Gen PSE SCL Transfer Worst Limiting

Sensitivity of Ingledow-Custer limits to

Sedro - Horse Ranch 230kV line PSE, SCL, and SNOH Generation # Gen Gen Limit Contingency Facility

4000

G3 100 775 3397 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Westside Limit=2000 MW SCL+SNOH Gen= 140 MW

WINTER 2012 G6 260 775 3479 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

SCL+SNOH Gen= 460 MW SCL+SNOH Gen= 775 MW

South-to-North (SN) G9 525 775 3675 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

3500

Light Loads G12 1000 775 3971 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]



Outage: W12 G2 100 465 3376 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Temp: 25F G5 260 460 3462 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

3000

G8 525 460 3660 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]



G11 1000 460 3948 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]









Ingledow-Custer limit (MW)

2500 G1 100 140 3100 3TM: Monroe-Echo LK-SnoK 500kV Branch BROAD ST (46409) TO UNION T (46451) CKT 1 [115.00 - 115.00 kV]

G4 260 140 3286 BFR: 4522 Echo Lk-Mon-SnoK #1 500kV & Mon Caps Branch BROAD ST (46409) TO UNION T (46451) CKT 1 [115.00 - 115.00 kV]

G7 525 140 3543 Branch

BFR: 4526 Monroe-EchoLK-SnoK 500 kV #1 & Mon-Cust #2 500kV MASS (46433) TO UNION T (46451) CKT 1 [115.00 - 115.00 kV]

G10 1000 140 3931 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

2000

Average Puget Sound Net Area Load = 3992

Gen Level Trans Worst Limiting

PSE SCL/ Limit Contingency Facility

SNOH 1500

100 140 3100 3TM: Monroe-Echo LK-SnoK 500kV Branch BROAD ST (46409) TO UNION T (46451) CKT 1 [115.00 - 115.00 kV]

100 460 3376 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

100 775 3397 1000

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

260 140 3286 BFR: 4522 Echo Lk-Mon-SnoK #1 500kV & Mon Caps Branch BROAD ST (46409) TO UNION T (46451) CKT 1 [115.00 - 115.00 kV]

260 460 3462 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

260 775 3479 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

500

525 140 3543 Branch MASS

BFR: 4526 Monroe-EchoLK-SnoK 500 kV #1 & Mon-Cust #2 500kV (46433) TO UNION T (46451) CKT 1 [115.00 - 115.00 kV]

525 460 3660 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

525 775 3675 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

0

1000 140 3931 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

0 100 200 300 400 500 600 700 800 900 1000

1000 460 3948 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

PSE Generation (MW)

1000 775 3971 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]







2000 0

2000 1050

Gen PSE SCL Transfer Worst Limiting

Sensitivity of Ingledow-Custer limits to

Sedro - Horse Ranch 230kV line PSE, SCL, and SNOH Generation # Gen Gen Limit Contingency Facility

4000

G3 100 775 3299 BFR: 4519 Cust-Mon #1 500kV & Mon Caps Branch MURRAY (40767) TO SEDRO NT (42103) CKT 1 [230.00 - 230.00 kV]

WINTER 2012 Westside Limit=2000 MW SCL+SNOH Gen= 140 MW G6 260 775 3407 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

South-to-North (SN) SCL+SNOH Gen= 460 MW SCL+SNOH Gen= 775 MW G9 525 775 3380 N-1: Monroe - Custer #1 500kV Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

3500

Light Loads G12 1000 775 3652 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Outage: W12 G2 100 465 3310 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Temp: 35F G5 260 460 3392 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

3000

G8 525 460 3346 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]



G11 1000 460 3621 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]









Ingledow-Custer limit (MW)

2500 G1 100 140 3291 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

G4 260 140 3374 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

G7 525 140 3571 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

G10 1000 140 3638 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

2000

Average Puget Sound Net Area Load = 3277

Gen Level Trans Worst Limiting

PSE SCL/ Limit Contingency Facility

SNOH 1500

100 140 3291 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

100 460 3310 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

100 775 3299 BFR: 4519 Cust-Mon #1 500kV & Mon Caps 1000

Branch MURRAY (40767) TO SEDRO NT (42103) CKT 1 [230.00 - 230.00 kV]

260 140 3374 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

260 460 3392 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

260 775 3407 kV]

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00500

525 140 3571 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

525 460 3346 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

525 775 3380 N-1: Monroe - Custer #1 500kV Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

