed where frames           As selected
             and subsills of windows, doors, louvers,
             and vents adjoin concrete, or metal frames.
             Use sealant at both exterior and interior
             surfaces of exterior wall penetrations.

        b.   Expansion and control joints.                     As selected

        c.   Voids where items pass through exterior           Match adjacent
             walls.                                            surface color

        d.   Metal-to-metal joints where sealant is            As selected
             indicated or specified.

        e.   Joints between ends of gravel stops, fascias,     As selected
             copings, and adjacent walls.

2.1.3     Floor Joint Sealant

 ASTM C 920, Type S or M, Grade P, Class 25, Use T.         Provide location(s) and
 color(s) of sealant as follows:

                  LOCATION                                     COLOR

        a.   Seats of metal thresholds for                     As selected
             exterior doors.

        b.   Control and expansion joints in floors,           As selected
             slabs, and walkways.

2.1.4     Acoustical Sealant

 Rubber or polymer-based acoustical sealant conforming to ASTM C 919 must
 have a flame spread of 25 or less and a smoke developed rating of 50 or
 less when tested in accordance with ASTM E 84. Acoustical sealant must
 have a consistency of 250 to 310 when tested in accordance with ASTM D 217,
 and must remain flexible and adhesive after 500 hours of accelerated
 weathering as specified in ASTM C 734, and must be non-staining.

2.2     PRIMERS

 Provide a nonstaining, quick-drying type and consistency recommended by the


                                SECTION 07 92 00   Page 3
Design MET Facility                                                      5490419


 sealant manufacturer for the particular application.

2.3     BOND BREAKERS

 Provide the type and consistency recommended by the sealant manufacturer to
 prevent adhesion of the sealant to backing or to bottom of the joint.

2.4     BACKSTOPS

 Provide glass fiber roving or neoprene, butyl, polyurethane, or
 polyethylene foams free from oil or other staining elements as recommended
 by sealant manufacturer. Provide 25 to 33 percent oversized backing for
 closed cell and 40 to 50 percent oversized backing for open cell material,
 unless otherwise indicated. Make backstop material compatible with
 sealant. Do not use oakum and other types of absorptive materials as
 backstops.

2.5     CLEANING SOLVENTS

 Provide type(s) recommended by the sealant manufacturer except for aluminum
 and bronze surfaces that will be in contact with sealant.

PART 3     EXECUTION

3.1     SURFACE PREPARATION

 Clean surfaces from dirt frost, moisture, grease, oil, wax, lacquer, paint,
 or other foreign matter that would tend to destroy or impair adhesion.
 Remove oil and grease with solvent. Surfaces must be wiped dry with clean
 cloths. When resealing an existing joint, remove existing caulk or sealant
 prior to applying new sealant. For surface types not listed below, contact
 sealant manufacturer for specific recommendations.

3.1.1     Steel Surfaces

 Remove loose mill scale by sandblasting or, if sandblasting is impractical
 or would damage finish work, scraping and wire brushing. Remove protective
 coatings by sandblasting or using a residue-free solvent.

3.1.2     Aluminum or Bronze Surfaces

 Remove temporary protective coatings from surfaces that will be in contact
 with sealant. When masking tape is used as a protective coating, remove
 tape and any residual adhesive just prior to sealant application. For
 removing protective coatings and final cleaning, use nonstaining solvents
 recommended by the manufacturer of the item(s) containing aluminum or
 bronze surfaces.

3.1.3     Concrete and Masonry Surfaces

 Where surfaces have been treated with curing compounds, oil, or other such
 materials, remove materials by sandblasting or wire brushing. Remove
 laitance, efflorescence and loose mortar from the joint cavity.

3.2     SEALANT PREPARATION

 Do not add liquids, solvents, or powders to the sealant. Mix
 multicomponent elastomeric sealants in accordance with manufacturer's
 instructions.


                              SECTION 07 92 00   Page 4
Design MET Facility                                                          5490419



3.3     APPLICATION

3.3.1     Joint Width-To-Depth Ratios

        a.   Acceptable Ratios:

                   JOINT WIDTH                           JOINT DEPTH
                                                    Minimum       Maximum

                   For metal, glass, or other
                   nonporous surfaces:

                      1/4 inch (minimum)            1/4 inch      1/4 inch
                      over 1/4 inch                 1/2 of        Equal to
                                                    width         width

                   For concrete:

                      1/4 inch (minimum)            1/4 inch      1/4 inch
                      Over 1/4 inch to 1/2 inch     1/4 inch      Equal to
                                                                  width

                      Over 1/2 inch to 2 inch       1/2 inch      5/8 inch
                      Over 2 inch.                  (As recommended by sealant
                                                    manufacturer)

        b.   Unacceptable Ratios: Where joints of acceptable width-to-depth
             ratios have not been provided, clean out joints to acceptable
             depths and grind or cut to acceptable widths without damage to the
             adjoining work. Grinding is not required on metal surfaces.

3.3.2     Masking Tape

 Place masking tape on the finish surface on one or both sides of a joint
 cavity to protect adjacent finish surfaces from primer or sealant smears.
 Remove masking tape within 10 minutes after joint has been filled and
 tooled.

3.3.3     Backstops

 Install backstops dry and free of tears or holes. Tightly pack the back or
 bottom of joint cavities with backstop material to provide a joint of the
 depth specified. Install backstops in the following locations:

        a.   Where indicated.

        b.   Where backstop is not indicated but joint cavities exceed the
             acceptable maximum depths specified in paragraph entitled, "Joint
             Width-to-Depth Ratios".

3.3.4     Primer

 Immediately prior to application of the sealant, clean out loose particles
 from joints. Where recommended by sealant manufacturer, apply primer to
 joints in concrete masonry units, wood, and other porous surfaces in
 accordance with sealant manufacturer's instructions. Do not apply primer
 to exposed finish surfaces.



                                 SECTION 07 92 00   Page 5
Design MET Facility                                                       5490419


3.3.5     Bond Breaker

 Provide bond breakers to the back or bottom of joint cavities, as
 recommended by the sealant manufacturer for each type of joint and sealant
 used, to prevent sealant from adhering to these surfaces. Carefully apply
 the bond breaker to avoid contamination of adjoining surfaces or breaking
 bond with surfaces other than those covered by the bond breaker.

3.3.6     Sealants

 Provide a sealant compatible with the material(s) to which it is applied.
 Do not use a sealant that has exceeded shelf life or has jelled and can not
 be discharged in a continuous flow from the gun. Apply the sealant in
 accordance with the manufacturer's printed instructions with a gun having a
 nozzle that fits the joint width. Force sealant into joints to fill the
 joints solidly without air pockets. Tool sealant after application to
 ensure adhesion. Make sealant uniformly smooth and free of wrinkles. Upon
 completion of sealant application, roughen partially filled or unfilled
 joints, apply sealant, and tool smooth as specified. Apply sealer over the
 sealant when and as specified by the sealant manufacturer.

3.4     PROTECTION AND CLEANING

3.4.1     Protection

 Protect areas adjacent to joints from sealant smears. Masking tape may be
 used for this purpose if removed 5 to 10 minutes after the joint is filled.

3.4.2     Final Cleaning

 Upon completion of sealant application, remove remaining smears and stains
 and leave the work in a clean and neat condition.

        a.   Masonry and Other Porous Surfaces: Immediately scrape off fresh
             sealant that has been smeared on masonry and rub clean with a
             solvent as recommended by the sealant manufacturer. Allow excess
             sealant to cure for 24 hour then remove by wire brushing or
             sanding.

        b.   Metal and Other Non-Porous Surfaces:   Remove excess sealant with a
             solvent-moistened cloth.

          -- End of Section --




                             SECTION 07 92 00   Page 6
Design MET Facility                                                   5490419




                              SECTION 08 11 13

                           STEEL DOORS AND FRAMES

                                      08/08

PART 1   GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to in the text by the
 basic designation only.

          AMERICAN WELDING SOCIETY (AWS)

 AWS D1.1/D1.1M                   (2008; Errata 2009) Structural Welding
                                  Code - Steel

          ASTM INTERNATIONAL (ASTM)

 ASTM A 653/A 653M                (2009) Standard Specification for Steel
                                  Sheet, Zinc-Coated (Galvanized) or
                                  Zinc-Iron Alloy-Coated (Galvannealed) by
                                  the Hot-Dip Process

 ASTM A 924/A 924M                (2008a) Standard Specification for General
                                  Requirements for Steel Sheet,
                                  Metallic-Coated by the Hot-Dip Process

 ASTM C 578                       (2008b) Standard Specification for Rigid,
                                  Cellular Polystyrene Thermal Insulation

 ASTM C 591                       (2008a) Standard Specification for Unfaced
                                  Preformed Rigid Cellular Polyisocyanurate
                                  Thermal Insulation

 ASTM C 612                       (2004e1) Mineral Fiber Block and Board
                                  Thermal Insulation

 ASTM D 2863                      (2008) Measuring the Minimum Oxygen
                                  Concentration to Support Candle-Like
                                  Combustion of Plastics (Oxygen Index)

          BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)

 ANSI/BHMA A156.115               (2006) Hardware Preparation in Steel Doors
                                  and Steel Frames

          NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)

 NAAMM HMMA HMM                   (1999; R2000) Hollow Metal Manual

          STEEL DOOR INSTITUTE (SDI/DOOR)

 SDI/DOOR 113                     (2001) Determining the Steady State
                                  Thermal Transmittance of Steel Door and


                          SECTION 08 11 13    Page 1
Design MET Facility                                                          5490419


                                      Frame Assemblies

 SDI/DOOR A250.11                     (2001) Recommended Erection Instructions
                                      for Steel Frames

 SDI/DOOR A250.6                      (2003) Hardware on Steel Doors
                                      (Reinforcement - Application)

 SDI/DOOR A250.8                      (2003) Recommended Specification for
                                      Standard Steel Doors and Frames

1.2   SUBMITTALS

 The following shall be submitted in accordance with Section 01 33 00
 SUBMITTAL PROCEDURES:

         SD-02 Shop Drawings

             Doors

             Frames

             Accessories

             Schedule of doors

             Schedule of frames

             Submit door and frame locations.

         SD-03 Product Data

             Doors

             Frames

          Accessories
1.3   DELIVERY, STORAGE, AND HANDLING

 Deliver doors, frames, and accessories undamaged and with protective
 wrappings or packaging. Provide temporary steel spreaders securely fastened
 to the bottom of each welded frame. Store doors and frames on platforms
 under cover in clean, dry, ventilated, and accessible locations, with 1/4
 inch airspace between doors. Remove damp or wet packaging immediately and
 wipe affected surfaces dry. Replace damaged materials with new.

PART 2     PRODUCTS

2.1   STANDARD STEEL DOORS

 SDI/DOOR A250.8, except as specified otherwise. Prepare doors to receive
 door hardware as specified in Section 08 71 00. Undercut where indicated.
 Exterior doors shall have top edge closed flush and sealed to prevent water
 intrusion. Doors shall be 1-3/4 inch thick, unless otherwise indicated.




                               SECTION 08 11 13   Page 2
Design MET Facility                                                           5490419


2.1.1     Classification - Level, Performance, Model

2.1.1.1      Maximum Duty Doors

 SDI/DOOR A250.8, Level 4, physical performance Level A, Model 1 with core
 construction as required by the manufacturer for interior doors and for
 indicated exterior doors, of size(s) and design(s) indicated.

2.2     CUSTOM HOLLOW METAL DOORS

 Provide custom hollow metal doors where nonstandard steel doors are
 indicated. At the Contractor's option, custom hollow metal doors may be
 provided in lieu of standard steel doors. Door size(s), design(s),
 materials, construction, gages, and finish shall be as specified for
 standard steel doors and shall comply with the requirement of NAAMM HMMA HMM.
 Fill all spaces in doors with insulation. Close top and bottom edges with
 steel channels not lighter than 16 gage. Close tops of exterior doors
 flush with an additional channel and seal to prevent water intrusion.
 Prepare doors to receive hardware specified in Section 08 71 00 DOOR
 HARDWARE. Undercut doors where indicated. Doors shall be 1-3/4 inch thick,
 unless otherwise indicated.

2.3     ACCESSORIES2.4      INSULATION CORES

 Insulated cores shall be of type specified, and provide an apparent
 U-factor of .48 in accordance with SDI/DOOR 113 and shall conform to:

        a.   Rigid Cellular Polyisocyanurate Foam: ASTM C 591, Type I or II,
             foamed-in-place or in board form, with oxygen index of not less
             than 22 percent when tested in accordance with ASTM D 2863; or

        b.   Rigid Polystyrene Foam Board:     ASTM C 578, Type I or II; or

        c.   Mineral board:    ASTM C 612, Type I.

2.5     STANDARD STEEL FRAMES

 SDI/DOOR A250.8, Level 4, except as otherwise specified. Form frames to
 sizes and shapes indicated, with welded corners . Provide steel frames for
 doors, unless otherwise indicated.

2.5.1     Welded Frames

 Continuously weld frame faces at corner joints. Mechanically interlock or
 continuously weld stops and rabbets. Grind welds smooth.

 Weld frames in accordance with the recommended practice of the Structural
 Welding Code Sections 1 through 6, AWS D1.1/D1.1M and in accordance with
 the practice specified by the producer of the metal being welded.

2.5.2     Stops and Beads

 Form stops and beads from 20 gage steel. Provide for glazed and other
 openings in standard steel frames. Secure beads to frames with oval-head,
 countersunk Phillips self-tapping sheet metal screws or concealed clips and
 fasteners. Space fasteners approximately 12 to 16 inch on center. Miter
 molded shapes at corners. Butt or miter square or rectangular beads at
 corners.



                                SECTION 08 11 13   Page 3
Design MET Facility                                                      5490419


2.5.3     Anchors

 Provide anchors to secure the frame to adjoining construction. Provide
 steel anchors, zinc-coated or painted with rust-inhibitive paint, not
 lighter than 18 gage.

2.5.3.1      Wall Anchors

 Provide at least three anchors for each jamb. For frames which are more
 than 7.5 feet in height, provide one additional anchor for each jamb for
 each additional 2.5 feet or fraction thereof.

        a.   Stud partitions: Weld or otherwise securely fasten anchors to
             backs of frames. Design anchors to be fastened to closed steel
             studs with sheet metal screws, and to open steel studs by wiring
             or welding

2.5.3.2      Floor Anchors

 Provide floor anchors drilled for 3/8 inch anchor bolts at bottom of each
 jamb member.

2.6     WEATHERSTRIPPING

 As specified in Section 08 71 00 DOOR HARDWARE.

2.7     HARDWARE PREPARATION

 Provide minimum hardware reinforcing gages as specified in SDI/DOOR A250.6.
 Drill and tap doors and frames to receive finish hardware. Prepare doors
 and frames for hardware in accordance with the applicable requirements of
 SDI/DOOR A250.8 and SDI/DOOR A250.6. For additional requirements refer to
 ANSI/BHMA A156.115. Drill and tap for surface-applied hardware at the
 project site. Build additional reinforcing for surface-applied hardware
 into the door at the factory. Locate hardware in accordance with the
 requirements of SDI/DOOR A250.8, as applicable. Punch door frames , with
 the exception of frames that will have weatherstripping gasketing, to
 receive a minimum of two rubber or vinyl door silencers on lock side of
 single doors and one silencer for each leaf at heads of double doors. Set
 lock strikes out to provide clearance for silencers.

2.8     FINISHES

2.8.1     Factory-Primed Finish

 All surfaces of doors and frames shall be thoroughly cleaned, chemically
 treated and factory primed with a rust inhibiting coating as specified in
 SDI/DOOR A250.8.

2.8.2     Hot-Dip Zinc-Coated and Factory-Primed Finish

 Fabricate exterior doors and frames from hot dipped zinc coated steel,
 alloyed type, that complies with ASTM A 924/A 924Mand ASTM A 653/A 653M.
 The coating weight shall meet or exceed the minimum requirements for
 coatings having 0.4 ounces per square foot, total both sides, i.e., A40.
 Repair damaged zinc-coated surfaces by the application of zinc dust paint.
 Thoroughly clean and chemically treat to insure maximum paint adhesion.
 Factory prime as specified in SDI/DOOR A250.8. .



                               SECTION 08 11 13   Page 4
Design MET Facility                                                   5490419


2.9     FABRICATION AND WORKMANSHIP

 Finished doors and frames shall be strong and rigid, neat in appearance,
 and free from defects, waves, scratches, cuts, dents, ridges, holes, warp,
 and buckle. Molded members shall be clean cut, straight, and true, with
 joints coped or mitered, well formed, and in true alignment. Dress exposed
 welded and soldered joints smooth. Design door frame sections for use with
 the wall construction indicated. Corner joints shall be well formed and in
 true alignment. Conceal fastenings where practicable.

2.9.1     Grouted Frames

 For frames to be installed in exterior walls and to be filled with mortar
 or grout, fill the stops with strips of rigid insulation to keep the grout
 out of the stops and to facilitate installation of stop-applied head and
 jamb seals.

PART 3     EXECUTION

3.1     INSTALLATION

3.1.1     Frames

 Set frames in accordance with SDI/DOOR A250.11. Plumb, align, and brace
 securely until permanent anchors are set. Anchor bottoms of frames with
 expansion bolts or powder-actuated fasteners. Build in or secure wall
 anchors to adjoining construction. Where frames require ceiling struts or
 overhead bracing, anchor frames to the struts or bracing.

3.1.2     Doors

 Hang doors in accordance with clearances specified in SDI/DOOR A250.8.
 After erection and glazing, clean and adjust hardware.

3.2     PROTECTION

 Protect doors and frames from damage. Repair damaged doors and frames
 prior to completion and acceptance of the project or replace with new, as
 directed. Wire brush rusted frames until rust is removed. Clean
 thoroughly. Apply an all-over coat of rust-inhibitive paint of the same
 type used for shop coat.

3.3     CLEANING

 Upon completion, clean exposed surfaces of doors and frames thoroughly.
 Remove mastic smears and other unsightly marks.

          -- End of Section --




                             SECTION 08 11 13   Page 5
Design MET Facility                                                   5490419



                              SECTION 08 33 23

                           OVERHEAD COILING DOORS
                                    07/07

PART 1   GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to within the text by the
 basic designation only.

          AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)

 ASCE 7-05                        (2006; Errata 2007) Minimum Design Loads
                                  for Buildings and Other Structures

          ASME INTERNATIONAL (ASME)

 ASME B29.400                     (2001; R 2008) Combination, "H" Type Mill
                                  Chains, and Sprockets

          ASTM INTERNATIONAL (ASTM)

 ASTM A 153/A 153M                (2009) Standard Specification for Zinc
                                  Coating (Hot-Dip) on Iron and Steel
                                  Hardware

 ASTM A 27/A 27M                  (2008) Standard Specification for Steel
                                  Castings, Carbon, for General Application

 ASTM A 307                       (2007b) Standard Specification for Carbon
                                  Steel Bolts and Studs, 60 000 PSI Tensile
                                  Strength

 ASTM A 36/A 36M                  (2008) Standard Specification for Carbon
                                  Structural Steel

 ASTM A 48/A 48M                  (2003; R 2008) Standard Specification for
                                  Gray Iron Castings

 ASTM A 53/A 53M                  (2007) Standard Specification for Pipe,
                                  Steel, Black and Hot-Dipped, Zinc-Coated,
                                  Welded and Seamless

 ASTM A 653/A 653M                (2009) Standard Specification for Steel
                                  Sheet, Zinc-Coated (Galvanized) or
                                  Zinc-Iron Alloy-Coated (Galvannealed) by
                                  the Hot-Dip Process

 ASTM A 780                       (2001; R 2006) Standard Practice for
                                  Repair of Damaged and Uncoated Areas of
                                  Hot-Dip Galvanized Coatings

 ASTM A 924/A 924M                (2008a) Standard Specification for General
                                  Requirements for Steel Sheet,
                                  Metallic-Coated by the Hot-Dip Process


                          SECTION 08 33 23   Page 1
Design MET Facility                                                      5490419



 ASTM D 2000                         (2008) Standard Classification System for
                                     Rubber Products in Automotive Applications

 ASTM E 330                          (2002) Structural Performance of Exterior
                                     Windows, Doors, Skylights and Curtain
                                     Walls by Uniform Static Air Pressure
                                     Difference

 ASTM F 568M                         (2007) Standard Specification for Carbon
                                     and Alloy Steel Externally Threaded Metric
                                     Fasteners

1.2     DESCRIPTION

 Overhead coiling doors to be counterbalanced doors by methods of
 manufacturer's standard mechanism with an adjustable-tension, steel helical
 torsion spring mounted around a steel shaft and contained in a spring
 barrel connected to top of curtain with barrel rings. Use grease-sealed or
 self-lubricating bearings for rotating members. Doors to be coiling type,
 with interlocking slats, complete with anchoring and door hardware, guides,
 hood, and operating mechanisms, and designed for use on openings as
 indicated.

1.3     PERFORMANCE REQUIREMENTS

1.3.1     Wind Loading

 Design and fabricate door assembly to withstand the wind loading pressure
 of at least 47.5 pounds per square foot with a maximum deflection of 1/120
 of the opening width. Provide test data showing compliance with ASTM E 330.
 Sound engineering principles may be used to interpolate or extrapolate test
 results to door sizes not specifically tested Complete assembly must meet
 or exceed the requirements of ASCE 7-05.

1.3.2     Operational Cycle Life

 All portions of the door, hardware and operating mechanism that are subject
 to movement, wear, or stress fatigue must be designed to operate through a
 minimum number of 10 cycles per day . One complete cycle of door operation
 is defined as when the door is in the closed position, moves to the fully
 open position, and returns to the closed position.

1.4     SUBMITTALS

 Submit the following in accordance with Section 01 33 00 SUBMITTAL
 PROCEDURES:

        SD-02 Shop Drawings

            Provide fabrication drawings that show complete assembly with
            hardware and framing details for the following items:

            Overhead Coiling Doors
            Counterbalancing Mechanism
            Manual Door Operators

            Bottom Bar
            Guides


                              SECTION 08 33 23   Page 2
Design MET Facility                                                   5490419


          Mounting Brackets
          Overhead Drum
          Painting

          Submit Installation Drawings in accordance with paragraph
          entitled, "Overhead Coiling Door Assemblies," of this section.

      SD-03 Product Data

          Submit manufacturer's catalog data for the following items listing
          all accessories including supports, locks and latches, and weather
          stripping.

          Overhead Coiling Doors
          Hardware
          Counterbalancing Mechanism
          Manual Door Operators



      SD-05 Design Data

          Submit equipment and performance data for the following items in
          accordance with the paragraph entitled, "Performance
          Requirements," of this section.

          Overhead Coiling Doors
          Hardware
          Counterbalancing Mechanism
          Manual Door Operators



      SD-10 Operation and Maintenance Data

          Submit Operation and Maintenance Manuals for Overhead Coiling Door
          Assemblies , including the following items:

          Materials
          Devices
          Procedures
          Manufacture's Brochures
          Parts Lists
          Cleaning

1.5   OVERHEAD COILING DOOR DETAIL SHOP DRAWINGS

 Provide installation drawings for overhead coiling door assemblies which
 show elevations of each door type, shape and thickness of materials,
 finishes, details of joints and connections, and details of guides and
 fittings, rough opening dimensions, location and description of hardware,
 anchorage locations, and counterbalancing mechanism and door operator
 details. Include a schedule showing the location of each door with the
 drawings.

 Contractor must submit 6 copies of the Operation and Maintenance Manuals 30
 calendar days prior to testing the Overhead Coiling Door Assemblies.
 Update and resubmit data for final approval no later than 30 calendar days
 prior to contract completion.


                           SECTION 08 33 23   Page 3
Design MET Facility                                                   5490419



 Provide operation and maintenance manuals which are consistent with
 manufacturer's standard brochures, schematics, printed instructions,
 general operating procedures, and safety precautions. Provide test data
 that is legible and of good quality.

1.6     WARRANTY, OPERATION AND MAINTENANCE DATA

 Submit Operation and Maintenance Manuals for Overhead Coiling Door
 Assemblies, including the following items:

         Materials
         Devices
         Manual Door Operators

         Counterbalancing Mechanism
         Painting
         Procedures
         Manufacture's Brochures
         Parts Lists

 Contractor must furnish a written guarantee that the helical spring and
 counterbalance mechanism are free from defects in material and workmanship
 and that they will remain so for not less than two years after completion
 and acceptance of the project.

 Contractor must warrant that upon notification by the Government, he will
 immediately make good any defects in material, workmanship, and door
 operation within the same time period covered by the guarantee, at no cost
 to the Government.

1.7     DELIVERY AND STORAGE

 Delivered doors to the jobsite wrapped in a protective covering with the
 brands and names clearly marked thereon. Store doors in a dry location
 that is adequately ventilated and free from dirt and dust, water, and other
 contaminants, and in a manner that permits easy access for inspection and
 handling.

PART 2     PRODUCTS

2.1     OVERHEAD COILING DOORS

2.1.1     Curtain Materials and Construction

 Provide curtain slats which are fabricated from steel sheets conforming to
 ASTM A 653/A 653M, Grade A, with the additional requirement of a minimum
 yield point of 33,000 psi. Provide sheets which are galvanized in
 accordance with ASTM A 653/A 653M and ASTM A 924/A 924M.


 Fabricate doors from interlocking cold-rolled slats, with section profiles
 as specified, designed to withstand the specified wind loading. Provide
 slats which are continuous without splices for the width of the door.

2.1.2     Non-Insulated Curtains

 Form Curtains from manufacturer's standard shapes of interlocking slats.



                                 SECTION 08 33 23   Page 4
Design MET Facility                                                      5490419


2.1.3     Curtain Bottom Bar

 Curtain bottom bars must be pairs of angles from the manufacturer's
 standard steel, stainless and aluminum extrusions not less than 2.0 by 2.0
 inches by 0.188 inch. Steel extrusions must conform to ASTM A 36/A 36M.
 Stainless steel extrusions conforming to ASTM A 666, Type 304. Aluminum
 extrusions conforming to ASTM B 221 or(ASTM B 221M). Galvanize angles and
 fasteners in accordance with ASTM A 653/A 653M and ASTM A 924/A 924M.
 Coat welds and abrasions with paint conforming to ASTM A 780.

2.1.4     Locks

 Provide end and/or wind locks of cast steel conforming to ASTM A 27/A 27M,
 Grade B; galvanized in accordance with ASTM A 653/A 653M, ASTM A 153/A 153M
 and ASTM A 924/A 924M and secured at every other curtain slat.

2.1.5     Weather Stripping

 Weather-stripping at the door-head and jamb must be 1/8-inch thick sheet
 of natural or neoprene rubber with air baffles, secured to the insides of
 hoods with galvanized-steel fasteners through continuous galvanized-steel
 pressure bars at least 5/8-inch wide and 1/8-inch thick.

 Threshold weather-stripping must be 1/8-inch thick sheet natural or
 neoprene rubber secured to the bottom bars.

 Provide weather-stripping of natural or neoprene rubber conforming to
 ASTM D 2000.

2.1.6     Locking Devices

 Slide Bolt to engage through slots in tracks for locking by padlock,
 located on both left and right jamb sides, operable from coil side.

2.1.7     Safety Interlock

 Equip power-operated doors with safety interlock switch to disengage power
 supply when door is locked.

2.1.8     Overhead Drum

 Fabricate drums from nominal 0.028-inch thick, hot-dip galvanized steel
 sheet with G90 (Z275) zinc coating, complying with ASTM A 653/A 653M.

2.2     HARDWARE

 All hardware must conform to ASTM A 153/A 153M, ASTM A 307, ASTM F 568M,
 and ASTM A 27/A 27M.

2.2.1     Guides

 Fabricate curtain jamb guides from the manufacturer's standard angles or
 channels of same material and finish as curtain slats unless otherwise
 indicated, with sufficient depth and strength to retain curtain, to allow
 curtain to operate smoothly, and to withstand loading. Slot bolt holes for
 track adjustment.




                               SECTION 08 33 23   Page 5
Design MET Facility                                                   5490419


2.2.2     Equipment Supports

 Fabricate door-operating equipment supports from the manufacturer's
 standard steel shapes and plates conforming to ASTM A 36/A 36M, galvanized
 in accordance with ASTM A 653/A 653M and ASTM A 924/A 924M. Size the
 shapes and plates in accordance with the industry standards for the size,
 weight, and type of door installation..

2.3     COUNTERBALANCING MECHANISM

 Counterbalance doors by means of manufacturer's standard mechanism with an
 adjustable-tension, steel helical torsion spring mounted around a steel
 shaft and contained in a spring barrel connected to top of curtain with
 barrel rings. Use grease-sealed or self-lubricating bearings for rotating
 members.

2.3.1     Brackets

 Provide the manufacturer's standard mounting brackets of either cast iron
 or cold-rolled steel with one located at each end of the counterbalance
 barrel conforming to ASTM A 48/A 48M.

2.3.2     Counterbalance Barrels

 Fabricate spring barrel of manufacturer's standard hot-formed,
 structural-quality, welded or seamless carbon-steel pipe, conforming to
 ASTM A 53/A 53M, of sufficient diameter and wall thickness to support
 rolled-up curtain without distortion of slats and to limit barrel
 deflection to not more than 0.03 inch per foot of span under full load.

2.3.3     Torsion Rod for Counter Balance

 Fabricate rod from the manufacturer's standard cold-rolled steel, sized to
 hold fixed spring ends and carry torsional load.

2.4     MANUAL DOOR OPERATORS

2.4.1     Manual Chain-Hoist Door Operators

 Provide door operators which consist of an endless steel hand chain,
 chain-pocket wheel, guard, and a geared reduction unit of at least a 3 to 1
 ratio with a maximum 25 lbf required pull for operation must not exceed 35
 pounds.

 Provide chain hoists to have a self-locking mechanism allowing the curtain
 to be stopped at any point in its upward or downward travel and to remain
 in that position until moved to the fully open or closed position. Provide
 hand chains of cadmium-plated alloy steel conforming to ASME B29.400.
 Yield point of the chain must be at least three times the required
 hand-chain pull.

 Provide chain sprocket wheels of cast iron conforming to ASTM A 48/A 48M.

2.5     SURFACE FINISHING

 Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal
 Products" for recommendations for applying and designating finishes.
 Noticeable variations in the same metal component are not acceptable.
 Variations in appearance of adjoining components are acceptable if they are


                                SECTION 08 33 23   Page 6
Design MET Facility                                                      5490419


 within the range of approved samples and are assembled or installed to
 minimize contrast.

PART 3     EXECUTION

3.1     GENERAL

 Install overhead coiling door assembly, anchors and inserts for guides,
 brackets, motors, switches, hardware, and other accessories in accordance
 with approved detail drawings and manufacturer's written instructions.
 Upon completion of installation, doors must be free from all distortion.

 Install overhead coiling doors, motors, hoods, and operators at the
 mounting locations as indicated for each door in the contract documents and
 as required by the manufacturer.

 Install overhead coiling doors, switches, and controls along accessible
 routes in compliance with regulatory requirements for accessibility and as
 required by the manufacturer.

3.2     FIELD PAINTED FINISH

 Steel doors and frames which are to be field painted must accordance with
 Section 09 90 00 - PAINTS AND COATINGS and manufacturer's written
 instructions. Protect weather stripping from paint. Finishes must be free
 of scratches or other blemishes.

3.3     ACCEPTANCE PROVISIONS

 After installation, adjust hardware and moving parts. Lubricate bearings
 and sliding parts as recommended by manufacturer to provide smooth
 operating functions for ease movement, free of warping, twisting, or
 distortion of the door assembly.

 Adjust seals to provide weather-tight fit around entire perimeter.

 Engage a factory-authorized service representative to perform startup
 service and checks according to manufacturer's written instructions.

 Test the door opening and closing operation when activated by controls or
 alarm-connected fire-release system. Adjust controls and safeties. Replace
 damaged and malfunctioning controls and equipment. Reset door-closing
 mechanism after successful test.

 Test and make final adjustment of new doors at no additional cost to the
 Government.

3.3.1     Maintenance and Adjustment

 Not more than 90 calendar days after completion and acceptance of the
 project, the Contractor must examine, lubricate, test, and re-adjust doors
 as required for proper operation.

3.3.2     CLEANING




                                SECTION 08 33 23   Page 7
Design MET Facility                                                   5490419


 Clean stainless steel doors in accordance with manufacturer's approved
 instructions.

        -- End of Section --




                           SECTION 08 33 23   Page 8
Design MET Facility                                                           5490419




                                     SECTION 08 71 00

                                      DOOR HARDWARE
                                          08/08

PART 1     GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to in the text by the
 basic designation only.

             BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)

 BHMA A156.2                            (2003) Bored and Preassembled Locks and
                                        Latches

 BHMA A156.7                            (2003) Template Hinge Dimensions

             NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

 NFPA 101                               (2009; Amd 1 & 2 2009) Life Safety Code

             UNDERWRITERS LABORATORIES (UL)

 UL Bld Mat Dir                         (2009) Building Materials Directory

1.2   SUBMITTALS

 Submit the following in accordance with Section 01 33 00 SUBMITTAL
 PROCEDURES.

         SD-02 Shop Drawings

             Hardware schedule

         SD-03 Product Data

             Hardware items

         SD-08 Manufacturer's Instructions

             Installation

         SD-10 Operation and Maintenance Data

             Hardware Schedule items, Data Package 1

             Submit data package in accordance with Section 01 78 23 OPERATION
             AND MAINTENANCE DATA.

         SD-11 Closeout Submittals

         Key Bitting




                               SECTION 08 71 00   Page 1
Design MET Facility                                                             5490419


1.3     HARDWARE SCHEDULE

 Prepare and submit hardware schedule in the following form:

                          Reference        Mfr.                 UL Mark
                          Publi-           Name       Key       (If fire   BHMA
  Hard-                   cation           and        Con-      rated      Finish
  ware       Quan-        Type             Catalog    trol      and        Designa-
  Item       tity Size    No.     Finish   No.        Symbols   listed)    tion
  -----      ----- ----   ------ ------    -------    -------   --------   ---------

1.4     KEY BITTING CHART REQUIREMENTS

 Submit key bitting charts to the Contracting Officer prior to completion of
 the work. Include:

        a.    Complete listing of all keys (AA1, AA2, etc.).

        b.    Complete listing of all key cuts (AA1-123456, AA2-123458).

        c.    Tabulation showing which key fits which door.

        d.    Copy of floor plan showing doors and door numbers.

        e.    Listing of 20 percent more key cuts than are presently required in
              each master system.

