Embed
Email

CAB

Document Sample

Shared by: ewghwehws
Categories
Tags
Stats
views:
1
posted:
1/6/2012
language:
pages:
1
CAB Alternating Relay



Specifications

Electrical

Input Voltage: 24 to 230VAC, ±10%, Physical

50/60Hz. Mounting: Plug-In

Control Signal: Termination:

100 mSec. min. to ensure transfer 8 or 11 Pin & Blade Base

Reset Times: 100 Milliseconds, Typical Packaging: Dust Cover

Protection: Varistor and/or R-C Network Weight: 7 Oz.

Power Consumption: 4VA

Output Relay: Ambient Temperatures

10 Amps @ 120/240VAC Operating: -10°C to 40°C

500,000 Full Load Electrical Cycles U.L Operating:: -10°C to 40°C

50,000,000 Mechanical Cycles

U.L and CSA Ratings:

5 Amps, 1/3 HP, 125VA @ 230VAC

5 Amps, 1/6 HP, 125VA @ 120VAC



• Duplex Pump Control Ordering Information

• CMOS Design CAB - 115A - 1

• 10 Amp Relay R-K Model Adjustments

1 - SPDT, 8 Pin

• DPDT Input Voltages 2 - DPDT, 11 Pin (T)*

2B - DPDT, Blade

• Indicating LEDs 24A - 24VAC

3 - X-Conn

115A - 115VAC

• Reliable 230A - 230VAC 4 - DPDT, 11 Pin (A-D)*



• Transient Protected * “T” Time Mark, “D” Diversified, “A” R-K ARB



®

Dimensions Connections

C US Input Voltage

+

C1

Input

Voltage -

E71902 3.7" (B)

.6" 1.8" - + C1

3.1"

6

Operation 4 5 5 7

4 8

Alternating Relay 3 6

2.3"

Input voltage and a customer supplied 3 9

contact are required. When input voltage 2 7

2 10

is first applied to the CAB, its internal relay 1 8 1 11

remains de-energized. First closure of the

contact (C1) does not cause a transfer Adj. Code 1 Adj. Code 2 (T)

of the internal relay. Opening the contact

(C1) for the first time causes the internal

Storage: -10°C to 85°C

Example: CAB-115A-1 Input

relay to energize, transferring the output 1 2 3 + Voltage -

C1

MS1 = Load #1 (Motor Starter)

contacts. Each subsequent opening of the 4 5 6 4 5

MS2 = Load #2 Motor Starter

contact (C1) will cause the relay to transfer

C1 = Control Contact 7 8 9 3 6

to the other position (alternating). Removal

Input Voltage

of input voltage from the CAB resets the + A B C1

- + C1 - 2 7

internal relay to its initial condition (de- Input

energized). Voltage 1 8

4 5

Adj. Code 2B Adj. Code 3

Close 3 6

C1 + Input -

Open C1 Voltage

2 7



MS1 1 8 6

CAB 5 7

4 8

Energized De-Energized MS2

3 9

2 10 Adj. Code 4 (A-D)

1 11

P1 5/28/07 513.204.6060 or 800.543.4936 • www.rke.com