					Rebate Application: Prescriptive Measures
Retrofit, New Construction and Major Renovation Projects



Application Instructions
1. Submit a Pre-Notification Application to reserve funding (required for Retrofit de-lamping and financing).
2. Install the qualified technology.
3. Complete, sign, submit Final Application within 6 months of project completion.
                         Use the Check list to ensure your application is complete.
                         Items to include:    Applicant Information
                                              Signed Agreement Form
                                              Equipment Worksheets
                                              Supporting Documentation (invoices, specification sheets, etc.)

4. The incentive check will be sent 4 to 6 weeks after approval of the Final Application.



APS Solutions for Business 2001 North 3rd Street, Suite 106, Phoenix, AZ 85004

Tel: 1-866-277-5605 Fax: 1-866-277-5604 Email: APS.solutionsforbusiness@kema.com

All official program updates will be posted on the APS website: aps.com/businessrebates.




Limited Time Offer
To qualify for the "special" rebate offers, you must submit your final application with all required documentation by
November 30, 2010.




                                                                                                  www.aps.com/businessrebates

                                              The Solutions for Business program is funded by APS customers and approved by
                                                                                         the Arizona Corporation Commission.




                                                                                                                Prescriptive Appl: June 1-Nov 30, 2010
                                           Limited Time Offer
The APS Solutions for Business program is temporarily raising the rebate amount for three
retrofit prescriptive measures! This offer is open to any APS non-residential customer that meets
the program’s standard eligibility requirements. To qualify for the increased rebate, you must
submit your final application by November 30, 2010.

These special, limited time offer rebates are available for:

       Variable Speed Drives: Rebate increases from $50 to $60 per horsepower
       HID Conversion: Rebate increases by $25 per fixture
       Specialty CFLs (PAR and R series downlight, dimmable, 3-way, locking base): Rebate
        increases from $1.75 to $5.00 per lamp

                    Look for this symbol on the lighting and motors worksheets to identify the special
                    offers. Be sure to submit your final application with all required documentation
                    by November 30, 2010, so you don’t miss out on this unique opportunity.




                                    Special Insert -- Good Through November 30, 2010




   Visit aps.com/businessrebates for program information                           Prescriptive Appl: June 1-Nov 30, 2010
                                                                               Prescriptive Measures                                                                                 APS Application #

                                                                                           Customer Information

     Click Below and Select Application Type                                                          Submission Date:                                                             Submission Date:

                                                                       Pre-Notification                                                                Final Application


Name of Project


Name of Organization
                                                                                                                                                                                  Business Type
                                                                                                    Tax Status                                                                   (Click and select below)
Taxpayer ID Number                                                                        (Click to the right and select status)
                                                                                            Corporation, Tax-Exempt, Other

Name as it appears on
your APS bill
                                                                                                                                                                                  K-12 School
APS Account Number                                                                                                                   Telephone #
                                                                                                                                                                              College / University
                                                                                                                                                                                     Office
Name of Contact Person
                                                                                                                                                                                     Retail
at Organization
                                                                                                                                                                                  Restaurant
                                                                                                                                                                                 Hotel / Motel
Title                                                                                                                                   Fax #
                                                                                                                                                                                    Medical
                                                                                                                                                                                    Grocery
Email Address                                                                                                                                                                     Warehouse
                                                                                                                                                                              Process Industrial
Address where                                                                                                                        Est. Square                               Other Industrial
Measures Installed                                                                                                                    Footage                                   Miscellaneous

City, State, Zip                                                                                                                                                                   I would like to be
(Measures Installed)                                                                                                                                                                 considered for
                                                                                                                                                                             financing under the
Mailing Address                                                                                                                                                            National Bank of Arizona
                                                                                                                                                                               financing option
City, State, Zip                                                                                                                                                           (customer signature required below)
(Mailing Address)

                                                                             Contractor Information
                                                                                                                                                                                   Building Age
                                                                                                                                                                              (Click and select below)
Company Name

                                                                                                                                      Contractor
Contact Person
                                                                                                                                       Phone #
Mailing Address
City, State, Zip
                                                                                                                                                                                    Pre-1970
                                                                                                                                      Contractor                                   1970 - 1989
Email Address
                                                                                                                                        Fax #                                      1990 - 2000
                                                                                                                                                                                  2001 - present
                                                                           Incentive Check Information

                                                                                                                                   I request that the incentive check be
Issue Incentive Check to:
                                                              Send to Customer listed above.                                       issued to the third party indicated
(check only one)
                                                                                                                                   below.

