Docstoc

Specification

Document Sample
Specification Powered By Docstoc
					Specification
Kalzip® SolarPowerSystems

A separate additional offer can be made for equivalent alternatives.
Only flexible amorphous silicon thin-film modules that have 3
semiconductor layers, are permanently laminated on aluminium, are
approved according to IEC 61646 and protection class II and identical in
appearance are considered as equivalent alternatives.
Carrying out the described services is based on the installation manual of
Kalzip GmbH, as well as the IEC 60364-712 and basic electrical standards.
The safety and health protection rules for the construction industry are an
integral part of the offer.
Kalzip® AluPlusSolar Module PVL-136 (number according to Systems specification)

0000 Building Integrated Photovoltaic Module
a-SI thin-film modules, factory-laminated to the roofing
(aluminium profile boards) by the manufacturer
Module length: 5.50 m
Nominal output: 136 W
Operating voltage VMPP: 33.0 V
Operating current IMPP: 4.13 A
Open-circuit voltage VOC: 46.2 V
Open-circuit voltage VOC at -10°C and 1250 W/m2: 52.7 V
Short-circuit current ISC: 5.1 A
Short-circuit current ISC at 75°C and 1250 W/m2: 6.7 A
Fuse in series, nom./blocking diode, nom.: 8.0 A
Maximum system voltage DC: 1000 V
Connection: pre-assembled connecting cable plug/socket
Type: Kalzip® AluPlusSolar PVL-136
When installing the roofing, connect ready for use and
wired up according to DC circuit diagram.


__ Item x Price per Item: .............€ = .............€


Kalzip® AluPlusSolar Module PVL 68 (number according to Systems specification)

0000 Building Integrated Photovoltaic Module
a-SI thin-film modules, factory-laminated to the roofing
(aluminium profile boards) by the manufacturer
Module length: 2.85 m
Nominal output: 68 W
Operating voltage VMPP: 16.5 V
Operating current IMPP: 4.13 A
Open-circuit voltage VOC: 23.1 V
Open-circuit voltage VOC at -10°C and 1250 W/m2: 26.3 V
Short-circuit current ISC: 5.1 A
Short-circuit current ISC at 75°C and 1250 W/m2: 6.7 A
Fuse in series, nom./blocking diode, nom. : 8.0 A
Maximum system voltage DC: 1000 V
Connection: pre-assembled connecting cable plug/socket
Type: Kalzip® AluPlusSolar PVL-68
When installing the roofing, connect ready for use and wire
up according to DC circuit diagram

__ Item x Price per Item: .............€ = .............€
1.1 Kalzip® SolarClad
1.1.1 Roof Parallel Installation (horizontal)
Kalzip® SolarClad Module PVL-136 (number according to Systems specification)

0000 Photovoltaic Module
Modules are made of painted aluminium edge profiles with
laminated a-Si thin-film module
Module width: 0.46 m
Module length: 5.50 m
Nominal output: 136 W
Operating voltage VMPP: 33.0 V
Operating current IMPP: 4.13 A
Open-circuit voltage VOC: 46.2 V
Open-circuit voltage VOC at -10°C and 1250 W/m2: 52.7 V
Short-circuit current ISC: 5.1 A
Short-circuit current ISC at 75°C and 1250 W/m2: 6.7 A
Fuse in series, nom./blocking diode, nom.: : 8.0 A
Maximum system voltage DC: 1000 V
Connection: pre-assembled connecting cable plug/socket
Type: Kalzip® SolarClad PVL-136
Impermeable horizontal roof-parallel installation using beam
notches and mounting rails that belong to the system;
deliver, install, connect ready for use and wire according to
DC wiring diagram

__ Item x Price per Item: .............€ = .............€

Kalzip® SolarClad Module PVL 68 (number according to Systems specification)

0000 Photovoltaic Module
Modules made of painted aluminium edge profiles with
laminated a-Si thin-film module
Module width: 0.46 m
Module length: 2.85 m
Nominal output: 68 W
Operating voltage VMPP: 16.5 V
Operating current IMPP: 4.13 A
Open-circuit voltage VOC: 23.1 V
Open-circuit voltage VOC at -10°C and 1250 W/m2: 26.3 V
Short-circuit current ISC: 5.1 A
Short-circuit current ISC at 75°C and 1250 W/m2: 6.7 A
Fuse in series, nom./blocking diode, nom.: : 8.0 A
Maximum system voltage DC: 1000 V
Connection: pre-assembled connecting cable plug/socket
Type: Kalzip® SolarClad PVL-68
Impermeable horizontal roof-parallel installation using beam
notches and mounting rails that belong to the system
Deliver, install, connect ready for use and wire according to
DC wiring diagram

