PC-Programmable Current/Voltage

CPA

and RTD/Thermocouple Limit Alarm Trips



June 2009







Description

The universal CPA PC-Programmable Alarms provide

on/off control, warn of unwanted process conditions,

and provide emergency shutdown. Very economical,

they accept a direct signal input from transmitters,

temperature sensors, and a wide array of other

monitoring and control devices:



• Current and Voltage Signals



• 23 RTD Types



• 9 Thermocouple Types



• Resistance and Potentiometer Devices



• Direct Millivolt Sources The CPA PC-Programmable Alarm features a metal, RFI

resistant housing that snaps onto standard DIN-style rails.

Single or Dual Alarm Trip Outputs

The 4-wire (line/mains-powered) CPA provides one

or two alarm relay outputs when a monitored process

Features

• Universal plant standard. There’s no need to

variable falls outside of user-set high and/or low

stock dozens of different fixed range alarm trips.

limits. This is typically used to activate a warning

light, annunciator, bell, or shutdown system. • 20-bit input resolution. Delivers industry-

best digital accuracy for both sensor (RTD and

thermocouple) and analog (current/voltage) inputs.



• PC-programmable with Windows® software.

From a single screen, you can choose, and then

view to confirm, all of your application specific

Figure 1. Available CPA models deliver versatile and

programmable input and output choices. operating parameters from a PC.



• Long-term stability. Provides up to 5 years

Programmable Programmable

Input Output between scheduled calibrations.

mA Single Relay

CPA

COMPUTER



V

PROGRAMMABLE

ALARM Dual Relay • Combined alarm trip and transmitter. The

INPUT

analog output (-AO) option reduces costs and

RTD READY

(Trip Points, installation time when both alarm and transmitter

T/C High Alarm, Low

ohms

ALARM 1

Alarm, Failsafe,

functions are needed at the same location.

ALARM 2

mV Non-Failsafe,

Normally Open, • Isolated and RFI/EMI protection. Delivers

COM Normally Closed) superior protection against the effects of ground

loops and plant noise, and radio frequency and

Analog Output

(optional)

electromagnetic interference.





Certifications*

4-Wire (Line/Mains) Powered CE Conformant – EMC Directive 89/336/EEC

24Vdc, 117Vac, 230Vac EN 61326; Low Voltage Directive 73/23/EEC EN 61010









 2009 Moore Industries-International, Inc. Page 1

225-710-01B

CPA

PC-Programmable Current/Voltage

and RTD/Thermocouple Limit Alarm Trips





One Window. One Minute. Figure 2. The CPA programs quickly from a single software window.





One Setup.

All operating parameters configure quickly and

easily using our Intelligent PC Configuration

Software. Programmable functions include:

• Input type and measurement range (zero

and full scale values)



• Input and output trimming



• High or low alarm(s) with trip points



• Failsafe or non-failsafe and normally open

or normally closed alarm relays



• Alarm deadband (0-100%) and alarm time

delay (0-120 seconds)



• T/C reference junction compensation (on/off) Programmable Process and Fault Alarms

Each individually-configurable CPA alarm trip relay

• Standard and custom linearization curves programs via the PC software as a:



• Analog output range* High or Low Process Alarm

Monitor a temperature, pressure, level, flow, position

• On input failure, upscale or downscale drive, fail or status variable, and use to warn of unwanted

to last value, or fail to selected value* process conditions, provide on/off control or provide

emergency shutdown.

• Analog signal output damping (0-120 seconds)*

Input Fault Alarm

*Models with Analog Output (-AO) option. Setting one of the CPA’s relays to trip on input or

self-diagnostic failure (without affecting the other

relay being used to monitor the process) is typically

implemented to warn of a failure, such as a broken

Powers a 2-Wire Transmitter sensor, without tripping more critical process alarms

The CPA (HLPRG: current/voltage input model) or shutting down the process.

comes standard with 2-wire transmitter excitation

that provides 24Vdc to power the loop. This saves Self-Diagnostic Alarm

the cost of specifying and installing an additional The CPA checks its own operation and configuration

instrument power supply. upon start up, and then continuously monitors its

status during operation. One of the CPA’s relays can

be configured to trip if it senses that it is not operating

Figure 3. The CPA provides transmitter excitation to power a

2-wire transmitter.

properly.