1.5     QUALITY ASSURANCE

1.5.1     Hardware Manufacturers and Modifications

 A.   The following specified manufacturers and products are intended to
      establish expected quality, design, function, and finish to be provided
      under this section of the specifications.

 B.   All Other materials, not specifically described, but required for a
      complete and proper finish hardware installation, are to be selected by
      the Door Hardware Contractor, subject to the approval of the Government.

1.5.1     Key Shop Drawings Coordination Meeting

 Prior to the submission of the key shop drawing, the
 Contracting Officer, Contractor, Door Hardware subcontractor, using
 Activity and Base Locksmith shall meet to discuss key requirements for the
 facility.

1.6     DELIVERY, STORAGE, AND HANDLING

 Deliver hardware in original individual containers, complete with necessary
 appurtenances including fasteners and instructions. Mark each individual
 container with item number as shown in hardware schedule. Deliver
 permanent keys and removable cores to the Contracting Officer, either
 directly or by certified mail. Deliver construction master keys with the
 locks.




                                SECTION 08 71 00     Page 2
Design MET Facility                                                      5490419


PART 2     PRODUCTS

2.1     TEMPLATE HARDWARE

 Provide hardware to be applied to metal or to prefinished doors
 manufactured to template. Promptly furnish template information or
 templates to door and frame manufacturers. Conform to BHMA A156.7 for
 template hinges. Coordinate hardware items to prevent interference with
 other hardware.

 Door Hardware: All applicable door hardware shall have been satisfactorily
 tested for and meet all requirements for positive pressure door opening in
 accordance with IBC 2003.

 Hollow Metal Doors: Provide acceptable positive pressure sealing for all
 hollow metal labeled doors. Sealing mechanism shall not interfere with
 normal door operation or function and shall be vandal-resistant.

2.2     HARDWARE FOR FIRE DOORS AND EXIT DOORS

 Provide all hardware necessary to meet the requirements NFPA 101 for exit
 doors, as well as to other requirements indicated, even if such hardware is
 not specifically mentioned under paragraph entitled "Hardware Schedule."
 Provide the label of Underwriters Laboratories, Inc. for such hardware
 listed in UL Bld Mat Dir or labeled and listed by another testing
 laboratory acceptable to the Contracting Officer.

2.3     HARDWARE ITEMS

 Clearly and permanently mark with the manufacturer's name or trademark,
 hinges, pivots, locks, latches, exit devices, bolts and closers where the
 identifying mark will be visible after the item is installed. For closers
 with covers, the name or trademark may be beneath the cover.

2.3.1     Hinges

 A.    All hinges and pivots, including single and double acting types,
       pocket hinges, electric hinges and continuous aluminum geared hinges to
       be of one manufacturer for continuity and consideration of warranty.

 B.    Unless otherwise specified, provide five-knuckle, heavy-duty, button
       tip, full mortise template type hinges with non-rising loose pins.
       Provide non-removable pins for exterior doors, outswinging doors, and
       secured areas as called for in this specification.

 C.    Exterior Door Hinges: Provide out-swinging door hinges of Wrought
       steel, polished and plated to US26D with non-removable pins or
       security studs as called for in this specification. Furnish three (3)
       hinges up to 90 inches high and one (1) additional hinge for every 18
       inches or fraction thereof.

 D.    Interior Door Hinges: Wrought steel, polished and plated to US26D
       unless specified otherwise. Furnish three (3) hinges up to 90 inches
       high and one (1) additional hinge for every 18 inches or fraction
       thereof.

      Door Thickness     Door Width     Hinge Height
      1-3/4 "             to 36 "           4 ½ "
      1-3/4 "          over 36"to 48"       5 " (0.180)


                              SECTION 08 71 00   Page 3
Design MET Facility                                                        5490419



 E.    Where required to clear trim or permit doors to swing 180 degrees,
       furnish hinges of sufficient throw. Provide heavy weight hinges on all
       doors over 36 inches in width. At labeled doors, provide ball
       bearing-type hinges. For all doors equipped with closers, provide ball
       bearing-type hinges.

 F.    The following are of acceptable products by Bommer Industries.:

      A8112     BB5000
      A5112     BB5002

2.3.2     Locks and Latches

2.3.2.1        Mortise Locks and Latches

 MORTISE LOCKSETS, LATCHSETS AND DEADLOCKS

 A.     To the maximum extent possible, locksets, latchsets, and deadlocks
        shall be the products of a single manufacturer. Lock fronts for
        double-acting doors shall be rounded. Strikes for wood frames and
        pair of wood doors shall be furnished with wrought boxes. Lock and
        latch set trim (handles, roses and escutcheons) shall be of a simple
        design in accordance with manufacturer's standard practice.

 B.     Handles, pulls, latches, locks, and other operating devices on
        accessible doors shall have a shape that is easy to grasp with one hand
        and does not require tight grasping, tight pinching, or twisting of the
        wrist to operate. Lever-operated mechanisms, push-type mechanisms, and
        U-shaped handles are acceptable designs. As a tactile warning to blind
        persons, provide levers with knurled surface texture on the access side
        of door, where openings are identified on the Door Schedule or detailed
        in the Hardware Types.

 C.     Locksets with latch bolts, regardless of trim, shall be listed by
        Underwriters Laboratories for "A" and lesser labeled door and conform
        to the standards of U.L. 10c and U.B.C. 7-2 (1997) positive pressure
        testing, single or pair. Lock trim, lever, sectional, type shall be
        through-bolted to assure correct alignment and proper operation.

 D.     Lock Mechanisms shall be metal throughout with all functions available
        in one size case; full ¾-inch throw anti-friction latch bolt; one-inch
        dead bolt with hardened-steel insert; and available for a minimum door
        thickness of 1-3/8 inches. Internal parts shall be heavy-gauge steel,
        zinc dichromate plated, and nickel-steel hubs.

 E.     Locksets shall conform to Federal Specification, type 86 and 86m and be
        certified as meeting ANSI A156.2 Grade I requirements. BHMA Series
        1000, operational and security grade 1.

          1.     Lock Backset shall be 2-3/4.
          2.     Cases shall be minimum .090 inches thick, steel, zincdichcomate
                 plates or castrol dipped; closed on all sides.
          3.     Strikes shall be wrought-box type for locksets, latchsets, and
                 deadlocks, with lip extensions sufficient to protect adjacent
                 trim.
          4.     Reinforcing Units shall be furnished for locksets, latchsets,
                 and deadbolts in steel doors.
          5.     Accessories shall be provided to match cylinders and dummy trim


                                SECTION 08 71 00   Page 4
Design MET Facility                                                        5490419


                 as scheduled.
          6.     Locksets shall have a ten (10) year warranty.

2.3.2.2        Bored Locks and Latches

 BHMA A156.2, Series 4000, Grade 1.

2.3.3     Exit Devices

 A.     All exit devices and trim, including electrified items, to be of one
        manufacturer specified and in the hardware sets for continuity of
        design and consideration of warranty. Electrified devices and trim to
        be the same series and design as mechanical devices and trim.

 B.     Exit Devices to be "UL" listed for life safety. All exit devices for
        labeled doors shall have "UL" label for "Fire Exit Hardware". All
        devices mounted on labeled wood doors shall be through-bolted or per
        the manufacturer's listing requirements. All devices to conform to NFPA
        80 and NFPA 101 requirements.

          1.    Labeled Exit Devices/Positive Pressure: All exit devices for
                labeled doors shall be have applicable factory-applied UL stamp
                and shall comply with and shall have been satisfactorily tested
                for compliance with IBC-7-12-1997 or UL10C requirements for
                positive pressure.

 C.     All exit devices to be touch-pad type heavy duty with one piece
        removable covers.

 D.     All devices shall have deadlocking latchbolts with ¾" throw, where
        applicable.

 E.     All trim to be through-bolted to the lock stile case. Center case shall
        be through-bolted to outside trim, and hinge end shall be
        through-bolted.
        Lever design to be the same as specified with locksets.

 F.     Lever trim shall be vandal resistant free wheeling, clutch type, or
        break away to deter lever abuse.

 G.     All metal end caps to be standard with all exit devices.

 H      Unless specified otherwise, all vertical rod devices on metal doors
        shall be concealed and have "latch retraction" hold back on top latch.
        Bottom latch shall have adjustable projection.

 I.     All devices shall be UL approved for all types and functions indicated
        in the Hardware Schedule.

 J.     Devices shall have published ten year warranty.

 K.     Finish: 630 (US32D)

 L.     Key Removable Mullion: Compatible with exit device and keyed to door.
        Use labeled mullions in labeled doors. Provide a mullion stabilizer on
        exterior doors.

 M.     When dummy exit push bars are specified, provide dummy push bars to
        match design and finish of adjacent exit device, and provide pulls on


                                SECTION 08 71 00   Page 5
Design MET Facility                                                         5490419


        pull side of door to match those of adjacent exit device.

 N.     The following are acceptable Products by Dorma Architectural Hardware.
             9300 x PRT03      Type 1 - F03 Grade 1


2.3.4      Cylinders and Cores

 CYLINDERS AND KEYING

 A      Furnish all locks and cylinders keyed to existing grandmaster key
        system as established by Government.

 B.     Supply each cylinder or lock with 3 change keys. 6 master keys to be
        supplied for each master key group. Supply six grandmaster keys to be
        supplied for the project.

 C.     Tag all cylinders and keys to indicate their intended location and to
        enable the Owner, with, a minimum of effort, to establish his key
        control system. Organize and install tagged keys in key cabinet
        according to Government's requirements.

 D.     Furnish all locks and cylinders construction master keyed. The use of
        permanent keying shall block out temporary construction keying and the
        completion of the project.

      1.   Supply 10 construction master keys for the project.
      2    Disable construction keying in the presence of the Government.

 E.     Stamp all change keys with appropriate keyset symbol and DO NOT
        DUPLICATE, but do not stamp with key section or bitting number.

 F.     Furnish 1 each key cabinet similar to model AWC as manufactured by
        Telkee with a Capacity of 1 hook per cylinder installed, plus an
        additional 50 percent expansion. Organize, label, tag, and install all
        tagged keys in the cabinet prior to occupancy. Organize amid install
        keys in an order and sequence acceptable to the Government.

 G.     All keying will be coordinated with the Government as required.
        Supplier shall meet with Government to finalize keying requirements and
        to obtain final instructions in writing. The hardware supplier shall
        coordinate the deactivation of the construction keying with the
        Government.
          1.   Coordinate keying with the Government so that only one keyway is
               used, and each keyway is exhausted prior to using another
               keyway.

2.3.5      Lock Trim

 Cast, forged, or heavy wrought construction and commercial plain design.

 MORTISE LOCK TRIM

 A.     Lock trim shall be cast or forged solid metal construction lever of
        commercial plain design and shall meet the test requirement of BHMA
        A156.2 or BHMA A156.13.

 B.     Levers are to be cast material; hollow or filled tubes are not
        acceptable.


                                 SECTION 08 71 00   Page 6
Design MET Facility                                                        5490419



 C.     All hardware functions to be exactly as listed in the individual
        hardware sets with no exceptions.

 D.     The following are acceptable products by Dorma Architectural Hardware :
        LRB Design
          F04   ML9050
          F05   ML9070
          F07   ML9080
          F20   ML9953

          E2171     DB863L     626

 E.     Finish:     630

2.3.5.1        Lever Handles

 Provide lever handles in lieu of knobs . Conform to the minimum
 requirements of BHMA A156.13 for mortise locks of lever handles for exit
 devices. Provide lever handle locks with a breakaway feature (such as a
 weakened spindle or a shear key) to prevent irreparable damage to the lock
 when force in excess of that specified in BHMA A156.13 is applied to the
 lever handle. Provide lever handles return to within 1/2 inch of the door
 face.

2.3.6     Closers

 SURFACE MOUNTED DOOR CLOSERS

 A.     All closers for this project to be the product of a single manufacturer
        for continuity of design and consideration of warranty. Warranty shall
        be a minimum advertised 25 years and tested by independent testing
        laboratory for 10,000,000 cycles.

 B.     All closers to be heavy duty, non-handed, surface mounted, hydraulic
        type, minimum efficiency of 60%, with a one piece high strength cast
        alloy body and steel piston. Full rack and pinion constructed of heavy
        steel.

          1.     Labeled Closers/Positive Pressure: All closers for labeled doors
                 shall be have applicable factory-applied UL stamp and shall
                 comply with and shall have been satisfactorily tested for
                 compliance with IBC-7-12-1997 or UL-lOC requirements for
                 positive pressure.

 C.     Size all closers in accordance with the manufacturer's recommendations
        at the factory for intended application, and sized to meet ADA opening
        force and requirement&

 D.     All closers to have adjustable spring power and separate tamper
        resistant, non-critical regulating screw valves for closing speed,
        latching speed, back check control and back check positioning as a
        standard feature.

 E.     All closer covers to be rectangular, full cover type of non-corrosive,
        finished to match closer and adjacent hardware.

 F.     Supply appropriate arm assembly for each closer so that closer body and
        arm are mounted on non-public side of door opening and on the interior


                                SECTION 08 71 00   Page 7
Design MET Facility                                                         5490419


        side of exterior openings, except where required otherwise in the
        hardware sets.

          1.    All parallel arm mounted closers to be factory indexed to ensure
                proper installation.
          2.    Furnish heavy duty cold forged parallel arms for all parallel arm
                mounted closers.

 G.     Provide closers with special application and, heavy-duty arms as
        specified in the hardware sets or as otherwise called for to ensure a
        proper-operating, long-lasting opening.

 H.     The base of the closers shall be of a dimension so the base does not
        extend past the edges of the top rail of the door, the base of the
        closers is not visible through the glass from the exterior, and the
        mounting screws of the closer do not interfere with the glass. Drop
        plates for mounting the closer to narrower than required top door rails
        are not acceptable. Coordinate with the aluminum, wood, or steel door
        descriptions in applicable individual specifications.

 I.     Door Opening Force: Maximum force for pushing or pulling open a door
        shall comply with this paragraph. For hinged doors the force shall be
        applied perpendicular to the door at the door opener or 30 inches from
        the hinged side whichever is farther from the hinge.

          1     Exterior hinged doors shall not exceed 8.5 lbf. Slight increases
                in opening force shall be allowed where 8.5 lbf. is insufficient
                to compensate for air pressure differentials.
          2.    Interior hinged doors shall not exceed 5.0 lbf.
          3.    Fire doors shall be adjusted to meet the minimum opening force
                permitted by governing fire safety standards.

 J.     Except for classrooms, all labeled doors shall be equipped with the
        proper closer. Except for classroom doors, labeled doors that appear in
        the hardware sets without closers shall be brought to the Contracting
        Officers attention for clarification.

 K.     The following is a list of acceptable Products: Dorma Architectural
        Hardware

               C02011-PT1-PT4C/D/H        8916 - AF89 x SNB
               C02021-PT1-PT4C/D/G/H      8916 - DS x SNB
               C02011-PT1-PT4C/D/G/H      8916 - S-IS x SNB

 L.     Closer Finish: 689 Alum. with corrosion resistant primer SRI.

2.3.6.1        Identification Marking

 Engrave each closer with manufacturer's name or trademark, date of
 manufacture, and manufacturer's size designation located to be visible
 after installation.

2.3.7     Door Protection Plates

 PUSH PLATES, DOOR PULLS, AND KICKPLATES

 A.     The following are acceptable Products by Burns Manufacturing.
             Push Plate 4 x l6   J301   54
             Pull Plate 4 x16    J405   5425B


                                SECTION 08 71 00   Page 8
Design MET Facility                                                        5490419



 B.     The following are acceptable Products by Burns Manufacturing.
        Kick plates to be of 16 gauge (0.050) inches thick stainless steel
        (US32D). For doors    with louvers or narrow bottom rails, kickplate
        height to be 1 inch less than the dimension shown from the bottom of
        the door to the bottom of the louver.

          1.     Kick Plates: 8" x 2" LDW.        BHMA # J102.
          2.     Mop Plates: 4" x 2" LDW.        BHMA # J103.
          3.     Armor Plates 16" x 2" LDW        BHMA # J101.

 C.     Where required, armor plates, edge guards and other protective hardware
        are to be supplied in sizes as scheduled in the hardware sets.

 D.     Finish: 630 (US32D).

2.3.7.1        Sizes of Kick Plates

  2 inch less than door width for single doors; one inch less than door
 width for pairs of doors. Provide 8 inch kick plates for flush doors .

2.3.8     Door Stops and Silencers

 DOOR STOPS AND HOLDERS

 A.     Door stops are to be furnished for every door leaf every door to have
        either a floor, wall, or an overhead stop. Special arms on door closers
        do not constitute door stops.

          1.    Wall Stops: Wall stops are the preferred and shall be used where
                possible.
          2.    Floor Stops: Floor stops may be used where a wall, stop is not
                feasible, provided the floor stop is not in the open, does not
                interfere with activities, or does not pose a safety threat.
          3.    Overhead Stop: Use overhead stops where wall stops and floor
                stops are not feasible.
          4.    Where floor, wall, and overhead stops are not feasible or will
                not work, use closers with a spring cushion on the stop arm and a
                back check.

 B.     Place door stops in such a position that they permit maximum door
        swing, but do not present a hazard or obstruction. Furnish floor
        strikes for floor holders of proper height to engage holders of doors.

 C.     Where overhead stops and holders are specified, or otherwise required
        for proper door operation, they are to be heavy duty and of extruded
        brass or bronze with no plastic parts.

 D.     Finish: Wall or Floor mounted stops shall be furnished in a 626 (US26D)
        finish. Where available 630 (32D) may be used.

 E.     The following are acceptable Products by Burns Manufacturing.

          Floor Stop     L12161     520
          Wall Stop      L12101     565

 F.     The following are acceptable Products by Dorma Architectural Hardware.
          1.   OVERHEAD STOPS/HOLDERS:
                Heavy Duty Stop      C02541   900S Series


                                  SECTION 08 71 00   Page 9
Design MET Facility                                                      5490419



 DOOR SILENCERS

 A.     Provide 2 at each pair of doors and 3 for each single door. Acceptable
        silencers are by Burns Manufacturing.
                Door Silencers   L03011   500

 FLUSH BOLTS AND COORDINATORS :

 A.     Provide Flush bolts with Dust Proof Strikes were required as scheduled
        in the hardware sets. The following are acceptable Products by Burns
        Manufacturing:

            Manual Flush Bolt   L14081   590 - 12"
            Dust Proof Strike   L14021   545

 B.     Where required for specific fire-rated egress applications furnish
        appropriate Automatic Flush Bolts for wood door and hollow metal doors.

2.3.9     Thresholds

 THRESHOLDS AND GASKETING

 A.     All thresholds must be in accordance with the requirements of the ADA
        and ANSI Al 17.1. Provide thresholds with machine screws and lead
        anchors. Supply all necessary anchoring devices for weatherstripping
        and sound seals.

 B.      The following is a list of acceptable Products by Pemko Manufacuring:
          Threshold (Flat Saddle)   J32130   l7lA
          Door Sweep   R3A545   3452ANB
          Weatherstrip   R3C265   315CR
          (Furnish Length as Required (LAR))

 C.      Furnish as listed above or as specified in the hardware sets.

2.3.10     Special Tools

 Provide special tools, such as spanner and socket wrenches and dogging
 keys, required to service and adjust hardware items.

2.4     FASTENERS

 Provide fasteners of proper type, quality, size, quantity, and finish with
 hardware. Provide stainless steel or nonferrous metal fasteners that are
 exposed to weather. Provide fasteners of type necessary to accomplish a
 permanent installation.

PART 3     EXECUTION

3.1     INSTALLATION

 Install hardware in accordance with manufacturers' printed installation
 instructions. Fasten hardware to wood surfaces with full-threaded wood
 screws or sheet metal screws. Provide machine screws set in expansion
 shields for fastening hardware to solid concrete and masonry surfaces.
 Provide toggle bolts where required for fastening to hollow core
 construction. Provide through bolts where necessary for satisfactory
 installation.


                            SECTION 08 71 00   Page 10
Design MET Facility                                                     5490419



3.1.1     Weather Stripping Installation

 Handle and install weather stripping to prevent damage. Provide full
 contact, weather-tight seals. Operate doors without binding.

3.1.1.1     Stop-Applied Weather Stripping

 Fasten in place with color-matched sheet metal screws not more than   9 inch
 on center after doors and frames have been finish painted.

3.1.2     Threshold Installation

 Extend thresholds the full width of the opening and notch end for jamb
 stops. Set thresholds in a full bed of sealant and anchor to floor with
 cadmium-plated, countersunk, steel screws in expansion sleeves.

3.2     EXIT DOORS

 NFPA 101 for exit doors .

3.3     FIELD QUALITY CONTROL

 After installation, protect hardware from paint, stains, blemishes, and
 other damage until acceptance of work. Submit notice of testing 15 days
 before scheduled, so that testing can be witnessed by the Contracting
 Officer. Adjust hinges, locks, latches, bolts, holders, closers, and other
 items to operate properly. Demonstrate that permanent keys operate
 respective locks, and give keys to the Contracting Officer. Correct,
 repair, and finish, as directed, errors in cutting and fitting and damage
 to adjoining work.

3.4     HARDWARE SETS

  MRAP EGRESS TRAINER, LYMAN ROAD




                            SECTION 08 71 00   Page 11
Design MET Facility                                                  5490419


 HW-1
 (Doors 100, 105, 106)
 3 ea.     Hinges                A5111 NRP                    630
 1 ea.     Rim Exit Device       Type 1 Function 08 Grade 1   630
 1 ea.     Closer                C02021 w/stop arm            689
 1 ea.     Kickplate             J102 2" LDW x 10"            630
 1 ea.     Threshold             J32130                       AL
 1 ea.     Weatherstripping      R3Y165                       AL
 1 ea.     Door Sweep            R3Y435                       AL

 HW-2
 (Doors 102, 103, 104)
 Hardware and locking mechanism by door manufacturer

 HW-3
 (Door 101)
 3 ea.      Hinges               A8112                        652
 1 ea.      Lockset              F109 Grade 1                 626
 1 ea.      Wallstop             L22102                       630
 3 ea.      Silencers            L03011                       Grey



 MRAP EGRESS TRAINER, MCAS

 HW-1
 (Doors 100, 102)
 3 ea.     Hinges                A5111 NRP                    630
 1 ea.     Rim Exit Device       Type 1 Function 08 Grade 1   630
 1 ea.     Closer                C02021 w/stop arm            689
 1 ea.     Kickplate             J102 2" LDW x 10"            630
 1 ea.     Threshold             J32130                       AL
 1 ea.     Weatherstripping      R3Y165                       AL
 1 ea.     Door Sweep            R3Y435                       AL


 HW-2
 (Doors 101)
 Hardware and locking mechanism by door manufacturer

 HW-3
 (Door 103, 104)
 3 ea.     Hinges                A5111 NRP                    630
 1 ea.     Push Plate            J301                         630
 1 ea.     Pull Plate            J405                         630
 1 ea.     Closer                C02021 w/stop arm            689
 1 ea.     Kickplate             J102 2" LDW x 10"            630
 3 ea.     Silencers             L03011                       Grey

 HW-4
 3 ea.      Hinges               A8112                        652
 1 ea.      Lockset              F76 Grade 1                  626
 1 ea.      Wallstop             L22102                       630
 3 ea.      Silencers            L03011                       Grey


         -- End of Section --




                           SECTION 08 71 00    Page 12
Design MET Facility                                                        5490419



                                SECTION 09 90 00

                               PAINTS AND COATINGS
                                      08/10

PART 1     GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to within the text by the
 basic designation only.

            AMERICAN CONFERENCE OF GOVERNMENTAL INDUSTRIAL HYGIENISTS (ACGIH)

 ACGIH 0100Doc                      (2005) Documentation of the Threshold
                                    Limit Values and Biological Exposure
                                    Indices

            ASTM INTERNATIONAL (ASTM)

 ASTM D 2092                        (1995; R 2001e1) Standard Guide for
                                    Preparation of Zinc-Coated (Galvanized)
                                    Steel Surfaces for Painting

 ASTM D 235                         (2002; R 2007) Mineral Spirits (Petroleum
                                    Spirits) (Hydrocarbon Dry Cleaning Solvent)

 ASTM D 4214                        (2007) Standard Test Method for Evaluating
                                    the Degree of Chalking of Exterior Paint
                                    Films

 ASTM D 4263                        (1983; R 2005) Indicating Moisture in
                                    Concrete by the Plastic Sheet Method

 ASTM D 523                         (2008) Standard Test Method for Specular
                                    Gloss

 ASTM F 1869                        (2009) Measuring Moisture Vapor Emission
                                    Rate of Concrete Subfloor Using Anhydrous
                                    Calcium Chloride

            MASTER PAINTERS INSTITUTE (MPI)

 MPI 139                            (Oct 2009) Interior High Performance
                                    Latex, MPI Gloss Level 3

 MPI 27                             (Oct 2009) Exterior / Interior Alkyd Floor
                                    Enamel, Gloss

 MPI 50                             (Oct 2009) Interior Latex Primer Sealer

 MPI 52                             (Oct 2009) Interior Latex, MPI Gloss Level
                                    3

 MPI 79                             (Oct 2009) Alkyd Anti-Corrosive Metal
                                    Primer



                            SECTION 09 90 00   Page 1
Design MET Facility                                                     5490419


 MPI 95                           (Oct 2009) Quick Drying Primer for Aluminum

          THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)

 SSPC PA 1                        (2000; E 2004) Shop, Field, and
                                  Maintenance Painting of Steel

 SSPC PA Guide 3                  (1982; E 1995) A Guide to Safety in Paint
                                  Application

 SSPC SP 1                        (1982; E 2004) Solvent Cleaning

 SSPC SP 10                       (2007) Near-White Blast Cleaning

 SSPC SP 12                       (2002) Surface Preparation and Cleaning of
                                  Metals by Waterjetting Prior to Recoating

 SSPC SP 2                        (1982; E 2004) Hand Tool Cleaning

 SSPC SP 3                        (1982; E 2004) Power Tool Cleaning

 SSPC SP 6                        (2007) Commercial Blast Cleaning

 SSPC SP 7                        (2007) Brush-Off Blast Cleaning

 SSPC VIS 1                       (2002) Guide and Reference Photographs for
                                  Steel Surfaces Prepared by Dry Abrasive
                                  Blast Cleaning

 SSPC VIS 3                       (2004) Guide and Reference Photographs for
                                  Steel Surfaces Prepared by Hand and Power
                                  Tool Cleaning

 SSPC VIS 4/NACE VIS 7            (1998; E 2000; E 2004) Guide and Reference
                                  Photographs for Steel Surfaces Prepared by
                                  Waterjetting

          U.S. ARMY CORPS OF ENGINEERS (USACE)

 EM 385-1-1                       (2008) Safety and Health Requirements
                                  Manual

          U.S. GENERAL SERVICES ADMINISTRATION (GSA)

 FED-STD-313                      (Rev D; Am 1) Material Safety Data,
                                  Transportation Data and Disposal Data for
                                  Hazardous Materials Furnished to
                                  Government Activities

          U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

 29 CFR 1910.1000                 Air Contaminants

1.2   SUBMITTALS

 The following shall be submitted in accordance with Section 01 33 00
 SUBMITTAL PROCEDURES:

 The current MPI, "Approved Product List" which lists paint by brand, label,


                          SECTION 09 90 00   Page 2
Design MET Facility                                                    5490419


 product name and product code as of the date of contract award, will be
 used to determine compliance with the submittal requirements of this
 specification. The Contractor may choose to use a subsequent MPI "Approved
 Product List", however, only one list may be used for the entire contract
 and each coating system is to be from a single manufacturer. All coats on
 a particular substrate must be from a single manufacturer. No variation
 from the MPI Approved Products List is acceptable.

 Samples of specified materials may be taken and tested for compliance with
 specification requirements.

      SD-02 Shop Drawings

      SD-03 Product Data

          Coating

          Manufacturer's Technical Data Sheets

      SD-04 Samples

          Color

          Submit manufacturer's samples of paint colors.   Cross reference
          color samples to color scheme as indicated.

      SD-07 Certificates

          Applicator's qualifications

      SD-08 Manufacturer's Instructions

          Application instructions

          Mixing

          Detailed mixing instructions, minimum and maximum application
          temperature and humidity, potlife, and curing and drying times
          between coats.

          Manufacturer's Material Safety Data Sheets

          Submit manufacturer's Material Safety Data Sheets for coatings,
          solvents, and other potentially hazardous materials, as defined in
          FED-STD-313.

      SD-10 Operation and Maintenance Data

          Coatings:

          Preprinted cleaning and maintenance instructions for all coating
          systems shall be provided.

      SD-11 Closeout Submittals

          Materials (LEED)




                             SECTION 09 90 00   Page 3
Design MET Facility                                                      5490419


1.3     APPLICATOR'S QUALIFICATIONS

1.3.1     Contractor Qualification

 Submit the name, address, telephone number, FAX number, and e-mail address
 of the contractor that will be performing all surface preparation and
 coating application. Submit evidence that key personnel have successfully
 performed surface preparation and application of coatings on military
 installations on a minimum of three similar projects within the past three
 years. List information by individual and include the following:

  a.    Name of individual and proposed position for this work.

  b.    Information about each previous assignment including:

        Position or responsibility

        Employer (if other than the Contractor)

        Name of facility owner

        Mailing address, telephone number, and telex number (if non-US) of
             facility owner

        Name of individual in facility owner's organization who can be
             contacted as a reference

        Location, size and description of structure

        Dates work was carried out

        Description of work carried out on structure


1.4     REGULATORY REQUIREMENTS

1.4.1     Lead Content

 Do not use coatings having a lead content over 0.06 percent by weight of
 nonvolatile content.

1.4.2     Chromate Content

 Do not use coatings containing zinc-chromate or strontium-chromate.

1.4.3     Asbestos Content

 Materials shall not contain asbestos.

1.4.4     Mercury Content

 Materials shall not contain mercury or mercury compounds.

1.4.5     Silica

 Abrasive blast media shall not contain free crystalline silica.




                             SECTION 09 90 00   Page 4
Design MET Facility                                                      5490419


1.4.6     Human Carcinogens

 Materials shall not contain ACGIH 0100Doc and ACGIH 0100Doc confirmed human
 carcinogens (A1) or suspected human carcinogens (A2).

1.5     PACKAGING, LABELING, AND STORAGE

 Paints shall be in sealed containers that legibly show the contract
 specification number, designation name, formula or specification number,
 batch number, color, quantity, date of manufacture, manufacturer's
 formulation number, manufacturer's directions including any warnings and
 special precautions, and name and address of manufacturer. Pigmented
 paints shall be furnished in containers not larger than 5 gallons. Paints
 and thinners shall be stored in accordance with the manufacturer's written
 directions, and as a minimum, stored off the ground, under cover, with
 sufficient ventilation to prevent the buildup of flammable vapors, and at
 temperatures between 40 to 95 degrees F.

1.6     SAFETY AND HEALTH

 Apply coating materials using safety methods and equipment in accordance
 with the following:

 Work shall comply with applicable Federal, State, and local laws and
 regulations, and with the ACCIDENT PREVENTION PLAN, including the Activity
 Hazard Analysis as specified in Section 01 35 29 SAFETY AND OCCUPATIONAL
 HEALTH REQUIREMENTS and in Appendix A of EM 385-1-1. The Activity Hazard
 Analysis shall include analyses of the potential impact of painting
 operations on painting personnel and on others involved in and adjacent to
 the work zone.

1.6.1     Safety Methods Used During Coating Application

 Comply with the requirements of SSPC PA Guide 3.

1.6.2     Toxic Materials

 To protect personnel from overexposure to toxic materials, conform to the
 most stringent guidance of:

  a.    The applicable manufacturer's Material Safety Data Sheets (MSDS) or
        local regulation.

  b.    29 CFR 1910.1000.

  c.    ACGIH 0100Doc, threshold limit values.



1.7     ENVIRONMENTAL CONDITIONS

 Comply, at minimum, with manufacturer recommendations for space ventilation
 during and after installation.

1.7.1     Coatings

 Do not apply coating when air or substrate conditions are:

  a.    Less than 5 degrees F above dew point;


                              SECTION 09 90 00   Page 5
Design MET Facility                                                      5490419



  b.    Below 50 degrees F or over 95 degrees F, unless specifically
        pre-approved by the Contracting Officer and the product manufacturer.
        Under no circumstances shall application conditions exceed manufacturer
        recommendations.

1.8     COLOR SELECTION

 Colors of finish coats shall be as indicated or specified. Where not
 indicated or specified, colors shall be selected by the Contracting
 Officer. Manufacturers' names and color identification are used for the
 purpose of color identification only. Named products are acceptable for
 use only if they conform to specified requirements. Products of other
 manufacturers are acceptable if the colors approximate colors indicated and
 the product conforms to specified requirements.

 Tint each coat progressively darker to enable confirmation of the number of
 coats.

 Color, texture, and pattern of wall coating systems shall be as selected.

1.9     LOCATION AND SURFACE TYPE TO BE PAINTED

1.9.1     Painting Included

 Where a space or surface is indicated to be painted, include the following
 unless indicated otherwise.

  a.    Surfaces behind portable objects and surface mounted articles readily
        detachable by removal of fasteners, such as screws and bolts.

  b.    New factory finished surfaces that require identification or color
        coding and factory finished surfaces that are damaged during
        performance of the work.

  c.    Existing coated surfaces that are damaged during performance of the
        work.

1.9.1.1     Exterior Painting

 Includes new surfaces of the buildings and appurtenances. Also included
 are existing coated surfaces made bare by cleaning operations.