Customer Signature
(Required for third party payment and
 when participating in financing option)


Name of Third Party
(Organization receiving check)

Name of Contact Person
                                                                                                                                     Telephone #
at Third Party                                                                                                                                                                      HVAC Type
                                                                                                                                                                              (Click and select below)
Title                                                                                                                                   Fax #

Third Party
Mailing Address
                                                                                                                                                                                      Chiller
City, State, Zip
                                                                                                                                                                                 Package Units
                                                                                                                                                                                  Combination
Email Address                                                                                                                                                                    District Cooling
Third Party Taxpayer                                                                                Tax Status
                                                                                          (Click to the right and select status)
ID Number                                                                                   Corporation, Tax-Exempt, Other

                                                                                                              2




                   Visit aps.com/businessrebates for program information                                                                                                                                         Prescriptive Appl: June 1-Nov 30, 2010
                              Key Terms and Conditions
Arizona Public Service Company (APS) is offering incentives under the Solutions for Business program to facilitate
implementation of cost-effective, energy-efficiency improvements. The program is funded by APS customers and is
approved by the Arizona Corporation Commission. KEMA implements this program for APS.

The complete set of terms and conditions are provided in program’s Policies and Procedures. Projects are subject to the
Policies and Procedures posted on aps.com on the date of application signature. Selective terms and conditions include:

   Eligibility: Incentives are available to non-residential customers within APS’ service territory; most non-residential
    rate schedules are eligible. The ineligible rate schedules are Solar 1 and 2, E-36, and some Special Contracts. The
    energy savings from installed measures must occur on a meter with an eligible rate schedule. The measures included
    in this program are not designed to promote fuel-switching.

   Incentive Caps: The total incentive paid cannot exceed 75% of the incremental measure cost for prescriptive and
    50% for custom projects and technical studies. Contractor labor costs can be considered in measure costs; however,
    customer labor costs can not. Pursuant to Arizona Corporation Commission Decisions when calculating incremental
    measure cost, APS is required to reduce the incremental measure costs by any known monetary incentives available
    from other entities (such as tax credits), regardless if a customer applies for these incentives. Customer certifies that
    the sum of American Recovery and Reinvestment Act (ARRA) dollars, other grant dollars, and APS Solutions for
    Business rebates shall not exceed 100% of the incremental project cost.

   Customer Caps: Customers with aggregated demand of 100 kW or less can receive up to $150,000 per customer per
    program year; customers above 100 kW aggregated monthly demand can receive up to $300,000 per customer per
    program year. All incentives paid through the APS Solutions for Business Program will be applied towards the
    customer incentive cap.

   Pre-Notification: Program funding is limited. All participants are strongly encouraged to submit a Pre-Notification
    Application to reserve funds for 120 days. Pre-Notification applications are required for whole building design and
    de-lamping projects.

   Final Application: The Final Application must be submitted within six months of project completion. The project
    completion date is defined as the date the energy-efficient equipment becomes operational. Required documentation
    includes copies of all itemized, paid invoices and receipts detailing the specific equipment and purchases, the services
    provided, and other costs. Any applications submitted more than six months following completion will be deemed
    ineligible for payment.

   Inspections: The Solutions for Business program team reserves the right to inspect all projects to verify compliance
    with the program rules and verify the accuracy of project documentation. This may include pre-installation (required
    for de-lamping) and/or post-installation inspections, detailed lighting layout descriptions, metering, data collection,
    interviews, and utility bill data analyses. The customer must allow access to records and installation sites for three
    years after receipt of incentive payment.

APS makes no representations and provides no warranty or guarantee with respect to design, manufacture, construction,
safety performance or effectiveness of newly installed equipment and the installing contractor, including any warranties of
merchantability or fitness, and including contractors listed on the program’s Trade Ally list. Customers are responsible for
disposing of any equipment and materials according to local code requirements.




                                                                     3




      Visit aps.com/businessrebates for program information                                                                     Prescriptive Appl: June 1-Nov 30, 2010
                                                         AGREEMENT
By signing this agreement I attest that I understand and agree to abide by all program terms and conditions including, but not limited
to, the following:
 I am an eligible APS customer, building owner, or owners' authorized representative.
 I contracted for or purchased and installed the indicated energy efficiency measures for use in my business facility and not for
     resale. I have attached documentation establishing proof of payment for the items installed according to this application.
 I agree to verification by Arizona Public Service Company (APS or “the utility”) or its representatives of both sales transactions
     and equipment installation.
 I understand that the Final Application and all required documentation must be received by KEMA within six months of project
     completion or it will be deemed ineligible for payment. All equipment must be purchased new and installed prior to submitting
     the Final Application.
 I understand that the program may be modified or terminated without prior notice and that the program has a limited budget.
     Applications will be processed on a first-come, first-served basis until allocated funds are spent. Final applications should be
     submitted by November 30, to be paid in the same calendar year.
 I recognize that this project must involve a capital improvement that results in improved energy efficiency. I also understand that
     all materials removed, including lamps and PCB ballasts, must be disposed of properly. Any and all environmental credits
     generated by the project described in this application will be retained by APS.
 As incentive payments assume related energy benefits over a five-year period or for the product’s lifetime, I agree that if: (1) I do
     not install the energy efficiency-related product(s) identified in my application, or (2) I remove the energy efficiency-related
     product(s) identified in my application before the end of the product’s life or within five years from receipt of the incentive,
     whichever is less; then I shall reimburse a prorated amount of incentive funds to APS based on the actual period of time in which
     the product(s) were installed and operating (or the full amount if the product was never installed).
 I understand that my company may be recognized as a program participant in promotional materials; however, project details will
     not be released without prior consent. If I choose to opt-out of any recognition, I will indicate my choice in a written letter to the
     APS Solutions for Business program.
 I understand that pursuant to Arizona Corporation Commission Decisions, when calculating the maximum rebate amount, APS is
     to consider other energy efficiency rebates and incentives, including tax incentives when calculating incremental measure cost.
     The customer energy efficiency incentive must be no more than the defined measure caps as compared to the incremental cost:
     75% for prescriptive measures and 50% for custom measures and studies. The utility will make the final determination of
     incentive levels for this project.
 I am an APS customer in good standing and I meet all eligibility criteria to be paid under this program.
 I certify that the information on this application is true and correct.