__ Item x Price per Item: .............€ = .............€
1.1.2 Roof Parallel Installation (vertical)
Kalzip® SolarClad Module PVL-136 (number according to Systems specification)

0000 Photovoltaic Module
Modules are made of painted aluminium edge profiles with
laminated a-Si thin-film module
Module width: 0.46 m
Module length: 5.50 m
Nominal output: 136 W
Operating voltage VMPP: 33.0 V
Operating current IMPP: 4.13 A
Open-circuit voltage VOC: 46.2 V
Open-circuit voltage VOC at -10°C and 1250 W/m2: 52.7 V
Short-circuit current ISC: 5.1 A
Short-circuit current ISC at 75°C and 1250 W/m2: 6.7 A
Fuse in series, nom./blocking diode, nom.: : 8.0 A
Maximum system voltage DC: 1000 V
Connection: pre-assembled connecting cable plug/socket
Type: Kalzip® SolarClad PVL-136
Impermeable vertical roof-parallel installation using beam
notches and mounting rails that belong to the system;
deliver, install, connect ready for use and wire according to
DC wiring diagram

__ Item x Price per Item: .............€ = .............€

Kalzip® SolarClad Module PVL 68 (number according to Systems specification)

0000 Photovoltaic Module
Modules made of painted aluminium edge profiles with
laminated a-Si thin-film module
Module width: 0.46 m
Module length: 2.85 m
Nominal output: 68 W
Operating voltage VMPP: 16.5 V
Operating current IMPP: 4.13 A
Open-circuit voltage VOC: 23.1 V
Open-circuit voltage VOC at -10°C and 1250 W/m2: 26.3 V
Short-circuit current ISC: 5.1 A
Short-circuit current ISC at 75°C and 1250 W/m2: 6.7 A
Fuse in series, nom./blocking diode, nom.: : 8.0 A
Maximum system voltage DC: 1000 V
Connection: pre-assembled connecting cable plug/socket
Type: Kalzip® SolarClad PVL-68
Impermeable vertical roof-parallel installation using beam
notches and mounting rails that belong to the system
Deliver, install, connect ready for use and wire according to
DC wiring diagram

__ Item x Price per Item: .............€ = .............€
1.1.3 Elevated installation
Kalzip® SolarClad Module PVL-136 (number according to Systems specification)

0000 Photovoltaic Module
Modules are made of painted aluminium edge profiles with
laminated a-Si thin-film module
Module width: 0.46 m
Module length: 5.50 m
Nominal output: 136 W
Operating voltage VMPP: 33.0 V
Operating current IMPP: 4.13 A
Open-circuit voltage VOC: 46.2 V
Open-circuit voltage VOC at -10°C and 1250 W/m2: 52.7 V
Short-circuit current ISC: 5.1 A
Short-circuit current ISC at 75°C and 1250 W/m2: 6.7 A
Fuse in series, nom./blocking diode, nom.: 8.0 A
Maximum system voltage DC: 1000 V
Connection: pre-assembled connecting cable plug/socket
Type: Kalzip® SolarClad PVL-136
Impermeable elevated installation using beam notches and
elevated rear panel profile that belongs to the system
Deliver, install, connect ready to use and wire according to
DC wiring diagram

__ Item x Price per Item: .............€ = .............€

Kalzip® SolarClad Module PVL 68 (number according to Systems specification)

0000 Photovoltaic Module
Modules are made of painted aluminium edge profiles with
laminated a-Si thin-film module
Module width: 0.46 m
Module length: 2.85 m
Nominal output: 68 W
Operating voltage VMPP: 16.5 V
Operating current IMPP: 4.13 A
Open-circuit voltage VOC: 23.1 V
Open-circuit voltage VOC at -10°C and 1250 W/m2: 26.3 V
Short-circuit current ISC: 5.1 A
Short-circuit current ISC at 75°C and 1250 W/m2: 6.7 A
Fuse in series, nom./blocking diode, nom.: 8.0 A
Maximum system voltage DC: 1000 V
Connection: pre-assembled connecting cable plug/socket
Type: Kalzip® SolarClad PVL-68
Impermeable elevated installation using beam notches and
elevated rear panel profile that belongs to the system
Deliver, install, connect ready to use and wire according to
DC wiring diagram

__ Item x Price per Item: .............€ = .............€
2 Connection of the modules (wiring)
For Kalzip®AluPlusSolar and Kalzip SolarClad roof parallel:
length = number of modules x 0,5 m

For Kalzip® Aluplussolar Elevated:
Length = number of modules x 1,0 m

0000 MODUL CABLING
(DC cables for the modules until the generator junction box)
PV module cable for DC wiring
Double protective isolation and protection type IP54
Temperature range -40°C to +80°C
Sizing: Piping loss < 1%