1.9.1.2     Interior Painting

 Includes new surfaces, existing coated surfaces of the buildings and
 appurtenances as indicated and existing coated surfaces made bare by
 cleaning operations. Where a space or surface is indicated to be painted,
 include the following items, unless indicated otherwise.

  a.    Exposed columns, girders, beams, joists, and metal deck; and

  b.    Other contiguous surfaces.

1.9.2     Painting Excluded

 Do not paint the following unless indicated otherwise.

  a.    Surfaces concealed and made inaccessible by panelboards, fixed


                                SECTION 09 90 00   Page 6
Design MET Facility                                                        5490419


        ductwork, machinery, and equipment fixed in place.

  b.    Surfaces in concealed spaces. Concealed spaces are defined as enclosed
        spaces above suspended ceilings, furred spaces, attic spaces, crawl
        spaces, elevator shafts and chases.

  c.    Steel to be embedded in concrete.

  d.    Copper, stainless steel, aluminum, brass, and lead except existing
        coated surfaces.

  e.    Hardware, fittings, and other factory finished items.


1.9.3     Mechanical and Electrical Painting

 Includes field coating of interior and exterior new       surfaces.

  a.    Where a space or surface is indicated to be painted, include the
        following items unless indicated otherwise.

        (1)    Exposed piping, conduit, and ductwork;

        (2)    Supports, hangers, air grilles, and registers;

        (3)    Miscellaneous metalwork and insulation coverings.



1.9.4     Definitions and Abbreviations

1.9.4.1       Qualification Testing

 Qualification testing is the performance of all test requirements listed in
 the product specification. This testing is accomplished by MPI to qualify
 each product for the MPI Approved Product List, and may also be
 accomplished by Contractor's third party testing lab if an alternative to
 Batch Quality Conformance Testing by MPI is desired.

1.9.4.2       Batch Quality Conformance Testing

 Batch quality conformance testing determines that the product provided is
 the same as the product qualified to the appropriate product
 specification. This testing shall only be accomplished by MPI testing lab.

1.9.4.3       Coating

 A film or thin layer applied to a base material called a substrate. A
 coating may be a metal, alloy, paint, or solid/liquid suspensions on
 various substrates (metals, plastics, wood, paper, leather, cloth, etc.).
 They may be applied by electrolysis, vapor deposition, vacuum, or
 mechanical means such as brushing, spraying, calendaring, and roller
 coating. A coating may be applied for aesthetic or protective purposes or
 both. The term "coating" as used herein includes emulsions, enamels,
 stains, varnishes, sealers, epoxies, and other coatings, whether used as
 primer, intermediate, or finish coat. The terms paint and coating are used
 interchangeably.




                               SECTION 09 90 00   Page 7
Design MET Facility                                                           5490419


1.9.4.4    DFT or dft

 Dry film thickness, the film thickness of the fully cured, dry paint or
 coating.

1.9.4.5    DSD

 Degree of Surface Degradation, the MPI system of defining degree of surface
 degradation. Five (5) levels are generically defined under the Assessment
 sections in the MPI Maintenance Repainting Manual.

1.9.4.6    EPP

 Environmentally Preferred Products, a standard for determining
 environmental preferability in support of Executive Order 13101.

1.9.4.7    EXT

 MPI short term designation for an exterior coating system.

1.9.4.8    INT

 MPI short term designation for an interior coating system.

1.9.4.9    micron / microns

 The metric measurement for 0.001 mm or one/one-thousandth of a millimeter.

1.9.4.10    mil / mils

 The English measurement for 0.001 in or one/one-thousandth of an inch,
 equal to 25.4 microns or 0.0254 mm.

1.9.4.11    mm

 The metric measurement for millimeter, 0.001 meter or one/one-thousandth of
 a meter.

1.9.4.12    MPI Gloss Levels

 MPI system of defining gloss. Seven (7) gloss levels (G1 to G7) are
 generically defined under the Evaluation sections of the MPI Manuals.
 Traditionally, Flat refers to G1/G2, Eggshell refers to G3, Semigloss
 refers to G5, and Gloss refers to G6.

 Gloss levels are defined by MPI as follows:

 Gloss     Description        Units               Units
 Level                        at 60 degrees       at 85 degrees

 G1        Matte or Flat      0 to 5              10   max
 G2        Velvet             0 to 10             10   to 35
 G3        Eggshell           10 to 25            10   to 35
 G4        Satin              20 to 35            35   min
 G5        Semi-Gloss         35 to 70
 G6        Gloss              70 to 85
 G7        High Gloss

 Gloss is tested in accordance with ASTM D 523.           Historically, the


                               SECTION 09 90 00    Page 8
Design MET Facility                                                   5490419


 Government has used Flat (G1 / G2), Eggshell (G3), Semi-Gloss (G5), and
 Gloss (G6).

1.9.4.13     MPI System Number

 The MPI coating system number in each Division found in either the MPI
 Architectural Painting Specification Manual or the Maintenance Repainting
 Manual and defined as an exterior (EXT/REX) or interior system (INT/RIN).
 The Division number follows the CSI Master Format.

1.9.4.14     Paint

 See Coating definition.

1.9.4.15     REX

 MPI short term designation for an exterior coating system used in
 repainting projects or over existing coating systems.

1.9.4.16     RIN

 MPI short term designation for an interior coating system used in
 repainting projects or over existing coating systems.

PART 2     PRODUCTS

2.1   MATERIALS

 Conform to the coating specifications and standards referenced in PART 3.
 Submit manufacturer's technical data sheets for specified coatings and
 solvents. Comply with applicable regulations regarding toxic and hazardous
 materials.

PART 3     EXECUTION

3.1   PROTECTION OF AREAS AND SPACES NOT TO BE PAINTED

 Prior to surface preparation and coating applications, remove, mask, or
 otherwise protect, hardware, hardware accessories, machined surfaces,
 radiator covers, plates, lighting fixtures, public and private property,
 and other such items not to be coated that are in contact with surfaces to
 be coated. Following completion of painting, workmen skilled in the trades
 involved shall reinstall removed items. Restore surfaces contaminated by
 coating materials, to original condition and repair damaged items.

3.2   SURFACE PREPARATION

 Remove dirt, splinters, loose particles, grease, oil, disintegrated
 coatings, and other foreign matter and substances deleterious to coating
 performance as specified for each substrate before application of paint or
 surface treatments. Oil and grease shall be removed prior to mechanical
 cleaning. Cleaning shall be programmed so that dust and other contaminants
 will not fall on wet, newly painted surfaces. Exposed ferrous metals such
 as nail heads on or in contact with surfaces to be painted with
 water-thinned paints, shall be spot-primed with a suitable
 corrosion-inhibitive primer capable of preventing flash rusting and
 compatible with the coating specified for the adjacent areas.




                             SECTION 09 90 00   Page 9
Design MET Facility                                                        5490419


3.2.1    Additional Requirements for Preparation of Surfaces With Existing
Coatings

 Before application of coatings, perform the following on surfaces covered
 by soundly-adhered coatings, defined as those which cannot be removed with
 a putty knife:

  a.    Test existing finishes for lead before sanding, scraping, or removing.
        If lead is present, refer to paragraph Toxic Materials.

  b.    Wipe previously painted surfaces to receive solvent-based coatings,
        except stucco and similarly rough surfaces clean with a clean, dry
        cloth saturated with mineral spirits, ASTM D 235. Allow surface to
        dry. Wiping shall immediately precede the application of the first
        coat of any coating, unless specified otherwise.

  c.    Sand existing glossy surfaces to be painted to reduce gloss. Brush, and
        wipe clean with a damp cloth to remove dust.

  d.    The requirements specified are minimum. Comply also with the
        application instructions of the paint manufacturer.

  e.    Previously painted surfaces shall be thoroughly cleaned of all grease,
        dirt, dust or other foreign matter.

  f.    Blistering, cracking, flaking and peeling or other deteriorated
        coatings shall be removed.

  g.    Chalk shall be removed so that when tested in accordance with
        ASTM D 4214, the chalk resistance rating is no less than 8.

  h.    Slick surfaces shall be roughened. Damaged areas such as, but not
        limited to, nail holes, cracks, chips, and spalls shall be repaired
        with suitable material to match adjacent undamaged areas.

  i.    Edges of chipped paint shall be feather edged and sanded smooth.

  j.    Rusty metal surfaces shall be cleaned as per SSPC requirements.
        Solvent, mechanical, or chemical cleaning methods shall be used to
        provide surfaces suitable for painting.

  k.    New, proposed coatings shall be compatible with existing coatings.

3.3     PREPARATION OF METAL SURFACES

3.3.1     Existing and New Ferrous Surfaces

  a.    Ferrous Surfaces including Shop-coated Surfaces and Small Areas That
        Contain Rust, Mill Scale and Other Foreign Substances: Solvent clean or
         detergent wash in accordance with SSPC SP 1 to remove oil and grease.
        Where shop coat is missing or damaged, clean according to SSPC SP 2,
        SSPC SP 3, or SSPC SP 10. Brush-off blast remaining surface in
        accordance with SSPC SP 7. Shop-coated ferrous surfaces shall be
        protected from corrosion by treating and touching up corroded areas
        immediately upon detection.

  b.    Surfaces With More Than 20 Percent Rust, Mill Scale, and Other Foreign
        Substances: Clean entire surface in accordance with SSPC SP 6/
        SSPC SP 12.


                            SECTION 09 90 00   Page 10
Design MET Facility                                                        5490419



3.3.2     Final Ferrous Surface Condition:

 For tool cleaned surfaces, the requirements are stated in SSPC SP 2 and
 SSPC SP 3. As a visual reference, cleaned surfaces shall be similar to
 photographs in SSPC VIS 3.

 For abrasive blast cleaned surfaces, the requirements are stated in
 SSPC SP 7, SSPC SP 6, and SSPC SP 10. As a visual reference, cleaned
 surfaces shall be similar to photographs in SSPC VIS 1.

 For waterjet cleaned surfaces, the requirements are stated in SSPC SP 12.
 As a visual reference, cleaned surfaces shall be similar to photographs in
 SSPC VIS 4/NACE VIS 7.

3.3.3     Galvanized Surfaces

  a.    New or Existing Galvanized Surfaces With Only Dirt and Zinc Oxidation
        Products: Clean with solvent, steam, or non-alkaline detergent
        solution in accordance with SSPC SP 1. If the galvanized metal has
        been passivated or stabilized, the coating shall be completely removed
        by brush-off abrasive blast. New galvanized steel to be coated shall
        not be "passivated" or "stabilized" If the absence of hexavalent stain
        inhibitors is not documented, test as described in ASTM D 2092,
        Appendix X2, and remove by one of the methods described therein.

3.3.4     Non-Ferrous Metallic Surfaces

 Aluminum and aluminum-alloy, lead, copper, and other nonferrous metal
 surfaces.

 Surface Cleaning: Solvent clean in accordance with SSPC SP 1 and wash with
 mild non-alkaline detergent to remove dirt and water soluble contaminants.

3.3.5     Terne-Coated Metal Surfaces

 Solvent clean surfaces with mineral spirits, ASTM D 235.      Wipe dry with
 clean, dry cloths.

3.3.6     Existing Surfaces with a Bituminous or Mastic-Type Coating

 Remove chalk, mildew, and other loose material by washing with a solution of
  1/2 cup trisodium phosphate, 1/4 cup household detergent, one quart 5
 percent sodium hypochlorite solution and 3 quarts of warm water.

3.4     PREPARATION OF CONCRETE AND CEMENTITIOUS SURFACE

3.4.1     Concrete and Masonry

  a.    Curing: Concrete, stucco and masonry surfaces shall be allowed to cure
        at least 30 days before painting, except concrete slab on grade, which
        shall be allowed to cure 90 days before painting.

  b.    Surface Cleaning:   Remove the following deleterious substances.

        (1)    Dirt, Chalking, Grease, and Oil: Wash new and existing uncoated
              surfaces with a solution composed of 1/2 cup trisodium phosphate,
              1/4 cuphousehold detergent, and 4 quarts of warm water. Then
              rinse thoroughly with fresh water. Wash existing coated surfaces


                              SECTION 09 90 00   Page 11
Design MET Facility                                                        5490419


              with a suitable detergent and rinse thoroughly.   For large areas,
              water blasting may be used.

        (2)    Fungus and Mold: Wash existing coated surfaces with a solution
              composed of 1/2 cup trisodium phosphate, 1/4 cup household
              detergent, 1 quart 5 percent sodium hypochlorite solution and 3
              quarts of warm water. Rinse thoroughly with fresh water.

        (3)   Paint and Loose Particles:   Remove by wire brushing.

        (4)    Efflorescence: Remove by scraping or wire brushing followed by
              washing with a 5 to 10 percent by weight aqueous solution of
              hydrochloric (muriatic) acid. Do not allow acid to remain on the
              surface for more than five minutes before rinsing with fresh
              water. Do not acid clean more than 4 square feet of surface, per
              workman, at one time.

  c.    Cosmetic Repair of Minor Defects: Repair or fill mortar joints and
        minor defects, including but not limited to spalls, in accordance with
        manufacturer's recommendations and prior to coating application.

  d.    Allowable Moisture Content: Latex coatings may be applied to damp
        surfaces, but not to surfaces with droplets of water. Do not apply
        epoxies to damp vertical surfaces as determined by ASTM D 4263 or
        horizontal surfaces that exceed 3 lbs of moisture per 1000 square feet
        in 24 hours as determined by ASTM F 1869. In all cases follow
        manufacturers recommendations. Allow surfaces to cure a minimum of 30
        days before painting.

3.5     APPLICATION

3.5.1     Coating Application

 Painting practices shall comply with applicable federal, state and local
 laws enacted to insure compliance with Federal Clean Air Standards. Apply
 coating materials in accordance with SSPC PA 1. SSPC PA 1 methods are
 applicable to all substrates, except as modified herein.

 At the time of application, paint shall show no signs of deterioration.
 Uniform suspension of pigments shall be maintained during application.

 Unless otherwise specified or recommended by the paint manufacturer, paint
 may be applied by brush, roller, or spray. Use trigger operated spray
 nozzles for water hoses. Rollers for applying paints and enamels shall be
 of a type designed for the coating to be applied and the surface to be
 coated. Wear protective clothing and respirators when applying oil-based
 paints or using spray equipment with any paints.

 Paints, except water-thinned types, shall be applied only to surfaces that
 are completely free of moisture as determined by sight or touch.

 Thoroughly work coating materials into joints, crevices, and open spaces.
 Special attention shall be given to insure that all edges, corners,
 crevices, welds, and rivets receive a film thickness equal to that of
 adjacent painted surfaces.

 Each coat of paint shall be applied so dry film shall be of uniform
 thickness and free from runs, drops, ridges, waves, pinholes or other
 voids, laps, brush marks, and variations in color, texture, and finish.


                              SECTION 09 90 00   Page 12
Design MET Facility                                                      5490419


 Hiding shall be complete.

 Touch up damaged coatings before applying subsequent coats.

  a.    Drying Time: Allow time between coats, as recommended by the coating
        manufacturer, to permit thorough drying, but not to present topcoat
        adhesion problems. Provide each coat in specified condition to receive
        next coat.

  b.    Primers, and Intermediate Coats: Do not allow primers or intermediate
        coats to dry more than 30 days, or longer than recommended by
        manufacturer, before applying subsequent coats. Follow manufacturer's
        recommendations for surface preparation if primers or intermediate
        coats are allowed to dry longer than recommended by manufacturers of
        subsequent coatings. Each coat shall cover surface of preceding coat
        or surface completely, and there shall be a visually perceptible
        difference in shades of successive coats.

  c.    Finished Surfaces: Provide finished surfaces free from runs, drops,
        ridges, waves, laps, brush marks, and variations in colors.

  d.    Thermosetting Paints: Topcoats over thermosetting paints (epoxies and
        urethanes) should be applied within the overcoating window recommended
        by the manufacturer.

  e.    Floors: For nonslip surfacing on level floors, as the intermediate
        coat is applied, cover wet surface completely with almandite garnet,
        Grit No. 36, with maximum passing U.S. Standard Sieve No. 40 less than
        0.5 percent. When the coating is dry, use a soft bristle broom to
        sweep up excess grit, which may be reused, and vacuum up remaining
        residue before application of the topcoat.

3.5.2    Mixing and Thinning of Paints

 Reduce paints to proper consistency by adding fresh paint, except when
 thinning is mandatory to suit surface, temperature, weather conditions,
 application methods, or for the type of paint being used. Obtain written
 permission from the Contracting Officer to use thinners. The written
 permission shall include quantities and types of thinners to use.

 When thinning is allowed, paints shall be thinned immediately prior to
 application with not more than quantity recommended by paint manufacturer
 of suitable thinner per gallon. The use of thinner shall not relieve the
 Contractor from obtaining complete hiding, full film thickness, or required
 gloss. Thinning shall not cause the paint to exceed limits on volatile
 organic compounds. Paints of different manufacturers shall not be mixed.

3.5.3    Two-Component Systems

 Two-component systems shall be mixed in accordance with manufacturer's
 instructions. Any thinning of the first coat to ensure proper penetration
 and sealing shall be as recommended by the manufacturer for each type of
 substrate.

3.5.4    Coating Systems

  a.    Systems by Substrates: Apply coatings that conform to the respective
        specifications listed in the following Tables:



                            SECTION 09 90 00   Page 13
Design MET Facility                                                        5490419


             Table


             Division 5.   Interior Metal, Ferrous and Non-Ferrous Paint Table

             Division 9:   Interior Plaster, Gypsum Board, Textured Surfaces
                            Paint Table

  b.   Minimum Dry Film Thickness (DFT): Apply paints, primers, varnishes,
       enamels, undercoats, and other coatings to a minimum dry film thickness
       of 1.5 mil each coat unless specified otherwise in the Tables. Coating
       thickness where specified, refers to the minimum dry film thickness.

  c.   Coatings for Surfaces Not Specified Otherwise: Coat surfaces which
       have not been specified, the same as surfaces having similar conditions
       of exposure.

  d.   Existing Surfaces Damaged During Performance of the Work, Including New
       Patches In Existing Surfaces: Coat surfaces with the following:

       (1)    One coat of primer.

       (2)    One coat of undercoat or intermediate coat.

       (3)    One topcoat to match adjacent surfaces.

  e.   Existing Coated Surfaces To Be Painted: Apply coatings conforming to
       the respective specifications listed in the Tables herein, except that
       pretreatments, sealers and fillers need not be provided on surfaces
       where existing coatings are soundly adhered and in good condition. Do
       not omit undercoats or primers.

3.6    COATING SYSTEMS FOR METAL

 Apply coatings of Tables in Division 5 for Exterior and Interior.

  a.   Apply specified ferrous metal primer on the same day that surface is
       cleaned, to surfaces that meet all specified surface preparation
       requirements at time of application.

  b.   Inaccessible Surfaces: Prior to erection, use one coat of specified
       primer on metal surfaces that will be inaccessible after erection.

  c.   Shop-primed Surfaces: Touch up exposed substrates and damaged coatings
       to protect from rusting prior to applying field primer.

3.7    COATING SYSTEMS FOR CONCRETE AND CEMENTITIOUS SUBSTRATES

 Apply coatings of Tables in Division 3, 4 and 9 for Exterior and Interior.

3.8    INSPECTION AND ACCEPTANCE

 In addition to meeting previously specified requirements, demonstrate
 mobility of moving components, including swinging and sliding doors,
 cabinets, and windows with operable sash, for inspection by the Contracting
 Officer. Perform this demonstration after appropriate curing and drying
 times of coatings have elapsed and prior to invoicing for final payment.




                              SECTION 09 90 00   Page 14
Design MET Facility                                                          5490419


3.9     PAINT TABLES

3.9.1     INTERIOR PAINT TABLES

        DIVISION 5:    INTERIOR METAL, FERROUS AND NON-FERROUS PAINT TABLE

INTERIOR STEEL / FERROUS SURFACES

A.  Metal, Mechanical, Electrical, Surfaces adjacent to
  painted surfaces (Match surrounding finish), exposed copper piping, and
  miscellaneous metal items not otherwise specified except floors, hot metal
  surfaces, and new prefinished equipment:

 1. High Performance Architectural Latex
    MPI INT 5.1R-G3 (Eggshell)
    Primer:              Intermediate:           Topcoat:
    MPI 79               MPI 139                 MPI 139
    System DFT:   5 mils


B.  Metal floors (non-shop-primed surfaces or non-slip deck surfaces) with
  non-skid additive (NSA), load at manufacturer's recommendations.:

 1. Alkyd Floor Paint
    MPI INT 5.1U-G6 (Gloss)
    Primer:             Intermediate:            Topcoat:
    MPI 79              MPI 27                   MPI 27 (+NSA)
    System DFT:   5.25 mils


C.  Miscellaneous non-ferrous metal items not otherwise specified except
  floors, hot metal surfaces, and new prefinished equipment. Match
  surrounding finish:

 1. High Performance Architectural Latex
    MPI INT 5.4F-G3 (Eggshell)
    Primer:              Intermediate:           Topcoat:
    MPI 95               MPI 139                 MPI 139
    System DFT:   5 mils


      DIVISION 9:   INTERIOR PLASTER, GYPSUM BOARD, TEXTURED SURFACES PAINT TABLE

A.  New Wallboard not
  otherwise specified:

 1. Latex
    New; MPI INT 9.2A-G3 (Eggshell) / Existing; RIN 9.2A-G3 (Eggshell)
    Primer:              Intermediate:      Topcoat:
    MPI 50               MPI 52             MPI 52
    System DFT:   4 mils



          -- End of Section --




                              SECTION 09 90 00   Page 15
Design MET Facility                                                        5490419



                                   SECTION 10 44 16

                                  FIRE EXTINGUISHERS
                                         05/09

PART 1     GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to within the text by the
 basic designation only.

             INTERNATIONAL CODE COUNCIL (ICC)

 IFC 1414                             (2004) Portable Fire Extinguishers(Where
                                      Required)(Construction, Alteration,
                                      Demolition)

 IFC 906                              (2004) Portable Fire Extinguishers

             NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

 NFPA 1                               (2008) Uniform Fire Code, 2006 Edition

 NFPA 10                              (2010) Standard for Portable Fire
                                      Extinguishers

 NFPA 101                             (2009; Amd 1 & 2 2009) Life Safety Code

             U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

 29 CFR 1910.157                      (2003) Portable Fire Extinguishers

             UNDERWRITERS LABORATORIES (UL)

 UL 299                               (2002; Rev thru Apr 20097) Standards for
                                      Dry Chemical Fire Extinguishers

1.2   SUBMITTALS

 Submit the following in accordance with Section 01 33 00 SUBMITTAL
 PROCEDURES:

         SD-01 Preconstruction Submittals

             Manufacturer's Data for each type of required Fire Extinguisher
             with all related details, cabinets, accessories, and recommended
             operation manuals.

         SD-02 Shop Drawings

             Submit fabrication drawings for the following items consisting of
             fabrication and assembly details performed in the factory. Submit
             installation drawings for the following items in accordance with
             the paragraph entitled, "Installation," of this section.

             Fire Extinguishers


                               SECTION 10 44 16   Page 1
Design MET Facility                                                       5490419


             Accessories

             Wall Brackets

         SD-03 Product Data

             Submit Manufacturer's catalog and warranty data for the following
             items:

             Fire Extinguishers
             Accessories

             Wall Brackets
             Replacement Parts

         SD-04 Samples

             One of each type of Fire Extinguisher being installed


             Three samples of Wall Brackets and Accessories of each type being
             used

             Approved samples may be used for installation, with proper
             identification and storage.

         SD-07 Certificates

             Submit Certificates showing the following:

             Certification that Fire Extinguishers comply with local codes and
             regulations.

             Certification that Fire Extinguishers comply with OSHA, NFPA, and
             UL requirements.

             Submit Manufacturer's Warranty with Inspection Tag on each
             extinguisher.



1.3   DELIVERY, HANDLING, AND STORAGE

 Protect materials from weather, soil, and damage during delivery, storage,
 and construction.

 Deliver materials in their original packages, containers, or bundles
 bearing the brand name and the name and type of the material.

PART 2     PRODUCTS

2.1   TYPES

 Provide Fire Extinguishers conforming to NFPA 10. Provide quantity and
 placement in compliance with the applicable sections of IFC 1414, IFC 906,
 NFPA 1, NFPA 101 and 29 CFR 1910.157.




                              SECTION 10 44 16   Page 2
Design MET Facility                                                      5490419




 Provide dry chemical type fire extinguishers compliant with UL 299.



 Submit Manufacturer's Data for each type of Fire Extinguisher required,
 Wall Mounting and Accessories information, complete with Manufacturer's
 Warranty with Inspection Tag.

2.2     MATERIAL

 Provide corrosion-resistant steel extinguisher shell.

2.3     SIZE




 10 pounds extinguishers.

2.4     ACCESSORIES

         Forged brass valve

         Fusible plug

         Safety release



         Pressure gage

2.5     WALL BRACKETS

 Providewall-hook fire extinguisher wall brackets.

 Provide wall bracket and accessories as approved.

PART 3     EXECUTION

3.1     INSTALLATION

 Verify exact locations prior to installation.

 Comply with the manufacturer's recommendations for all installations.

 Provide extinguishers which are fully charged and ready for operation upon
 installation. Provide extinguishers complete with Manufacturer's Warranty
 with Inspection Tag attached.

3.2     ACCEPTANCE PROVISIONS

3.2.1     Repairing

 Remove and replace damaged and unacceptable portions of completed work with


                                SECTION 10 44 16   Page 3
Design MET Facility                                                   5490419


 new work at no additional cost to the Government.

 Provide Replacement Parts list indicating specified items replacement part,
 replacement cost, and name, address and contact for replacement parts
 distributor.

3.2.2   Cleaning

 Clean all surfaces of the work, and adjacent surfaces which are soiled as a
 result of the work. Remove from the site all construction equipment,
 tools, surplus materials and rubbish resulting from the work.

        -- End of Section --




                           SECTION 10 44 16   Page 4
Design MET Facility                                                       5490419



                                   SECTION 13 12 50

                                      BLEACHERS
                                        07/10

PART 1     GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to within the text by the
 basic designation only.

             ASTM INTERNATIONAL (ASTM)

 ASTM A 36/A 36M                      (2008) Standard Specification for Carbon
                                      Structural Steel

 ASTM A 529/A 529M                    (2005R 2009) Standard Specification for
                                      High-Strength Carbon-Manganese Steel of
                                      Structural Quality



1.2   SUBMITTALS

 Submit the following in accordance with Section 01 33 00 SUBMITTAL
 PROCEDURES:

         SD-02 Shop Drawings

             Angle Frame Bleachers

         SD-03 Product Data

             Angle Frame Bleachers

         SD-05 Design Data

             Angle Frame Bleachers

1.3   QUALITY ASSURANCE

1.4   WARRANTY

 A. Warranty shall guarantee bleachers to be free from defect in materials
 and workmanship for a period of 1 year under normal use. Warranty period
 shall befin on date of completion for projects installed by manufacturer,
 or its subcontractors, or warranty period shall befin on date of final
 delivery on projects installed by others.

 B. Anodized finish of plank extrusions shall be covered by 5 year warranty
 against loss of structural strength or finish deterioration due to exposure
 to weather conditions or UV rays. Discoloration of mill finish aluminum due
 to galvanic reation not covered.




                               SECTION 13 12 50   Page 1
Design MET Facility                                                      5490419


1.5    ENGINEERING

 Engineering certifications and calculations by a Registered Professional
 Engineer will be provided upon request.

PART 2     PRODUCTS

2.1    DESIGN

 A.   Design Loads:

      1. Live Loads: Uniform loading-Structure=100psf Uniform loading Seat
         and Foot plank=120 plf

      2. Sway Loads: Perpendicular to seats=10 plf Parallel to seats=24 plf

      3. Guardrail Loads: Uniform vertical load=100 plf
         Uniform horizontal load=50 plf
         Concentrated horizontal load=200 pounds

2.2      ANGLE FRAME BLEACHERS

 A. Quantity and Size
    Refer to drawings for net seating capacity per unit

 B. Framework
    Prefabricated aluminum angle or galvanized steel angle at max. 6'
    spacing joined by means of aluminum angle cross bracing.

 C. Shop connections
    Welded to meet AWS standards and local code requirements.

 D. Joint Sleeve Assembly
    Internal splices, where required shall be two per joint, and shall
    penetrate the joint a minimum of 8 in each direction and be riveted at
    one end only to allow for contraction and expansion.

 E. Rise and Depth Dimensions
    8" vertical rise and 24" tread depth, Seat height is 17" above its
    respective tread

 F. Seats
    Nominal 2"x10" anodized aluminum with anodized end caps

 G. Treads
    Nominal two 2"x10" mill finish aluminum with anodized end caps on rows 2
    and up

 H. Risers
    Nominal 2"x10" mill finish aluminum with end caps on top row
    Nominal 1"x6" mill finish aluminum with end caps on all other rows

 I. Aisles
    Aisle footboards shall be of aluminum alloy 6063-T6 and be of mill
    finish with contrasting aisle markings. Three aisle stiffner angles
    shall be used to strengthen the aisle step. There shall be 1 aisle 48"
    wide.

 J. Aisle Handrail


                             SECTION 13 12 50   Page 2
Design MET Facility                                                     5490419


      Anodized aluminum pipe with intermediate rail

 K. Guardrail
    Rails shall be anodized aluminum tube with end plugs and elbows where
    required. All rails shall be secured to support with galvanized
    fasteners. Top rails at sides, rear and front shall be 42" above the
    leading edge of seat or walking surfaces. Rear rail support members
    shall be aluminum channel, side and front rail support shall be
    aluminum angle.

         1. Chainlink System
            Fencing shall consist of 9 gauge, 2" mesh galvanized chainlink
            fabric, heavy duty tension bands, ension bars, brace bands, combo
            rail endcaps, and wire ties.

         2. Vertical Picket System
            Aluminum pipe and bar anodized after fabricatin & attached to
            supports with galvanized fasteners.

2.3    MATERIALS

 A. Framework

      1. Aluminum
         Structural fabrication with aluminum alloy 6061-T6 mill finish. Each
         frame shall be unit-welded, using metal inert gas method, under
         guidelines but th eAmerican Welding Society. Galvanized Steel:
         ASTM A 36/A 36M & ASTM A 529/A 529M after fabrication all steel is
         hot dipped galvanized to ASTM A 123 specifications. All crossbracing
         and horizontal bracing shall be aluminum angle 60 61-T6 mill finish.

 B. Extruded Aluminum

      1. Seat planks
         Aluminum alloy 6063-T6, clear anodized 204R1, AA-M10C22A31, Class II
         with a wall thickness nominally 0.078" impact and deformation
         resistance.

      2. Tread and Riser Planks
         Aluminum alloy 6063-T6, mill finish with a wall thickness nominally
         0.078" for impact and deformation reisitance.

      3. Guardrail Pipe
         1-5/8" OD schedule 40 aluminum alloy 6105-T5, clear anodized
         204R1, AA-M10C22A31, Class II.

      4. Handrail Pipe
         1-5/8" OD schedule 40 aluminum alloy 6105-T1, clear anodized 204R1,
         AA-M10C22A31, Class II.

 C. Accessories

      1. Channel End Caps
         Aluminum alloy 6063-T6, clear anodized 204R1, AA-M10C22A31, Class II.

      2. Hardware
         Bolts and Nuts shall be hot dipped galvanized.

      3. Hold Down Clip Assembly


                            SECTION 13 12 50   Page 3
Design MET Facility                                              5490419


         Aluminum alloy 6063-T6 mill finish

      4. Joint Sleeve Assembly
         Aluminum alloy 6061-T6, mill finish

PART 3     EXECUTION

3.1    INSTALLATION

 A. Install bleacher unit accordance with manufacturer written
    instructions and shop drawings.

         -- End of Section --




                                SECTION 13 12 50   Page 4
Design MET Facility                                                       5490419



                                SECTION 13 34 19

                             METAL BUILDING SYSTEMS
                                      01/08

PART 1     GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to within the text by the
 basic designation only.