0

1000 140 3638 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

0 100 200 300 400 500 600 700 800 900 1000

1000 460 3621 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

PSE Generation (MW)

1000 775 3652 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]







2000 0

2000 1050

Gen PSE SCL Transfer Worst Limiting

Sensitivity of Ingledow-Custer limits to

Sedro - Horse Ranch 230kV line PSE, SCL, and SNOH Generation # Gen Gen Limit Contingency Facility

4000 G3 100 775 3173 BFR: 4519 Cust-Mon #1 500kV & Mon Caps Branch MURRAY (40767) TO SEDRO NT (42103) CKT 1 [230.00 - 230.00 kV]

Westside Limit=2000 MW SCL+SNOH Gen= 140 MW

WINTER 2012 G6 260 775 3104 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

South-to-North (SN) SCL+SNOH Gen= 460 MW SCL+SNOH Gen= 775 MW G9 525 775 3282 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Light Loads 3500 G12 1000 775 3577 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Outage: W12 G2 100 465 3002 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Temp: 45F G5 260 460 3322 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

3000

G8 525 460 3298 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]



G11 1000 460 3563 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]









Ingledow-Custer limit (MW)

2500 G1 100 140 3214 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

G4 260 140 3067 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

G7 525 140 3286 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

G10 1000 140 3542 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

2000

Average Puget Sound Net Area Load = 2616

Gen Level Trans Worst Limiting

PSE SCL/ Limit Contingency Facility

SNOH 1500

100 140 3214 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

100 460 3002 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

100 775 3173 BFR: 4519 Cust-Mon #1 500kV & Mon Caps 1000

Branch MURRAY (40767) TO SEDRO NT (42103) CKT 1 [230.00 - 230.00 kV]

260 140 3067 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

260 460 3322 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

260 775 3104 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

500

525 140 3286 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

525 460 3298 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

525 775 3282 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

0

1000 140 3542 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

0 100 200 300 400 500 600 700 800 900 1000

1000 460 3563 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

PSE Generation (MW)

1000 775 3577 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]







2000 0

2000 1050

Gen PSE SCL Transfer Worst Limiting

Sensitivity of Ingledow-Custer limits to

Sedro - Horse Ranch 230kV line PSE, SCL, and SNOH Generation # Gen Gen Limit Contingency Facility

4000 G3 100 775 2761 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Westside Limit=2000MW SCL+SNOH Gen= 140 MW

WINTER 2012 G6 260 775 2843 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

SCL+SNOH Gen= 460 MW SCL+SNOH Gen= 775 MW

South-to-North (SN) G9 525 775 3055 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Light Loads 3500 G12 1000 775 3350 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Outage: W12 G2 100 460 2748 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Temp: 60F G5 260 460 2829 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

3000

G8 525 460 3045 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]



G11 1000 460 3366 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]









Ingledow-Custer limit (MW)

2500 G1 100 140 2735 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

G4 260 140 2816 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

G7 525 140 3030 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

G10 1000 140 3323 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

2000

Average Puget Sound Net Area Load = 3079

Gen Level Trans Worst Limiting

PSE SCL/ Limit Contingency Facility

SNOH 1500

100 140 2735 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

100 460 2748 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

100 775 2761 1000

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

260 140 2816 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

260 460 2829 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

260 775 2843 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

500

525 140 3030 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

525 460 3045 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

525 775 3055 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

0

1000 140 3323 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

0 100 200 300 400 500 600 700 800 900 1000

1000 460 3366 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

PSE Generation (MW)

1000 775 3350 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]







2000 0

2000 1050

Gen PSE SCL Transfer Worst Limiting

Sensitivity of Ingledow-Custer limits to

Sedro - Horse Ranch 230kV line PSE, SCL, and SNOH Generation # Gen Gen Limit Contingency Facility

4000 G3 100 775 2594 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Westside Limit=2000 MW SCL+SNOH Gen= 140 MW

WINTER 2012 G6 260 775 2681 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

SCL+SNOH Gen= 460 MW SCL+SNOH Gen= 775 MW

South-to-North (SN) G9 525 775 2890 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Light Loads 3500 G12 1000 775 3172 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Outage: W12 G2 100 465 2599 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Temp: 70F G5 260 460 2680 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

3000

G8 525 460 2894 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]



G11 1000 460 3185 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]