   Please indicate below if your organization intends to file for tax                      Please indicate below if your organization will recieve grants (e.g.
   incentives related to the measures in this application.                                 ARRA, state funds) related to the measures in this application.




                                                                Enter Completion Date in
                                                                       Worksheet                                         Issuing check to third party?
               Customer Signature                                   Project Completion Date                              Customer must initial here.
                                                            Enter Cost then Incentive will Calculate


                      Print Name                                           Total Project Cost

                                                                                $0.00
                        Date                                            Total Incentive Requested
   Application Type

   Select Type on                             Please print out, sign, and return with Pre -Notification Application.
   Applicant Info                       For Final Applications, sign and submit after all equipment has been installed.


                                                                                 4




                        Visit aps.com/businessrebates for program information                                                                                     Prescriptive Appl: June 1-Nov 30, 2010
                                Submitting An Application
Please review the project and measure requirements listed in the application and the Policies & Procedures document to
verify that your project is eligible. Use the checklist to ensure your application is complete. Then:

1. Submit the Pre-Notification Application. Check the "Pre-Notification" box at the top of the application. Retrofit
projects with de-lamping require Pre-Notification and pre-inspection.

The Solutions for Business program team will review applications in the order received. Funds will be reserved when the
team receives a complete application and determines that the project meets the eligibility requirements described in the
program’s Policies & Procedures. The Solutions for Business program team will send the applicant a letter acknowledging
the funds reserved for eligible projects with the reservation expiration date.
     The program team retains the right to contact the customer after 30 days to ensure that the project is moving
        forward and may cancel the commitment based on the customer's response.
     Funds that have been reserved are not transferable to other projects, facilities or customers.

2. Install equipment according to the terms and conditions described for the eligible measures. Ensure the measures
meet all requirements detailed on the corresponding specification sheet and the current Policies & Procedures. If you have
questions about eligibility requirements, please contact program staff before installation.

3. Submit the Final Application with all required documentation within six months of project completion. Project
documentation includes copies of all itemized, paid invoices and receipts, which detail the specific equipment and
purchases, the services provided and other costs. An updated copy of the Pre-Notification Application can be submitted
with “Final Application” selected at the top. Applications submitted after six months will be ineligible for payment.

Use the checklist provided to ensure your application is complete. Please note the following:
    The location or business name on the invoice must be consistent with the application information.
    The project invoice must provide sufficient detail to separate the cost of the prescriptive measures from the cost
        for other services such as repairs and building code compliance.
    If the contractor will receive the incentive payment directly, the submitted invoices must include the full cost of
        the measures and not simply show the portion of the project cost that the APS customer will pay.

APS reserves the right to request additional supporting documentation to ensure measure eligibility and verify that the
expected energy savings will occur. This information could include: equipment purchase dates, installation dates, proof
that the equipment is operational, manufacturer specifications, warranty information, and proof of customer co-payment.
All project-specific customer information will be held in confidence.

4. The Solutions for Business program team will review the final project documentation for eligibility and
completeness. Incentives will be processed within 4 to 6 weeks after the Final Application is approved.

Applicants who submit incomplete applications will be notified of deficiencies and will lose their position in the review
process until all requested information is received. Incentives cannot be processed for payment until the complete
application and all required documentation is received and approved. Final, complete applications must be submitted by
November 30, to be paid in the same calendar year.

Contact Information
APS Solutions for Business
2001 North 3rd Street
Suite 106
Phoenix, AZ 85004

Tel: 1-866-277-5605
Fax: 1-866-277-5604
Email: APS.solutionsforbusiness@kema.com




                                                             5




 Visit aps.com/businessrebates for program information                                                                       Prescriptive Appl: June 1-Nov 30, 2010
                                            Customer Checklist
 Verify: Application is being submitted within 6 months of project completion and includes
  the following components.