            ALUMINUM ASSOCIATION (AA)

 AA ADM1                            (2005; Errata 2005) Aluminum Design Manual

 AA ASD1                            (2006; Errata 2007) Aluminum Standards and
                                    Data

            AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)

 AAMA 101                           (2005) Standard Specification for Windows,
                                    Doors, and Unit Skylights

            AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)

 AISC 325                           (2005) Manual of Steel Construction

 AISC 341                           (2005; Supp 2005) Seismic Provisions for
                                    Structural Steel Buildings

 AISC 350                           (2005) Load and Resistance Factor Design
                                    (LRFD)Specification for Structural Steel
                                    Buildings

 AISC 360                           (2005) Specification for Structural Steel
                                    Buildings, with Commentary

            AMERICAN IRON AND STEEL INSTITUTE (AISI)

 AISC/AISI 121                      (2004) Standard Definitions for Use in the
                                    Design of Steel Structures

 AISI SG03-3                        (2002) Cold-Formed Steel Design Manual Set

            AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)

 ASCE 7-05                          (2006; Errata 2007) Minimum Design Loads
                                    for Buildings and Other Structures

            AMERICAN WELDING SOCIETY (AWS)

 AWS A5.1/A5.1M                     (2004; Errata 2004) Carbon Steel
                                    Electrodes for Shielded Metal Arc Welding

 AWS D1.1/D1.1M                     (2008; Errata 2009) Structural Welding
                                    Code - Steel


                            SECTION 13 34 19   Page 1
Design MET Facility                                                   5490419



 AWS D1.3/D1.3M                   (2008; Errata 2008) Structural Welding
                                  Code - Sheet Steel

          ASTM INTERNATIONAL (ASTM)

 ASTM A 1008/A 1008M              (2009) Standard Specification for Steel,
                                  Sheet, Cold-Rolled, Carbon, Structural,
                                  High-Strength Low-Alloy and High-Strength
                                  Low-Alloy with Improved Formability,
                                  Solution Hardened, and Bake Hardened

 ASTM A 1011/A 1011M              (2009b) Standard Specification for Steel,
                                  Sheet, and Strip, Hot-Rolled, Carbon,
                                  Structural, High-Strength Low-Alloy and
                                  High-Strength Low-Alloy with Improved
                                  Formability and Ultra-High Strength

 ASTM A 123/A 123M                (2009) Standard Specification for Zinc
                                  (Hot-Dip Galvanized) Coatings on Iron and
                                  Steel Products

 ASTM A 193/A 193M                (2008b) Standard Specification for
                                  Alloy-Steel and Stainless Steel Bolting
                                  Materials for High-Temperature Service

 ASTM A 307                       (2007b) Standard Specification for Carbon
                                  Steel Bolts and Studs, 60 000 PSI Tensile
                                  Strength

 ASTM A 325                       (2009) Standard Specification for
                                  Structural Bolts, Steel, Heat Treated,
                                  120/105 ksi Minimum Tensile Strength

 ASTM A 36/A 36M                  (2008) Standard Specification for Carbon
                                  Structural Steel

 ASTM A 500/A 500M                (2007) Standard Specification for
                                  Cold-Formed Welded and Seamless Carbon
                                  Steel Structural Tubing in Rounds and
                                  Shapes

 ASTM A 501                       (2007) Standard Specification for
                                  Hot-Formed Welded and Seamless Carbon
                                  Steel Structural Tubing

 ASTM A 529/A 529M                (2005R 2009) Standard Specification for
                                  High-Strength Carbon-Manganese Steel of
                                  Structural Quality

 ASTM A 53/A 53M                  (2007) Standard Specification for Pipe,
                                  Steel, Black and Hot-Dipped, Zinc-Coated,
                                  Welded and Seamless

 ASTM A 563                       (2007a) Standard Specification for Carbon
                                  and Alloy Steel Nuts

 ASTM A 572/A 572M                (2007) Standard Specification for
                                  High-Strength Low-Alloy Columbium-Vanadium


                          SECTION 13 34 19   Page 2
Design MET Facility                                               5490419


                             Structural Steel

 ASTM A 606/A 606M           (2009) Standard Specification for Steel
                             Sheet and Strip, High-Strength, Low-Alloy,
                             Hot-Rolled and Cold-Rolled, with Improved
                             Atmospheric Corrosion Resistance

 ASTM A 653/A 653M           (2009) Standard Specification for Steel
                             Sheet, Zinc-Coated (Galvanized) or
                             Zinc-Iron Alloy-Coated (Galvannealed) by
                             the Hot-Dip Process

 ASTM A 755/A 755M           (2003; R 2008) Standard Specification for
                             Steel Sheet, Metallic Coated by the
                             Hot-Dip Process and Prepainted by the
                             Coil-Coating Process for Exterior Exposed
                             Building Products

 ASTM A 780                  (2001; R 2006) Standard Practice for
                             Repair of Damaged and Uncoated Areas of
                             Hot-Dip Galvanized Coatings

 ASTM A 792/A 792M           (2008) Standard Specification for Steel
                             Sheet, 55% Aluminum-Zinc Alloy-Coated by
                             the Hot-Dip Process

 ASTM A 992/A 992M           (2006a) Standard Specification for
                             Structural Steel Shapes

 ASTM B 117                  (2009) Standing Practice for Operating
                             Salt Spray (Fog) Apparatus

 ASTM B 209                  (2007) Standard Specification for Aluminum
                             and Aluminum-Alloy Sheet and Plate

 ASTM B 221                  (2008) Standard Specification for Aluminum
                             and Aluminum-Alloy Extruded Bars, Rods,
                             Wire, Profiles, and Tubes

 ASTM B 221M                 (2007) Standard Specification for Aluminum
                             and Aluminum-Alloy Extruded Bars, Rods,
                             Wire, Profiles, and Tubes (Metric)

 ASTM B 695                  (2004) Standard Specification for Coatings
                             of Zinc Mechanically Deposited on Iron and
                             Steel

 ASTM C 1363                 (2005) Standard Test Method for Thermal
                             Performance of Building Materials and
                             Envelope Assemblies by Means of a Hot Box
                             Apparatus

 ASTM C 518                  (2004) Steady-State Thermal Transmission
                             Properties by Means of the Heat Flow Meter
                             Apparatus

 ASTM C 553                  (2008) Standard Specification for Mineral
                             Fiber Blanket Thermal Insulation for
                             Commercial and Industrial Applications


                      SECTION 13 34 19   Page 3
Design MET Facility                                                 5490419



 ASTM C 612                  (2004e1) Mineral Fiber Block and Board
                             Thermal Insulation

 ASTM C 665                  (2006) Mineral-Fiber Blanket Thermal
                             Insulation for Light Frame Construction
                             and Manufactured Housing

 ASTM C 920                  (2008) Standard Specification for
                             Elastomeric Joint Sealants

 ASTM C 991                  (2008e1) Flexible Glass Fiber Insulation
                             for Metal Buildings

 ASTM D 1056                 (2007) Standard Specification for Flexible
                             Cellular Materials - Sponge or Expanded
                             Rubber

 ASTM D 1308                 (2002; R 2007) Effect of Household
                             Chemicals on Clear and Pigmented Organic
                             Finishes

 ASTM D 1667                 (2005) Flexible Cellular Materials - Poly
                             (Vinyl Chloride) Foam (Closed-Cell)

 ASTM D 2244                 (2007) Calculation of Color Tolerances and
                             Color Differences from Instrumentally
                             Measured Color Coordinates

 ASTM D 2247                 (2002) Testing Water Resistance of
                             Coatings in 100% Relative Humidity

 ASTM D 2794                 (1993; R 2004) Resistance of Organic
                             Coatings to the Effects of Rapid
                             Deformation (Impact)

 ASTM D 3363                 (2005) Film Hardness by Pencil Test

 ASTM D 4214                 (2007) Standard Test Method for Evaluating
                             the Degree of Chalking of Exterior Paint
                             Films

 ASTM D 522                  (1993a; R 2008) Mandrel Bend Test of
                             Attached Organic Coatings

 ASTM D 523                  (2008) Standard Test Method for Specular
                             Gloss

 ASTM D 714                  (2002e1) Evaluating Degree of Blistering
                             of Paints

 ASTM D 822                  (2001; R 2006) Filtered Open-Flame
                             Carbon-Arc Exposures of Paint and Related
                             Coatings

 ASTM D 968                  (2005e1) Abrasion Resistance of Organic
                             Coatings by Falling Abrasive

 ASTM DEF                    (2005) ASTM Dictionary of Engineering


                      SECTION 13 34 19   Page 4
Design MET Facility                                                 5490419


                             Science and Technology, 10th Edition

 ASTM E 119                  (2008a) Standard Test Methods for Fire
                             Tests of Building Construction and
                             Materials

 ASTM E 136                  (2009) Behavior of Materials in a Vertical
                             Tube Furnace at 750 Degrees C

 ASTM E 1592                 (2005) Structural Performance of Sheet
                             Metal Roof and Siding Systems by Uniform
                             Static Air Pressure Difference

 ASTM E 1646                 (1995; R 2003) Standard Test Method for
                             Water Penetration of Exterior Metal Roof
                             Panel Systems by Uniform Air Pressure
                             Difference

 ASTM E 168                  (2006) General Techniques of Infrared
                             Quantitative Analysis

 ASTM E 283                  (2004) Determining the Rate of Air Leakage
                             Through Exterior Windows, Curtain Walls,
                             and Doors Under Specified Pressure
                             Differences Across the Specimen

 ASTM E 331                  (2000; R 2009) Water Penetration of
                             Exterior Windows, Skylights, Doors, and
                             Curtain Walls by Uniform Static Air
                             Pressure Difference

 ASTM E 84                   (2009) Standard Test Method for Surface
                             Burning Characteristics of Building
                             Materials

 ASTM E 96/E 96M             (2005) Standard Test Methods for Water
                             Vapor Transmission of Materials

 ASTM F 1554                 (2007a)Standard Specification for Anchor
                             Bolts, Steel, 36, 55, and 105-ksi Yield
                             Strength

 ASTM F 1852                 (2008) Standard Specification for "Twist
                             Off" Type Tension Control Structural
                             Bolt/Nut/Washer Assemblies, Steel, Heat
                             Treated, 120/105 ksi Minimum Tensile
                             Strength

 ASTM F 436                  (2009) Hardened Steel Washers

 ASTM F 844                  (2007a) Washers, Steel, Plain (Flat),
                             Unhardened for General Use

 ASTM G 23                   (1996) Operating Light-Exposure Apparatus
                             (Carbon-Arc Type) With and Without Water
                             for Exposure of Nonmetallic Materials




                      SECTION 13 34 19   Page 5
Design MET Facility                                                          5490419


            METAL BUILDING MANUFACTURERS ASSOCIATION (MBMA)

 MBMA MBSM                            (2002) Metal Building Systems Manual

            NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)

 NAAMM AMP 500                        (2006) Metal Finishes Manual

            NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

 NFPA 252                             (2007) Standard Methods of Fire Tests of
                                      Door Assemblies

 NFPA 80                              (2006; Errata 2008) Standard for Fire
                                      Doors and Other Opening Protectives

            NATIONAL ROOFING CONTRACTORS ASSOCIATION (NRCA)

 NRCA RWM                             (2003) Roofing and Waterproofing Manual

            SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION
            (SMACNA)

 SMACNA 1793                          (2006) Architectural Sheet Metal Manual,
                                      Sixth Edition, Second Printing

            THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)

 SSPC A                               (2000) Good Painting Practice Steel
                                      Structures Painting Manual, Volume 1

 SSPC Paint 15                        (1999; E 2004) Steel Joist Shop
                                      Primer/Metal Building Primer

 SSPC SP 2                            (1982; E 2004) Hand Tool Cleaning

            UNDERWRITERS LABORATORIES (UL)

 UL Bld Mat Dir                       (2009) Building Materials Directory

1.2     GENERAL REQUIREMENTS

1.2.1     Structural Performance

 Provide metal building systems capable of withstanding the effects of
 gravity loads and the following loads and stresses within the limits and
 conditions indicated.

1.2.1.1     Engineering

 Design metal building systems conforming to procedures described in
 MBMA MBSM.

1.2.1.2     Design Loads

 Conform to the requirements of MBMA MBSM, ASCE 7-05, and the building code
 applicable to the project geographical location.




                               SECTION 13 34 19   Page 6
Design MET Facility                                                      5490419


1.2.1.3     Live Loads

 Include all vertical loads induced by the building occupancy indicated on
 the drawings, as well as loads induced by maintenance workers, materials
 and equipment for roof live loads.

1.2.1.4     Roof Snow Loads

 Include vertical loads induced by the weight of snow, as determined by 50
 year Mean-Recurrence-Interval (MRI) ground snow load at the project site.
 Allow for unbalanced and drift loads.

1.2.1.5     Wind Loads

 Include horizontal loads induced by a basic wind speed corresponding to a 50
 -year, mean-recurrence interval at Project site.

1.2.1.6     Collateral Loads

 Include additional dead loads other than the weight of metal building
 system for permanent items such as mechanical systems, electrical systems,
 and ceilings.

1.2.1.7     Auxiliary Loads

 Include dynamic live loads, such as those generated by cranes and
 materials-handling equipment indicated on detail drawings.

1.2.1.8     Load Combinations

 Design metal building systems to withstand the most critical effects of
 load factors and load combinations as required by MBMA MBSM, ASCE 7-05, and
 the building code applicable to the project location.

1.2.1.9     Deflection Limits

 Engineer assemblies to withstand design loads with deflections no greater
 than the following:

  a.    Purlins and Rafters; vertical deflection of 1/180 of the span.

  b.    Girts; horizontal deflection of 1/240 of the span.

  c.    Metal Roof Panels; vertical deflection of 1/180 of the span.

  d.    Metal Wall Panels; horizontal deflection of 1/180 of the span.

 Design secondary framing system to accommodate deflection of primary
 building structure and construction tolerances, and to maintain clearances
 at openings. Provide metal panel assemblies capable of withstanding the
 effects of loads and stresses indicated, based on testing according to
 ASTM E 1592.

1.2.2     Seismic Performance

 Design and engineer metal building system capable of withstanding the
 effects of earthquake motions determined according to ASCE 7-05, AISC 341,
 and the applicable portions of the building code in the geographic area
 where the construction will take place.


                                SECTION 13 34 19   Page 7
Design MET Facility                                                       5490419



1.2.3     Thermal Movements

 Provide metal panel systems that allow for thermal movements resulting from
 the following maximum change (range) in ambient and surface temperatures by
 preventing buckling, opening of joints, overstressing of components,
 failure of joint sealants, failure of connections, and other detrimental
 effects. Base engineering calculation on surface temperatures of materials
 due to both solar heat gain and nighttime-sky heat loss as follows:

  a.     Temperature Change (Range); 120 F, ambient; 180 F, material surfaces.

1.2.4     Thermal Performance

 Provide insulated metal panel assemblies with the following maximum
 U-factors and minimum R-values for opaque elements when tested according to
 ASTM C 1363 or ASTM C 518.

1.2.4.1     Metal Roof Panel Assemblies

  a.     R-Value:   30

1.2.4.2     Metal Wall Panel Assemblies

  a.     R-Value:   19

1.2.5     Air Infiltration for Metal Roof Panels

 Air leakage through assembly must not exceed 0.06 cfm/sq.ft. of roof area
 when tested according to ASTM E 168 at negative test-pressure difference of
 1.57 lb/sq.ft.

1.2.6     Air Infiltration for Metal Wall Panels

 Air leakage through assembly of not more than 0.06 cfm/sq.ft. of wall area
 when tested according to ASTM E 283 at static-air-pressure difference of
 6.24 lbf/sq.ft.

1.2.7     Water Penetration for Metal Roof Panels

 No water penetration when tested according to ASTM E 1646 at test-pressure
 difference of 2.86 lbf/sq.ft.

1.2.8     Water Penetration for Metal Wall Panels

 No water penetration when tested according to ASTM E 331 at a minimum
 differential pressure of 20 percent of inward-acting, wind-load design
 pressure of not less than 6.24 lbf/sq.ft. . and not more than 12 lbf/sq. ft.

1.2.9     Wind-Uplift Resistance

 Provide metal roof panel assemblies that comply with ASCE 7-05,.

1.2.10     Drift Provisions

 Lateral deflections, or drift, at the roof level of a structure in relation
 to the floor or slab on grade, caused by deflection of horizontal force
 resisting elements, shall be less than 0.75 inches.



                                SECTION 13 34 19   Page 8
Design MET Facility                                                        5490419


1.3     DEFINITIONS

 ASTM DEF applies to this definition paragraph.

        a.   Bay: Dimension between main frames measured normal to frame (at
             centerline of frame) for interior bays, and dimension from
             centerline of first interior main frame measured normal to end
             wall (outside face of end-wall girt) for end bays.

        b.   Building Length: Dimension of the building measured perpendicular
             to main framing from end wall to end wall (outside face of girt to
             outside face of girt).

        c.   Building Width: Dimension of the building measured parallel to
             main framing from sidewall to sidewall (outside face of girt to
             outside face of girt).

        d.   Clear Span: Distance between supports of beams, girders, or
             trusses (measured from lowest level of connecting area of a column
             and a rafter frame or knee).

        e.   Eave Height: Vertical dimension from finished floor to eave (the
             line along the sidewall formed by intersection of the planes of
             the roof and wall).

        f.   Clear Height under Structure: Vertical dimension from finished
             floor to lowest point of any part of primary or secondary
             structure, not including crane supports, located within clear span.

        g.   Terminology Standard: Refer to MBMA "Metal Building Systems
             Manual" for definitions of terms for metal building system
             construction not otherwise defined in this Section or in
             referenced standards.

1.4     SYSTEM DESCRIPTION

 General: Provide a complete, integrated set of mutually dependent
 components and assemblies that form a metal building system capable of
 withstanding structural and other loads, thermally induced movement, and
 exposure to weather without failure or infiltration of water into building
 interior. Include primary and secondary framing, metal roof panels, metal
 wall panels, and accessories complying with requirements indicated.

        a.Provide metal building system of size and with spacing, slopes, and
            spans indicated.

1.4.1     Primary Frame Type

        a.   Rigid Clear Span:   Solid-member, structural-framing system without
             interior columns.

1.4.2     Fixed End-Wall Framing

 Provide manufacturer's standard fixed end wall, for buildings not required
 to be expandable, consisting of primary frame, capable of supporting
 one-half of a bay design load, and end-wall columns.




                               SECTION 13 34 19   Page 9
Design MET Facility                                                     5490419


1.4.3     Secondary Frame Type

 Provide manufacturer's standard purlins and joists and flush-framed girts.

1.4.4     Eave Height

 Eave height must be Manufacturer's standard height, as indicated by nominal
 height on Drawings.The eave height must be based off the interior haunch
 height of minimum of 18'-0" above finish floor.

1.4.5     Bay Spacing

 Bay Spacing must be As determined by manufacturer.

1.4.6     Roof Slope

 Roof slope must be 2 inches per 12 inches.

1.4.7     Roof System

 Provide manufacturer's standard vertical-rib, standing-seam metal roof
 panels with insulation.

1.4.8     Exterior Wall System

 Provide manufacturer's standard field-assembled, insulated metal wall panels
  complete with vapor barrier conforming to ASTM E 96/E 96M.

1.5     SUBMITTALS

 Submit the following in accordance with Section 01 33 00 SUBMITTAL
 PROCEDURES:

        SD-01 Preconstruction Submittals

            Manufacturer's Qualifications

        SD-02 Shop Drawings

            Detail Drawings

        SD-03 Product Data

            Manufacturer's data indicating percentage of recycle material of
            the following to verify sustainable acquisition compliance

            Manufacturer's catalog data

        SD-04 Samples

            Coil Stock, 12 inches long by the actual panel width

            Roof Panels, 12 inches long by actual panel width

            Wall Panels, 12 inches long by actual panel width

            Fasteners

            Metal Closure Strips250 millimeter 10 inches long of each type


                              SECTION 13 34 19   Page 10
Design MET Facility                                                      5490419



             Insulation, approximately 200 by 280 millimeter 8 by 11 inches

             Vapor Barrier

             Manufacturer's color charts and chips,4 by 4 inches

        SD-05 Design Data

             Manufacturer's descriptive and technical literature

             Manufacturer's building design analysis

        SD-06 Test Reports

             test reports

             Coatings and base metals

             Factory Color Finish Performance Requirements

        SD-07 Certificates

             system components

             Coil Stock certification

             Aluminized Steel Repair Paint

             Galvanizing Repair Paint

             Enamel Repair Paint

             Qualification of Manufacturer

             Qualification of Erector

        SD-08 Manufacturer's Instructions

             Installation of Roof and Wall panels

             shipping, handling, and storage

        SD-11 Closeout Submittals

             Manufacturer's Warranty

             Contractor's Warranty for Installation

1.6     QUALITY ASSURANCE

1.6.1     Pre-Erection Conference

 After submittals are received and approved but before metal building system
 work, including associated work, is performed, the Contracting Officer will
 hold a pre-erection conference to review the following:

        a.   The detail drawings, specifications, and manufacturer's
             descriptive and technical literature.


                             SECTION 13 34 19   Page 11
Design MET Facility                                                      5490419



        b.   Finalize construction schedule and verify availability of
             materials, erector's personnel, equipment, and facilities needed
             to make progress and avoid delays

        c.   Methods and procedures related to metal building system erection,
             including, but not limited to: qualification of manufacturer,
             qualification of erector, manufacturer's catalog data, building
             design analysis, written instructions and test reports.

        d.   Support conditions for compliance with requirements, including
             alignment between and erection of structural members

        e.   Flashing, special roofing and siding details, roof and wall
             penetrations, openings, and condition of other construction that
             will affect metal building system, including coatings and base
             metals, factory color finish performance requirements, system
             components, and certificates for coil stock.

        f.   Governing regulations and requirements for, certificates,
             insurance, tests and inspections if applicable

        g.   Temporary protection requirements for metal panel assembly during
             and after installation

        h.   Samples of aluminized steel repair paint, galvanizing repair paint,
             and enamel repair paint.

1.6.1.1      Pre-Roofing and Siding Installation Conference

 After structural framing system erection and approval but before roofing,
 siding, insulation and vapor barrier work, including associated work, is
 performed; the Contracting Officer will hold a pre-roofing and siding
 conference to review the following:

        a.   Examine purlins, sub-girts and formed shapes conditions for
             compliance with requirements, including flatness and attachment to
             structural members.

        b.   Review structural limitations of purlins, sub-girts and formed
             shapes during and after roofing and siding.

        c.   Review flashings, special roof and wall details, roof drainage,
             roof and wall penetrations, roof equipment curbs, and condition of
             other construction that will affect the metal building system.

        d.   Review temporary protection requirements for metal roof and wall
             panels' assembly during and after installation.

        e.   Review roof and wall observation and repair procedures after metal
             building system erection.

1.6.2     Manufacturer's Technical Representative

 The representative must have authorization from manufacturer to approve
 field changes and be thoroughly familiar with the products, erection of
 structural framing and installation of roof and wall panels in the
 geographical area where construction will take place.



                             SECTION 13 34 19   Page 12
Design MET Facility                                                      5490419


1.6.3    Manufacturer's Qualifications

 Metal building system manufacturer must have a minimum of five (5) years
 experience as a quailed manufacturer of metal building systems and
 accessory products.

 Provide engineering services by an authorized currently licensed engineer
 in the geographical area where construction will take place, having a
 minimum of four (4) years experience as an engineer knowledgeable in
 building design analysis, protocols and procedures for the "Metal Building
 Systems Manual" (MBMA MBSM); ASCE 7-05, the building code in the geographic
 area where the construction will take place and ASTM E 1592.

 Provide certified engineering calculations using the products submitted for:

        a.   Roof and Wall Wind Loads with basic wind speed, exposure category,
             co-efficient, importance factor, designate type of facility,
             negative pressures for each zone, methods and requirements of
             attachment.

        b.   Roof Dead and Live Loads

        c.   Collateral Loads

        d.   Foundation Loads

        e.   Roof Snow Load

        f.   Seismic Loads

1.6.4    Qualification of Erection Contractor

 An experienced erector who has specialized in erecting and installing work
 similar in material, design, and extent to that indicated for this Project
 and must be approved and certified by the metal building system
 manufacturer.

1.6.5    Single Source

 Obtain primary and secondary components and structural framing members,
 each type of metal roof, wall and liner panel assemblies, clips, closures
 and other accessories from the standard products of the single source from
 a single manufacturer to operate as a complete system for the intended use.

1.6.6    Welding

 Qualify procedures and personnel according to AWS A5.1/A5.1M, AWS D1.1/D1.1M,
 and AWS D1.3/D1.3M."

1.6.7    Structural Steel

 Comply with AISC 325, AISC 341 for seismic impacted designs, AISC 350, and
 AISC 360, for design requirements and allowable stresses.

1.6.8    Cold-Formed Steel

 Comply with AISC/AISI 121 and AISI SG03-3 for design requirements and
 allowable stresses.



                                SECTION 13 34 19   Page 13
Design MET Facility                                                         5490419


1.6.9     Fire-Resistance Ratings

 Where indicated, provide metal panels identical to those of assemblies
 tested for fire resistance per ASTM E 119 by a qualified testing agency.
 Identify products with appropriate markings of applicable testing agency.

 Indicate design designations from UL Bld Mat Dir or from the listings of
 another qualified testing agency. Combustion Characteristics must conform
 to ASTM E 136.

1.6.10        Surface-Burning Characteristics

 Provide metal panels having insulation and vapor barrier material with the
 following surface-burning characteristics as determined by testing
 identical products according to ASTM E 84 by a qualified testing agency.
 Identify products with appropriate markings of applicable testing agency
 showing:

         a.    Flame-Spread Index: 25 or less.
         b.    Smoke-Developed Index: 450 or less.

1.6.11        Fabrication

 Fabricate and finish metal panels and accessories at the factory to
 greatest extent possible, by manufacturer's standard procedures and
 processes and as necessary to fulfill indicated performance requirements.
 Comply with indicated profiles with dimensional and structural requirements

 Provide metal panel profile, including major ribs and intermediate
 stiffening ribs, if any, for full length of panel. Aluminum and
 aluminum-alloy sheet and plate must conform to ASTM B 209.

 Fabricate metal panel side laps with factory-installed captive gaskets or
 separator strips that provide a tight seal and prevent metal-to-metal
 contact, in a manner that will seal weather-tight and minimize noise from
 movements within panel assembly.

 Sheet Metal Accessories: Fabricate flashing and trim to comply with
 recommendations in SMACNA 1793 that apply to the design, dimensions, metal,
 and other characteristics of item indicated:

         a.    Form exposed sheet metal accessories that are without excessive
               oil canning, buckling, and tool marks and that are true to line
               and levels indicated, with exposed edges folded back to form hems.

         b.    End Seams: Fabricate nonmoving seams with flat-lock seams.   Form
               seams and seal with epoxy seam sealer. Rivet joints for
               additional strength.

         c.    Sealed Joints: Form non-expansion but movable joints in metal to
               accommodate elastomeric sealant to comply with SMACNA standards.

         d.    Conceal fasteners and expansion provisions where possible.
               Exposed fasteners are not allowed on faces of accessories exposed
               to view.

         e.    Fabricate cleats and attachment devices of size and metal
               thickness recommended by SMACNA or by metal building system
               manufacturer for application, but not less than thickness of metal


                               SECTION 13 34 19   Page 14
Design MET Facility                                                   5490419


            being secured.

1.6.12     Finishes

 Comply with NAAMM AMP 500 for recommendations for applying and designating
 finishes.

 Appearance of Finished Work: Noticeable variations in same piece are not
 acceptable. Variations in appearance of adjoining components are
 acceptable if they are within the range of approved Samples and are
 assembled or installed to minimize contrast.

1.7     SHIPPING, HANDLING AND STORAGE

1.7.1     Delivery

 Package and deliver components, sheets, metal panels, and other
 manufactured items so as not to be damaged or deformed and protected during
 transportation and handling.

 Stack and store metal panels horizontally on platforms or pallets, covered
 with suitable weather-tight and ventilated covering to ensure dryness, with
 positive slope for drainage of water. Store in a manner to prevent
 bending, warping, twisting, and surface damage. Do not store metal wall
 panels in contact with other materials that might cause staining, denting,
 or other surface damage. Retain strippable protective covering on metal
 panel for entire period up to metal panel installation.

 Complete installation and concealment of plastic materials as rapidly as
 possible in each area of construction to minimize ultraviolet exposure.

1.8     PROJECT CONDITIONS

1.8.1     Weather Limitations

 Proceed with installation preparation only when existing and forecasted
 weather conditions permit Work to proceed without water entering into
 existing panel system or building.

1.8.2     Field Measurements

1.8.2.1     Established Dimensions for Foundations

 Comply with established dimensions on approved anchor-bolt plans,
 established foundation dimensions, and proceed with fabricating structural
 framing. Do not proceed without verifying field measurements. Coordinate
 anchor-bolt installation to ensure that actual anchorage dimensions
 correspond to established dimensions.

1.8.2.2     Established Dimensions for Metal Panels

 Where field measurements cannot be made without delaying the Work, either
 establish framing and opening dimensions and proceed with fabricating metal
 panels without field measurements, or allow for field trimming metal
 panels. Coordinate construction to ensure that actual building dimensions,
 locations of structural members, and openings correspond to established
 dimensions.




                               SECTION 13 34 19   Page 15
Design MET Facility                                                      5490419


1.8.2.3     Verification Record

 Verify locations of all framing and opening dimensions by field
 measurements before metal panel fabrication and indicate measurements on
 Shop Drawings.

1.9    COORDINATION

 Coordinate size and location of concrete foundations and casting of
 anchor-bolt inserts into foundation walls and footings. Concrete,
 reinforcement, and formwork requirements are specified in Division 03
 Section "Cast-in-Place Concrete".


 Coordinate installation of HVAC system equipment supports ductwork and
 supports piping and supports and accessories, which are specified in
 Division 23 - HEATING, VENTILATING AND AIR-CONDITIONING (HVAC).

 Coordinate installation of equipment supports and roof penetrations, which
 are specified in Division 07 - THERMAL AND MOISTURE PROTECTION.

 Coordinate metal panel assemblies with rain drainage work, flashing, trim,
 and construction of supports and other adjoining work to provide a
 leak-proof, secure, and non-corrosive installation.

1.10     WARRANTY

1.10.1     Building System Warranty

 Furnish manufacturer's no-dollar-limit warranty for the metal building
 system. The warranty period is to be no less than 20 years from the date
 of acceptance of the work and be issued directly to the Government. The
 warranty must provide that if within the warranty period, the metal
 building system shows evidence of deterioration resulting from defective
 materials and/or workmanship, correcting of any defects is the
 responsibility of the metal building system manufacturer. Repairs that
 become necessary because of defective materials and workmanship while metal
 building system is under warranty are to be performed within 32 hours after
 notification, unless additional time is approved by the Contracting
 Officer. Failure to perform repairs within 32 hours of notification will
 constitute grounds for having emergency repairs performed by others and
 will not void the warranty.

1.10.2     Roof System Weather-Tightness Warranty

 Furnish manufacturer's no-dollar-limit warranty for the metal panel
 system. The warranty period is to be no less than 20 years from the date
 of acceptance of the work and be issued directly to the Government.

 The warranty is to provide that if within the warranty period the roof
 panel system shows evidence of corrosion, perforation, rupture, lost of
 weather-tightness or excess weathering due to deterioration of the panel
 system resulting from defective materials and correction of the defective
 workmanship is to be the responsibility of the metal building system
 manufacturer.

 Repairs that become necessary because of defective materials and
 workmanship while roof panel system is under warranty are to be performed
 within 24 hours after notification, unless additional time is approved by


                            SECTION 13 34 19   Page 16
Design MET Facility                                                      5490419


 the Contracting Officer. Failure to perform repairs within 24 hours of
 notification will constitute grounds for having emergency repairs performed
 by others and not void the warranty.

1.10.3     Roof and Wall Panel Finish Warranty

 Furnish manufacturer's no-dollar-limit warranty for the metal panel
 system. The warranty period is to be no less than 20 years from the date
 of acceptance of the work and be issued directly to the Government.

 The warranty is to provide that if within the warranty period the metal
 panel system shows evidence of checking, delaminating cracking, peeling,
 chalk in excess of a numerical rating of eight, as determined by ASTM D 4214
  test procedures; or change colors in excess of five CIE or Hunter units in
 accordance with ASTM D 2244 or excess weathering due to deterioration of
 the panel system resulting from defective materials and finish or
 correction of the defective workmanship is to be the responsibility of the
 metal building system manufacturer.

 Liability under this warranty is exclusively limited to replacing the
 defective coated materials.

 Repairs that become necessary because of defective materials and
 workmanship while roof and wall panel system is under warranty are to be
 performed within 32 hours after notification, unless additional time is
 approved by the Contracting Officer. Failure to perform repairs within 32
 hours of notification will constitute grounds for having emergency repairs
 performed by others and not void the warranty.

PART 2     PRODUCTS

2.1     STRUCTURAL FRAMING MATERIALS

2.1.1     W-Shapes

 ASTM A 992/A 992M; ASTM A 572/A 572M or ASTM A 529/A 529M.

2.1.2     Channel, Angles, M-Shapes and S-Shapes

 ASTM A 36/A 36M; ASTM A 572/A 572M or ASTM A 529/A 529M.

2.1.3     Plate and Bar

 ASTM A 36/A 36M, ASTM A 572/A 572M or ASTM A 529/A 529M.

2.1.4     Steel Pipe

 ASTM A 36/A 36M, ASTM A 53/A 53M, ASTM A 572/A 572M or ASTM A 529/A 529M.

2.1.5     Cold-Formed and Hot Formed Hollow Structural Sections

 Cold formed:ASTM A 500/A 500M or ASTM B 221, ASTM B 221M.    Hot-formed:
 ASTM A 501.

2.1.6     Structural-Steel Sheet

 Hot-rolled, ASTM A 1011/A 1011M or cold-rolled, ASTM A 1008/A 1008M.




                            SECTION 13 34 19     Page 17
Design MET Facility                                                               5490419


2.1.7     Metallic-Coated Steel Sheet

 ASTM A 653/A 653M, ASTM A 606/A 606M.

2.1.8     Metallic-Coated Steel Sheet Pre-painted with Coil Stock Coating

 Steel sheet metallic coated by the hot-dip process and pre-painted by the
 coil-coating process to comply with ASTM A 755/A 755M.

         a. Zinc-Coated (Galvanized) Steel Sheet:        ASTM A 653/A 653M, and
         ASTM A 123/A 123M.

2.1.9     High-Strength Bolts, Nuts, and Washers

 ASTM A 325, heavy hex steel structural bolts; ASTM A 563 heavy hex
 carbon-steel nuts; and ASTM F 436 hardened carbon-steel washers.

         Finish:       Mechanically deposited zinc coating, ASTM B 695.

         Tension-Control, High-Strength Bolt-Nut-Washer Assemblies:       ASTM F 1852,
         heavy-hex-head steel structural bolts with spline.

               Finish:     Mechanically deposited zinc coating, ASTM B 695 .

2.1.10        Non-High-Strength Bolts, Nuts, and Washers

 ASTM A 307, ASTM A 563, and ASTM F 844.

         Finish: ASTM B 695.

2.1.11        Anchor Rods

 ASTM F 1554 .

         a.    Configuration: Straight.
         b.    Nuts: ASTM A 563 hex carbon steel.
         c.    Plate Washers: ASTM A 36/A 36M carbon steel.
         d.    Washers: ASTM F 436 hardened carbon steel.
         e.    Finish: Mechanically deposited zinc coating, ASTM B 695.

2.1.12        Threaded Rods

 ASTM A 193/A 193M .

         a.    Nuts: ASTM A 563 hex carbon steel.
         b.    Washers: ASTM F 436 hardened carbon steel.
         c.    Finish: Mechanically deposited zinc coating, ASTM B 695.

2.1.13        Primer

 SSPC-Paint 15, Type I, red oxide.

2.2     FABRICATION

2.2.1     General

 Comply with MBMA MBSM - "Metal Building Systems Manual":          Chapter IV,
 Section 9, "Fabrication and Erection Tolerances."