Ingledow-Custer limit (MW)

2500 G1 100 140 2568 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

G4 260 140 2669 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

G7 525 140 2878 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

G10 1000 140 3172 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

2000

Average Puget Sound Net Area Load = 3230

Gen Level Trans Worst Limiting

PSE SCL/ Limit Contingency Facility

SNOH 1500

100 140 2568 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

100 460 2599 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

100 775 2594 1000

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

260 140 2669 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

260 460 2680 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

260 775 2681 kV]

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00500

525 140 2878 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

525 460 2894 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

525 775 2890 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

0

1000 140 3172 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

0 100 200 300 400 500 600 700 800 900 1000

1000 460 3185 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

PSE Generation (MW)

1000 775 3172 BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]







2000 0

2000 1050

25F 35F 45F 60F 70F Description:

G0 3099.87 3290.82 3213.75 2735.22 2567.58

G1 3375.95 3309.84 3001.62 2747.79 2599.04 Season/Year:

G2 3396.83 3298.66 3172.66 2760.68 2594.45 Direction:

G3 3286.27 3374.14 3066.67 2816.17 2669.05 Case Loads:

G4 3462.19 3391.78 3321.54 2828.73 2680.07 Outage:

G5 3479.36 3406.79 3104.13 2843.08 2681.00 Power World:

G6 3543.26 3571.30 3285.69 3029.58 2878.11 File Location:

G7 3659.51 3346.10 3298.37 3044.54 2893.56 Study Person:

G8 3675.04 3380.46 3281.68 3054.52 2890.47 Source:

G9 3931.46 3637.54 3541.85 3323.19 3171.72

G10 3947.52 3620.73 3563.33 3365.69 3185.28

G11 3970.78 3651.65 3577.28 3350.14 3171.79





*Note: The presence of a "red" box indicates a further examination in Powerworld is required





FULL CTG_FAIL_IN_FULL

CTG_FAIL_IN_FULL FULL FULL

CTG_FAIL_IN_FULL FULL

CTG_FAIL_IN_FULL FULL FULL

CTG_FAIL_IN_FULL FULL

CTG_FAIL_IN_FULL FULL FULL

FULL FULL

CTG_FAIL_IN_FULL FULL FULL

CTG_FAIL_IN_FULL FULL

CTG_FAIL_IN_FULL CTG_FAIL_IN_FULL FULL

CTG_FAIL_IN_FULL FULL

CTG_FAIL_IN_FULL FULL FULL

FULL FULL

CTG_FAIL_IN_FULL FULL FULL

FULL

CTG_FAIL_IN_FULL FULL FULL FULL

FULL

CTG_FAIL_IN_FULL FULL FULL FULL

FULL

CTG_FAIL_IN_FULL FULL FULL FULL

FULL

CTG_FAIL_IN_FULL FULL FULL FULL

FULL

CTG_FAIL_IN_FULL FULL FULL FULL

Sedro - Horse Ranch 230kV line





WINTER 2012

South-to-North (SN)