Loop CPA Quick Ranging Calibration

Power (HLPRG Using the PC software (instead of potentiometers

+ +TX Input)

which can drift), precise zero and span settings can

2-Wire 4-20mA 24Vdc be made in seconds. Just select the zero and span

Transmitter Power values, and a push of a button on the PC keyboard

Input locks the values into the CPA’s memory.

– +IN









Page 2

PC-Programmable Current/Voltage

CPA

and RTD/Thermocouple Limit Alarm Trips



Combination Alarm and Figure 5. When ordered with the Analog Output (-AO) option, the

CPA is a combination alarm trip and signal transmitter.

Isolated Transmitter

When ordered with the Analog Output (-AO) option,

the CPA provides a proportional and isolated analog Programmable Programmable

Input Alarm Trip(s)

retransmission of the input signal that can be sent to CPA

COMPUTER

PROGRAMMABLE



mA

ALARM





remote monitoring/control devices like a DCS, PLC, V INPUT





PC, indicator, or data recorder. All analog param- READY

Isolated

ALARM 1

eters can be selected using the CPA Intelligent PC RTD ALARM 2

Analog

Configuration Software. T/C Output

ohms Any Range

Upon input failure, the analog output can be mV

COM

Between 0-20mA

user-set for upscale or downscale drive, fail to last

value, or fail to selected value.



Custom 128-Point Linearization Curves Trim to Specific Curve Segments

The ability to plot a custom linearization curve is The CPA can be trimmed with two data points

beneficial when non-linear input signals must be within the selected zero and span measurement

converted to linear output representations. Typical range. This allows a complete process range to be

applications include monitoring a non-linear monitored, while placing measurement emphasis on

transducer, the level of odd-shaped tanks, and flow a critical segment of the range.

meter linearization. In the figure below, the ideal RTD curve is

optimized between 20°C and 27°C to match the curve

Figure 4. Custom linearization points can be selected and saved in of the sensor used. This provides incredible precision

the CPA’s memory to compensate for non-linear input signals.

over a limited portion of the span, while measuring

Output = Function of the Input

the remainder of the span with outstanding accuracy.

Full

100%

Scale

(20mA, 100%)

Figure 6. The CPA can be set to measure the segment most

(16mA, 87%) critical to the process.

75%

(12mA, 70%)

100

98

IDEAL RTD CURVE

% Display









50%

(USED BY DEFAULT)

(8mA, 50%)





(6mA, 35%) ˚C ACTUAL

SENSOR

25% Custom CURVE

Linearization

27

Points Full CAPTURED



0%

Scale 20 20˚C-27˚C

UPPER TRIM

4mA 8mA 12mA 16mA 20mA 1 POINT #2

Input mA 0 LOWER TRIM

POINT #1

Lower Full

Superior Cold Junction Compensation (Zero) (High)

Range Range

Uncompensated plastic terminals are very susceptible

to ambient temperature changes that may result

in readings that are “off” by several degrees. CPA Total Sensor Diagnostics for RTD Inputs

models that accept temperature inputs (TPRG input) If the RTD input breaks, the user can decide whether

feature metal terminals and advanced electronic or not to trip one alarm to indicate trouble. A plain-

compensation techniques that provide a stable English error message on the PC software indicates

measurement in fluctuating ambient temperature exactly which RTD wire has broken. Specific error

conditions. messages eliminate the work of removing the sensor

or checking all lead wires to diagnose a problem.





Page 3

CPA

PC-Programmable Current/Voltage

and RTD/Thermocouple Limit Alarm Trips





Specifications (HLPRG: mA and V Input Model)

Performance Alarm Trip Repeatability: Performance Power Consumption: Indicators LED Type: INPUT LED:

Current, ±0.01% of max. (continued) 3W typical, 4W max. Dual color LED indicates

span (±2 microamps); Power Supply Effect: input failure

Voltage, ±0.01% of max. ±0.002% of span per 1% of READY LED: Green LED

span (±1mV) line change indicates unit is operating

Input Accuracy: Current, Input Impedance: properly

±0.01% of max. span 20ohms for current inputs; ALARM 1 and ALARM 2

(±2 microamps); Voltage, 1.1Mohm for voltage inputs LED: Dual color LED per

±0.01% of max. span Input Over-Range relay indicates alarm status

(±1mV) Protection: ±100mA for

Overall Accuracy: The current inputs; ±30Vdc for Ambient Operating & Storage

overall accuracy of the unit voltage inputs Conditions Range: -40°C to +85°C

is the combined input and (-40°F to +185°F)

output (if any) accuracies. Performance WITH ANALOG OUTPUT: Relay Range: -25°C to