 APPLICANT INFORMATION FORM
Customer Information
 Customer name matches the name that appears on the                    APS account number is complete and accurate.
   APS bill.                                                             Note: New Construction account information may not
 Taxpayer ID is complete and accurate.                                  be available for pre-application, but is required for
 (For Schools) School Supplement Form is complete.                      the final application.
Contractor Information
 Contractor contact information is provided. (We may need to contact your contractor to verify project details.)
Incentive Check Information
If a third party will receive the incentive check:
      Third party contact information and Taxpayer ID                       Third party has read and agrees to the program
         is complete.                                                         terms and conditions.
      Customer has signed box indicating third party                        For final application, third party has signed
         payment.                                                             Agreement form and customer has signed and
                                                                              initialed Agreement form.
 PRESCRIPTIVE INCENTIVE WORKSHEET(S)
 Incentive worksheet has been completed for each applicable measure.
 The measures installed meet the specifications listed in the application (e.g. “Specifications for Lighting Measures”).

 AGREEMENT FORM
 Customer has read and agrees with the terms and conditions of the Solutions for Business program.
 The customer has signed, dated, and filled in all sections of the Agreement, including:
     o Project completion date
     o Total project cost
     o Total incentive requested

 SUPPORTING DOCUMENTATION
Specification Sheets                                                   Invoices
 A manufacturer’s specification sheet is provided for                  The installation address is listed on the invoice and is
   each measure installed.                                                in APS service territory.
 Specification sheets include all eligibility                          Invoice shows correct model number for each measure
   requirements for the measure (e.g., CRI of lamps,                      installed.
   Ballast factors, IPLV for AC Units, etc.).                           Invoice indicates that it has been paid by the customer
   Note: ARI offers a helpful website for cooling                         (e.g., show zero balance due, stamped paid, or check
   specifications: www.ahridirectory.org                                  number and paid date are included).
 The model numbers of all installed components match
   those listed on the invoices.

Third Party Authorization Letter: If a third party will be applying on behalf of the customer, the APS Solutions for Business
program requires the customer to sign the Third Party Authorization Letter agreeing to the terms and conditions of the program and
allowing the third party to sign the application on their behalf. Please contact us for more information on this process.


                                                                        6




               Visit aps.com/businessrebates for program information                                                                 Prescriptive Appl: June 1-Nov 30, 2010
                             Retrofit Lighting Incentive Worksheet 1
                                                                 Incentive                             Number of               Incentive
                          Equipment Type                                            Replacing
                                                                   /Unit                                 Units                  Subtotal

           T8/T5 and electronic ballast (1) (indicate lamp type with X)                                   Lamps
           2-foot                   T8                   T5         $5.00           T12 Lamps
           3-foot                   T8                   T5         $5.00           T12 Lamps
           4-foot                   T8                   T5         $5.00           T12 Lamps
           8-foot                   T8                              $5.00           T12 Lamps
                                                                  (1)                                     Lamps
           Premium T8 and electronic ballast
           2-foot premium T8                                        $8.00           T12 Lamps
           3-foot premium T8                                        $8.00           T12 Lamps
           4-foot premium T8                                        $8.00           T12 Lamps
           8-foot premium T8                                        $8.00           T12 Lamps

           De-lamping                                                                                    Lamps
           Pre-Notification application and pre-inspection are required                                 Removed
           Remove 2-foot lamp                        $5.00         NA
           Remove 3-foot lamp                        $5.00         NA
           Remove 4-foot lamp                       $10.00         NA
           Remove 8-foot lamp                       $10.00         NA
                                                                          (1)                              Signs
           Exit Signs (LED or Electroluminescent)
           Double or Single Face                                   $25.00        Incandescent
           Double or Single Face                                   $25.00            CFL

                                                                                 Connected
           Sensors and Daylighting Controls                                                # of Sensors
                                                                                   Watts
           Occupancy Sensors (2)                                    $0.12
           Daylighting Controls (2)                                 $0.30
          (1)
                Manufacturer's specification sheets for the lamps and ballast must accompany the final application.
          (2)
                Manufacturer's specification sheets and supporting room by room calculations must accompany the final application.

           Compact Fluorescent / Cold Cathode Lamps
                                       CFL (Screw In)               CFL (Hardwired Fixture)           Cold Cathode
                                  $1.75       $5                        $15             $20                 $3.50
                                               Downlight                                                                       Incentive
                         Lamp    Standard      Dimmable
                                                                                                             All                Subtotal
                          Size                   3-way
                                              GU24 Locking         <32 watt                                 Sizes
           (Installed Watts)
                                                 Base               fixture       ≥32 watt fixture
                Item #             Qty          Quantity           Quantity          Quantity             Quantity
                 1
                 2
                 3
                 4
                 5
                 6
                 7
                 8
                 9
                 10
                    Project Completion Date
                                                                                                     Lighting Total              $0.00
Incentives cannot exceed 75% of incremental measure cost.