Light Loads

W12

15

RS4F01\Wrkgrp\Tot\Northern Intertie\Archives\2012\WINTER 2012

JLJ5166

W12v1SNL









rld is required

South-to-North (SN) Light Loads W12 Sedro - Horse Ranch 230kV line

PSE Gen 100 100 100 260 260 260 525 525 525 1000 1000 1000

SCL Gen LOAD 140 460 775 140 460 775 140 460 775 140 460 775

25F 3992 3100 3376 3397 3286 3462 3479 3543 3660 3675 3931 3948 3971

35F 3277 3291 3310 3299 3374 3392 3407 3571 3346 3380 3638 3621 3652

45F 2616 3214 3002 3173 3067 3322 3104 3286 3298 3282 3542 3563 3577

60F 3079 2735 2748 2761 2816 2829 2843 3030 3045 3055 3323 3366 3350

70F 3230 2568 2599 2594 2669 2680 2681 2878 2894 2890 3172 3185 3172

Interface Scenario I0

25F Trans Lim

G0 3102.45

G1 3375.03

G2 3395.95

G3 3286.35

G4 3461.32

G5 3478.57

G6 3542.41

G7 3659.61

G8 3675.21

G9 3929.24

G10 3948.67

G11 3970.05



35F Trans Lim

G0 3290.71

G1 3308.25

G2 3297.4

G3 3372.75

G4 3391.75

G5 3406.89

G6 3571.16

G7 3345.93

G8 3380.37

G9 3638.17

G10 3621.23

G11 3652.12



45F Trans Lim

G0 3212.07

G1 3000.01

G2 3172.58

G3 3065.41

G4 3320.31

G5 3102.91

G6 3284.58

G7 3297.32

G8 3280.08

G9 3542.01

G10 3563.52

G11 3577.43



60F Trans Lim

G0 2734.17

G1 2746.68

G2 2759.7

G3 2815.16

G4 2827.74

G5 2841.93

G6 3028.35

G7 3043.31

G8 3055.11

G9 3324.76

G10 3366

G11 3351.65



70F Trans Lim

G0 2566.38

G1 2599.93

G2 2594.89

G3 2669.25

G4 2678.87

G5 2678.54

G6 2876.04

G7 2891.61

G8 2889.41

G9 3173.87

G10 3186.38

G11 3172.85



W12v1SNL

Limiting Element

Branch BROAD ST (46409) TO UNION T (46451) CKT 1 [115.00 - 115.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch BROAD ST (46409) TO UNION T (46451) CKT 1 [115.00 - 115.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch MASS (46433) TO UNION T (46451) CKT 1 [115.00 - 115.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]



Limiting Element

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch MURRAY (40767) TO SEDRO NT (42103) CKT 1 [230.00 - 230.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]



Limiting Element

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch MURRAY (40767) TO SEDRO NT (42103) CKT 1 [230.00 - 230.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]



Limiting Element

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]



Limiting Element

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Branch CUST MON2 (95010) TO MONROE2 (95013) CKT 2 [500.00 - 500.00 kV]

Limiting CTG % OTDF Pre-Trans Est Limit Used

3TM: Monroe-Echo LK-SnoK 500kV -4.53 -234.72 -234.7

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -60.36 -2666.91 -2666.82

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -60.36 -2666.98 -2666.9

BFR: 4522 Echo Lk-Mon-SnoK #1 500kV & Mon Caps -4.53 -235.2 -235.33

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -60.36 -2666.95 -2666.88

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -60.36 -2666.94 -2666.88

BFR: 4526 Monroe-EchoLK-SnoK 500 kV #1 & Mon-Cust #2 500kV 4.58 235.41 235.52

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -63.22 -2665.66 -2666.92

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -63.22 -2665.61 -2666.89

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -63.22 -2667.17 -2666.73

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -63.22 -2665.68 -2666.75

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -63.22 -2666.77 -2666.82



Limiting CTG % OTDF Pre-Trans Est Limit Used

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -63.22 -2567.71 -2569

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -63.22 -2568.69 -2568.97

BFR: 4519 Cust-Mon #1 500kV & Mon Caps 12.57 514.2 514.24

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -63.22 -2568.78 -2568.99

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -63.22 -2567.57 -2568.95

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -63.22 -2569.56 -2568.83

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -63.22 -2567.84 -2568.98

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2440.97 -2440.16

N-1: Monroe - Custer #1 500kV -67.72 -2435.21 -2436.25

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2442.79 -2442.93

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2427.29 -2426.65

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2439 -2438.86



Limiting CTG % OTDF Pre-Trans Est Limit Used

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -63.22 -2469.62 -2469.89

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2358.74 -2358.25

BFR: 4519 Cust-Mon #1 500kV & Mon Caps 13.7 494.22 494.47

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2356.56 -2358.05

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -63.22 -2469.74 -2469.94

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2355.75 -2355.62

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2363.4 -2364.1

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2362.22 -2362.36

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2346.6 -2347.51

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2347 -2346.29

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2346.64 -2347.96

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2345.19 -2346.48



Limiting CTG % OTDF Pre-Trans Est Limit Used

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2228.18 -2228.88

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2226.6 -2227.38

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2225 -2225.89

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2226.41 -2227.29

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2224.74 -2225.62

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2223.7 -2224.65

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2230.67 -2232.6

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2230.34 -2230.73

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2227.51 -2229.52

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2231.61 -2231.06

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2242.01 -2242.09

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2227.83 -2228.13



Limiting CTG % OTDF Pre-Trans Est Limit Used

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2152.65 -2150.75

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2154.79 -2153.42

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2148.22 -2148.5

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2155.83 -2154.06

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2151.76 -2152.75

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2147.29 -2147.6

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2156.62 -2158.1

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2157.39 -2156.21

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2152.38 -2150.7

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2156.92 -2156.39

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2154.53 -2155.19

BFR: 4268 Mon-Cust #1 500kV & Cust 500/230kV Bk#1 -69.12 -2141.44 -2141.67

ATC Mon: MW flow Puget Sound Area Net Load (207) ATC Mon: MW flow Custer - Ingledow SN (201)