It includes the combined with Analog Output Accuracy: +70°C (-13°F to +158°F)

effects of linearity, Output (-AO Current, ±0.01% of max Relative Humidity:

hysteresis, repeatability, Option) span (±2 microamps); 0-95%, non-condensing

and adjustment resolution. Voltage, ±0.01% of max. Ambient Temperature

It does not include ambient span (±1mV) Effect: ±0.015% of

temperature effect Minimum Output Span: maximum span/°C

Minimum Input Span Current,4mA; Voltage, 1V RFI/EMI Immunity

at Specified Accuracy: Response Time: (Standard Unit):

Current,4mA; Voltage, 1V 256msec maximum 10V/M@20-1000MHz,

Stability: See Table 1 (128msec typical) for the 1KHz when tested

Response Time: output to change from 10 according to

300msec (Defined as time to 90% of its scale for an IEC1000-4-3-1995 with

from step change on input input step change of 0 to 0.5% of span or less error

to alarm state change when 100% RFI Immunity (with -RF

alarm is set to trip midpoint) Ripple: 50mVp-p Option):

Alarm Deadband: maximum on voltage 30V/M@20-1000MHz,

Programmable from output; 10mVp-p measured 1KHz AM when tested

0-100% across a 250 ohm load according to

Alarm Trip Delay: resistor for current output IEC1000-4-3-1995 with

0-120 seconds (Frequencies up to 120Hz) 0.5% of span or less error

Line Voltage Effect: Output Limiting: Noise Rejection:

±0.002% of span per 1% Input over range, Common mode:

change in line voltage -0.2V/0mA and 100dB@50/60Hz;

(ac or dc) 10.5V/21.4mA; Input Normal Mode: Current

Isolation: Standard unit, failure, -0.5V/0mA and Input, 100dB typical at

1000Vrms between case, 11V/24mA 50mAp-p@50/60Hz;

input and output. Output Current Limiting: Voltage Input, 100dB typical

1500Vrms between power 25mA max. at 1Vp-p@50/60Hz

and input and between Load Effect (current

power and output.; Unit outputs): 0.01% of span Weight 653 g (21 oz)

with -RF option, 500Vrms from 0 to maximum load

between case, input, output resistance on current

and power output

Maximum Load

Resistance: Current

outputs, 1Kohm; Voltage

outputs, 2Kohms





Table 1. Long-Term Stability for HLPRG (mA and V) Input Model.



Stability Input-to-Analog Input-to-Relay

(% of maximum Output (Years) Output (Years)

span)

1 3 5 1 3 5

Current Inputs 0.081 0.14 0.18 0.047 0.081 0.105



Voltage Inputs 0.093 0.16 0.21 0.066 0.114 0.147







Page 4

PC-Programmable Current/Voltage

CPA

and RTD/Thermocouple Limit Alarm Trips





Specifications (TPRG: RTD, T/C, Ohm, mV and Pot Input Model)

Performance Alarm Trip Repeatability: Performance Input Impedance: T/C Indicators LED Type: INPUT LED:

See Table 4 on Page 6 (continued) and mV inputs, 40Mohms, Dual color LED indicates

Input Accuracy: nominal input failure

See Table 4 on Page 6 Input Over-Range READY LED: Green LED

Overall Accuracy: The Protection: ±5Vdc indicates unit is operating

overall accuracy of the unit Excitation Current (RTD properly

is the combined input and and Ohm Inputs Only): ALARM 1 & ALARM 2 LED:

output (if any) accuracies. 250microamps, ±10% Dual color LED per relay

It includes the combined indicates alarm status

effects of linearity, Performance WITH ANALOG

hysteresis, repeatability, with Analog OUTPUT: Ambient Operating & Storage

and adjustment resolution. Output (-AO Output Accuracy: Conditions Range: -40°C to +85°C