                                                                                7




                  Visit aps.com/businessrebates for program information                                                                    Prescriptive Appl: June 1-Nov 30, 2010
     Specifications for Retrofit Lighting Measures 1
Linear Fluorescent T8 or T5 Lamps with Electronic Ballasts
Measure: Replace T12 lamps and magnetic ballasts with T5 or T8 lamps and electronic ballasts.
 T8/T5 lamps must have a color rendering index (CRI) ≥ 80.
 Electronic ballast must be high frequency (≥ 20 kHz), UL listed, and warranted against defects for 5 years.
 Electronic ballasts must have a power factor (PF) ≥ 0.90.
    Ballasts for 4-foot lamps must have total harmonic distortion (THD) ≤ 20% at full light output.
    For 2- and 3-foot lamps, ballasts must have THD ≤ 32% at full light output.
 Replacement of T12 fixtures with T5HO fixtures should be applied for on the Custom Application.

Premium T8 Lamps and Ballasts
Measure: Replace T12 lamps and magnetic ballasts with premium T8 lamps and electronic ballasts.
 Apply all of the requirements described above for standard T8 lamps and electronic ballast measure.
 Additional requirements: CRI ≥ 81 and either a ballast factor ≤ 0.78 or a mean lumens per Watt of ≥ 90.
 Eight foot lamp requirements: CRI ≥ 81 and lamp wattage of < 57 Watts and mean lumens per Watt of ≥ 90.
A manufacturer's specification sheet must accompany the application.

De-lamping
Measure: Permanent removal of existing fluorescent lamps.
 Customers must determine whether to use reflectors when de-lamping to maintain adequate lighting levels.
 Unused lamps, lamp holders, and ballasts must be permanently removed from the fixture to claim the de-lamping
   credit.
 Applicable when retrofitting T12 to T8 or simply de-lamping a T8 fixture; not available for de-lamping a T12 fixture.
A Pre-Notification Application and pre-inspection are required for de-lamping projects.

Exit Signs
Measure: Replace incandescent or CFL exit sign with an electroluminescent or light-emitting diode (LED) exit sign.
 Exit signs must be UL or ETL listed, have a minimum lifetime of 10 years, and have an input Wattage ≤ 5 Watts.
 Non-electrified and remote exit signs are not eligible.

Occupancy Sensors (Wall Box and Ceiling Mount)
Measure: Install occupancy-based controls on lighting.
 Only passive infrared and/or ultrasonic detectors are eligible.
 Wall box and wall-, ceiling-, or fixture- mounted sensors must be hardwired to control interior lighting fixtures.
A room-by-room count or the calculation used to determine connected Watts must accompany application.

Daylighting Controls
Measure: Install a photo sensor that controls dimming ballasts.
 Dimming can be continuous or stepped at three or more levels (including on/off).
 Systems that allow on/off overrides are not eligible.
 This measure is not eligible for incentives in conjunction with the daylighting incentive from APS’ Solar Program.
A manufacturer's specification sheet must accompany the application.
                                                                                                                 Limited Time
Compact Fluorescent Lamps                                                                                             Offer!
Measure: Replace incandescent lamp with screw-in, or hardwired compact fluorescent lamp (CFL).                   $5.00 per lamp
                                                                                                                   for specialty
 The lamp/ballast combination must have an efficacy ≥ 40 lumens per Watt (LPW).
                                                                                                                      CFLs:
 Screw-in CFLs must be ENERGY STAR® rated and lamps ≥ 18 Watt require electronic ballasts.                         downlight,
 GU24 locking base CFLs must be ENERGY STAR® rated.                                                                dimmable,
 For hardwired CFLs, only complete new fixtures or modular retrofits with hardwired electronic ballasts qualify. 3-way and
 The CFL ballast must be programmed start or programmed rapid start with a PF ≥ 90 and THD ≤ 20%.                locking base.
 Lamps receiving a retail buy-down by APS are not eligible.                                                        Available
                                                                                                                     through
Cold Cathode                                                                                                        11/30/10.
Measure: Replace incandescent lamp with Cold Cathode Fluorescent Lamp (CCFL). CCFL lamps must be rated for at
least 18,000 hours average life.
Note: Replaced PCB ballasts and lamps must be disposed of properly. Documentation of disposal may be requested
by the program staff.
                                                                 8




       Visit aps.com/businessrebates for program information                                                              Prescriptive Appl: June 1-Nov 30, 2010
                                            Retrofit Lighting Incentive Worksheet 2
                                                         Incentive                                                                     Number of      Incentive
                   Equipment Type                                                               Replacing
                                                           /Unit                                                                         Units         Subtotal