                                  SECTION 13 34 19   Page 18
Design MET Facility                                                      5490419


2.3     STRUCTURAL FRAMING

2.3.1     General

 Clean all framing members to remove loose rust and mill scale. Provide 1
 shop coat of primer to an average dry film thickness of 1 mil according to
 SSPC SP 2. Balance of painting and coating procedures must conform to
 SSPC Paint 15 and SSPC A.

2.3.2     Primary Framing

 Manufacturer's standard structural primary framing system includes
 transverse and lean-to frames; rafter, rakes, and canopy beams; sidewall,
 intermediate, end-wall, and corner columns; and wind bracing designed to
 withstand required loads and specified requirements. Provide frames with
 attachment plates, bearing plates, and splice members. Provide frame span
 and spacing indicated.

 Shop fabricate framing components by welding or by using high-strength
 bolts to the indicated size and section with base-plates, bearing plates,
 stiffeners, and other items required. Cut, form, punch, drill, and weld
 framing for bolted field erection.

        a. Rigid Clear-Span Frames: I-shaped frame sections fabricated from
        shop-welded, built-up steel plates or structural-steel shapes.
        Interior columns are not permitted.

        b.   Frame Configuration:    Single gable .

        c.   Exterior Column Type:      Tapered.

        d.   Rafter Type:    Tapered.

2.3.3     Secondary Framing

 Manufacturer's standard secondary framing members, including purlins,
 girts, eave struts, flange bracing, base members, gable angles, clips,
 headers, jambs, and other miscellaneous structural members. Fabricate
 framing from cold-formed, structural-steel sheet or roll-formed,
 metallic-coated steel sheet pre-painted with coil coating, unless otherwise
 indicated.

 Shop fabricate framing components by roll-forming or break-forming to the
 indicated size and section with base-plates, bearing plates, stiffeners,
 and other plates required for erection. Cut, form, punch, drill, and weld
 secondary framing for bolted field connections to primary framing.

        a. Purlins: C or Z-shaped sections; fabricated from steel sheet,
        built-up steel plates, or structural-steel shapes; minimum depth As
        required to comply with system performance requirements .

        b. Girts: C or Z-shaped sections; fabricated from steel sheet,
        built-up steel plates, or structural-steel shapes. Form ends of
        Z-sections with stiffening lips angled 40 to 50 degrees to flange
        minimum depth as required to comply with system performance requirements.

        c. Eave Struts: Unequal-flange, C-shaped sections; fabricated from
        steel sheet, built-up steel plates, or structural-steel shapes; to
        provide adequate backup for metal panels.


                               SECTION 13 34 19    Page 19
Design MET Facility                                                          5490419



        d. Flange Bracing: Structural-steel angles or cold-formed structural
        tubing to stiffen primary frame flanges.

        e.   Sag Bracing:   Structural-steel angles.

        f.   Base or Sill Angles:   Zinc-coated (galvanized) steel sheet.

        g. Purlin and Girt Clips: Steel sheet. Provide galvanized clips
        where clips are connected to galvanized framing members.

        h. Secondary End-Wall Framing: Manufacturer's standard sections
        fabricated from zinc-coated (galvanized) steel sheet .

        i. Framing for Openings: Channel shapes; fabricated cold-formed,
        structural-steel sheet or structural-steel shapes. Frame head and jamb
        of door openings, and head, jamb, and sill of other openings.

        j. Miscellaneous Structural Members: Manufacturer's standard sections
        fabricated from cold-formed, structural-steel sheet; built-up steel
        plates; or zinc-coated (galvanized) steel sheet; designed to withstand
        required loads.

2.3.4     Bracing

 Provide adjustable wind bracing as follows:

        a.   Angles: Fabricated from structural-steel shapes to match primary
             framing, of size required to withstand design loads.

        b.   Rigid Portal Frames: Fabricate from shop-welded, built-up steel
             plates or structural-steel shapes to match primary framing; of
             size required to withstand design loads.

        c.   Fixed-Base Columns: Fabricate from shop-welded, built-up steel
             plates or structural-steel shapes to match primary framing; of
             size required to withstand design loads.

        d.   Bracing: Provide wind bracing using any method specified above,
             at manufacturer's option.

2.4     PANEL MATERIALS

2.4.1     Aluminum Sheet

 Roll-form aluminum panels to the specified profile, with fy = 40 ksi, .032"
 thickness and depth as indicated. Material must be plumb and true, and
 within the tolerances listed:

        a.   Aluminum Sheet conforming to ASTM B 209, AA ADM1 and AA ASD1.

        b. Individual panels to have continuous length to cover the entire
        length with no joints or seams and formed without warping, waviness,
        or ripples that are not part of the panel profile and free of damage to
        the finish coating system.

        c. Provide panels with thermal expansion and contraction consistent
        with the type of system specified.



                              SECTION 13 34 19   Page 20
Design MET Facility                                                        5490419


            1. Profile and coverage to be a minimum height and width from
            manufacturer's standard .

2.4.2    Steel Sheet

 Roll-form steel panels to the specified profile, with fy = 40 ksi, 24 gauge
 and depth as indicated. Material must be plumb and true, and within the
 tolerances listed:

        a. Aluminum-Zinc Alloy-coated Steel Sheet conforming to
        ASTM A 792/A 792M and AISI SG03-3.

        b. Individual panels to have continuous length to cover the entire
        length of any unbroken area with no joints or seams and formed without
        warping, waviness, or ripples that are not part of the panel profile
        and free of damage to the finish coating system.

        c. Provide panels with thermal expansion and contraction consistent
        with the type of system specified;

              profile and coverage to be a minimum height and width from
            manufacturer's standard.

2.4.3    Insulated Panel Construction

 Shop fabricate or field assemble insulated panel construction with
 specified exterior and interior aluminum sheet in accordance with
 manufacturer's printed instructions.

 Insulation to be glass-fiber-ASTM C 991 conforming to ASTM C 553 and
 ASTM C 612 of thickness and density as required for the geographical area
 where construction will take place. Glass-Fiber and Mineral-Wool-Fiber are
 materials listed in the EPA's Comprehensive Procurement Guidelines (CPG)
 (http://www.epa.gov/cpg/), and are a component of sustainable acquisition
 compliance.

 Insulation fasteners to be adhesively attached, plate welded to projecting
 spindle anchors; capable of holding insulation of thickness indicated,
 secured in position with self-locking washer and complying with the
 following requirements:

        a. Plate: Perforated galvanized carbon-steel sheet, 0.030 inch (0.762
        mm) thick by 2 inches (50 mm) square.

        b. Spindle: Copper-coated, low carbon steel; fully annealed; 0.105
        inch (2.67 mm) in diameter; length to suit depth of insulation
        indicated.

        c. Insulation-Retaining Washers: Self-locking washers formed from
        0.016-inch- (0.41-mm-) thick galvanized steel sheet, with beveled edge
        for increased stiffness, sized as required to hold insulation securely
        in place, but not less than 1-1/2 inches (38 mm) square or in diameter.

        d. Anchor adhesive to be a product with demonstrated capability to
        bond insulation anchors securely to substrates indicated without
        damaging insulation, fasteners, and substrates.




                            SECTION 13 34 19   Page 21
Design MET Facility                                                      5490419


2.4.4    Finish

 All panels are to receive a factory-applied Kynar 500/Hylar 5000 finish
 consisting of a baked-on top-coat with a manufacturer's recommended prime
 coat conforming to the following:

        a. Metal Preparation: All metal is to have the surfaces carefully
        prepared for painting on a continuous process coil coating line by
        alkali cleaning, hot water rinsing, application of chemical conversion
        coating, cold water rinsing, sealing with acid rinse, and thorough
        drying.

        b. Prime Coating: A base coat of epoxy paint, specifically formulated
        to interact with the top-coat, is to be applied to the prepared
        surfaces by roll coating to a dry film thickness of 0.20 + 0.05 mils.
        This prime coat must be oven cured prior to application of finish coat.

        c. Exterior Finish Coating: Apply the finish coating over the primer
        by roll coating to dry film thickness of 0.80 + 5 mils (3.80 + 0.50
        mils for Vinyl Plastisol) for a total dry film thickness of 1.00 + 0.10
        mils (4.00 + 0.10 mils for Vinyl Plastisol). This finish coat must be
        oven-cured.

        d. Interior Finish Coating: Apply a wash-coat on the reverse side
        over the primer by roll coating to a dry film thickness of 0.30 + 0.05
        mils for a total dry film thickness of 0.50 + 0.10 mils. The wash-coat
        must be oven-cured.

        e. Color: The exterior finish chosen from the manufacturer's color
        charts and chips. The roof panels shall be Slate Grey and the wall
        panels shall be Sandstone.

        f. Physical Properties: Coating must conform to the industry and
        manufacturer's standard performance criteria as listed by the following
        certified test reports:

            Chalking: ASTM DEF
            Color Change and Conformity: ASTM D 2244
            Weatherometer: ASTM G 23 and ASTM D 822
            Humidity: ASTM D 2247 and ASTM D 714
            Salt Spray: ASTM B 117
            Chemical Pollution: ASTM D 1308
            Gloss at 60°: ASTM D 523
            Pencil Hardness: ASTM D 3363
            Reverse Impact: ASTM D 2794
            Flexibility: ASTM D 522
            Abrasion: ASTM D 968
            Flame Spread: ASTM E 84

2.4.5    Repair Of Finish Protection

 Repair paint for color finish enameled metal panel must be compatible paint
 of the same formula and color as the specified finish furnished by the
 metal panel manufacturer, conforming to ASTM A 780.




                            SECTION 13 34 19   Page 22
Design MET Facility                                                        5490419


2.5     MISCELLANEOUS METAL FRAMING

2.5.1     General

 Cold-formed metallic-coated steel sheet conforming to ASTM A 653/A 653M
 unless other wise indicated.

2.5.2     Fasteners for Miscellaneous Metal Framing

 Refer to the following paragraph "FASTENERS".

2.6     FASTENERS

2.6.1     General

 Type, material, corrosion resistance, size and      sufficient length to
 penetrate the supporting member a minimum of 1      inch with other properties
 required to fasten miscellaneous metal framing      members to substrates in
 accordance with the metal panel manufacturer's      and ASCE 7-05 requirements.

2.6.2     Exposed Fasteners

 Fasteners for metal panels to be corrosion resistant coated steel,
 aluminum, stainless steel, or nylon capped steel compatible with the sheet
 panel or flashing and of a type and size recommended by the manufacturer to
 meet the performance requirements and design loads. Fasteners for
 accessories to be the manufacturer's standard. Provide an integral metal
 washer matching the color of attached material with compressible sealing
 EPDM gasket approximately 3/32 inch thick.

2.6.3     Screws

 Screws to be corrosion resistant coated steel, aluminum and/or stainless
 steel being the type and size recommended by the manufacturer to meet the
 performance requirements.

2.6.4     Rivets

 Rivets to be closed-end type, corrosion resistant coated steel, aluminum or
 stainless steel where watertight connections are required.

2.6.5     Attachment Clips

 Fabricate clips from steel hot-dipped galvanized in accordance with
 ASTM A 653/A 653M or Series 300 stainless steel. Size, shape, thickness
 and capacity as required meeting the insulation thickness and design load
 criteria specified.

2.7     FRAMES AND MATERIALS FOR OPENINGS

2.7.1     Doors

 Fire-Rated and Non-Fire-Rated Door Assemblies conforming with NFPA 80 and
 based on testing according to NFPA 252 as specified in Division 08 -
 OPENINGS unless other wise indicated.

2.7.2     Windows

 Aluminum Window Assemblies conforming to AAMA 101 as specified in Division


                              SECTION 13 34 19   Page 23
Design MET Facility                                                   5490419


 08 - OPENINGS unless other wise indicated.

2.8     ACCESSORIES

2.8.1     General

 All accessories to be compatible with the metal panels; sheet metal
 flashing, trim, metal closure strips, caps and similar metal accessories
 must not be less than the minimum thickness specified for the metal panels.
 Exposed metal accessories/finishes to match the panels furnished, except as
 otherwise indicated. Molded foam rib, ridge and other closure strips to be
 non-absorbent closed-cell or solid-cell synthetic rubber or pre-molded
 neoprene to match configuration of the panels.

2.8.2     Roof and Wall Accessories and Specialties

 Aluminum roof curbs, equipment supports, roof hatches, dropout-type heat
 and smoke vents, hatch-type heat and smoke vents, gravity and roof ridge
 ventilators, wall louvers and other miscellaneous roof and wall equipment
 or penetrations conforming to AAMA, ASTM, and UL as specified in Division
 07 unless other wise indicated.

2.8.3     Insulation

 Faced, Glass-Fiber Blanket Insulation: ASTM C 665, Type II, blankets with
 non-reflecting coverings ; Class A, membrane-faced surface with a flame
 spread of 25 or less when tested in accordance with ASTM E 84.

2.8.3.1     Polyethylene Vapor Retarder

 Install polyethylene vapor retarder membrane over entire wall and roof
 surface. Use fully compatible polyethylene tape to seal the edges of the
 sheets to provide a vapor tight membrane. Lap sheets not less than 6 inch.
 Provide sufficient material to avoid inducing stresses in sheets due to
 strecthing or binding. All tears or punctures visible in the finished
 surface, at anytime during the construction process, must be sealed with
 polyethylene tape.

2.8.3.2     Wall Liner

 Securely fasten wall liner into place in accordance with the manufacturer's
 recommendation and in a neatly presented appearance.

2.8.4     Rubber Closure Strips

 Closed-cell, expanded cellular rubber conforming to ASTM D 1056 and
 ASTM D 1667; extruded or molded to the configuration of the specified metal
 panel and in lengths supplied by the metal panel manufacturer.

2.8.5     Metal Closure Strips

 Factory fabricated aluminum closure strips to be the same gauge , color,
 finish and profile of the specified panel.

2.8.6     2.6.6     Joint Sealants

2.8.6.1     Sealants

 Sealants are to be an approved gun type for use in hand or air-pressure


                              SECTION 13 34 19   Page 24
Design MET Facility                                                   5490419


 caulking guns at temperatures above 40 degrees F 4 degrees C (or frost-free
 application at temperatures above 10 degrees F minus 12 degrees C) with
 minimum solid content of 85 percent of the total volume. Sealant is to dry
 with a tough, durable surface skin which permits it to remain soft and
 pliable underneath, providing a weather-tight joint. No migratory staining
 is permitted on painted or unpainted metal, stone, glass, vinyl, or wood.

 Prime all joints to receive sealants with a compatible one-component or
 two-component primer as recommended by the metal panel manufacturer.

2.8.6.2     Shop-Applied

 Sealant for shop-applied caulking must be an approved gun grade, non-sag
 one component polysulfide or silicone conforming to ASTM C 920, Type II,
 and with a curing time to ensure the sealant's plasticity at the time of
 field erection.

2.8.6.3     Field-Applied

 Sealant for field-applied caulking must be an approved gun grade, non-sag
 one component polysulfide or two-component polyurethane with an initial
 maximum Shore A durometer hardness of 25, and conforming to ASTM C 920,
 Type II. Color to match panel colors.

2.8.6.4     Tape Sealant

 Pressure sensitive, 100% solid with a release paper backing; permanently
 elastic, non-sagging, non-toxic and non-staining as approved by the metal
 panel manufacturer.

2.9     SHEET METAL FLASHING AND TRIM

2.9.1     Fabrication

 Shop fabricate sheet metal flashing and trim where practicable to comply
 with recommendations in SMACNA 1793 that apply to design, dimensions,
 metal, and other characteristics of item indicated. Obtain field
 measurements for accurate fit before shop fabrication.

 Fabricate sheet metal flashing and trim without excessive oil canning,
 buckling, and tool marks and true to line and levels indicated, with
 exposed edges folded back to form hems.

2.10     FINISHES

2.10.1     General

 Comply with NAAMM AMP 500 for recommendations for applying and designating
 finishes.

2.10.2     Appearance of Finished Work

 Variations in appearance of abutting or adjacent pieces are acceptable if
 they are within one-half of the range of approved Samples. Noticeable
 variations in the same piece are not acceptable. Variations in appearance
 of other components are acceptable if they are within the range of approved
 Samples and are assembled or installed to minimize contrast.




                            SECTION 13 34 19   Page 25
Design MET Facility                                                     5490419


PART 3   EXECUTION

3.1   EXAMINATION

 Before erection proceeds examine with the erector present the concrete
 foundation dimensions, concrete and/or masonry bearing surfaces, anchor
 bolt size and placement, survey slab elevation, locations of bearing
 plates, and other embedment's to receive structural framing with the metal
 building manufacturer's templates and drawings before erecting any steel
 components for compliance with requirements for installation tolerances and
 other conditions affecting performance of the Work.

 Examine primary and secondary framing to verify that rafters, purlins,
 angles, channels, and other structural and metal panel support members and
 anchorages have been installed within alignment tolerances required by
 metal building manufacturer, UL, ASTM, ASCE 7-05 and as required by the
 building code for the geographical area where construction will take place.

 Examine roughing-in for components and systems penetrating metal roof or
 wall panels to verify actual locations of penetrations relative to seam
 locations of metal panels before metal roof or wall panel installation.

 Submit to the Contracting Officer a written report, endorsed by Erector,
 listing conditions detrimental to performance of the Work.

 Proceed with erection only after unsatisfactory conditions have been
 corrected.

3.2   PREPARATION

 Provide temporary shoring, guys, braces, and other supports during erection
 to keep the structural framing secure, plumb, and in alignment against
 temporary construction loading or loads equal in intensity of the building
 design loads. Remove temporary support systems when permanent structural
 framing, connections, and bracing are in place, unless otherwise indicated.

 Clean substrates of substances harmful to insulation, including removing
 projections capable of interfering with insulation attachment and
 performance.

 Miscellaneous Framing: Install sub-purlins, girts, angles, furring, and
 other miscellaneous support members or anchorage for the metal roof or wall
 panels, doors, windows, roof curbs, ventilators and louvers according to
 metal building manufacturer's written instructions.

3.3   ERECTION OF STRUCTURAL FRAMING

 Erect metal building system according to manufacturer's written erection
 instructions, approved shop drawings and other erection documents in
 accordance with MBMA MBSM - "Metal Building Systems Manual".

 Do not field cut, drill, or alter structural members without written
 approval from metal building system manufacturer's professional engineer
 and the Contracting Officer.

 Set structural framing accurately in locations and to elevations indicated
 and according to AISC 325 specifications. Maintain structural stability of
 frame during erection.



                          SECTION 13 34 19   Page 26
Design MET Facility                                                      5490419


 Clean and roughen concrete and masonry bearing surfaces prior to setting
 plates. Clean bottom surface of plates.

 Align and adjust structural framing before permanent bolt-up and
 connections. Perform necessary adjustments and alignment to compensate for
 changes or discrepancies in elevations.

 Maintain erection tolerances of structural framing in accordance with
 AISC 360.

3.4   METAL WALL PANEL INSTALLATION

 Provide metal wall panels of full length from sill to eave as indicated,
 unless otherwise indicated or restricted by shipping limitations. Anchor
 metal wall panels and other components of the Work securely in place, in
 accordance with MBMA MBSM.

 Erect wall panel system in accordance with the approved erection drawings,
 the printed instructions and safety precautions of the metal building
 manufacturer.

 Sheets are not to be subjected to overloading, abuse, or undue impact.    Do
 not install bent, chipped, or defective sheets.

 Sheets must be erected true and plumb and in exact alignment with the
 horizontal and vertical edges of the building, securely anchored, and with
 the indicated eave, and sill.

 Work is to allow for thermal movement of the wall panel, movement of the
 building structure, and to provide permanent freedom from noise due to wind
 pressure.

 Field cutting metal wall panels by torch is not permitted.

3.5   ROOF PANEL INSTALLATION

 Provide metal roof panels of full length from eave to ridge or eave to wall
 as indicated, unless otherwise indicated or restricted by shipping
 limitations. Anchor metal roof panels and other components of the Work
 securely in place in accordance with NRCA RWM and MBMA MBSM.

 Erect roofing system in accordance with the approved erection drawings, the
 printed instructions and safety precautions of the metal building
 manufacturer.

 Sheets are not to be subjected to overloading, abuse, or undue impact.    Do
 not install bent, chipped, or defective sheets.

 Sheets must be erected true and plumb and in exact alignment with the
 horizontal and vertical edges of the building, securely anchored, and with
 the indicated rake and eave overhang.

 Work must allow for thermal movement of the roofing, movement of the
 building structure, and provide permanent freedom from noise due to wind
 pressure.

 Field cutting metal roof panels by torch is not permitted.

 Roofing sheets must be laid with corrugations in the direction of the roof


                          SECTION 13 34 19   Page 27
Design MET Facility                                                   5490419


 slope. End laps of exterior roofing must not be less than 8 inches; the
 side laps of standard exterior corrugated sheets must not be not less than
 2-1/2 corrugations.

 Do not permit storage, walking, wheeling, and trucking directly on applied
 roofing materials. Provide temporary walkways, runways, and platforms of
 smooth clean boards or planks as necessary to avoid damage to the installed
 roofing materials, and to distribute weight to conform to the indicated
 live load limits of roof construction.

3.6    METAL PANEL FASTENER INSTALLATION

 Anchor metal panels and other components of the Work securely in place,
 using manufacturer's approved fasteners according to manufacturers' written
 instructions.

3.7    FLASHING, TRIM AND CLOSURE INSTALLATION

 A.   Comply with performance requirements, manufacturer's written
 installation instructions, and SMACNA 1793. Provide concealed fasteners
 where possible, and set units true to line and level as indicated. Install
 work with laps, joints, and seams that will be permanently watertight and
 weather resistant.

 B.   Sheet metalwork is to be accomplished to form weather-tight
 construction without waves, warps, buckles, fastening stresses or
 distortion, and allow for expansion and contraction. Cutting, fitting,
 drilling, and other operations in connection with sheet metal required to
 accommodate the work of other trades is to be performed by sheet metal
 mechanics.

3.8    DOOR AND FRAME INSTALLATION

 Install doors and frames plumb, rigid, properly aligned, and securely
 fastened in place according to manufacturer's written instructions.
 Coordinate installation with metal panel flashings and other components.
 Caulk and seal perimeter of each door frame with elastomeric sealant
 compatible with metal panels. Comply with installation requirements in
 Division 08 -OPENINGS.

3.9    WINDOW INSTALLATION

 Install windows plumb, rigid, properly aligned, without warp or rack of
 frames or sash, and securely fastened in place according to manufacturer's
 written instructions. Coordinate installation with metal panel flashings
 and other components. Caulk and seal perimeter of each window frame with
 elastomeric sealant compatible with for metal panels. Comply with
 installation requirements in Division 08 - OPENINGS.

3.10     ACCESSORY INSTALLATION

3.10.1     General

 Install accessories with positive anchorage to building and weather-tight
 mounting, and provide for thermal expansion. Coordinate installation with
 flashings and other components.




                             SECTION 13 34 19   Page 28
Design MET Facility                                                   5490419


3.10.2     Dissimilar Metals

 Where dissimilar metals contact one another or corrosive substrates are
 present, protect against galvanic action by painting dissimilar metal
 surfaces with bituminous coating, by applying rubberized-asphalt
 underlayment to each surface, or by other permanent separation techniques
 as recommended by the metal building manufacturer.

3.10.3     Gutters and Downspouts

 Comply with performance requirements, manufacturer's written installation
 instructions, and install sheet metal roof drainage items to produce
 complete roof drainage system according to SMACNA 1793 recommendations and
 as indicated. Coordinate installation of roof perimeter flashing with
 installation of roof drainage system.

3.10.4     Insulation

 Comply with performance requirements and manufacturer's written
 installation instructions. Install insulation concurrently with metal panel
 installation, in thickness indicated to cover entire roof and wall area, as
 specified in Division 07 - THERMAL AND MOISTURE PROTECTION.

3.10.5     Roof and Wall Accessories and Specialties

 Install roof and wall accessories and specialties complete with necessary
 hardware, anchors, dampers, weather guards, rain caps, and equipment
 supports as specified in Division 07 - THERMAL AND MOISTURE PROTECTION,
 unless other wise indicated.

3.11     CLEAN-UP AND PROTECTION

3.11.1     Structural Framing

 Clean all exposed structural framing at completion of installation. Remove
 metal shavings, filings, bolts, and wires from work area. Remove grease
 and oil films, excess sealants, handling marks, contamination from steel
 wool, fittings and drilling debris and scrub the work clean. Exposed metal
 surfaces to be free of dents, creases, waves, scratch marks, solder or weld
 marks, and damage to the finish coating.

3.11.2     Metal Panels

 Clean all exposed sheet metal work at completion of installation. Remove
 metal shavings, filings, nails, bolts, and wires from work area. Remove
 protective coverings/films, grease and oil films, excess sealants, handling
 marks, contamination from steel wool, fittings and drilling debris and
 scrub the work clean. Exposed metal surfaces to be free of dents, creases,
 waves, scratch marks, solder or weld marks, and damage to the finish
 coating.

3.11.3     Touch-Up Painting

 After erection, promptly clean, prepare, and prime or re-prime field
 connections, rust spots, and abraded surfaces of prime-painted structural
 framing and accessories. Clean and touch-up paint with manufacturer's
 touch-up paint.




                               SECTION 13 34 19   Page 29
Design MET Facility                                                   5490419


3.12     WARRANTY

3.12.1     MANUFACTURER'S WARRANTY

 Submit all manufacturers' signed warranties to Contracting Officer prior to
 final commissioning and acceptance.

3.12.2     CONTRACTOR'S WARRANTY for INSTALLATION

 Submit contractor's warranty for installation to the Contracting Officer
 prior to final commissioning and acceptance.




                            SECTION 13 34 19   Page 30
Design MET Facility                                                    5490419


3.12.3   CONTRACTOR'S FIVE (5) YEAR NO PENAL SUM WARRANTY


               CONTRACTOR'S FIVE (5) YEAR NO PENAL SUM WARRANTY
                                      FOR
                             METAL BUILDING SYSTEM

FACILITY DESCRIPTION:________________________________________________________

BUILDING NUMBER:_____________________________________________________________

CORPS OF ENGINEERS CONTRACT NUMBER:__________________________________________


                                  CONTRACTOR


CONTRACTOR:__________________________________________________________________
ADDRESS:_____________________________________________________________________

POINT OF CONTACT:____________________________________________________________

TELEPHONE NUMBER:____________________________________________________________


                                    OWNER


OWNER:_______________________________________________________________________
ADDRESS:_____________________________________________________________________

POINT OF CONTACT:____________________________________________________________

TELEPHONE NUMBER:____________________________________________________________


                              CONSTRUCTION AGENT


CONSTRUCTION AGENT:__________________________________________________________
ADDRESS:_____________________________________________________________________

POINT OF CONTACT:____________________________________________________________
_
TELEPHONE NUMBER:____________________________________________________________




                          SECTION 13 34 19     Page 31
Design MET Facility                                                    5490419




               CONTRACTOR'S FIVE (5) YEAR NO PENAL SUM WARRANTY
                                      FOR
                             METAL BUILDING SYSTEM
                                  (continued)

THE METAL BUILDING SYSTEM INSTALLED ON THE ABOVE NAMED BUILDING IS WARRANTED
BY (____) FOR A PERIOD OF FIVE 5 YEARS AGAINST WORKMANSHIP AND MATERIAL
DEFICIENCIES, WIND DAMAGE AND STRUCTURAL FAILURE WITHIN PROJECT SPECIFIED
DESIGN LOADS, AND LEAKAGE. THE METAL BUILDING SYSTEM COVERED UNDER THIS
WARRANTY INCLUDES, BUT IS NOT LIMITED TO, THE FOLLOWING:

FRAMING AND STRUCTURAL MEMBERS, ROOFING AND SIDING PANELS AND SEAMS, INTERIOR
OR EXTERIOR GUTTERS AND DOWNSPOUTS, ACCESSORIES, TRIM, FLASHINGS AND
MISCELLANEOUS BUILDING CLOSURE ITEMS SUCH AS DOORS AND WINDOWS (WHEN
FURNISHED BY THE MANUFACTURER), CONNECTORS, COMPONENTS, AND FASTENERS, AND
OTHER SYSTEM COMPONENTS AND ASSEMBLIES INSTALLED TO PROVIDE A WEATHERTIGHT
SYSTEM; AND ITEMS SPECIFIED IN OTHER SECTIONS OF THESE SPECIFICATIONS THAT
BECOME PART OF THE METAL BUILDING SYSTEM.

ALL MATERIAL AND WORKMANSHIP DEFICIENCIES, SYSTEM DETERIORATION CAUSED BY
EXPOSURE TO THE ELEMENTS AND/OR INADEQUATE RESISTANCE TO SPECIFIED SERVICE
DESIGN LOADS, WATER LEAKS AND WIND UPLIFT DAMAGE MUST BE REPAIRED AS APPROVED
BY THE CONTRACTING OFFICER.

ALL MATERIAL DEFICIENCIES, WIND DAMAGE, STRUCTURAL FAILURE AND LEAKAGE
ASSOCIATED WITH THE METAL BUILDING SYSTEM COVERED UNDER THIS WARRANTY MUST BE
REPAIRED AS APPROVED BY THE CONTRACTING OFFICER.

THIS WARRANTY COVERS THE ENTIRE COST OF REPAIR OR REPLACEMENT, INCLUDING ALL
MATERIAL, LABOR, AND RELATED MARKUPS. THE ABOVE REFERENCED WARRANTY
COMMENCED ON THE DATE OF FINAL ACCEPTANCE ON (____) AND WILL REMAIN IN
EFFECT FOR STATED DURATION FROM THIS DATE.

SIGNED, DATED, AND NOTARIZED (BY COMPANY PRESIDENT)

______________________________________________________________
(Company President)                                     (Date)




                          SECTION 13 34 19   Page 32
Design MET Facility                                                    5490419



               CONTRACTOR'S FIVE (5) YEAR NO PENAL SUM WARRANTY
                                      FOR
                             METAL BUILDING SYSTEM
                                  (continued)

THE CONTRACTOR HEREBY SUPPLEMENTS THIS WARRANTY WITH WRITTEN WARRANTIES FROM
THE MANUFACTURER AND/OR INSTALLER OF THE METAL BUILDING SYSTEM, WHICH IS
SUBMITTED ALONG WITH THE CONTRACTOR'S WARRANTY. HOWEVER, THE CONTRACTOR IS
ULTIMATELY RESPONSIBLE FOR THIS WARRANTY AS OUTLINED IN THE SPECIFICATIONS
AND AS INDICATED IN THIS WARRANTY.


                           EXCLUSIONS FROM COVERAGE


1. NATURAL DISASTERS, ACTS OF GOD (LIGHTNING, FIRE, EXPLOSIONS, SUSTAINED
WIND FORCES IN EXCESS OF THE DESIGN CRITERIA, EARTHQUAKES, AND HAIL).

2. ACTS OF NEGLIGENCE OR ABUSE OR MISUSE BY GOVERNMENT OR OTHER
PERSONNEL,INCLUDING ACCIDENTS, VANDALISM, CIVIL DISOBEDIENCE, WAR, OR DAMAGE
CAUSED BY FALLING OBJECTS.

3. DAMAGE BY STRUCTURAL FAILURE, SETTLEMENT, MOVEMENT, DISTORTION, WARPAGE,
OR DISPLACEMENT OF THE BUILDING STRUCTURE OR ALTERATIONS MADE TO THE BUILDING.

4. CORROSION CAUSED BY EXPOSURE TO CORROSIVE CHEMICALS, ASH OR FUMES
GENERATED OR RELEASED INSIDE OR OUTSIDE THE BUILDING FROM CHEMICAL PLANTS,
FOUNDRIES, PLATING WORKS, KILNS, FERTILIZER FACTORIES, PAPER PLANTS, AND THE
LIKE.

5. FAILURE OF ANY PART OF THE BUILDING SYSTEM DUE TO ACTIONS BY THE OWNER
WHICH INHIBIT FREE DRAINAGE FROM THE ROOF, GUTTERS AND DOWNSPOUTS; OR
CONDITIONS WHICH CREATE PONDING WATER ON THE ROOF OR AGAINST THE BUILDING
SIDING.

6. THIS WARRANTY APPLIES TO THE METAL BUILDING SYSTEM. IT DOES NOT INCLUDE
ANY CONSEQUENTIAL DAMAGE TO THE BUILDING INTERIOR OR CONTENTS WHICH IS
COVERED BY THE WARRANTY OF CONSTRUCTION CLAUSE INCLUDED IN THIS CONTRACT.