It does not include ambient Option) Current, ±0.01% of max. (-40°F to +185°F)

temperature effect span (±2 microamps) Relay Range: -25°C to

Mimimum Span at Voltage, ±0.01% of max. +70°C (-13°F to +158°F)

Specified Accuracy: span (±1mV) Effect of Ambient

See Table 4 on Page 6 Response Time: Temperature on Cold

Cold Junction 256msec maximum Junction Compensation

Compensation Accuracy (128msec typical) for the (T/C Inputs Only):

(T/C Inputs Only): ±0.45°C output to change from 10 ±0.005°C per °C change of

Stability: See Table 2 to 90% of its scale for an ambient temperature

Response Time: input step change of 0 to Relative Humidity:

300msec (Defined as time 100% 0-95%, non-condensing

from step change on input Ripple: 50mVp-p Ambient Temperature

to alarm state change when maximum on voltage Effect: ±0.015% of

alarm is set to trip midpoint) output; 10mVp-p maximum span/°C

Alarm Deadband: measured across a RFI/EMI Immunity

Programmable from 250 ohm load resistor (Standard Unit):

0-100% for current output. 10V/M@20-1000MHz,

Alarm Trip Delay: (Frequencies up to 1KHz when tested

0-120 seconds 120Hz) according to

Line Voltage Effect: Output Limiting: IEC1000-4-3-1995 with

±0.002% of span per 1% Input over range, 0.5% of span or less error

change in line voltage -0.2V/0mA and RFI Immunity (with -RF

(ac or dc) 10.5V/21.4mA; Input Option):

Isolation: Standard unit, failure, -0.5V/0mA and 30V/M@20-1000MHz,

1000Vrms between case, 11V/24mA 1KHz AM when tested

input and output. 1500Vrms Output Current Limiting: according to

between power and input 25mA max. IEC1000-4-3-1995 with

and between power and Load Effect (current 0.5% of span or less error

output; Unit with -RF option, outputs): 0.01% of span Noise Rejection: Common

500Vrms between case, from 0 to maximum load mode,

input, output and power resistance on current 100dB@50/60Hz;

Power Consumption: output Normal Mode, See Table 3

3W typical, 4W max. Maximum Load

Power Supply Effect: Resistance: Current Weight 653 g (21 oz)

±0.002% of span per 1% of outputs, 1Kohms; Voltage

line change outputs, 2Kohms







Table 2. Long-Term Stability for TPRG (RTD, T/C, mV, ohm, Pot) Input Model. Table 3. Normal Mode Rejection Ratio Table.

Input-to-Relay Sensor Type Max. p-p Voltage Injection for

Stability Input-to-Analog 100dB at 50/60Hz

(% of maximum Output (Years) Output (Years) T/C: J, K, N, C, E 150mV

T/C: T, R, S, B 80mV

span) 1 3 5 1 3 5 Pt RTD: 100, 200, 300 ohms 250mV

Pt RTD: 400, 500, 1000 ohms 1V

RTD, Ohm, & Pot Inputs 0.066 0.114 0.147 0.47 0.081 0.104 Ni: 120 ohms 500mV

Cu: 9.03 ohms 100mV

Resistance mV

T/C & mV Inputs 0.047 0.082 0.106 0.008 0.014 0.019 1-4kohms 250-1000 1V

0.25-1kohms 62.5-250 250mV

0.125-0.25kohms 31.25-62.5 100mV









Specifications and information subject to change without notice. Page 5

CPA

PC-Programmable Current/Voltage

and RTD/Thermocouple Limit Alarm Trips



Table 4. Accuracy with RTD, Thermocouple, Ohms, and Millivolt Inputs (Models with TPRG Input).



Input Type α Ohms Conformance

Range

Minimum

Span

Input

Accuracy/Repeatability

Maximum

Range

RTD 100

(2-, 3-,

4-Wire) 200



300

-200 to 850°C -240 to 960°C

0.003850 -400 to 1760°F

-328 to 1562°F

400



500



1000

Platinum

10°C ±0.1°C

100

(18°F) (±0.18°F)