      High/Low Bay Lighting

            HID Lamp Wattage
                                                        Incentive per
                                                                           Retrofit Fixture Type
                                                                                                          Number of Lamps per          Quantity of      Total
                                         HID Type
                                                          Fixture (1)                                          Fixture                 HID Fixtures   Incentive
             150             400                 MH                          T5HO        2xT5HO               2 Lamp       4 Lamp
             175             750
                                                 HPS                         T8/T8HO     2XT8/T8HO            3 Lamp       6 Lamp
             250             1000
             150             400                 MH                          T5HO        2xT5HO               2 Lamp       4 Lamp
             175             750                                                                              3 Lamp
                                                 HPS                         T8/T8HO     2XT8/T8HO                         6 Lamp
             250             1000
             150             400                 MH                          T5HO        2xT5HO               2 Lamp       4 Lamp
             175             750                                                                              3 Lamp       6 Lamp
                                                 HPS                         T8/T8HO     2XT8/T8HO
             250             1000
             150             400                 MH                          T5HO        2xT5HO               2 Lamp       4 Lamp
             175             750                                                                              3 Lamp       6 Lamp
                                                 HPS                         T8/T8HO     2XT8/T8HO
             250             1000
             150             400                 MH                          T5HO                             2 Lamp       4 Lamp
                                                                                         2xT5HO
             175             750
                                                 HPS                         T8/T8HO     2XT8/T8HO            3 Lamp       6 Lamp
             250             1000
             150             400                 MH                          T5HO        2xT5HO               2 Lamp       4 Lamp
             175             750
                                                 HPS                         T8/T8HO     2XT8/T8HO            3 Lamp       6 Lamp
             250             1000
             150             400                 MH                          T5HO        2xT5HO               2 Lamp        4 Lamp
             175             750
                                                 HPS                         T8/T8HO     2XT8/T8HO            3 Lamp        6 Lamp
             250             1000


      Induction Lighting
                                           (2)                                                          (1)
                Existing MH / HPS                         Incentive                 Induction Fixture                  % Reduction                      Total
                                           Lamp          per Fixture                                       Lamp        (Minimum 30%)
             HID Lamp Range
                                          Wattage
                                                                           Induction Lamp Range
                                                                                                          Wattage
                                                                                                                                         Quantity     Incentive
            MH ≥70W ≤200W
                                                                                    ≤100W
        HPS ≥100W ≤200W
            MH ≥70W ≤200W
                                                                                    ≤100W
        HPS ≥100W ≤200W
            MH ≥70W ≤200W
                                                                                    ≤100W
        HPS ≥100W ≤200W

            MH >200W ≤250W
                                                                                    ≤165W
        HPS >200W ≤400W
            MH >200W ≤250W
                                                                                    ≤165W
        HPS >200W ≤400W
            MH >200W ≤250W
                                                                                    ≤165W
        HPS >200W ≤400W
      (1)
            See Lighting Spec 2 for details.
      (2)
            MH=Metal Halide; HPS=High Pressure Sodium, see Lighting Spec 2 for details.
                      Project Completion Date
                                                                                                                             Lighting Total 2          $0.00
Incentives cannot exceed 75% of incremental measure cost.


                                                                                            9




                   Visit aps.com/businessrebates for program information                                                                                          Prescriptive Appl: June 1-Nov 30, 2010
     Specifications for Retrofit Lighting Measures 2
High/Low Bay Lighting                                                                 Limited Time
Measure: Replace Metal Halide (MH)/High Pressure Sodium (HPS) fixtures                      Offer!
with new fixtures containing at least two lamps and electronic ballast.                Additional $25
 All fixtures must have a reflector with a minimum of 90% reflectivity.               per fixture for
     Replace 150 Watt lamp HID fixtures with 2-lamp four-foot T5HO / T8               HID conversion
        linear fixtures or 4-lamp two-foot T5HO or T8 linear fixtures. Incentive       available
        is $75 per HID fixture replaced.                                               through
                                                                                       11/30/10.
     Replace 175 Watt lamp HID fixtures with 2-lamp four-foot linear fixtures
        or 4-lamp two-foot linear fixtures. Incentive is $75 per HID fixture replaced.
     Replace 250 Watt lamp HID fixtures with 3-lamp four-foot T5HO or 3-lamp
        or 4-lamp T8 linear fixtures. Incentive is $100 per HID fixture replaced.
     Replace 400 Watt lamp HID fixtures with 6-lamp T5HO linear fixtures. Incentive is $100
        per HID fixture replaced.
     Replace 400 Watt lamp HID fixtures with 4-lamp T5HO or 6-lamp T8 linear fixtures.
        Incentive is $125 per HID fixture replaced.
     Replace 750 Watt lamp HID fixtures with 6-lamp or two 4-lamp T5HO or two 6-lamp
        T8 linear fixtures. Incentive is $150 per HID fixture replaced.
     Replace 1,000 Watts lamp HID fixtures with two 4-lamp T5HO or two 6-lamp T8 linear
        fixtures. Incentive is $200 per HID fixture replaced.
 This incentive does not apply to replacing Low Pressure Sodium (LPS) and Mercury Vapor
    (MV) fixtures or lamps. When replacing these fixtures please use the Custom application.
 The number of fixtures indicated on the worksheet shall be the minimum of the number of
    existing HID fixtures or the number of installed fixtures.
 Lamps must have a color rendering index CRI ≥ 80.
 Ballasts must be high frequency (≥ 20 kHz), UL listed, and warranted against defects for 5
    years.
 Ballasts must have a power factor (PF) ≥ 0.90.
 Ballasts for 4-foot lamps must have total harmonic discharge (THD) ≤ 20% at full light
    output.

