electric

Document Sample
electric
ELECTRICAL EQUIPMENT

In accordance with the Electricity at Work Regulations (1989), all portable electrical

appliances should be visually examined on a regular basis to check for obvious defects,

e.g. loose wires, cracked casement, plugs show no signs of burning Any item found to

be faulty should be taken out of action and repaired by an approved electrician, or if not

disposed of. The main user of the equipment should perform this maintenance

inspection.



All equipment must be properly earthed and connections should be made permanent

where possible. Any temporary connections must be made safe. Extension leads are

not recommended for anything but temporary use and even then should be securely

anchored, to minimise any potential hazard.



When equipment is not in use it should be switched off at the mains.



It should be borne in mind that certain equipment, for example calculator chargers, might

not be suitable for continuous running. Care should be exercised to ensure that such

items are not left on, especially overnight, where overheating could constitute a potential

fire hazard.



Centrifuges: Personnel unfamiliar with centrifuges must read the instruction manual

supplied with the instrument and seek the assistance of an experienced member of the

department for the first few occasions of use. On no account should centrifuges be used

without prior instruction.



Please note that centrifuges not fitted with an “interlock” device have been

prohibited since 1984.



Fume cupboards: In accordance with College policy, fume cupboards are tested every

12 months for adequate performance. Pieces of equipment and other Items, which may

restrict airflow and reduce performance below acceptable levels, should not be stored in

fume cupboards. Fume cupboards are fitted with audible and visual “high sash alarms”

and “low air flow alarms”. Fume hood must not be used if alarm is sounding. Any

breakdowns contact the UCl customer services centre on ext 30000.



Safety Cabinets: In accordance with safety legislation safety cabinets must be tested

every 12 months depending on usage. Due to the high usage of the cabinets at UCLCI

all class II biological exhaust protective cabinets will be annually tested for airflow,

containment and HEPA filter efficiency (containment level 3 cabinets will be tested every

6 months). This will be organised by the CI Safety who will notify staff in advance. Prior

to maintenance, cabinets must be decontaminated and a decontamination certificate

completed – this is the responsibility of the cabinet user. Safety cabinets are fitted with

audible and visual low airflow alarms. If the cabinet goes into alarm e.g. power

failure, while an individual is working, stop all work immediately, evacuate room

and contact the helpdesk and the DSO.









Rev: 10/2007


Share This Document


Related docs
Other docs by DHarperii
MSc Marine Engineering
Views: 32  |  Downloads: 0
Funded Research Projects full_report
Views: 15  |  Downloads: 0
Financial Mathematics Exercise 8[724]
Views: 52  |  Downloads: 0
blood
Views: 103  |  Downloads: 0
Summary of linear systems
Views: 6  |  Downloads: 0
39[200]
Views: 15  |  Downloads: 0
European Legal Studies
Views: 7  |  Downloads: 0
by registering with docstoc.com you agree to our
privacy policy

You are almost ready to download!

You are almost ready to download!