200

-100 to 650°C -150 to 720°C

0.003902 400

-148 to 1202°F -238 to 1328°F

500



1000

-200 to 510°C -240 to 580°C

0.003916 100

-328 to 950°F -400 to 1076°F

-80 to 320°C -100 to 360°C

Nickel 0.00672 120

-112 to 608°F -148 to 680°F

-50 to 250°C ±0.85°C -65 to 280°C

Copper 0.00427 9.035

-58 to 482°F (±1.53°F) -85 to 536°F

Direct Resistance 0-4000 0-4000ohms 10ohms ±0.4ohms 0-4000ohms

Ohms n/a

Potentiometer 4000 max. 0-100% 10% ±0.1% 0-100%



-180 to 760°C 35°C ±0.25°C -210 to 770°C

T/C J n/a n/a

-292 to 1400°F 63°F (±0.45°F) -346 to 1418°F



-150 to 1370°C 40°C ±0.3°C -270 to 1390°C

K n/a n/a

-238 to 2498°F 72°F (±0.54°F) -454 to 2534°F



-170 to 1000°C 35°C ±0.2°C -270 to 1013°C

E n/a n/a

-274 to 1832°F 63°F (±0.36°F) -454 to 1855.4°F



-170 to 400°C 35°C ±0.25°C -270 to 407°C

T n/a n/a

-274 to 752°F 63°F (±0.45°F) -454 to 764.6°F



0 to 1760°C 50°C ±0.55°C -50 to 1786°C

R n/a n/a

32 to 3200°F 90°F (±0.99°F) -58 to 3246.8°F



0 to 1760°C 50°C ±0.55°C -50 to 1786°C

S n/a n/a

32 to 3200°F 90°F (±0.99°F) -58 to 3246.8°F



400 to 1820°C 75°C ±0.75°C 200 to 1836°C

B n/a n/a

752 to 3308°F 135°F (±1.35°F) 392 to 3336.8°F



-130 to 1300°C 45°C ±0.4°C -270 to 1316°C

N n/a n/a

-202 to 2372°F 81°F (±0.72°F) -454 to 2400.8°F



0 to 2300°C 100°C ±0.8°C 0 to 2338°C

C n/a n/a

32 to 4172°F 180°F (±1.44°F) 32 to 4240.4°F



mV DC n/a n/a -50 to 1000mV 4mV 15 microvolts -50 to 1000mV







Page 6

PC-Programmable Current/Voltage

CPA

and RTD/Thermocouple Limit Alarm Trips



Ordering Information

Unit Input Output Power Options Housing



CPA HLPRG 1PRG Single Relay 24DC ±10% -AO Analog DIN Universal

PC-Programmable Programs to accept: (Relay is double-pole/ 117AC ±10% output (isolated DIN-style

Limit Alarm Trip double-throw (DPDT, 2 230AC ±10% and linearized) housing mounts

Current: Any range form C, rated 5A@250Vac, scaleable for on 32mm

between 0-50mA 50/60Hz, non-inductive) Current output (EN50035)

including: 2.4mA minimum G-type

0-20mA 2PRG Dual Relays or for Voltage and 35mm

4-20mA (Relays are output 1Vdc (EN50022) Top

10-50mA single-pole/double-throw minimum (see Hat DIN-rails

(SPDT, 1 form C, rated “Specifications”

Voltage: Any range 5A@250Vac, 50/60Hz, for additional

between 0-10Vdc non-inductive) information)

including: NOTE: Output

0-5Vdc Each relay individually can be user-set

1-5Vdc configures for: for internal or

0-10Vdc High or Low Trip external power

Normally Open or (source or sink)

TPRG Programs to Normally Closed -RF Enhanced

accept (see Table 3 on Failsafe or Non-Failsafe RFI/EMI

Page 6 for details): protection (see

“Specifications”

RTD: 2-, 3-, and for details)

4-wire; platinum, copper,

and nickel



Thermocouple:

J, K, E, T, R, S, N, C, B



Ohms:

0-4000ohms

(Potentiometer,

4000 ohms maximum)



Millivolts:

–50 to +1000mV



When ordering, specify: Unit / Input / Output / Power / Options [Housing]

Model number example: CPA / TPRG / 2PRG / 117AC / - AO -RF [DIN]









Accessories

Part Number Moore Industries’ Interface Solution Configuration

750-75E05-01 and Installation CD (One copy of CD provided free

with each order)



Part Number Configuration Communications Cable for use

803-053-26 in connecting the instrument to the PC (one cable

provided free with each order)



Part Number USB Communications Cable for use in connecting

208-836-00 the instrument to the PC (optional cable)







All product names are the trademarks of their respective companies.