New Induction Lighting Fixtures
Measure: Replace Metal Halide (MH) / High Pressure Sodium (HPS) fixtures with new induction
lighting fixtures.
 All Induction lamps must have a CRI of 80 or greater.
 All Induction lamps must have an expected life of 60,000 hours or greater.
 All Induction retrofits must save at least 30% from the MH/HPS lamp Wattage.
     Replace MH fixtures with lamps of 70 Watts through 200 Watts with Induction fixtures
         using lamps of 40 Watts through 100 Watts. Incentive is $75 per fixture replaced.
     Replace HPS fixtures with lamps of 100 Watts through 200 Watts with Induction fixtures
         using lamps of 40 Watts through 100 Watts. Incentive is $75 per fixture replaced.
     Replace MH fixtures greater than 200 Watts through 250 Watts with Induction fixtures
         using lamps of 100 Watts through 165 Watts. Incentive is $150 per fixture replaced.
     Replace HPS fixtures greater than 200 Watts through 400 Watts with Induction fixtures
         using lamps of 100 Watts through 165 Watts. Incentive is $150 per fixture replaced.

Note: Replaced PCB ballasts and HID lamps must be disposed of properly. Program staff may
request documentation of disposal.

                                                             10




     Visit aps.com/businessrebates for program information                                               Prescriptive Appl: June 1-Nov 30, 2010
                    New Construction Lighting Incentive Worksheet
                                                Lighting Power
                                                                         Actual LPD      Building Area                      Incentive Subtotal
                Building Type                      Density(1)                                               Watts Reduced
                                                                           (W/ft2)             ft2                            ($0.35/Watt)(2)
                                                    (W/ft2)

 Automotive                                             0.9
 Convention Center                                      1.2
 Court House                                            1.2
 Dining: Bar Lounge/Leisure                             1.3
 Dining: Cafeteria/Fast Food                            1.4
 Dining: Family                                         1.6
 Dormitory                                              1.0
 Exercise Center                                        1.0
 Gymnasium                                              1.1
 Health Care                                            1.0
 Hospital                                               1.2
 Hotel                                                  1.0
 Library                                                1.3
 Manufacturing Facility                                 1.3
 Motel                                                  1.0
 Motion Picture Theatre                                 1.2
 Multi-Family                                           0.7
 Museum                                                 1.1
 Office                                                 1.0
 Parking Garage                                         0.3
 Penitentiary                                           1.0
 Performing Arts Theater                                1.6
 Police/Fire Station                                    1.0
 Post Office                                            1.1
 Religious Building                                     1.3
 Retail                                                 1.5
 School/University                                      1.2
 Sports Arena                                           1.1
 Town Hall                                              1.1
 Transportation                                         1.0
 Warehouse                                              0.8
 Workshop                                               1.4
                                                 Unit Incentive          Connected
 Sensors & Daylighting Controls                                                         # of Sensors                            Incentive
                                                     $/Watt                Watts
                               (3)                    $0.12
 Occupancy Sensors
 Daylighting Controls(3)                              $0.30
  (1)
        Lighting Power Density (LPD) maximum values are based on ASHRAE 90.1-2004.
  (2)
        Incentive = (LPD baseline - LPD actual) x Area x $0.35.
  (3)
        Manufacturer's specification sheets and supporting calculations must accompany the final application.
                  Project Completion Date
                                                                                                          Lighting Total         $0.00
Incentives cannot exceed 75% of incremental measure cost.


                                                                              11




                      Visit aps.com/businessrebates for program information                                                                      Prescriptive Appl: June 1-Nov 30, 2010
    Specifications for New Construction Lighting Measures
Lighting Power Density
Measure: Install energy efficient lighting with LPD in Watts per square foot less than values listed in ASHRAE 90.1-
2004 corresponding to the building type (See table on Lighting Worksheet).