__ m    x    Price per m:............€ = .............€


Automatically 1 piece per each Inverter Typ IG 15 – IG 30

0000 GENERATOR TERMINAL BOX
Connections (input): max. 6 mm² screw terminals for 4
lines of modules
Connections (output): max. 16 mm2 screw terminals for
each DC- and DC+ main lead
Protection type: IP44
Protection class: I I
Max. open circuit voltage: 500 V
Max. input current: 20 A (at 150 V), 7 A (at 400 V )
Max DC output current: 16 A
Type: Fronius DC isolating box for IG15-30

__ Item x Price / Item .............€ = .............€


Automatically 1 piece per each Inverter Typ IG 40 – IG 60

0000 GENERATOR TERMINAL BOX
Connections (input): max. 6 mm² screw terminals for 8
lines of modules
Connections (output): max. 25mm2 screw terminals for
each DC- and DC+ main lead
Protection type: IP54
Protection class: I I
Max. open circuit voltage: 530 V
Max. input current: 37 A (at 150 V), 14 A (at 400 V )
Max DC output current: 25 A
Type: Fronius DC isolating box for IG40-60

__ Item x Price / Item .............€ = .............€
Default: 10 m, otherwise questioned by the program

0000 PV DIRECT CURRENT MAIN LEAD
Generator terminal box connection to inverters
Double protective isolation and protection type IP54
Temperature range -40°C to +80°C
Sizing: Piping loss < 1%
__ m x Item Price .............€ = .............€

3 Inverter

0000 INVERTER
Photovoltaic inverter for supplying network with solar
energy
Graphic display galvanic insulation with HF transformer,
Data communication option with plug-in cards, integrated
MSD,
Housing, DC connections as screw terminals for max 10 mm² cables without multicore cable
end or 6 mm² with multicore cable end
Max. input current: 500 V
MPP voltage range: 150-400 V
PV output: 1300 – 2000 Wp
AC nominal output: 1300 W
Distortion factor: < 3.5 %
Power factor: 1
Ambient temperature: -20...+50°C
Installation: Indoor installation, with wall mounting
Protection type: IP21
Type:FRONIUS IG 15

__ Item x Price / Item .............€ = .............€

0000 INVERTER
Photovoltaic inverter for supplying network with solar
energy.
Graphic display, galvanic insulation with HF transformer,
Data communication option using plug-in cards, integrated
MSD,
Housing, DC connections as screw terminals for max 10 mm² cables without multicore cable
end or 6 mm² with multicore cable end
Max. input current: 500 V
MPP voltage range: 150-400 V
PV output: 1800 – 2700 Wp
AC nominal output: 1800 W
Distortion factor: < 3.5 %
Power factor: 1
Ambient temperature: -20...+50°C
Installation: Indoor installation, with wall mounting
Protection type: IP21
Type: FRONIUS IG 20

__ Item x Price / Item .............€ = .............€
0000 INVERTER
Photovoltaic inverter for supplying network with solar
energy.
Graphic display, galvanic insulation with HF transformer,
Data communication option using plug-in cards, integrated
MSD,
Housing, DC connections as screw terminals for max 10 mm² cables without multicore cable
end or 6 mm² with multicore cable end
Max. input current: 500 V
MPP voltage range: 150-400 V
PV output: 2500 – 3600 Wp
AC nominal output: 2500 W
Distortion factor: < 3.5 %
Power factor: 1
Ambient temperature: -20...+50°C
Installation: Indoor installation, with wall mounting
Protection type: IP21
Type: FRONIUS IG 30

__ Item x Price / Item .............€ = .............€

0000 INVERTER
Photovoltaic inverter for supplying network with solar
energy.
Graphic display, galvanic insulation with HF transformer,
internal master-slave operation of 2 power elements,
Data communication option using plug-in cards, integrated
MSD,
Housing, DC connections as screw terminals for max 10 mm² cables without multicore cable
end or 6 mm² with multicore cable end
Max. input current: 500 V
MPP voltage range: 150-400 V
PV output: 3500 – 5500 Wp
AC nominal output: 3500 W
Distortion factor: < 3.5 %
Power factor: 1
Ambient temperature: -20...+50°C
Installation: Indoor installation, with wall mounting
Protection type: IP21
Type: FRONIUS IG 40

__ Item x Price / Item .............€ = .............€
0000 INVERTER
Photovoltaic inverter for supplying network with solar
energy.
Graphic display, galvanic insulation with HF transformer,
internal master-slave operation of 2 power elements,
Data communication option using plug-in cards, integrated
MSD,
Housing, DC connections as screw terminals for max 10 mm² cables without multicore cable
end or 6 mm² with multicore cable end
Max. input current: 500 V
MPP voltage range: 150-400 V
PV output: 4600 – 6700 Wp
AC nominal output: 4600 W
Distortion factor: < 3.5 %
Power factor: 1
Ambient temperature: -20...+50°C
Installation: Indoor installation, with wall mounting
Protection type: IP21
Type: FRONIUS IG 60