7. THIS WARRANTY CANNOT BE TRANSFERRED TO ANOTHER OWNER WITHOUT WRITTEN
CONSENT OF THE CONTRACTOR AND THIS WARRANTY AND THE CONTRACT PROVISIONS TAKE
PRECEDENCE OVER ANY CONFLICTS WITH STATE STATUTES. REPORTS OF LEAKS AND
BUILDING SYSTEM DEFICIENCIES MUST BE RESPONDED TO WITHIN 48 HOURS OF RECEIPT
OF NOTICE BY TELEPHONE OR IN WRITING FROM EITHER THE OWNER, OR CONTRACTING
OFFICER. EMERGENCY REPAIRS, TO PREVENT FURTHER ROOF LEAKS, MUST BE INITIATED
IMMEDIATELY; A WRITTEN PLAN MUST BE SUBMITTED FOR APPROVAL TO REPAIR OR
REPLACE THIS SSSMR SYSTEM WITHIN SEVEN CALENDAR DAYS. ACTUAL WORK FOR
PERMANENT REPAIRS OR REPLACEMENT MUST BE STARTED WITHIN 30 DAYS AFTER RECEIPT
OF NOTICE, AND COMPLETED WITHIN A REASONABLE TIME FRAME. IF THE CONTRACTOR
FAILS TO ADEQUATELY RESPOND TO THE WARRANTY PROVISIONS, AS STATED




                          SECTION 13 34 19   Page 33
Design MET Facility                                                    5490419



               CONTRACTOR'S FIVE (5) YEAR NO PENAL SUM WARRANTY
                                      FOR
                             METAL BUILDING SYSTEM
                     (Exclusions from Coverage Continued)

IN THE CONTRACT AND AS CONTAINED HEREIN, THE CONTRACTING OFFICER MAY HAVE THE
METAL BUILDING SYSTEM REPLACED OR REPAIRED BY OTHERS AND CHARGE THE COST TO
THE CONTRACTOR. IN THE EVENT THE CONTRACTOR DISPUTES THE EXISTENCE OF A
WARRANTABLE DEFECT, THE CONTRACTOR MAY CHALLENGE THE OWNER'S DEMAND FOR
REPAIRS AND/OR REPLACEMENT DIRECTED BY THE OWNER OR CONTRACTING OFFICER
EITHER BY REQUESTING A CONTRACTING OFFICER'S DECISION, UNDER THE CONTRACT
DISPUTES ACT, OR BY REQUESTING THAT AN ARBITRATOR RESOLVE THE ISSUE. THE
REQUEST FOR AN ARBITRATOR MUST BE MADE WITHIN 48 HOURS OF BEING NOTIFIED OF
THE DISPUTED DEFECTS. UPON BEING INVOKED THE PARTIES MUST, WITHIN 10 DAYS
JOINTLY REQUEST A LIST OF FIVE (5) ARBITRATORS FROM THE FEDERAL MEDIATION AND
CONCILIATION SERVICE. THE PARTIES MUST CONFER WITHIN 10 DAYS AFTER RECEIPT
OF THE LIST TO SEEK AGREEMENT ON AN ARBITRATOR. IF THE PARTIES CANNOT AGREE
ON AN ARBITRATOR, THE CONTRACTING OFFICER AND THE PRESIDENT OF THE
CONTRACTOR'S COMPANY WILL STRIKE ONE (1) NAME FROM THE LIST ALTERNATIVELY
UNTIL ONE NAME REMAINS. THE REMAINING PERSON WILL BE THE DULY SELECTED
ARBITRATOR. THE COSTS OF THE ARBITRATION, INCLUDING THE ARBITRATOR'S FEE AND
EXPENSES, COURT REPORTER, COURTROOM OR SITE SELECTED ETC., MUST BE BORNE
EQUALLY BETWEEN THE PARTIES. EITHER PARTY DESIRING A COPY OF THE TRANSCRIPT
MUST PAY FOR THE TRANSCRIPT. A HEARING WILL BE HELD AS SOON AS THE PARTIES
CAN MUTUALLY AGREE. A WRITTEN ARBITRATOR'S DECISION WILL BE REQUESTED NOT
LATER THAN 30 DAYS FOLLOWING THE HEARING. THE DECISION OF THE ARBITRATOR
WILL NOT BE BINDING; HOWEVER, IT WILL BE ADMISSIBLE IN ANY SUBSEQUENT APPEAL
UNDER THE CONTRACT DISPUTES ACT.

POST A FRAMED COPY OF THIS WARRANTY IN THE MECHANICAL ROOM OR OTHER APPROVED
LOCATION DURING THE ENTIRE WARRANTY PERIOD.

        -- End of Section --




                          SECTION 13 34 19   Page 34
Design MET Facility                                                       5490419



                                SECTION 23 03 00.00 20

                      BASIC MECHANICAL MATERIALS AND METHODS
                                       01/07

PART 1     GENERAL

1.1     REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to within the text by the
 basic designation only.

            ASTM INTERNATIONAL (ASTM)

 ASTM B 117                           (2009) Standing Practice for Operating
                                      Salt Spray (Fog) Apparatus

            INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

 IEEE C2                              (2007; Errata 2006; Errata 2007; INT 44-56
                                      2007; INT 47, 49, 50, 52-56 2008; INT 57,
                                      58, 51, 48 2009) National Electrical
                                      Safety Code

            NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

 NEMA MG 1                            (2007; Errata 2008) Standard for Motors
                                      and Generators

 NEMA MG 10                           (2001; R 2007) Energy Management Guide for
                                      Selection and Use of Fixed Frequency
                                      Medium AC Squirrel-Cage Polyphase
                                      Induction Motors

 NEMA MG 11                           (1977; R 2007) Energy Management Guide for
                                      Selection and Use of Single Phase Motors

            NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

 NFPA 70                              (2008; AMD 1 2008) National Electrical
                                      Code - 2008 Edition

1.2     RELATED REQUIREMENTS

 This section applies to all sections of Divisions: 22, PLUMBING; and 23,
 HEATING, VENTILATING, AND AIR CONDITIONING of this project specification,
 unless specified otherwise in the individual section.

1.3     QUALITY ASSURANCE

1.3.1     Material and Equipment Qualifications

 Provide materials and equipment that are standard products of manufacturers
 regularly engaged in the manufacture of such products, which are of a
 similar material, design and workmanship. Standard products shall have
 been in satisfactory commercial or industrial use for 2 years prior to bid
 opening. The 2-year use shall include applications of equipment and


                            SECTION 23 03 00.00 20   Page 1
Design MET Facility                                                   5490419


 materials under similar circumstances and of similar size. The product
 shall have been for sale on the commercial market through advertisements,
 manufacturers' catalogs, or brochures during the 2 year period.

1.3.2     Alternative Qualifications

 Products having less than a two-year field service record will be
 acceptable if a certified record of satisfactory field operation for not
 less than 6000 hours, exclusive of the manufacturer's factory or laboratory
 tests, can be shown.

1.3.3     Service Support

 The equipment items shall be supported by service organizations. Submit a
 certified list of qualified permanent service organizations for support of
 the equipment which includes their addresses and qualifications. These
 service organizations shall be reasonably convenient to the equipment
 installation and able to render satisfactory service to the equipment on a
 regular and emergency basis during the warranty period of the contract.

1.3.4     Manufacturer's Nameplate

 Each item of equipment shall have a nameplate bearing the manufacturer's
 name, address, model number, and serial number securely affixed in a
 conspicuous place; the nameplate of the distributing agent will not be
 acceptable.

1.3.5     Modification of References

 In each of the publications referred to herein, consider the advisory
 provisions to be mandatory, as though the word, "shall" had been
 substituted for "should" wherever it appears. Interpret references in
 these publications to the "authority having jurisdiction", or words of
 similar meaning, to mean the Contracting Officer.

1.3.5.1     Definitions

 For the International Code Council (ICC) Codes referenced in the contract
 documents, advisory provisions shall be considered mandatory, the word
 "should" shall be interpreted as "shall." Reference to the "code official"
 shall be interpreted to mean the "Contracting Officer." For Navy owned
 property, references to the "owner" shall be interpreted to mean the
 "Contracting Officer." For leased facilities, references to the "owner"
 shall be interpreted to mean the "lessor." References to the "permit
 holder" shall be interpreted to mean the "Contractor."

1.3.5.2     Administrative Interpretations

 For ICC Codes referenced in the contract documents, the provisions of
 Chapter 1, "Administrator," do not apply. These administrative
 requirements are covered by the applicable Federal Acquisition Regulations
 (FAR) included in this contract and by the authority granted to the Officer
 in Charge of Construction to administer the construction of this project.
 References in the ICC Codes to sections of Chapter 1, shall be applied
 appropriately by the Contracting Officer as authorized by his
 administrative cognizance and the FAR.




                            SECTION 23 03 00.00 20   Page 2
Design MET Facility                                                   5490419


1.4     DELIVERY, STORAGE, AND HANDLING

 Handle, store, and protect equipment and materials to prevent damage before
 and during installation in accordance with the manufacturer's
 recommendations, and as approved by the Contracting Officer. Replace
 damaged or defective items.

1.5     ELECTRICAL REQUIREMENTS

 Furnish motors, controllers, disconnects and contactors with their
 respective pieces of equipment. Motors, controllers, disconnects and
 contactors shall conform to and have electrical connections provided under
 Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM. Furnish internal wiring for
 components of packaged equipment as an integral part of the equipment.
 Extended voltage range motors will not be permitted. Controllers and
 contactors shall have a maximum of 120 volt control circuits, and shall
 have auxiliary contacts for use with the controls furnished. When motors
 and equipment furnished are larger than sizes indicated, the cost of
 additional electrical service and related work shall be included under the
 section that specified that motor or equipment. Power wiring and conduit
 for field installed equipment shall be provided under and conform to the
 requirements of Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM.

1.6     ELECTRICAL INSTALLATION REQUIREMENTS

 Electrical installations shall conform to IEEE C2, NFPA 70, and
 requirements specified herein.

1.6.1     New Work

 Provide electrical components of mechanical equipment, such as motors,
 motor starters, control or push-button stations, float or pressure
 switches, solenoid valves, integral disconnects, and other devices
 functioning to control mechanical equipment, as well as control wiring and
 conduit for circuits rated 100 volts or less, to conform with the
 requirements of the section covering the mechanical equipment. Extended
 voltage range motors shall not be permitted. The interconnecting power
 wiring and conduit, control wiring rated 120 volts (nominal) and conduit,
 and the electrical power circuits shall be provided under Division 26,
 except internal wiring for components of package equipment shall be
 provided as an integral part of the equipment. When motors and equipment
 furnished are larger than sizes indicated, provide any required changes to
 the electrical service as may be necessary and related work as a part of
 the work for the section specifying that motor or equipment.

1.6.2     Modifications to Existing Systems

 Where existing mechanical systems and motor-operated equipment require
 modifications, provide electrical components under Division 26.

1.6.3     High Efficiency Motors

1.6.3.1     High Efficiency Single-Phase Motors

 Unless otherwise specified, single-phase fractional-horsepower
 alternating-current motors shall be high efficiency types corresponding to
 the applications listed in NEMA MG 11.




                          SECTION 23 03 00.00 20   Page 3
Design MET Facility                                                   5490419


1.6.3.2     High Efficiency Polyphase Motors

 Unless otherwise specified, polyphase motors shall be selected based on
 high efficiency characteristics relative to the applications as listed in
 NEMA MG 10. Additionally, polyphase squirrel-cage medium induction motors
 with continuous ratings shall meet or exceed energy efficient ratings in
 accordance with Table 12-6C of NEMA MG 1.

1.6.4     Three-Phase Motor Protection

 Provide controllers for motors rated one one horsepower and larger with
 electronic phase-voltage monitors designed to protect motors from
 phase-loss, undervoltage, and overvoltage. Provide protection for motors
 from immediate restart by a time adjustable restart relay.

1.7     INSTRUCTION TO GOVERNMENT PERSONNEL

 When specified in other sections, furnish the services of competent
 instructors to give full instruction to the designated Government personnel
 in the adjustment, operation, and maintenance, including pertinent safety
 requirements, of the specified equipment or system. Instructors shall be
 thoroughly familiar with all parts of the installation and shall be trained
 in operating theory as well as practical operation and maintenance work.

 Instruction shall be given during the first regular work week after the
 equipment or system has been accepted and turned over to the Government for
 regular operation. The number of man-days (8 hours per day) of instruction
 furnished shall be as specified in the individual section. When more than
 4 man-days of instruction are specified, use approximately half of the time
 for classroom instruction. Use other time for instruction with the
 equipment or system.

 When significant changes or modifications in the equipment or system are
 made under the terms of the contract, provide additional instruction to
 acquaint the operating personnel with the changes or modifications.

1.8     ACCESSIBILITY

 Install all work so that parts requiring periodic inspection, operation,
 maintenance, and repair are readily accessible. Install concealed valves,
 expansion joints, controls, dampers, and equipment requiring access, in
 locations freely accessible through access doors.

PART 2     PRODUCTS

 Not Used

PART 3     EXECUTION

3.1     PAINTING OF NEW EQUIPMENT

 New equipment painting shall be factory applied or shop applied, and shall
 be as specified herein, and provided under each individual section.

3.1.1     Factory Painting Systems

 Manufacturer's standard factory painting systems may be provided subject to
 certification that the factory painting system applied will withstand 125
 hours in a salt-spray fog test, except that equipment located outdoors


                          SECTION 23 03 00.00 20   Page 4
Design MET Facility                                                      5490419


 shall withstand 500 hours in a salt-spray fog test. Salt-spray fog test
 shall be in accordance with ASTM B 117, and for that test the acceptance
 criteria shall be as follows: immediately after completion of the test,
 the paint shall show no signs of blistering, wrinkling, or cracking, and no
 loss of adhesion; and the specimen shall show no signs of rust creepage
 beyond 0.125 inch on either side of the scratch mark.

 The film thickness of the factory painting system applied on the equipment
 shall not be less than the film thickness used on the test specimen. If
 manufacturer's standard factory painting system is being proposed for use
 on surfaces subject to temperatures above 120 degrees F, the factory
 painting system shall be designed for the temperature service.

3.1.2    Shop Painting Systems for Metal Surfaces

 Clean, pretreat, prime and paint metal surfaces; except aluminum surfaces
 need not be painted. Apply coatings to clean dry surfaces. Clean the
 surfaces to remove dust, dirt, rust, oil and grease by wire brushing and
 solvent degreasing prior to application of paint, except metal surfaces
 subject to temperatures in excess of 120 degrees F shall be cleaned to bare
 metal.

 Where more than one coat of paint is specified, apply the second coat after
 the preceding coat is thoroughly dry. Lightly sand damaged painting and
 retouch before applying the succeeding coat. Color of finish coat shall be
 aluminum or light gray.

        a.   Temperatures Less Than 120 Degrees F: Immediately after cleaning,
             the metal surfaces subject to temperatures less than 120 degrees F
             shall receive one coat of pretreatment primer applied to a minimum
             dry film thickness of 0.3 mil, one coat of primer applied to a
             minimum dry film thickness of one mil; and two coats of enamel
             applied to a minimum dry film thickness of one mil per coat.

        b.   Temperatures Between 120 and 400 Degrees F: Metal surfaces
             subject to temperatures between 120 and 400 degrees F shall
             receive two coats of 400 degrees F heat-resisting enamel applied
             to a total minimum thickness of 2 mils.

        c.   Temperatures Greater Than 400 Degrees F: Metal surfaces subject to
             temperatures greater than 400 degrees F shall receive two coats of
             600 degrees F heat-resisting paint applied to a total minimum dry
             film thickness of 2 mils.

         -- End of Section --




                          SECTION 23 03 00.00 20    Page 5
Design MET Facility                                                      5490419



                              SECTION 26 00 00.00 20

                      BASIC ELECTRICAL MATERIALS AND METHODS
                                       07/06

PART 1     GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to in the text by the
 basic designation only.

             ASTM INTERNATIONAL (ASTM)

 ASTM D 709                          (2001; R 2007) Laminated Thermosetting
                                     Materials

             INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

 IEEE C2                             (2007; Errata 2006; Errata 2007; INT 44-56
                                     2007; INT 47, 49, 50, 52-56 2008; INT 57,
                                     58, 51, 48 2009) National Electrical
                                     Safety Code

 IEEE C57.12.28                      (2005) Standard for Pad-Mounted Equipment
                                     - Enclosure Integrity

 IEEE C57.12.29                      (2005) Pad-Mounted Equipment - Enclosure
                                     Integrity for Coastal Environments

 IEEE Std 100                        (2000) The Authoritative Dictionary of
                                     IEEE Standards Terms

             NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

 NEMA 250                            (2008) Enclosures for Electrical Equipment
                                     (1000 Volts Maximum)

             NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

 NFPA 70                             (2008; AMD 1 2008) National Electrical
                                     Code - 2008 Edition

1.2   RELATED REQUIREMENTS

 This section applies to certain sections of Division 02, EXISTING CONDITIONS
  Divisions 22 and 23, PLUMBING and HEATING VENTILATING AND AIR CONDITIONING.
 This section applies to all sections of Division 26 and 33, ELECTRICAL and
 UTILITIES, of this project specification unless specified otherwise in the
 individual sections. This section has been incorporated into, and thus,
 does not apply to, and is not referenced in the following sections.

         Section 26 51 00 INTERIOR LIGHTING
         Section 26 56 00 EXTERIOR LIGHTING
         Section 33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT




                          SECTION 26 00 00.00 20   Page 1
Design MET Facility                                                       5490419


1.3     DEFINITIONS

        a.   Unless otherwise specified or indicated, electrical and
             electronics terms used in these specifications, and on the
             drawings, shall be as defined in IEEE Std 100.

        b.   The technical sections referred to herein are those specification
             sections that describe products, installation procedures, and
             equipment operations and that refer to this section for detailed
             description of submittal types.

        c.   The technical paragraphs referred to herein are those paragraphs
             in PART 2 - PRODUCTS and PART 3 - EXECUTION of the technical
             sections that describe products, systems, installation procedures,
             equipment, and test methods.

1.4     ELECTRICAL CHARACTERISTICS

 Electrical characteristics for this project shall be as indicated.   Final
 connections to the power distribution system at the existing pole shall be
 made by the Contractor as directed by the Contracting Officer.

1.5     ADDITIONAL SUBMITTALS INFORMATION

 Submittals required in other sections that refer to this section must
 conform to the following additional requirements as applicable.

1.5.1     Shop Drawings (SD-02)

 Include wiring diagrams and installation details of equipment indicating
 proposed location, layout and arrangement, control panels, accessories,
 piping, ductwork, and other items that must be shown to ensure a
 coordinated installation. Wiring diagrams shall identify circuit terminals
 and indicate the internal wiring for each item of equipment and the
 interconnection between each item of equipment. Drawings shall indicate
 adequate clearance for operation, maintenance, and replacement of operating
 equipment devices.

1.5.2     Product Data (SD-03)

 Submittal shall include performance and characteristic curves.

1.6     QUALITY ASSURANCE

1.6.1     Regulatory Requirements

 In each of the publications referred to herein, consider the advisory
 provisions to be mandatory, as though the word, "shall" had been
 substituted for "should" wherever it appears. Interpret references in
 these publications to the "authority having jurisdiction," or words of
 similar meaning, to mean the Contracting Officer. Equipment, materials,
 installation, and workmanship shall be in accordance with the mandatory and
 advisory provisions of NFPA 70 unless more stringent requirements are
 specified or indicated.

1.6.2     Standard Products

 Provide materials and equipment that are products of manufacturers
 regularly engaged in the production of such products which are of equal


                            SECTION 26 00 00.00 20   Page 2
Design MET Facility                                                    5490419


 material, design and workmanship. Products shall have been in satisfactory
 commercial or industrial use for 2 years prior to bid opening. The 2-year
 period shall include applications of equipment and materials under similar
 circumstances and of similar size. The product shall have been on sale on
 the commercial market through advertisements, manufacturers' catalogs, or
 brochures during the 2-year period. Where two or more items of the same
 class of equipment are required, these items shall be products of a single
 manufacturer; however, the component parts of the item need not be the
 products of the same manufacturer unless stated in the technical section.

1.6.2.1    Alternative Qualifications

 Products having less than a 2-year field service record will be acceptable
 if a certified record of satisfactory field operation for not less than
 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is
 furnished.

1.6.2.2    Material and Equipment Manufacturing Date

 Products manufactured more than 3 years prior to date of delivery to site
 shall not be used, unless specified otherwise.

1.7   WARRANTY

 The equipment items shall be supported by service organizations which are
 reasonably convenient to the equipment installation in order to render
 satisfactory service to the equipment on a regular and emergency basis
 during the warranty period of the contract.

1.8   POSTED OPERATING INSTRUCTIONS

 Provide for each system and principal item of equipment as specified in the
 technical sections for use by operation and maintenance personnel. The
 operating instructions shall include the following:

      a.   Wiring diagrams, control diagrams, and control sequence for each
           principal system and item of equipment.

      b.   Start up, proper adjustment, operating, lubrication, and shutdown
           procedures.

      c.   Safety precautions.

      d.   The procedure in the event of equipment failure.

      e.   Other items of instruction as recommended by the manufacturer of
           each system or item of equipment.

 Print or engrave operating instructions and frame under glass or in
 approved laminated plastic. Post instructions where directed. For
 operating instructions exposed to the weather, provide weather-resistant
 materials or weatherproof enclosures. Operating instructions shall not
 fade when exposed to sunlight and shall be secured to prevent easy removal
 or peeling.

1.9   MANUFACTURER'S NAMEPLATE

 Each item of equipment shall have a nameplate bearing the manufacturer's
 name, address, model number, and serial number securely affixed in a


                         SECTION 26 00 00.00 20   Page 3
Design MET Facility                                                        5490419


 conspicuous place; the nameplate of the distributing agent will not be
 acceptable.

1.10     FIELD FABRICATED NAMEPLATES

 ASTM D 709. Provide laminated plastic nameplates for each equipment
 enclosure, relay, switch, and device; as specified in the technical
 sections or as indicated on the drawings. Each nameplate inscription shall
 identify the function and, when applicable, the position. Nameplates shall
 be melamine plastic, 0.125 inch thick, white with black center core.
 Surface shall be matte finish. Corners shall be square. Accurately align
 lettering and engrave into the core. Minimum size of nameplates shall be
 one by 2.5 inches. Lettering shall be a minimum of 0.25 inch high normal
 block style.

1.11     WARNING SIGNS

 Provide warning signs for the enclosures of electrical equipment including
 substations, pad-mounted transformers, pad-mounted switches, generators,
 and switchgear having a nominal rating exceeding 600 volts.

         a.    When the enclosure integrity of such equipment is specified to be
               in accordance with IEEE C57.12.28 or IEEE C57.12.29, such as for
               pad-mounted transformers and pad-mounted SF6 switches, provide
               self-adhesive warning signs on the outside of the high voltage
               compartment door(s). Sign shall be a decal and shall have nominal
               dimensions of 7 by 10 inches with the legend "DANGER HIGH VOLTAGE"
               printed in two lines of nominal 2 inch high letters. The word
               "DANGER" shall be in white letters on a red background and the
               words "HIGH VOLTAGE" shall be in black letters on a white
               background. Decal shall be Panduit No. PPSO710D72 or approved
               equal.

1.12     ELECTRICAL REQUIREMENTS

 Electrical installations shall conform to IEEE C2, NFPA 70, and
 requirements specified herein.

1.13     INSTRUCTION TO GOVERNMENT PERSONNEL

 Where specified in the technical sections, furnish the services of
 competent instructors to give full instruction to designated Government
 personnel in the adjustment, operation, and maintenance of the specified
 systems and equipment, including pertinent safety requirements as required.
 Instructors shall be thoroughly familiar with all parts of the installation
 and shall be trained in operating theory as well as practical operation and
 maintenance work. Instruction shall be given during the first regular work
 week after the equipment or system has been accepted and turned over to the
 Government for regular operation. The number of man-days (8 hours per day)
 of instruction furnished shall be as specified in the individual section.

PART 2        PRODUCTS

2.1    FACTORY APPLIED FINISH

 Electrical equipment shall have factory-applied painting systems which
 shall, as a minimum, meet the requirements of NEMA 250 corrosion-resistance
 test.



                            SECTION 26 00 00.00 20   Page 4
Design MET Facility                                                   5490419


PART 3    EXECUTION

3.1   FIELD APPLIED PAINTING

 Paint electrical equipment as required to match finish of adjacent surfaces
 or to meet the indicated or specified safety criteria.

3.2   FIELD FABRICATED NAMEPLATE MOUNTING

 Provide number, location, and letter designation of nameplates as
 indicated. Fasten nameplates to the device with a minimum of two
 sheet-metal screws or two rivets.

3.3   WARNING SIGN MOUNTING

 Provide the number of signs required to be readable from each accessible
 side, but space the signs a maximum of 30 feet apart.

         -- End of Section --




                         SECTION 26 00 00.00 20   Page 5
Design MET Facility                                                      5490419




                                SECTION 26 20 00

                          INTERIOR DISTRIBUTION SYSTEM

                                        01/07




PART 1   GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to in the text by the
 basic designation only.

            ASTM INTERNATIONAL (ASTM)

 ASTM B 1                           (2001; R 2007) Standard Specification for
                                    Hard-Drawn Copper Wire

 ASTM B 8                           (2004) Standard Specification for
                                    Concentric-Lay-Stranded Copper Conductors,
                                    Hard, Medium-Hard, or Soft

            NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

 NEMA C80.1                         (1994) Rigid Steel Conduit - Zinc Coated

 NEMA C80.3                         (1994) Electrical Metallic Tubing - Zinc
                                    Coated (EMT)

 NEMA FU 1                          (2002) Low Voltage Cartridge Fuses

 NEMA ICS 4                         (2000) Industrial Automation Control
                                    Products and Systems Section Terminal
                                    Blocks

 NEMA ICS 6                         (1993; R 2006) Standard for Industrial
                                    Controls and Systems Enclosures

 NEMA KS 1                          (2001) Enclosed and Miscellaneous
                                    Distribution Equipment Switches (600 Volts
                                    Maximum)

 NEMA TC 14                         (2002) Filament-Wound Reinforced
                                    Thermosetting Resin Conduit (RTRC) and
                                    Fittings

 NEMA TC 2                          (1998) Electrical Polyvinyl Chloride (PVC)
                                    Tubing and Conduit

 NEMA TC 3                          (1999) PVC Fittings for Use with Rigid PVC
                                    Conduit and Tubing

 NEMA WD 1                          (1999) General Color Requirements for


                            SECTION 26 20 00    Page 1
Design MET Facility                                                       5490419


                                   Wiring Devices

 NEMA WD 6                         (2002) Wiring Devices - Dimensional
                                   Specifications

           NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

 NFPA 70                           (2008; AMD 1 2008) National Electrical
                                   Code - 2008 Edition

           UNDERWRITERS LABORATORIES (UL)

 UL 1                              (2000) Flexible Metal Conduit

 UL 198E                           (1988; R 1988) Class R Fuses

 UL 20                             (2000; R 2002, Bul. 2002) General-Use Snap
                                   Switches

 UL 360                            (1996; R 2001, Bul. 2002) Liquid-Tight
                                   Flexible Steel Conduit

 UL 467                            (1993; R 2001) Grounding and Bonding
                                   Equipment

 UL 486A                           (1997; R 2001, Bul. 2002, 2003) Wire
                                   Connectors and Soldering Lugs for Use with
                                   Copper Conductors

 UL 486B                           (1997; R 2001, Bul. 2002, 2003) Wire
                                   Connectors for Use with Aluminum Conductors

 UL 486C                           (2000; R 2002) Splicing Wire Connectors

 UL 489                            (2002; R 2002, Bul. 2003) Molded-Case
                                   Circuit Breakers, Molded-Case Switches,
                                   and Circuit-Breaker Enclosures

 UL 498                            (2001; R 2002) Attachment Plugs and
                                   Receptacles

 UL 50                             (1995; R 1999, Bul. 2001) Enclosures for
                                   Electrical Equipment

 UL 510                            (1994; R 1998) Polyvinyl Chloride,
                                   Polyethylene, and Rubber Insulating Tape

 UL 514A                           (1996; R 2001, Bul. 2002) Metallic Outlet
                                   Boxes

 UL 514B                           (1997; R 2002, Bul. 2002) Fittings for
                                   Cable and Conduit

 UL 514C                           (1996; R 2002) Nonmetallic Outlet Boxes,
                                   Flush-Device Boxes, and Covers

 UL 6                              (2007) Standard for Electrical Rigid Metal
                                   Conduit-Steel



                           SECTION 26 20 00   Page 2
Design MET Facility                                                        5490419


 UL 651                                (1995; R 2002) Schedule 40 and 80 Rigid
                                       PVC Conduit

 UL 67                                 (1993; R 2002) Panelboards

 UL 797                                (2000; Bul. 2002) Electrical Metallic
                                       Tubing

 UL 83                                 (20086) Standard for
                                       Thermoplastic-Insulated Wires and Cables

 UL 854                                (1999; R 2002) Service-Entrance Cables

 UL 869A                               (1998; Bul. 2002) Reference Standard for
                                       Service Equipment

 UL 943                                (1993; R 2002, Bul. 2002) Ground-Fault
                                       Circuit-Interrupters

 1.2     RELATED REQUIREMENTS

 Section 26 00 00.00 20, "Basic Electrical Materials and Methods," applies
 to this section with additions and modifications specified herein.

1.3    SUBMITTALS

 The following shall be submitted in accordance with Section 01 33 00
 SUBMITTAL PROCEDURES:

       SD-02 Shop Drawings

            Panelboards

       SD-03 Product Data

            Receptacles

            Circuit breakers

            Switches

            Grounding Block

       SD-06 Test Reports

            600-volt wiring test

            Grounding system test

            Ground-fault receptacle test

       SD-07 Certificates

            Fuses

       SD-09 Manufacturer's Field Reports

            Transformer factory tests



                                SECTION 26 20 00   Page 3
Design MET Facility                                                         5490419


         SD-10 Operation and Maintenance Data

               Electrical Systems, Data Package 5

               Submit operation and maintenance data in accordance with Section
               01 78 23, "Operation and Maintenance Data" and as specified herein.

1.4     QUALITY ASSURANCE

1.4.1     Fuses

 Submit coordination data as specified in article entitled, "FUSES" of this
 section.

1.5     MAINTENANCE

1.5.1     Electrical Systems

 Submit operation and maintenance manuals for electrical systems that
 provide basic data relating to the design, operation, and maintenance of
 the electrical distribution system for the building. This shall include:

         a.    Manufacturers' operating and maintenance manuals on active
               electrical equipment.

PART 2        PRODUCTS

2.1     MATERIALS AND EQUIPMENT

 Materials, equipment, and devices shall, as a minimum, meet requirements of
 UL, where UL standards are established for those items, and requirements of
 NFPA 70.

2.2     CONDUIT AND FITTINGS

 Shall conform to the following:

2.2.1     Rigid Metallic Conduit

2.2.1.1        Rigid, Threaded Zinc-Coated Steel Conduit

 NEMA C80.1, UL 6.

2.2.2     Rigid Nonmetallic Conduit

 PVC Type EPC-40, and EPC-80 in accordance with NEMA TC 2,UL 651, or
 fiberglass conduit, in accordance with NEMA TC 14.

2.2.3     Electrical, Zinc-Coated Steel Metallic Tubing (EMT)

 UL 797, NEMA C80.3.

2.2.4     Flexible Metal Conduit

 UL 1.

2.2.4.1        Liquid-Tight Flexible Metal Conduit, Steel

 UL 360.


                                SECTION 26 20 00    Page 4
Design MET Facility                                                      5490419



2.2.5     Fittings for Metal Conduit, EMT, and Flexible Metal Conduit

 UL 514B. Ferrous fittings shall be cadmium- or zinc-coated in accordance
 with UL 514B.

2.2.5.1     Fittings for Rigid Metal Conduit and IMC

 Threaded-type.    Split couplings unacceptable.

2.2.5.2     Fittings for EMT

 Steel compression type.

2.2.6     Fittings for Rigid Nonmetallic Conduit

 NEMA TC 3, UL 514B.

2.3     OUTLET BOXES AND COVERS

 UL 514A, cadmium- or zinc-coated, if ferrous metal.       UL 514C, if
 nonmetallic.

2.4     CABINETS, JUNCTION BOXES, AND PULL BOXES

 Volume greater than 100 cubic inches, UL 50, hot-dip, zinc-coated, if sheet
 steel.

2.5     WIRES AND CABLES

 Wires and cables shall meet applicable requirements of NFPA 70 and UL for
 type of insulation, jacket, and conductor specified or indicated. Wires
 and cables manufactured more than 12 months prior to date of delivery to
 site shall not be used.

2.5.1     Conductors

 Conductors No. 8 AWG and larger diameter shall be stranded. Conductors No.
 10 AWG and smaller diameter shall be solid, except that conductors for
 remote control, alarm, and signal circuits, classes 1, 2, and 3, shall be
 stranded unless specifically indicated otherwise. Conductor sizes and
 ampacities shown are based on copper, unless indicated otherwise. All
 conductors shall be copper.

2.5.1.1     Equipment Manufacturer Requirements

 When manufacturer's equipment requires copper conductors at the
 terminations or requires copper conductors to be provided between
 components of equipment, provide copper conductors or splices, splice
 boxes, and other work required to satisfy manufacturer's requirements.

2.5.1.2     Minimum Conductor Sizes

 Minimum size for branch circuits shall be No. 12 AWG; for Class 1
 remote-control and signal circuits, No. 14 AWG; for Class 2 low-energy,
 remote-control and signal circuits, No. 16 AWG; and for Class 3 low-energy,
 remote-control, alarm and signal circuits, No. 22 AWG.




                               SECTION 26 20 00   Page 5
Design MET Facility                                                   5490419


2.5.2     Color Coding

 Provide for service, feeder, branch, control, and signaling circuit
 conductors. Color shall be green for grounding conductors and white for
 neutrals; except where neutrals of more than one system are installed in
 same raceway or box, other neutral shall be white with colored (not green)
 stripe. Color of ungrounded conductors in different voltage systems shall
 be as follows:

        a.   208/120 volt, three-phase

             (1)   Phase A - black

             (2)   Phase B - red

             (3)   Phase C - blue

2.5.3     Insulation

 Unless specified or indicated otherwise or required by NFPA 70, power and
 lighting wires shall be 600-volt, Type THWN/THHN conforming to UL 83,
 except that grounding wire may be type TW conforming to UL 83;
 remote-control and signal circuits shall be Type TW or TF, conforming to
 UL 83. Where lighting fixtures require 90-degree Centigrade (C)
 conductors, provide only conductors with 90-degree C insulation or better.

2.5.4     Bonding Conductors

 ASTM B 1, solid bare copper wire for sizes No. 8 AWG and smaller diameter;
 ASTM B 8, Class B, stranded bare copper wire for sizes No. 6 AWG and larger
 diameter.

2.5.5     Service Entrance Cables

 Service Entrance (SE) and Underground Service Entrance (USE) Cables, UL 854.

2.6     SPLICES AND TERMINATION COMPONENTS

 UL 486A and UL 486B, as applicable, for wire connectors and UL 510 for
 insulating tapes. Connectors for No. 10 AWG and smaller diameter wires
 shall be insulated, pressure-type in accordance with UL 486A or UL 486C
 (twist-on splicing connector). Provide solderless terminal lugs on
 stranded conductors.