3978.22 3099.87

3977.13 3375.95

3989.89 3396.83

4004.13 3286.27

3990.69 3462.19

3989.68 3479.36

4006.05 3543.26

3990.05 3659.51

3988.81 3675.04

4011.43 3931.46

3990.16 3947.52

3989.93 3970.78



ATC Mon: MW flow Puget Sound Area Net Load (207) ATC Mon: MW flow Custer - Ingledow SN (201)

3271.18 3290.82

3258.82 3309.84

3272.22 3298.66

3294.12 3374.14

3272.51 3391.78

3272.54 3406.79

3293.78 3571.3

3270.67 3346.1

3271.86 3380.46

3293.81 3637.54

3273.76 3620.73

3274.89 3651.65



ATC Mon: MW flow Puget Sound Area Net Load (207) ATC Mon: MW flow Custer - Ingledow SN (201)

2608.05 3213.75

2596.42 3001.62

2611.48 3172.66

2630.33 3066.67

2613.28 3321.54

2612.8 3104.13

2630.66 3285.69

2611.81 3298.37

2613.27 3281.68

2635.05 3541.85

2616.41 3563.33

2618.33 3577.28



ATC Mon: MW flow Puget Sound Area Net Load (207) ATC Mon: MW flow Custer - Ingledow SN (201)

3069.51 2735.22

3059.02 2747.79

3074.1 2760.68

3093.04 2816.17

3073.66 2828.73

3075.13 2843.08

3093.51 3029.58

3074.37 3044.54

3075.99 3054.52

3097.97 3323.19

3079.37 3365.69

3080.54 3350.14



ATC Mon: MW flow Puget Sound Area Net Load (207) ATC Mon: MW flow Custer - Ingledow SN (201)

3220.73 2567.58

3211.11 2599.04

3225.36 2594.45

3244.55 2669.05

3225.43 2680.07

3226.33 2681

3244.99 2878.11

3225.75 2893.56

3227.06 2890.47

3248.12 3171.72

3229.56 3185.28

3231.32 3171.79

Iteratively Found ATC Mon: ATC Mon:

FULL 0 0

CTG_FAIL_IN_FULL 0 0

CTG_FAIL_IN_FULL 0 0

FULL 0 0

CTG_FAIL_IN_FULL 0 0

CTG_FAIL_IN_FULL 0 0

FULL 0 0

CTG_FAIL_IN_FULL 0 0

CTG_FAIL_IN_FULL 0 0

CTG_FAIL_IN_FULL 0 0

CTG_FAIL_IN_FULL 0 0

CTG_FAIL_IN_FULL 0 0



Iteratively Found ATC Mon: ATC Mon:

CTG_FAIL_IN_FULL 0 0

CTG_FAIL_IN_FULL 0 0

CTG_FAIL_IN_FULL 0 0

CTG_FAIL_IN_FULL 0 0

CTG_FAIL_IN_FULL 0 0

CTG_FAIL_IN_FULL 0 0

CTG_FAIL_IN_FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0



Iteratively Found ATC Mon: ATC Mon:

CTG_FAIL_IN_FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

CTG_FAIL_IN_FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0



Iteratively Found ATC Mon: ATC Mon:

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0



Iteratively Found ATC Mon: ATC Mon:

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0

FULL 0 0



Other docs by huanghengdong
6th-syllabus-Threet-2011-2012
Views: 0  |  Downloads: 0
Gina Cillo rd
Views: 0  |  Downloads: 0
szoftverfejlesztok.xls
Views: 1  |  Downloads: 0
cv-notes-exemple
Views: 0  |  Downloads: 0
Damascus Steel_seth Willouhby
Views: 0  |  Downloads: 0
UP_HolderReportingManual
Views: 0  |  Downloads: 0
4
Views: 0  |  Downloads: 0
ScienceFairLesson2
Views: 0  |  Downloads: 0
By registering with docstoc.com you agree to our
privacy policy

You are almost ready to download!

You are almost ready to download!