__ Item x Price / Item .............€ = .............€

4 Data Communication
if only one Inverter in the system, you will need only one

0000 Datalogger Box easy
Datalogger in external housing;
The datalogger registers and saves the following data of one FRONIUS IG inverter: DC-current, DC-
voltage, AC-current, AC-voltage, AC-power, daily yield, yearly yield, measuring values of the sensors
connected to a FRONIUS IG Sensor Card/Box. Fault information via text message when a modem is
connected. The inverter can be called up and maintained remotely;

    Memory capacity:               540 kByte
    Memory duration:               about 1000 days (memory cycle 30minutes)
    L x w x h:                     197 x 110 x 57 mm
    Sockets:                       9-pole submin (RS232 interface for PC)
                                   9- pole submin (RS232 interface for modem)
                                   36-pole Pin-plug type connection
                                   2 RJ 45 sockets for RS 485 transmission
    Degree of protection:          IP 20
    Type:                          FRONIUS IG Datalogger Box easy (or comparable)

__ Item x Price / Item .............€ = .............€
if more than one inverter the number of Com cards is equal with the number of inverters

0000 Communication between the inverters
COM Card
Plug-in card for data connection;
Inverters data linked with one another, data transmitted onto the datalogger, power supply for the
datalogger and other plug-in cards, galvanic separation between inverter and data communication;
Each inverter with data communication requires its own COM Card.

      L x w x h:                                 140 x 100 x 33 mm
      Sockets:                                   2x RJ 45 sockets for RS 485 transmission
      Type:                                      FRONIUS IG COM Card (or comparable)

__ Item x Price / Item .............€ = .............€



always one piece

0000 Datalogger Box pro
Datalogger in external housing;
The datalogger registers and saves the following data (up to 100 FRONIUS IG): DC-current, DC-
voltage, AC-current, AC-voltage, AC-power, daily yield, yearly yield, measuring values of the sensors
connected to a FRONIUS IG Sensor Card/Box. Fault information via text message when a modem is
connected; The inverter can be called up and maintained remotely;

     Memory capacity:                      540 kByte
     Memory duration:                      about 1000 days (1 FRONIUS IG and memory cycle 30 min)
     L x w x h:                            197 x 110 x 57 mm
     Sockets:                              9-pole submin (RS232 interface for PC)
                                           9- pole submin (RS232 interface for modem)
                                           36-pole Pin-plug type connection
                                           2 RJ 45 sockets for RS 485 transmission
     Degree of protection:                 IP 20
     Type:                                 FRONIUS IG Datalogger Box pro (or comparable)

__ Item x Price / Item .............€ = .............€


always one piece

0000 Display Box
Plug-in card in an external housing for the visualisation of pv data on a large screen display; The
Public Display Box is compatible with the Public Display FRONIUS IG as well as with the whole
display range of the company RiCo. Display and Box are connected with a standard cable. The cable
is provided with the Public Display Box.

     Dimensions (l x w x h):               197 x 110 x 57 mm
     Sockets:                              9-pole submin (RS232 interface for display)
                                           2x RJ 45 sockets for RS 485 transmission
     Degree of protection:                 IP 20
Type:    FRONIUS IG Public Display Box (or comparable


__ Item x Price / Item .............€ = .............€
0000 Photovoltaic Display

large screen for the indication of all data of the whole system ( Power output, Energy gain, CO²
reduction)
The connection of a Public Display is only possible if the inverter(s) is (are) equipped with a COM
Card and a Datalogger.

     Dimensions:                           500 x 700
     Display screen:                       very bright LED (red)
     Typ:                                  Kalzip Solardisplay

__ Item x Price / Item .............€ = .............€




5 Miscellaneous
0000 LIGHTNING PROTECTION
Including the electrical lines on the building entrance
(junction of lighting protection zone 0 ->1) using a
requirement class B lightning surge arrester in the
equipotential bonding.

Flat rate x Item Price ............€ = .............€


0000 AC WIRING
Wiring up the inverters for AC side feed-in line according to
the guidelines of the energy supply company for grid
connection.
Sizing: Piping loss < 1%
Changing and expanding the existing meter cupboard for
placing the feed meter.

Flat rate x Item Price .............€ = .............€


0000 PV COMMISSIONING
Documentation:
General circuit diagram (1-pole) and connection schemes
with specifications about the type, manufacturer, wiring
and function
Register at the appropriate energy supply company
Certification and commissioning

Flat rate x Item Price .............€ = .............€

				
DOCUMENT INFO
Shared By:
Categories:
Tags:
Stats:
views:1
posted:1/5/2012
language:
pages:11