2.7     DEVICE PLATES

 Provide UL listed, one-piece device plates for outlets to suit the devices
 installed. For metal outlet boxes, plates on unfinished walls shall be of
 zinc-coated sheet steel or cast metal having round or beveled edges. For
 nonmetallic boxes and fittings, other suitable plates may be provided.
 Plates on finished walls shall be satin finish stainless steel or
 brushed-finish aluminum, minimum 0.03 inch thick. Screws shall be
 machine-type with countersunk heads in color to match finish of plate.
 Sectional type device plates will not be permitted. Plates installed in
 wet locations shall be gasketed and UL listed for "wet locations."




                               SECTION 26 20 00   Page 6
Design MET Facility                                                   5490419


2.8     SWITCHES

2.8.1     Toggle Switches

 NEMA WD 1, UL 20, single pole, double pole, and three-way, totally enclosed
 with bodies of thermoplastic and/or thermoset plastic and mounting strap
 with grounding screw. Handles shall be brown thermoplastic. Wiring
 terminals shall be screw-type, side-wired. Contacts shall be
 silver-cadmium and contact arm shall be one-piece copper alloy. Switches
 shall be rated quiet-type ac only, 120/277 volts, with current rating and
 number of poles indicated.

2.8.2     Switch with Red Pilot Handle

 NEMA WD 1. Provide pilot lights that are integrally constructed as a part
 of the switch's handle. The pilot light shall be red and shall illuminate
 whenever the switch is closed or "on". The pilot lighted switch shall be
 rated 20 amps and 120 volts or 277 volts as indicated. Provide the
 circuit's neutral conductor to each switch with a pilot light.

2.8.3     Disconnect Switches

 NEMA KS 1. Provide heavy duty-type switches where indicated, where
 switches are rated higher than 240 volts, and for double-throw switches.
 Fused switches shall utilize Class R fuseholders and fuses, unless
 indicated otherwise. Switches serving as motor-disconnect means shall be
 horsepower rated. Provide switches in NEMA 1, enclosure unless noted
 otherwise per NEMA ICS 6.

2.8.4     Breakers Used as Switches

 For 120- and 277-Volt fluorescent fixtures, mark breakers "SWD" in
 accordance with UL 489.

2.9     RECEPTACLES

 UL 498, hard use, heavy-duty, grounding-type. Ratings and configurations
 shall be as indicated. Bodies shall be of brown as per NEMA WD 1. Face
 and body shall be thermoplastic supported on a metal mounting strap.
 Dimensional requirements shall be per NEMA WD 6. Provide screw-type,
 side-wired wiring terminals. Connect grounding pole to mounting strap.
 The receptacle shall contain triple-wipe power contacts and double or
 triple-wipe ground contacts.

2.9.1     Weatherproof Receptacles

 Provide in cast metal box with gasketed, weatherproof, cast-metal cover
 plate and gasketed cap over each receptacle opening. Provide caps with a
 spring-hinged flap. Receptacle shall be UL listed for use in "wet
 locations with plug in use."

2.9.2     Ground-Fault Circuit Interrupter Receptacles

 UL 943, duplex type for mounting in standard outlet box. Device shall be
 capable of detecting current leak of 6 milliamperes or greater and tripping
 per requirements of UL 943 for Class A GFI devices. Provide screw-type,
 side-wired wiring terminals or pre-wired (pigtail) leads.




                                SECTION 26 20 00   Page 7
Design MET Facility                                                   5490419


2.10     PANELBOARDS

 UL 67 and UL 50 having a short-circuit current rating as indicated.
 Panelboards for use as service disconnecting means shall additionally
 conform to UL 869A. Panelboards shall be circuit breaker-equipped. Design
 shall be such that individual breakers can be removed without disturbing
 adjacent units or without loosening or removing supplemental insulation
 supplied as means of obtaining clearances as required by UL. "Specific
 breaker placement" is required in panelboards to match the breaker
 placement indicated in the panelboard schedule on the drawings. Use of
 "Subfeed Breakers" is not acceptable unless specifically indicated
 otherwise. Main breaker shall be "separately" mounted "above" branch
 breakers. Where "space only" is indicated, make provisions for future
 installation of breakers. Panelboard locks shall be keyed same.
 Directories shall indicate load served by each circuit in panelboard.
 Directories shall also indicate source of service to panelboard (e.g.,
 Panel PA served from Panel MDP). Type directories and mount in holder
 behind transparent protective covering. Panelboards shall be listed and
 labeled for their intended use.

2.10.1     Panelboard Buses

 Support bus bars on bases independent of circuit breakers. Main buses and
 back pans shall be designed so that breakers may be changed without
 machining, drilling, or tapping. Provide isolated neutral bus in each
 panel for connection of circuit neutral conductors. Provide separate
 ground bus identified as equipment grounding bus per UL 67 for connecting
 grounding conductors; bond to steel cabinet.

2.10.2     Circuit Breakers

 UL 489, thermal magnetic-type having a minimum short-circuit current rating
 equal to the short-circuit current rating of the panelboard in which the
 circuit breaker shall be mounted. Breaker terminals shall be UL listed as
 suitable for type of conductor provided.   Series rated circuit breakers
 and plug-in circuit breakers are unacceptable.

2.10.2.1     Multipole Breakers

 Provide common trip-type with single operating handle. Breaker design
 shall be such that overload in one pole automatically causes all poles to
 open. Maintain phase sequence throughout each panel so that any three
 adjacent breaker poles are connected to Phases A, B, and C, respectively.

2.10.2.2     Circuit Breaker With GFCI

 UL 943 and NFPA 70. Provide with "push-to-test" button, visible indication
 of tripped condition, and ability to detect and trip on current imbalance
 of 6 milliamperes or greater per requirements of UL 943 for Class A GFCI
 devices, for personnel protection, and 20 milliamperes or greater per
 requirements of UL 943 for Class B GFCI per equipment protection.

2.10.2.3     Circuit Breakers for HVAC Equipment

 Circuit breakers for HVAC equipment having motors (group or individual)
 shall be marked for use with HACR type and UL listed as HACR type.




                              SECTION 26 20 00   Page 8
Design MET Facility                                                        5490419


2.11     ENCLOSED CIRCUIT BREAKERS

 UL 489. Individual molded case circuit breakers with voltage and
 continuous current ratings, number of poles, overload trip setting, and
 short circuit current interrupting rating as indicated. Enclosure type as
 indicated. Provide solid neutral.

2.12     FUSES

 NEMA FU 1. Provide complete       set of fuses for each fusible switch.
 Time-current characteristics      curves of fuses serving motors or connected in
 series with circuit breakers      shall be coordinated for proper operation.
 Submit coordination data for      approval. Fuses shall have voltage rating not
 less than circuit voltage.

2.12.1     Cartridge Fuses, Current Limiting Type (Class R)

 UL 198E, Class RK-1.    Associated fuseholders shall be Class R only.

2.13     MOTOR CONTROLLERS

2.13.1     Terminal Blocks

 NEMA ICS 4.

2.14     MANUAL MOTOR STARTERS (MOTOR RATED SWITCHES)

 Double pole designed for surface mounting with overload protection.

2.15     GROUNDING AND BONDING EQUIPMENT

 UL 467. Ground rods shall be copper-clad steel, with minimum diameter of
 3/4 in and minimum length of 10 ft.

2.16     NAMEPLATES

 Provide as specified in Section 26 00 00.00 20, "Basic Electrical Materials
 and Methods."

PART 3     EXECUTION

3.1     INSTALLATION

 Electrical installations shall conform to requirements of NFPA 70 and to
 requirements specified herein.

3.1.1     Underground Service

 Underground service conductors and associated conduit shall be continuous
 from service entrance equipment to outdoor power system connection.

3.1.2     Service Entrance Identification

 Service entrance disconnect devices, switches, and enclosures shall be
 labeled and identified as such.

3.1.2.1     Labels

 Wherever work results in service entrance disconnect devices in more than


                                SECTION 26 20 00   Page 9
Design MET Facility                                                      5490419


 one enclosure, as permitted by NFPA 70, each enclosure, new and existing,
 shall be labeled as one of several enclosures containing service entrance
 disconnect devices. Label, at minimum, shall indicate number of service
 disconnect devices housed by enclosure and shall indicate total number of
 enclosures that contain service disconnect devices. Provide laminated
 plastic labels conforming to paragraph entitled "Nameplates." Use
 lettering of at least 0.25 in in height, and engrave on black-on-white
 matte finish. Service entrance disconnect devices in more than one
 enclosure, shall be provided only as permitted by NFPA 70.

3.1.3     Wiring Methods

 Provide insulated conductors installed in rigid steel conduit, IMC, rigid
 nonmetallic conduit, or EMT, except where specifically indicated or
 specified otherwise or required by NFPA 70 to be installed otherwise.
 Grounding conductor shall be separate from electrical system neutral
 conductor. Provide insulated green equipment grounding conductor for
 circuit(s) installed in conduit and raceways. Shared neutral, or
 multi-wire branch circuits, are not permitted with arc-fault circuit
 interrupters. Minimum conduit size shall be 1/2 in in diameter for low
 voltage lighting and power circuits.

3.1.3.1      Restrictions Applicable to EMT

        a.   Do not install underground.

        b.   Do not encase in concrete, mortar, grout, or other cementitious
             materials.

        c.   Do not use in areas subject to severe physical damage including
             but not limited to equipment rooms where moving or replacing
             equipment could physically damage the EMT.

        d.   Do not use outdoors.

3.1.3.2      Restrictions Applicable to Nonmetallic Conduit

        a.   PVC Schedule 40 and PVC Schedule 80

             (1) Do not use in areas where subject to severe physical damage,
             including but not limited to, mechanical equipment rooms,
             electrical equipment rooms, hospitals, power plants, missile
             magazines, and other such areas.

             (2) Do not use above grade, except where allowed in this section
             for rising through floor slab or indicated otherwise.

3.1.3.3      Restrictions Applicable to Flexible Conduit

 Use only as specified in paragraph entitled "Flexible Connections."

3.1.3.4      Service Entrance Conduit, Underground


 PVC, Type-EPC 40, galvanized rigid steel or steel IMC. Underground portion
 shall be encased in minimum of 3 in of concrete and shall be installed
 minimum 18 in below slab or grade.




                             SECTION 26 20 00   Page 10
Design MET Facility                                                   5490419


3.1.3.5     Underground Conduit Other Than Service Entrance

 Plastic-coated rigid steel; plastic-coated steel IMC; PVC, Type EPC-40; or
 fiberglass. Convert nonmetallic conduit, other than PVC Schedule 40 or 80,
 to plastic-coated rigid, or IMC, steel conduit before rising through floor
 slab. Plastic coating shall extend minimum 6 in above floor.

3.1.3.6     Conduit in Floor Slabs

 PVC, Type EPC-40, unless indicated otherwise.

3.1.4     Conduit Installation

 Unless indicated otherwise, conceal conduit under floor slabs and within
 finished walls, ceilings, and floors. Keep conduit minimum 6 in away from
 parallel runs of flues and steam or hot water pipes. Install conduit
 parallel with or at right angles to ceilings, walls, and structural members
 where located above accessible ceilings and where conduit will be visible
 after completion of project.

3.1.4.1     Conduit Installed Under Floor Slabs

 Conduit run under floor slab shall be located a minimum of 6 in below the
 vapor barrier. Seal around conduits at penetrations thru vapor barrier.

3.1.4.2     Conduit Through Floor Slabs

 Where conduits rise through floor slabs, curved portion of bends shall not
 be visible above finished slab.

3.1.4.3     Conduit Support

 Support conduit by pipe straps, wall brackets, hangers, or ceiling trapeze.
 Fasten by wood screws to wood; by toggle bolts on hollow masonry units; by
 concrete inserts or expansion bolts on concrete or brick; and by machine
 screws, welded threaded studs, or spring-tension clamps on steel work.
 Threaded C-clamps may be used on rigid steel conduit only. Do not weld
 conduits or pipe straps to steel structures. Load applied to fasteners
 shall not exceed one-fourth proof test load. Fasteners attached to
 concrete ceiling shall be vibration resistant and shock-resistant. Holes
 cut to depth of more than 1 1/2 in in reinforced concrete beams or to depth
 of more than 3/4 in in concrete joints shall not cut main reinforcing
 bars. Fill unused holes. In partitions of light steel construction, use
 sheet metal screws. In suspended-ceiling construction, run conduit above
 ceiling. Do not support conduit by ceiling support system. Conduit and
 box systems shall be supported independently of both (a) tie wires
 supporting ceiling grid system, and (b) ceiling grid system into which
 ceiling panels are placed. Supporting means shall not be shared between
 electrical raceways and mechanical piping or ducts. Installation shall be
 coordinated with above-ceiling mechanical systems to assure maximum
 accessibility to all systems. Spring-steel fasteners may be used for
 lighting branch circuit conduit supports in suspended ceilings in dry
 locations. Where conduit crosses building expansion joints, provide
 suitable watertight expansion fitting that maintains conduit electrical
 continuity by bonding jumpers or other means. For conduits greater than 2
 1/2 in inside diameter, provide supports to resist forces of 0.5 times the
 equipment weight in any direction and 1.5 times the equipment weight in the
 downward direction.



                              SECTION 26 20 00   Page 11
Design MET Facility                                                   5490419


3.1.4.4     Directional Changes in Conduit Runs

 Make changes in direction of runs with symmetrical bends or cast-metal
 fittings. Make field-made bends and offsets with hickey or conduit-bending
 machine. Do not install crushed or deformed conduits. Avoid trapped
 conduits. Prevent plaster, dirt, or trash from lodging in conduits, boxes,
 fittings, and equipment during construction. Free clogged conduits of
 obstructions.

3.1.4.5     Pull Wire

 Install pull wires in empty conduits. Pull wire shall be plastic having
 minimum 200-lb tensile strength. Leave minimum 36 in of slack at each end
 of pull wire.

3.1.4.6     Locknuts and Bushings

 Fasten conduits to sheet metal boxes and cabinets with two locknuts where
 required by NFPA 70, where insulated bushings are used, and where bushings
 cannot be brought into firm contact with the box; otherwise, use at least
 minimum single locknut and bushing. Locknuts shall have sharp edges for
 digging into wall of metal enclosures. Install bushings on ends of
 conduits, and provide insulating type where required by NFPA 70.

3.1.4.7     Stub-Ups

 Provide conduits stubbed up through concrete floor for connection to
 free-standing equipment with adjustable top or coupling threaded inside for
 plugs, set flush with finished floor. Extend conductors to equipment in
 rigid steel conduit, except that flexible metal conduit may be used 6 in
 above floor. Where no equipment connections are made, install
 screwdriver-operated threaded flush plugs in conduit end.

3.1.4.8     Flexible Connections

 Provide flexible steel conduit between 3 and 6 ft in length for recessed
 and semirecessed lighting fixtures; for equipment subject to vibration,
 noise transmission, or movement; and for motors. Install flexible conduit
 to allow 20 percent slack. Minimum flexible steel conduit size shall be
 1/2 in diameter.

3.1.5     Boxes, Outlets, and Supports

 Provide boxes in wiring and raceway systems wherever required for pulling
 of wires, making connections, and mounting of devices or fixtures. Boxes
 for metallic raceways shall be cast-metal, hub-type when located in wet
 locations, when surface mounted on outside of exterior surfaces, when
 surface mounted on interior walls exposed up to 7 ft above floors and
 walkways, and when specifically indicated. Boxes in other locations shall
 be sheet steel, except that aluminum boxes may be used with aluminum
 conduit, and nonmetallic boxes may be used with nonmetallic sheathed cable
 conduit system. Each box shall have volume required by NFPA 70 for number
 of conductors enclosed in box. Boxes for mounting lighting fixtures shall
 be minimum 4 in square, or octagonal, except that smaller boxes may be
 installed as required by fixture configurations, as approved. Boxes for
 use in masonry-block or tile walls shall be square-cornered, tile-type, or
 standard boxes having square-cornered, tile-type covers. Provide gaskets
 for cast-metal boxes installed in wet locations and boxes installed flush
 with outside of exterior surfaces. Provide separate boxes for flush or


                            SECTION 26 20 00   Page 12
Design MET Facility                                                   5490419


 recessed fixtures when required by fixture terminal operating temperature;
 fixtures shall be readily removable for access to boxes unless ceiling
 access panels are provided. Support boxes and pendants for surface-mounted
 fixtures on suspended ceilings independently of ceiling supports. Fasten
 boxes and supports with wood screws on wood, with bolts and expansion
 shields on concrete or brick, with toggle bolts on hollow masonry units,
 and with machine screws or welded studs on steel. In open overhead spaces,
 cast boxes threaded to raceways need not be separately supported except
 where used for fixture support; support sheet metal boxes directly from
 building structure or by bar hangers. Where bar hangers are used, attach
 bar to raceways on opposite sides of box, and support raceway with
 approved-type fastener maximum 24 in from box. When penetrating reinforced
 concrete members, avoid cutting reinforcing steel.

3.1.5.1     Boxes

 Boxes for use with raceway systems shall be minimum 1 1/2 in deep, except
 where shallower boxes required by structural conditions are approved.
 Boxes for other than lighting fixture outlets shall be minimum 4 in
 square, except that 4 by 2 in boxes may be used where only one raceway
 enters outlet. Telephone outlets shall be minimum of 4 in square by 2 1/8
 in deep, except for wall mounted telephones and outlet boxes for handicap
 telephone stations.

3.1.5.2     Pull Boxes

 Construct of at least minimum size required by NFPA 70 of code-gauge
 aluminum or galvanized sheet steel, and compatible with nonmetallic raceway
 systems, except where cast-metal boxes are required in locations specified
 herein. Provide boxes with screw-fastened covers. Where several feeders
 pass through common pull box, tag feeders to indicate clearly electrical
 characteristics, circuit number, and panel designation.

3.1.5.3     Extension Rings

 Extension rings are not permitted for new construction. Use only on
 existing boxes in concealed conduit systems where wall is furred out for
 new finish.

3.1.6     Mounting Heights

 Mount panelboards, enclosed circuit breakers, motor controller and
 disconnecting switches so height of operating handle at its highest
 position is maximum 78 in above floor. Mount lighting switches 48 in above
 finished floor, receptacles 18 in above finished floor unless otherwise
 indicated, and other devices as indicated. Measure mounting heights of
 wiring devices and outlets in non-hazardous areas to center of device or
 outlet.

3.1.7     Covers and Device Plates

 Install with edges in continuous contact with finished wall surfaces
 without use of mats or similar devices. Plaster fillings are not
 permitted. Install plates with alignment tolerance of 1/16 in. Use of
 sectional-type device plates are not permitted. Provide gasket for plates
 installed in wet locations.




                              SECTION 26 20 00   Page 13
Design MET Facility                                                   5490419


3.1.8     Grounding and Bonding

 In accordance with NFPA 70. Ground exposed, non-current-carrying metallic
 parts of electrical equipment, metallic raceway systems, grounding
 conductor in metallic and nonmetallic raceways, telephone system grounds,
 grounding conductor of nonmetallic sheathed cables, and neutral conductor
 of wiring systems. Make ground connection at main service equipment, and
 extend grounding conductor to point of entrance of metallic water service.
 Make connection to water pipe by suitable ground clamp or lug connection to
 plugged tee. If flanged pipes are encountered, make connection with lug
 bolted to street side of flanged connection. Supplement metallic water
 service grounding system with additional made electrode in compliance with
 NFPA 70. Make ground connection to driven ground rods on exterior of
 building. Interconnect all grounding media in or on the structure to
 provide a common ground potential. This shall include electrical service,
 telephone system grounds, as well as underground metallic piping systems.
 Where ground fault protection is employed, ensure that connection of ground
 and neutral does not interfere with correct operation of fault protection.

3.1.8.1     Resistance

 Maximum resistance-to-ground of grounding system shall not exceed 5 ohms
 under dry conditions. Where resistance obtained exceeds 5 ohms, contact
 Contracting Officer for further instructions.

3.1.8.2     Telephone Service

 Provide main telephone service equipment ground consisting of separate
 ground wire, No. 6 AWG, in conduit between equipment backboard and readily
 accessible grounding connection. Equipment end of ground wire shall
 consist of coiled length at least twice as long as terminal cabinet or
 backboard height.

3.1.9     Equipment Connections

 Provide power wiring for the connection of motors and control equipment
 under this section of the specification. Except as otherwise specifically
 noted or specified, automatic control wiring, control devices, and
 protective devices within the control circuitry are not included in this
 section of the specifications but shall be provided under the section
 specifying the associated equipment.

3.1.10     Repair of Existing Work3.1.10.1     Workmanship

 Lay out work in advance. Exercise care where cutting, channeling, chasing,
 or drilling of floors, walls, partitions, ceilings, or other surfaces is
 necessary for proper installation, support, or anchorage of conduit,
 raceways, or other electrical work. Repair damage to buildings, piping,
 and equipment using skilled craftsmen of trades involved.

3.1.10.2     Existing Concealed Wiring to be Removed

 Existing concealed wiring to be removed shall be disconnected from its
 source. Remove conductors; cut conduit flush with floor, underside of
 floor, and through walls; and seal openings.

3.1.10.3     Removal of Existing Electrical Distribution System

 Removal of existing electrical distribution system equipment shall include


                            SECTION 26 20 00    Page 14
Design MET Facility                                                    5490419


 equipment's associated wiring, including conductors, cables, exposed
 conduit, surface metal raceways, boxes, and fittings, back to equipment's
 power source as indicated.

3.1.10.4     Continuation of Service

 Maintain   continuity of existing circuits of equipment to remain. Existing
 circuits   of equipment shall remain energized. Circuits which are to remain
 but were   disturbed during demolition shall have circuits wiring and power
 restored   back to original condition.

3.2     FIELD QUALITY CONTROL

 Furnish test equipment and personnel and submit written copies of test
 results. Give Contracting Officer 5 working days notice prior to tests.

3.2.1     Devices Subject to Manual Operation

 Each device subject to manual operation shall be operated at least five
 times, demonstrating satisfactory operation each time.

3.2.2     600-Volt Wiring Test

 Test wiring rated 600 volt and less to verify that no short circuits or
 accidental grounds exist. Perform insulation resistance tests on wiring
 No. 6 AWG and larger diameter using instrument which applies voltage of
 approximately 500 volts to provide direct reading of resistance. Minimum
 resistance shall be 250,000 ohms.

3.2.3     Ground-Fault Receptacle Test

 Test ground-fault receptacles with a "load" (such as a plug in light) to
 verify that the "line" and "load" leads are not reversed.

3.2.4     Grounding System Test

 Test grounding system to ensure continuity, and that resistance to ground
 is not excessive. Test each ground rod for resistance to ground before
 making connections to rod; tie grounding system together and test for
 resistance to ground. Make resistance measurements in dry weather, not
 earlier than 48 hours after rainfall. Submit written results of each test
 to Contracting Officer, and indicate location of rods as well as resistance
 and soil conditions at time measurements were made.

         -- End of Section --




                            SECTION 26 20 00    Page 15
Design MET Facility                                                        5490419



                                SECTION 26 51 00

                                INTERIOR LIGHTING
                                      07/07

PART 1     GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to in the text by the
 basic designation only.

            ASTM INTERNATIONAL (ASTM)

 ASTM A 1008/A 1008M                (2009) Standard Specification for Steel,
                                    Sheet, Cold-Rolled, Carbon, Structural,
                                    High-Strength Low-Alloy and High-Strength
                                    Low-Alloy with Improved Formability,
                                    Solution Hardened, and Bake Hardened

 ASTM A 641/A 641M                  (2009a) Standard Specification for
                                    Zinc-Coated (Galvanized) Carbon Steel Wire

 ASTM A 653/A 653M                  (2009) Standard Specification for Steel
                                    Sheet, Zinc-Coated (Galvanized) or
                                    Zinc-Iron Alloy-Coated (Galvannealed) by
                                    the Hot-Dip Process

 ASTM B 633                         (2007) Standard Specification for
                                    Electrodeposited Coatings of Zinc on Iron
                                    and Steel

            ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA (IESNA)

 IESNA HB-9                         (2000; Errata 2004; Errata 2005) IES
                                    Lighting Handbook

            INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

 IEEE C2                            (2007; Errata 2006; Errata 2007; INT 44-56
                                    2007; INT 47, 49, 50, 52-56 2008; INT 57,
                                    58, 51, 48 2009) National Electrical
                                    Safety Code

 IEEE C62.41.1                      (2002; R 2008) IEEE Guide on the Surges
                                    Environment in Low-Voltage (1000 V and
                                    Less) AC Power Circuits

 IEEE C62.41.2                      (2002) IEEE Recommended Practice on
                                    Characterization of Surges in Low-Voltage
                                    (1000 V and Less) AC Power Circuits

 IEEE Std 100                       (2000) The Authoritative Dictionary of
                                    IEEE Standards Terms




                            SECTION 26 51 00   Page 1
Design MET Facility                                                        5490419


            NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

 NEMA 250                           (2008) Enclosures for Electrical Equipment
                                    (1000 Volts Maximum)

 NEMA ANSLG C78.42                  (2007) Standard for High-Pressure Sodium
                                    Lamps

 NEMA C78.1381                      (1998) Electric Lamps - 250-Watt, 70 Watt,
                                    M85 Metal-Halide Lamps

 NEMA C78.43                        (2007) Standard for Electric Lamps -
                                    Single-Ended Metal-Halide Lamps

 NEMA C78.81                        (2005) Electric Lamps - Double-capped
                                    Fluorescent Lamps Dimensional and
                                    Electrical Characteristics

 NEMA C78.901                       (2005) Electric Lamps - Single Base
                                    Fluorescent Lamps Dimensional and
                                    Electrical Characteristics

 NEMA C82.11                        (2002) High-Frequency Fluorescent Lamp
                                    Ballasts

 NEMA C82.4                         (2002) Ballasts for
                                    High-Intensity-Discharge and Low-Pressure
                                    Sodium Lamps (Multiple-Supply Type)

 NEMA LL 1                          (1997; R 2002) Procedures for Linear
                                    Fluorescent Lamp Sample Preparation and
                                    the TCLP Extraction

            NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

 NFPA 101                           (2009; Amd 1 & 2 2009) Life Safety Code

 NFPA 70                            (2008; AMD 1 2008) National Electrical
                                    Code - 2008 Edition

            U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)

 Energy Star                        (1992; R 2006) Energy Star Energy
                                    Efficiency Labeling System

            UNDERWRITERS LABORATORIES (UL)

 UL 1029                            (1994; Rev thru Jul 2009) Standard for
                                    Safety High-Intensity-Discharge Lamp
                                    Ballasts

 UL 1598                            (2008; Rev thru Feb 2009) Luminaires

 UL 924                             (2006; Rev thru Sep 2009) Standard for
                                    Emergency Lighting and Power Equipment

 UL 935                             (2001; Rev thru Jul 2009) Standard for
                                    Fluorescent-Lamp Ballasts



                            SECTION 26 51 00   Page 2
Design MET Facility                                                      5490419


1.2     RELATED REQUIREMENTS

 Materials not considered to be lighting equipment or lighting fixture
 accessories are specified in Section 26 20 00 INTERIOR DISTRIBUTION
 SYSTEM. Lighting fixtures and accessories mounted on exterior surfaces of
 buildings are specified in this section.

1.3     DEFINITIONS

  a.    Unless otherwise specified or indicated, electrical and electronics
        terms used in these specifications, and on the drawings, shall be as
        defined in IEEE Std 100.

  b.    Average life is the time after which 50 percent will have failed and 50
        percent will have survived under normal conditions.

  c.    Total harmonic distortion (THD) is the root mean square (RMS) of all
        the harmonic components divided by the total fundamental current.

1.4     SYSTEM DESCRIPTION

1.4.1     Lighting Control System

 Provide lighting control system as indicated. Lighting control equipment
 shall include, if indicated: control modules, power packs, dimming
 ballasts, occupancy sensors, and light level sensors.

1.5     SUBMITTALS

 The following shall be submitted in accordance with Section 01 33 00
 SUBMITTAL PROCEDURES:

 Data, drawings, and reports shall employ the terminology, classifications,
 and methods prescribed by the IESNA HB-9, as applicable, for the lighting
 system specified.

        SD-03 Product Data

            Fluorescent lighting fixtures

            Fluorescent electronic ballasts

            Fluorescent electromagnetic ballasts

            Fluorescent lamps

            High-intensity-discharge (HID) lighting fixtures

            HID ballasts

            High-pressure sodium (HPS) lamps

            Metal-halide lamps

            Lighting contactor

            Time switch

            Photocell switch


                               SECTION 26 51 00   Page 3
Design MET Facility                                                     5490419



            Power hook fixture hangers

            Exit signs

            Emergency lighting equipment

        SD-06 Test Reports

            Operating test

            Submit test results as stated in paragraph entitled "Field Quality
            Control."

        SD-10 Operation and Maintenance Data

            Lighting Control System, Data Package 5

            Submit operation and maintenance data in accordance with Section
            01 78 23 OPERATION AND MAINTENANCE DATA and as specified herein,
            showing all light fixtures, control modules, control zones,
            occupancy sensors, light level sensors, power packs, dimming
            ballasts, schematic diagrams and all interconnecting control
            wire, conduit, and associated hardware.

            Operational Service

            Submit documentation that includes contact information, summary of
            procedures, and the limitations and conditions applicable to the
            project. Indicate manufacturer's commitment to reclaim materials
            for recycling and/or reuse.

1.6     QUALITY ASSURANCE

1.6.1     Fluorescent Electronic Ballasts

 Submit ballast catalog data as required in the paragraph entitled
 "Fluorescent Lamp Electronic Ballasts" contained herein. As an option,
 submit the fluorescent fixture manufacturer's electronic ballast
 specification information in lieu of the actual ballast manufacturer's
 catalog data. This information shall include published specifications and
 sketches, which covers the information required by the paragraph entitled
 "Fluorescent Lamp Electronic Ballasts" herein. This information may be
 supplemented by catalog data if required, and shall contain a list of
 vendors with vendor part numbers.

1.6.2     Regulatory Requirements

 In each of the publications referred to herein, consider the advisory
 provisions to be mandatory, as though the word, "shall" had been
 substituted for "should" wherever it appears. Interpret references in
 these publications to the "authority having jurisdiction," or words of
 similar meaning, to mean the Contracting Officer. Equipment, materials,
 installation, and workmanship shall be in accordance with the mandatory and
 advisory provisions of NFPA 70 unless more stringent requirements are
 specified or indicated.




                             SECTION 26 51 00   Page 4
Design MET Facility                                                   5490419


1.6.3     Standard Products

 Provide materials and equipment that are products of manufacturers
 regularly engaged in the production of such products which are of equal
 material, design and workmanship. Products shall have been in satisfactory
 commercial or industrial use for 2 years prior to bid opening. The 2-year
 period shall include applications of equipment and materials under similar
 circumstances and of similar size. The product shall have been on sale on
 the commercial market through advertisements, manufacturers' catalogs, or
 brochures during the 2-year period. Where two or more items of the same
 class of equipment are required, these items shall be products of a single
 manufacturer; however, the component parts of the item need not be the
 products of the same manufacturer unless stated in this section.

1.6.3.1     Alternative Qualifications

 Products having less than a 2-year field service record will be acceptable
 if a certified record of satisfactory field operation for not less than
 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is
 furnished.

1.6.3.2     Material and Equipment Manufacturing Date

 Products manufactured more than 3 years prior to date of delivery to site
 shall not be used, unless specified otherwise.

1.6.3.3     Energy Efficiency

 Comply with National Energy Policy Act and Energy Star requirements for
 lighting products. Submit documentation for Energy Star qualifications for
 equipment provided under this section. Submit data indicating lumens per
 watt efficiency and color rendition index of light source.

1.7     WARRANTY

 The equipment items shall be supported by service organizations which are
 reasonably convenient to the equipment installation in order to render
 satisfactory service to the equipment on a regular and emergency basis
 during the warranty period of the contract.

1.7.1     Electronic Ballast Warranty

 Furnish the electronic ballast manufacturer's warranty. The warranty
 period shall not be less than 5 years from the date of manufacture of the
 electronic ballast. Ballast assembly in the lighting fixture,
 transportation, and on-site storage shall not exceed 12 months, thereby
 permitting 4 years of the ballast 5 year warranty to be in service and
 energized. The warranty shall state that the malfunctioning ballast shall
 be exchanged by the manufacturer and promptly shipped to the using
 Government facility. The replacement ballast shall be identical to, or an
 improvement upon, the original design of the malfunctioning ballast.

PART 2     PRODUCTS

2.1     FLUORESCENT LIGHTING FIXTURES

 UL 1598.    Fluorescent fixtures shall have electronic ballasts.




                                SECTION 26 51 00   Page 5
Design MET Facility                                                         5490419


2.1.1     Fluorescent Lamp Electronic Ballasts

 The electronic ballast shall as a minimum meet the following
 characteristics:

  a.    Ballast shall comply with UL 935, NEMA C82.11, and NFPA 70 unless
        specified otherwise. Ballast shall be 100% electronic high frequency
        type with no magnetic core and coil components. Ballast shall provide
        transient immunity as recommended by IEEE C62.41.1 and IEEE C62.41.2.
        Ballast shall be designed for the wattage of the lamps used in the
        indicated application. Ballasts shall be designed to operate on the
        voltage system to which they are connected.

  b.    Power factor shall be 0.95 (minimum).

  c.    Ballast shall operate at a frequency of 20,000 Hertz (minimum).
        Ballast shall be compatible with and not cause interference with the
        operation of occupancy sensors or other infrared control systems.
        Provide ballasts operating at or above 40,000 Hertz where available.

  d.    Ballast shall have light regulation of plus or minus 10 percent lumen
        output with a plus or minus 10 percent input voltage regulation.
        Ballast shall have 10 percent flicker (maximum) using any compatible
        lamp.

  e.    Ballast factor shall be between 0.85 (minimum) and 1.00 (maximum).
        Current crest factor shall be 1.7 (maximum).

  f.    Ballast shall be UL listed Class P with a sound rating of "A."

  g.    Ballast shall have circuit diagrams and lamp connections displayed on
        the ballast.

  h.    Ballasts shall be instant start unless otherwise indicated. Ballasts
        shall be programmed start where indicated. Instant start ballasts
        shall operate lamps in a parallel circuit configuration that permits
        the operation of remaining lamps if one or more lamps fail or are
        removed. Ballasts shall be programmed start unless otherwise
        indicated. Programmed start ballasts may operate lamps in a series
        circuit configuration. Provide series/parallel wiring for programmed
        start ballasts where available.

  i.    Ballasts for compact fluorescent fixtures shall be programmed start.

  j.    Ballasts for T-5 and smaller lamps shall have end-of-life protection
        circuits as required by NEMA C78.81 and NEMA C78.901 as applicable.

  k.    Ballast shall be capable of starting and maintaining operation at a
        minimum of 0 degrees F unless otherwise indicated.

  l.    Electronic ballast shall have a full replacement warranty of 5 years
        from date of manufacture as specified in paragraph entitled "Electronic
        Ballast Warranty" herein.