Page 7

CPA

PC-Programmable Current/Voltage

and RTD/Thermocouple Limit Alarm Trips



Figure 7. Installation Dimensions.

126mm

50mm (4.97 in)

(1.97 in) 100mm

(3.96 in)

NOTE: While all CPA models (model with

HLPRG input shown) are dimensionally

identical, the CPA that accepts temperature

CPA inputs (TPRG input) features metal

COMPUTER

PROGRAMMABLE



terminal blocks for enhanced cold junction

ALARM





INPUT

compensation.

READY

100mm

ALARM 1

(3.94 in)

ALARM 2









COM









Table 5. Terminal Designations.



Top Terminals (Left to Right)

Input Type

T1 T2 T3 T4 T5 T6 T7 T8 T9

Not Not +IO –IO Source –VO

Current Input (HLPRG) Tx +I COM

Used Present Source +IO Sink

+VO

–IO Sink



Not Not +IO –IO Source –VO

Voltage Input (HLPRG) Tx

Used

COM +V

Present Source +IO Sink

+VO

–IO Sink

Not +IO –IO Source –VO

RTD, Ohm & Pot Input (TPRG) See Figure 8

Present Source +IO Sink +VO

–IO Sink

Not +IO –IO Source –VO

T/C & mV Input + – Present Source +IO Sink +VO –IO Sink





Bottom Terminals (Left to Right)

Output Type/Power

B1 B2 B3 B4 B5 B6 B7 B8 B9



Single Alarm (DPDT Relay) NO1 CM1 NC1 NO2 CM2 NC2 AC/DC ACC/DCC GND



Relay 1 Relay 1 Relay 1 Relay 2 Relay 2 Relay 2

Dual Alarms (SPDT Relays) NO1 CM1 NC1 NO2 CM2 NC2

AC/DC ACC/DCC GND





NOTES:

1. Terminal blocks can accomodate 14-22 AWG KEY:

solid wiring. AC/DC = Power Input IO = Current Output Source = Current Source

2. ±IO/±VO labeling is present only when the unit ACC/DCC = Power Input NO = Normally Open SPDT = Single-Pole/Double-Throw

is equipped with the Analog Output (-AO) option. CM = Relay Common NC = Normally Closed VO = Voltage Output

COM = Analog Common Sink = Current Sink

DPDT = Double-Pole/Double-Throw

GND = Ground





Figure 8. Temperature Sensor Hook-Up Guide (Models with TPRG Input).



Thermocouple 2-Wire RTD 3-Wire RTD 4-Wire RTD Potentiometer

and Millivolt or Decade or Decade or Decade Input

Input Resistance Box Resistance Box Resistance Box





+ –



1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4





United States • info@miinet.com Belgium • info@mooreind.be China • sales@mooreind.sh.cn

Tel: (818) 894-7111 • FAX: (818) 891-2816 Tel: 03/448.10.18 • FAX: 03/440.17.97 Tel: 86-21-62491499 • FAX: 86-21-62490635

Australia • sales@mooreind.com.au The Netherlands • sales@mooreind.nl United Kingdom • sales@mooreind.com

Tel: (02) 8536-7200 • FAX: (02) 9525-7296 Tel: (0)344-617971 • FAX: (0)344-615920 Tel: 01293 514488 • FAX: 01293 536852



Page 8



Related docs
Other docs by xiaoyounan
AUSRANK2011W
Views: 0  |  Downloads: 0
G117464796
Views: 0  |  Downloads: 0
absolutist_vs_constitutionalist
Views: 0  |  Downloads: 0
Seminar_10_12_2011
Views: 0  |  Downloads: 0
Excel-Tool Potentialanalyse VDA-6.3-2010_en
Views: 1  |  Downloads: 0
07sanin-ballot-hirei
Views: 0  |  Downloads: 0
DOGs
Views: 0  |  Downloads: 0
smith-waterman_NDSS
Views: 0  |  Downloads: 0
t31c015
Views: 0  |  Downloads: 0
2011-02-13_sermon
Views: 0  |  Downloads: 0
By registering with docstoc.com you agree to our
privacy policy

You are almost ready to download!

You are almost ready to download!