2.1.1.1     T-8 Lamp Ballast

  a.    Total harmonic distortion (THD):   Shall be 20 percent (maximum).

  b.    Input wattage.


                               SECTION 26 51 00   Page 6
Design MET Facility                                                          5490419



        1.   32 watts (maximum) when operating one F32T8 lamp

        2.   62 watts (maximum) when operating two F32T8 lamps

        3.   92 watts (maximum) when operating three F32T8 lamps

        4.   114 watts (maximum) when operating four F32T8 lamps

  c.    Provide three and four lamp fixtures with two ballasts per fixture
        where multilevel switching is indicated.

  d.    A single ballast may be used to serve multiple fixtures if they are
        continuously mounted and factory manufactured for that installation
        with an integral wireway.

2.1.1.2      F17T8 Lamp Ballast

  a.    Total harmonic distortion (THD):    Shall be 25 percent (maximum).

  b.    Input wattage:

        1.   34 watts (maximum) when operating two F17T8 lamps.

2.1.2     Fluorescent Lamp Electronic Dimming Ballast

2.1.2.1      T-8 Lamp Ballast

 Input wattage, for indicated lamp quantity shall be:

  a.    35 watts (maximum) when operating one F32T8 lamp.

  b.    70 watts (maximum) when operating two F32T8 lamps.

  c.    104 watts (maximum) when operating three F32T8 lamps.

2.1.3     Fluorescent Lamps

  a.    T-8 rapid start low mercury lamps shall be rated 32 watts (maximum),
        2800 initial lumens (minimum), CRI of 75 (minimum), color temperature
        of 3500 K, and an average rated life of 20,000 hours. Low mercury
        lamps shall have passed the EPA Toxicity Characteristic Leachate
        Procedure (TCLP) for mercury by using the lamp sample preparation
        procedure described in NEMA LL 1.

  b.    Compact fluorescent lamps shall be: CRI 80, minimum, 3500 K, 10,000
        hours average rated life, and as follows:
        1. T-4, double twin tube, rated 13 watts, 900 initial lumens
            (minimum), 18 watts, 1200 initial lumens (minimum), and 26 watts,
            1800 initial lumens (minimum), as indicated.

 Average rated life is based on 3 hours operating per start.

2.1.4     Compact Fluorescent Fixtures

 Compact fluorescent fixtures shall be manufactured specifically for compact
 fluorescent lamps with ballasts integral to the fixture. Providing
 assemblies designed to retrofit incandescent fixtures is prohibited except
 when specifically indicated for renovation of existing fixtures. Fixtures


                                SECTION 26 51 00   Page 7
Design MET Facility                                                         5490419


 shall use lamps as indicated, with a minimum CRI of 80.

2.1.5     Open-Tube Fluorescent Fixtures

 Provide with self-locking sockets, or lamp retainers (two per lamp).
 Provide lamps with shatter resistant coating, non-yellowing, nominal
 thickness of 15 mils, and with 97 percent (minimum) light transmission.
 Provide a clear polycarbonate protective sleeve with end caps, over lamp,
 with 95 percent (minimum) light transmission. The sleeve shall be rated to
 withstand the thermal profile of the lamp and ballast.

2.2     HIGH-INTENSITY-DISCHARGE (HID) LIGHTING FIXTURES

 UL 1598. Provide HID fixtures with tempered glass lenses when using
 metal-halide lamps.

2.2.1     HID Ballasts

 UL 1029 and NEMA C82.4 and shall be constant wattage autotransformer (CWA)
 or regulator, high power factor type (minimum 90%). Provide single-lamp
 ballasts which shall have a minimum starting temperature of minus 30
 degrees C. Ballasts shall be:

  a.    Designed to operate on the voltage system to which they are connected.

  b.    Designed for installation in a normal ambient temperature of 40 degrees
        C.

  c.    Constructed so that open circuit operation will not reduce the average
        life.

 High-pressure sodium (HPS) ballasts shall have a solid-state
 igniter/starter with an average life in the pulsing mode of 3500 hours at
 the intended ambient temperature. Igniter case temperature shall not
 exceed 90 degrees C in any mode.

2.2.2     High-Pressure Sodium (HPS) Lamps

 NEMA ANSLG C78.42 wattage as indicated.        150 watt lamps, if required, shall
 be 55 volt type.

2.2.2.1      Standby HPS Lamps

 Standby HPS lamps shall have two arc tubes and an average rated life of
 40,000 hours (minimum) and hot restart instant lumen output shall be 8
 percent, minimum, of total light output.

2.2.2.2      Luminaire Efficiency Rating (LER)

  a.    Upward efficiency of 0%

        1.   150-399 watts: minimum 58 LER for closed fixture; minimum 68 for
             open fixture

        2.   400-999 watts: minimum 63 LER for closed fixture; minimum 84 for
             open fixture

  b.    Upward efficiency of 1%-10%



                                 SECTION 26 51 00   Page 8
Design MET Facility                                                      5490419


        1.   150-399 watts: minimum 64 LER for closed fixture; minimum 63 for
             open fixture

        2.   400-999 watts: minimum 82 LER for closed fixture; minimum 89 for
             open fixture

        3.   1000+ watts: minimum 109 LER for open fixture

  c.    Upward efficiency of 11% to 20%

        1.   150-399 watts: minimum 78 LER for open fixture

        2.   400-999 watts: minimum 94 for open fixture

  d.    Upward efficiency greater than 20%

        1.   150-399 watts: minimum 75 LER for closed fixture; minimum 77 for
             open fixture

2.2.3     Metal-Halide Lamps

  a.    Double-ended, 70 watt, conforming to NEMA C78.1381

  b.    Single-ended, wattage as indicated, conforming to NEMA C78.43

2.2.3.1      Luminaire Efficiency Rating (LER)

  a.    Upward efficiency of 0%

        1.   150-399 watts: minimum 41 LER for closed fixture

        2.   400-999 watts: minimum 53 LER for closed fixture; minimum 59 for
             open fixture

        3.   1000+ watts: minimum 77 LER for closed fixture

  b.    Upward efficiency of 1%-10%

        1.   150-399 watts: minimum 56 LER for closed fixture

        2.   400-999 watts: minimum 62 LER for closed fixture; minimum 64 for
             open fixture

        3.   1000+ watts: minimum 88 LER for open fixture

  c.    Upward efficiency greater than 20%

        1.   150-399 watts: minimum 62 LER for closed fixture; minimum 77 for
             open fixture

        2.   400-999 watts: minimum 65 LER for closed fixture

2.3     RECESS- AND FLUSH-MOUNTED FIXTURES

 Provide type that can be relamped from the bottom. Access to ballast shall
 be from the bottom. Trim for the exposed surface of flush-mounted fixtures
 shall be as indicated.




                               SECTION 26 51 00   Page 9
Design MET Facility                                                   5490419


2.4     SUSPENDED FIXTURES

 Provide hangers capable of supporting twice the combined weight of fixtures
 supported by hangers. Provide with swivel hangers to ensure a plumb
 installation. Hangers shall be cadmium-plated steel with a swivel-ball
 tapped for the conduit size indicated.Hangers shall allow fixtures to swing
 within an angle of 45 degrees. Multiple-unit or continuous row fluorescent
 fixtures shall have a tubing or stem for wiring at one point and a tubing
 or rod suspension provided for each unit length of chassis, including one
 at each end.

2.5     SWITCHES

2.5.1     Toggle Switches

 Provide toggle switches as specified in Section 26 20 00 INTERIOR
 DISTRIBUTION SYSTEM.

2.6     EXIT SIGNS

 UL 924, NFPA 70, and NFPA 101. Exit signs shall be self-powered type.
 Exit signs shall use no more than 5 watts.

2.6.1     Self-Powered LED Type Exit Signs (Battery Backup)

 Provide with automatic power failure device, fully automatic high/low
 trickle charger in a self-contained power pack. Battery shall be sealed
 electrolyte type, shall operate unattended, and require no maintenance,
 including no additional water, for a period of not less than 5 years. LED
 exit sign shall have emergency run time of 1 1/2 hours (minimum). The
 light emitting diodes shall have rated lamp life of 70,000 hours (minimum).

2.7     EMERGENCY LIGHTING EQUIPMENT

 UL 924, NFPA 70, and NFPA 101. Provide lamps in wattage indicated.
 Provide accessories required for remote-mounted lamps where indicated.
 Remote-mounted lamps shall be as indicated.

2.7.1     Emergency Lighting Unit

 Provide as indicated. Emergency lighting units shall be rated for 12 volts.
   Equip units with brown-out sensitive circuit to activate battery when ac
 input falls to 75 percent of normal voltage and 15 minute time delay
 feature for areas with HID lighting. Provide integral self-testing module.

2.7.2     Fluorescent Emergency System

 Each system shall consist of an automatic power failure device, test switch
 operable from outside of the fixture, pilot light visible from outside the
 fixture, and fully automatic solid-state charger in a self-contained power
 pack. Provide self-testing module integral to the fixture. Charger shall
 be either trickle, float, constant current or constant potential type, or a
 combination of these. Battery shall be sealed electrolyte type with
 capacity as required to supply power to the number of lamps shown for each
 system for 90 minutes at a minimum of 600 lumens per lamp output. Battery
 shall operate unattended and require no maintenance, including no
 additional water, for a period of not less than 5 years. Emergency
 ballasts provided with fixtures containing solid-state ballasts shall be
 fully compatible with the solid-state ballasts.


                             SECTION 26 51 00   Page 10
Design MET Facility                                                      5490419



2.8     SUPPORT HANGERS FOR LIGHTING FIXTURES IN SUSPENDED CEILINGS

2.8.1     Wires

 ASTM A 641/A 641M, galvanized regular coating, soft temper, 0.1055 inches
 in diameter (12 gage).

2.8.2     Straps

 Galvanized steel, one by 3/16 inch, conforming to ASTM A 653/A 653M, with a
 light commercial zinc coating or ASTM A 1008/A 1008M with an
 electrodeposited zinc coating conforming to ASTM B 633, Type RS.

2.8.3     Rods

 Threaded steel rods, 3/16 inch diameter, zinc or cadmium coated.

2.9     EQUIPMENT IDENTIFICATION

2.9.1     Manufacturer's Nameplate

 Each item of equipment shall have a nameplate bearing the manufacturer's
 name, address, model number, and serial number securely affixed in a
 conspicuous place; the nameplate of the distributing agent will not be
 acceptable.

2.9.2     Labels

 Provide labeled luminaires in accordance with UL 1598 requirements. All
 luminaires shall be clearly marked for operation of specific lamps and
 ballasts according to proper lamp type. The following lamp characteristics
 shall be noted in the format "Use Only _____":

  a.    Lamp diameter code (T-4, T-5, T-8, T-12), tube configuration (twin,
        quad, triple), base type, and nominal wattage for fluorescent and
        compact fluorescent luminaires.

  b.    Lamp type, wattage, bulb type (ED17, BD56, etc.) and coating (clear or
        coated) for HID luminaires.

  c.    Start type (preheat, rapid start, instant start) for fluorescent and
        compact fluorescent luminaires.

  d.    ANSI ballast type (M98, M57, etc.) for HID luminaires.

  e.    Correlated color temperature (CCT) and color rendering index (CRI) for
        all luminaires.

 All markings related to lamp type shall be clear and located to be readily
 visible to service personnel, but unseen from normal viewing angles when
 lamps are in place. Ballasts shall have clear markings indicating
 multi-level outputs and indicate proper terminals for the various outputs.

2.10     FACTORY APPLIED FINISH

 Electrical equipment shall have factory-applied painting systems which
 shall, as a minimum, meet the requirements of NEMA 250 corrosion-resistance
 test.


                            SECTION 26 51 00   Page 11
Design MET Facility                                                   5490419



PART 3     EXECUTION

3.1     INSTALLATION

 Electrical installations shall conform to IEEE C2, NFPA 70, and to the
 requirements specified herein.

3.1.1     Lamps

 Lamps of the type, wattage, and voltage rating indicated shall be delivered
 to the project in the original cartons and installed just prior to project
 completion. Lamps installed and used for working light during construction
 shall be replaced prior to turnover to the Government if more than 15
 percent of their rated life has been used. Lamps shall be tested for
 proper operation prior to turn-over and shall be replaced if necessary with
 new lamps from the original manufacturer. Provide 10 percent spare lamps
 of each type from the original manufacturer.

3.1.2     Lighting Fixtures

 Set lighting fixtures plumb, square, and level with ceiling and walls, in
 alignment with adjacent lighting fixtures, and secure in accordance with
 manufacturers' directions and approved drawings. Installation shall meet
 requirements of NFPA 70. Mounting heights specified or indicated shall be
 to the bottom of fixture for ceiling-mounted fixtures and to center of
 fixture for wall-mounted fixtures. Obtain approval of the exact mounting
 for lighting fixtures on the job before commencing installation and, where
 applicable, after coordinating with the type, style, and pattern of the
 ceiling being installed. Recessed and semi-recessed fixtures shall be
 independently supported from the building structure by a minimum of four
 wires or straps or rods per fixture and located near each corner of each
 fixture. Ceiling grid clips are not allowed as an alternative to
 independently supported light fixtures. Round fixtures or fixtures smaller
 in size than the ceiling grid shall be independently supported from the
 building structure by a minimum of four wires or straps or rods per fixture
 spaced approximately equidistant around the fixture. Do not support
 fixtures by ceiling acoustical panels. Where fixtures of sizes less than
 the ceiling grid are indicated to be centered in the acoustical panel,
 support such fixtures independently and provide at least two 3/4 inch metal
 channels spanning, and secured to, the ceiling tees for centering and
 aligning the fixture. Provide wires or straps or rods for lighting fixture
 support in this section.

3.1.3     Suspended Fixtures

 Suspended fixtures shall be provided with 45 degree swivel hangers so that
 they hang plumb and shall be located with no obstructions within the 45
 degree range in all directions. The stem, canopy and fixture shall be
 capable of 45 degree swing. Pendants, rods, or chains 4 feet or longer
 excluding fixture shall be braced to prevent swaying using three cables at
 120 degree separation. Suspended fixtures in continuous rows shall have
 internal wireway systems for end to end wiring and shall be properly
 aligned to provide a straight and continuous row without bends, gaps, light
 leaks or filler pieces. Aligning splines shall be used on extruded
 aluminum fixtures to assure hairline joints. Steel fixtures shall be
 supported to prevent "oil-canning" effects. Fixture finishes shall be free
 of scratches, nicks, dents, and warps, and shall match the color and gloss
 specified. Pendants shall be finished to match fixtures. Aircraft cable


                               SECTION 26 51 00   Page 12
Design MET Facility                                                   5490419


 shall be stainless steel. Canopies shall be finished to match the ceiling
 and shall be low profile unless otherwise shown. Maximum distance between
 suspension points shall be 10 feet or as recommended by the manufacturer,
 whichever is less.

3.1.4     Photocell Switch Aiming

 Aim switch according to manufacturer's recommendations.

3.2     FIELD APPLIED PAINTING

 Paint electrical equipment as required to match finish of adjacent surfaces
 or to meet the indicated or specified safety criteria. Painting shall be
 as specified in Section 09 90 00 PAINTS AND COATINGS.

3.3     FIELD QUALITY CONTROL

 Upon completion of installation, verify that equipment is properly
 installed, connected, and adjusted. Conduct an operating test to show that
 equipment operates in accordance with requirements of this section.

          -- End of Section --




                            SECTION 26 51 00   Page 13
Design MET Facility                                                        5490419



                                SECTION 26 56 00

                                EXTERIOR LIGHTING
                                      07/06

PART 1     GENERAL

1.1   REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to in the text by the
 basic designation only.

            ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA (IESNA)

 IESNA HB-9                         (2000; Errata 2004; Errata 2005) IES
                                    Lighting Handbook

            INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

 IEEE C2                            (2007; Errata 2006; Errata 2007; INT 44-56
                                    2007; INT 47, 49, 50, 52-56 2008; INT 57,
                                    58, 51, 48 2009) National Electrical
                                    Safety Code

 IEEE Std 100                       (2000) The Authoritative Dictionary of
                                    IEEE Standards Terms

            NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

 NEMA 250                           (2008) Enclosures for Electrical Equipment
                                    (1000 Volts Maximum)

 NEMA C136.10                       (2006) American National Standard for
                                    Roadway Lighting Equipment-Locking-Type
                                    Photocontrol Devices and Mating
                                    Receptacles - Physical and Electrical
                                    Interchangeability and Testing

 NEMA C78.43                        (2007) Standard for Electric Lamps -
                                    Single-Ended Metal-Halide Lamps

 NEMA C82.4                         (2002) Ballasts for
                                    High-Intensity-Discharge and Low-Pressure
                                    Sodium Lamps (Multiple-Supply Type)

 NEMA ICS 2                         (2000; Errata 2002; R 2005; Errata 2006)
                                    Standard for Industrial Control and
                                    Systems: Controllers, Contactors, and
                                    Overload Relays Rated Not More than 2000
                                    Volts AC or 750 Volts DC: Part 8 -
                                    Disconnect Devices for Use in Industrial
                                    Control Equipment

 NEMA ICS 6                         (1993; R 2006) Standard for Industrial
                                    Controls and Systems Enclosures




                            SECTION 26 56 00   Page 1
Design MET Facility                                                         5490419


           NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

 NFPA 70                             (2008; AMD 1 2008) National Electrical
                                     Code - 2008 Edition

           UNDERWRITERS LABORATORIES (UL)

 UL 1029                             (1994; Rev thru Jul 2009) Standard for
                                     Safety High-Intensity-Discharge Lamp
                                     Ballasts

 UL 1598                             (2008; Rev thru Feb 2009) Luminaires

 UL 773                              (1995; Rev thru Mar 2002) Standard for
                                     Plug-In Locking Type Photocontrols for Use
                                     with Area Lighting

 UL 773A                             (2006) Nonindustrial Photoelectric
                                     Switches for Lighting Control

1.2    DEFINITIONS

  a.   Unless otherwise specified or indicated, electrical and electronics
       terms used in these specifications, and on the drawings, shall be as
       defined in IEEE Std 100.

  b.   Average life is the time after which 50 percent will have failed and 50
       percent will have survived under normal conditions.

  c.   Groundline section is that portion between one foot above and 2 feet
       below the groundline.

1.3    SUBMITTALS

 The following shall be submitted in accordance with Section 01 33 00
 SUBMITTAL PROCEDURES:

       SD-02 Shop Drawings

           Luminaire drawings

       SD-03 Product Data

           Luminaires

           Lamps

           Ballasts

           Lighting contactor

           Time switch

           Photocell switch




                              SECTION 26 56 00   Page 2
Design MET Facility                                                      5490419


1.4     QUALITY ASSURANCE

1.4.1     Drawing Requirements

1.4.1.1     Luminaire Drawings

 Include dimensions, effective projected area (EPA), accessories, and
 installation and construction details and photometric data.

1.4.2     Design Data for Luminaires

  a.    Distribution data according to IESNA classification type as defined in
        IESNA HB-9.

1.4.3     Regulatory Requirements

 In each of the publications referred to herein, consider the advisory
 provisions to be mandatory, as though the word, "shall" had been
 substituted for "should" wherever it appears. Interpret references in
 these publications to the "authority having jurisdiction," or words of
 similar meaning, to mean the Contracting Officer. Equipment, materials,
 installation, and workmanship shall be in accordance with the mandatory and
 advisory provisions of NFPA 70 unless more stringent requirements are
 specified or indicated.

1.4.4     Standard Products

 Provide materials and equipment that are products of manufacturers
 regularly engaged in the production of such products which are of equal
 material, design and workmanship. Products shall have been in satisfactory
 commercial or industrial use for 2 years prior to bid opening. The 2-year
 period shall include applications of equipment and materials under similar
 circumstances and of similar size. The product shall have been on sale on
 the commercial market through advertisements, manufacturers' catalogs, or
 brochures during the 2-year period. Where two or more items of the same
 class of equipment are required, these items shall be products of a single
 manufacturer; however, the component parts of the item need not be the
 products of the same manufacturer unless stated in this section.

1.4.4.1     Alternative Qualifications

 Products having less than a 2-year field service record will be acceptable
 if a certified record of satisfactory field operation for not less than
 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is
 furnished.

1.4.4.2     Material and Equipment Manufacturing Date

 Products manufactured more than 3 years prior to date of delivery to site
 shall not be used, unless specified otherwise.

1.5     WARRANTY

 The equipment items shall be supported by service organizations which are
 reasonably convenient to the equipment installation in order to render
 satisfactory service to the equipment on a regular and emergency basis
 during the warranty period of the contract.




                              SECTION 26 56 00   Page 3
Design MET Facility                                                       5490419


PART 2     PRODUCTS

2.1     PRODUCT COORDINATION

 Products and materials not considered to be lighting equipment or lighting
 fixture accessories are specified in Section 26 20 00 INTERIOR
 DISTRIBUTION SYSTEM.

2.2     LUMINAIRES

 UL 1598. Provide luminaires as indicated. Provide luminaires complete
 with lamps of number, type, and wattage indicated. Details, shapes, and
 dimensions are indicative of the general type desired, but are not intended
 to restrict selection to luminaires of a particular manufacturer.
 Luminaires of similar designs, light distribution and brightness
 characteristics, and of equal finish and quality will be acceptable as
 approved.

2.2.1     Lamps2.2.1.1    Metal-Halide Lamps

 Provide luminaires with tempered glass lens.

  a.     Single-ended, wattage as indicated, conforming to NEMA C78.43

2.2.2     Ballasts for High-Intensity-Discharge (HID) Luminaires

 UL 1029 and NEMA C82.4, and shall be constant wattage autotransformer (CWA)
 or regulator, high power-factor type (minimum 90%). Provide single-lamp
 ballasts which shall have a minimum starting temperature of minus 30
 degrees C. Ballasts shall be:

  a.     Designed to operate on voltage system to which they are connected.

  b.     Constructed so that open circuit operation will not reduce the average
         life.

 HID ballasts shall have a solid-state igniter/starter with an average life
 in the pulsing mode of 10,000 hours at the intended ambient temperature.
 Igniter case temperature shall not exceed 90 degrees C.

2.3     LIGHTING CONTACTOR

 NEMA ICS 2, mechanically held contactor. Rate contactor as indicated.
 Provide in NEMA 1 enclosure conforming to NEMA ICS 6. Contactor shall have
 silver alloy double-break contacts and coil clearing contacts for
 mechanically held contactor and shall require no arcing contacts. Provide
 contactor with hand-off-automatic selector switch. Contactor shall be
 hermetically sealed.

2.4     TIME SWITCH

 Astronomic dial type or electronic type, arranged to turn "ON" at sunset,
 and turn "OFF" at predetermined time between 8:30 p.m. and 2:30 a.m. or
 sunrise, automatically changing the settings each day in accordance with
 seasonal changes of sunset and sunrise. Provide time switch with a manual
 on-off bypass switch. Housing for the time switch shall be surface
 mounted, NEMA 1 enclosure conforming to NEMA ICS 6.




                               SECTION 26 56 00   Page 4
Design MET Facility                                                          5490419


2.5     PHOTOCELL SWITCH

 UL 773 or UL 773A, hermetically sealed cadmium-sulfide or silicon diode
 type cell rated 240 volts ac, 60 Hz with single-throw contacts. Switch
 shall turn on at or below 3 footcandles and off at 4 to 10 footcandles. A
 time delay shall prevent accidental switching from transient light sources.
   Provide switch:

  a.     In a high-impact-resistant, noncorroding and nonconductive molded
         plastic housing with a fixture mounted, locking-type receptacle
         conforming to NEMA C136.10 and rated 1800 VA, minimum.

2.6     EQUIPMENT IDENTIFICATION

2.6.1     Manufacturer's Nameplate

 Each item of equipment shall have a nameplate bearing the manufacturer's
 name, address, model number, and serial number securely affixed in a
 conspicuous place; the nameplate of the distributing agent will not be
 acceptable.

2.6.2     Labels

 Provide labeled luminaires in accordance with UL 1598 requirements.
 Luminaires shall be clearly marked for operation of specific lamps and
 ballasts according to proper lamp type. The following lamp characteristics
 shall be noted in the format "Use Only _____":

  a.     Lamp diameter code (T-4, T-5, T-8, T-12), tube configuration (twin,
         quad, triple), base type, and nominal wattage for fluorescent and
         compact fluorescent luminaires.

  b.     Lamp type, wattage, bulb type (ED17, BD56, etc.) and coating (clear or
         coated) for HID luminaires.

  c.     ANSI ballast type (M98, M57, etc.) for HID luminaires.

  d.     Correlated color temperature (CCT) and color rendering index (CRI) for
         all luminaires.

 Markings related to lamp type shall be clear and located to be readily
 visible to service personnel, but unseen from normal viewing angles when
 lamps are in place. Ballasts shall have clear markings indicating
 multi-level outputs and indicate proper terminals for the various outputs.

2.7     FACTORY APPLIED FINISH

 Electrical equipment shall have factory-applied painting systems which
 shall, as a minimum, meet the requirements of NEMA 250 corrosion-resistance
 test.

PART 3     EXECUTION

3.1     INSTALLATION

 Electrical installations shall conform to IEEE C2, NFPA 70, and to the
 requirements specified herein.




                              SECTION 26 56 00   Page 5
Design MET Facility                                                   5490419


3.1.1     Photocell Switch Aiming

 Aim switch according to manufacturer's recommendations.

3.1.2     GROUNDING

 Ground noncurrent-carrying parts of equipment includingluminaires, mounting
 arms, brackets, and metallic enclosures. Where copper grounding conductor
 is connected to a metal other than copper, provide specially treated or
 lined connectors suitable for this purpose.

3.1.3     FIELD APPLIED PAINTING

 Paint electrical equipment as required to match finish of adjacent surfaces
 or to meet the indicated or specified safety criteria.

3.2     FIELD QUALITY CONTROL

 Upon completion of installation, verify that equipment is properly
 installed, connected, and adjusted. Conduct an operating test to show that
 the equipment operates in accordance with the requirements of this section.

          -- End of Section --




                                SECTION 26 56 00   Page 6
Design MET Facility                                                       5490419




                                 SECTION 27 10 00

             STRUCTURED TELECOMMUNICATIONS CABLING AND PATHWAY SYSTEM

3/09


PART 1     GENERAL

1.1    REFERENCES

 The publications listed below form a part of this specification to the
 extent referenced. The publications are referred to in the text by the
 basic designation only.

            ELECTRONIC INDUSTRIES ALLIANCE (EIA)

 TIA/EIA-568-B.1                    (2001; Addendum 2001) Commercial Building
                                    Telecommunications Cabling Standard - Part
                                    1: General Requirements
                                    (ANSI/TIA/EIA-568-B.1)

 TIA/EIA-568-B.2                    (2001) Commercial Building
                                    Telecommunications Cabling Standard - Part
                                    2: Balanced Twisted Pair Cabling
                                    Components (ANSI/TIA/EIA-568-B.2)

 TIA/EIA-568-B.3                    (2000; Addendum 2002) Optical Fiber
                                    Cabling Components Standard
                                    (ANSI/TIA/EIA-568-B.3)

 TIA/EIA-569-A                      (1998; Addenda 2000, 2001) Commercial
                                    Building Standards for Telecommunications
                                    Pathways and Spaces (ANSI/TIA/EIA-569-A)

 ANSI/TIA/EIA-606-A                 (2002) Administration Standard for the
                                    Telecommunications Infrastructure
                                    (ANSI/TIA/EIA-606)

 TIA J-STD-607-A                    (2002) Commercial Building Grounding
                                    (Earthen) and Bonding Requirements for
                                    Telecommunications

            NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

 NEMA WC 63.1                       (2000) Twisted Pair Premise Voice and Data
                                    Communications Cables

            NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

 NFPA 70                            (2008; AMD 1 2008) National Electrical
                                    Code - 2008 Edition

            UNDERWRITERS LABORATORIES (UL)

 UL 1863                            (2000) Communication Circuit Accessories



                             SECTION 27 10 00   Page 1
Design MET Facility                                                          5490419


 UL 467                               (1993; R 2001) Grounding and Bonding
                                      Equipment

 UL 497                               (2001) Protectors for Paired Conductor
                                      Communication Circuits

 UL 514C                              (1996; R 2002) Nonmetallic Outlet Boxes,
                                      Flush-Device Boxes, and Covers

 UL 969                               (1995; Rev thru Nov 2001) Marking and
                                      Labeling Systems

1.2     RELATED REQUIREMENTS

 Section 26 00 00.00 20, "Basic Electrical Materials and Methods"; and
 Section 51 20 00, "Interior Distribution System"; and Section 33 82 00,
 "Telephone Distribution System, Outside Plant," apply to this section with
 additions and modifications specified herein.

1.3     DEFINITIONS

1.3.1     Main Distribution Frame (MDF)

 A physical structure at a central location for terminating permanent
 backbone cables to interconnect with service provider (SP) equipment at the
 activity minimum point of presence. The MDF generally includes vendor
 specific

 components to support voice and data circuits, building surge protector
 assemblies, main cross connect blocks, equipment support frames, and wood
 backboard (if MDF is wall mounted). Depending upon local site conditions,
 the MDF and BDF may be identical.

1.3.2     Building Distribution Frame (BDF)

 A structure with terminations for connecting backbone, campus, and
 horizontal cabling. The BDF generally includes a cross connect, equipment
 support frame, and wooden backboard or terminal cabinet. The BDF shall
 include building protector assemblies when used for campus backbone or SP
 cabling.

1.4     ENVIRONMENTAL REQUIREMENTS

 Connecting hardware shall be rated for operation under ambient conditions
 of 0 to 60 degrees C (32 to 140 degrees F) and in the range of 0 to 95
 percent relative humidity, non-condensing.

1.5     SYSTEM DESCRIPTION

 The structured telecommunications pathway system shall include permanently
 installed horizontal pathways, service entrance facilities, work area
 pathways, telecommunications outlet assemblies, conduit, and raceway, and
 hardware for splicing, terminating, and interconnecting. The horizontal
 system includes the pathway between the telecommunications room and the
 work area telecommunications outlet. The horizontal system shall be
 suitable for star topology with the IDF at the center or hub of the star.




                               SECTION 27 10 00   Page 2
Design MET Facility                                                        5490419


1.6     SUBMITTALS

 The following shall be submitted in accordance with Section 01 33 00
 "Submittal Procedures":

        SD-02 Shop Drawings

            Telecommunications drawings

            Distribution frames

        SD-03 Product Data

            Telecommunications cabling

            Patch panels

            Telecommunications outlet/connector assemblies

            Equipment support frame

            Building protector assemblies

            Connector blocks

            Protector modules

        SD-06 Test Reports

            Telecommunications cabling testing

        SD-07 Certificates

            Contractor Qualifications

            Manufacturer Qualifications

            Test plan

        SD-10 Operation and Maintenance Data

            Telecommunications cabling and pathway system Data Package 5

            Submit operations and maintenance data in accordance with Section
            01 78 23, Operation and Maintenance Data and as specified herein.

1.7     ADDITIONAL SUBMITTAL REQUIREMENTS

   All submittals of material, equipment and desgin must be approved by the
Base Telephone Office.

1.7.2     Distribution Frames

 Provide shop drawing showing layout of applicable equipment including
 incoming cable stub or connector blocks, building protector assembly,
 outgoing cable connector blocks and equipment spaces and racks.




                                SECTION 27 10 00   Page 3
Design MET Facility                                                            5490419


1.7.1     Qualifications

1.7.1.1        Minimum Contractor Qualifications

 Prior to installation, submit data of provider's experience and
 qualifications. All work under this section shall be performed by and all
 equipment shall be provided by a certified Telecommunications Contractor,
 hereinafter referred to as the Contractor. The Contractor shall have the
 following qualifications in Telecommunications Systems installation:

         a.    Contractor shall have a minimum of 3 years experience in the
               application, installation and testing of the specified systems and
               equipment.

         b.    All supervisors and installers assigned to the installation of
               this system or any of its components shall be Building INdustry
               Consulting Services International (BICSI) Certified Cabling
               Installation Technicians, Installer Level 2, or have a minimum of
               3 current consective years experience in the installation of the
               specified copper and fiber optic cable and components.

         c.    Contractor shall include names and locations of two projects
               successfully completed using optical fiber and copper
               communications cabling systems. Include specific experience in
               installing and testing structured telecommuinications distribution
               systems using optical fiber and Category 5E/6 cabling systems.
               Include written correspondence from users that systems have
               performed satisfactorily for not less than 18 months.

1.7.1.2        Minimum Manufacturer Qualifications

 The equipment and hardware provided under this contract will be from
 manufacturers that have a minimum of 3 years experience in producing the
 types of systems and equipment specified.

1.7.2     Test Plan

 Provide      a complete and detailed test plan for the telecommunications
 cabling      system including a complete list of test equipment for the UTP and
 optical      fiber components and accessories 60 days prior to the proposed test
 date.        Include procedures for certification, validation, and testing.

1.7.3     Additions to Operation and Maintenance Manuals

 In addition to requirements of Data package 5 for the telecommunications
 cabling and pathway system, include the requirements of paragraph entitled
 "Telecommunications Drawings."

1.8     DELIVERY AND STORAGE

 Provide protection from weather, moisture, dirt, dust, and other
 contaminants for telecommunications cabling and pathway equipment placed in
 storage.

PART 2        PRODUCTS

2.1     PATHWAYS (BACKBONE AND HORIZONTAL)

 TIA/EIA-569-A.          Pathway shall be co