    Light levels should meet IES recommendations for each space type
    Documentation showing how LPD was calculated must accompany Final Application
          Minimum requirement: Detailed room by room survey with associated calculations
          ComCheck stamped by PE is strongly recommended and preferred
    Incentive = (LPD baseline - LPD actual) x Area x $0.35.
    Area is gross lighted area of each space type.
    Incentive is for interior lighting only (except Parking Garage).
    Installed interior lighting power includes all power used by the luminaires, including lamps, ballasts, current
     regulators, and control devices.
    The following lighting equipment and applications are excluded from the calculation of interior lighting power:
     1. Display or accent lighting for galleries, museums, and monuments
     2. Lighting integral to equipment , instrumentation, or appliances
     3. Lighting in retail display windows
     4. Lighting integral to advertising or directional signage
         Exit signs
     5. Lighting for theatrical purposes, including performance, stage, film, and video production
     6. Lighting for television broadcasting in sporting activity areas
     7. Casino gaming areas.
    Use the following procedure to calculate the actual Lighting Power Density of the building or space:
     1. Determine the building type(s) and LPD baseline(s) from the table on the Lighting Worksheet
     2. Determine the gross lighted area corresponding to the building type and enter in Lighting Worksheet
     3. Determine the interior lighting power for corresponding building type and enter in Lighting Worksheet
     4. Incentive = (LPD baseline – LPD actual) x Gross Lighted Area x $0.35.

Occupancy Sensors (Wall Box, Ceiling and Fixture Mount)
Measure: Install occupancy-based controls on lighting.
 Only passive infrared and/or ultrasonic detectors are eligible.
 Wall box and wall-, ceiling-, or fixture- mounted sensors must be hardwired to control interior lighting fixtures.
A room-by-room count or the calculation used to determine connected Watts must accompany application.

Daylighting Controls
Measure: Install a photosensor that controls dimming ballasts.
 Dimming can be continuous or stepped at three or more levels (including on/off).
 Systems that allow on/off overrides are not eligible.
 This measure is not eligible for incentives in conjunction with the daylighting incentive from APS’ Solar Program.
A manufacturer's specification sheet must accompany the application.




                                                              12




      Visit aps.com/businessrebates for program information                                                            Prescriptive Appl: June 1-Nov 30, 2010
                                                                     Cooling Incentive Worksheet
                                                                                                                                                                                                           Efficiency
                                                                                                                                                                                        Equipment          Incentive
                                                                                                Size Category                                            Qualifying
                                Equipment Type                                                                                                                                           Incentive        (per unit Eff.
                                                                                            (1 Ton = 12,000 Btu/h)                                      Efficiency (1)
                                                                                                                                                                                          (per ton)      over Qual. Eff.
                                                                                                                                                                                                            per ton)

  AC & Heat Pump (HP) Units, Air Cooled (1 Phase) - Min. 11.5 EER (4)                            <65,000 Btu/h                                      14 SEER & 11.5 EER                    $50.00             $30.00

                                                                                                 <65,000 Btu/h                                             11.1 EER                       $50.00             $50.00
                                                                                        65,000 Btu/h - 134,999 Btu/h                                  11.4 IPLV (EER)                     $50.00             $50.00
             AC & Heat Pump (HP) Units, Air Cooled (3 Phase)
                                                                                       135,000 Btu/h - 239,999 Btu/h                                  11.2 IPLV (EER)                     $25.00             $50.00
                                                                                            240,000 Btu/h or greater                                  10.4 IPLV (EER)                     $25.00             $50.00
      Outside Air Economizer Packaged for Air Cooled AC & HP Units                                 All Sizes                                                  n/a                         $40.00                n/a
                                                                                                  All Sizes
                 Packaged Terminal Air Conditioning &
                                                                                                 Generally                                      12.5-(0.213 x cap/1000) EER(3)            $45.00             $15.00
              Packaged Terminal Heat Pump (PTAC & PTHP)
                                                                                            5000 to 24,000 Btu/h
                                                                                                  <150 Tons                                          1.15 kW/Ton - IPLV                    $7.00            $300.00
                              Air-Cooled Chillers
                                                                                                  ≥150 Tons                                          1.15 kW/Ton - IPLV                   $10.00            $300.00
                                                                                                  <150 Tons                                          0.68 kW/Ton - IPLV                    $7.00            $300.00
                            Water-Cooled Chillers                                           ≥150 Tons to <300 Tons                                   0.63 kW/Ton - IPLV                    $7.00            $300.00
                                                                                                  ≥300 Tons                                          0.57 kW/Ton - IPLV                   $10.00            $300.00

       Programmable Thermostats                                                                                                                                                           $40.00          per thermostat




                                                                                                                                                            Measurement
                                                                           Equipment Type




                                                                                                               Economizer



                                                                                                                                    Quantity
                                                                                                                                                                            Equip.




                                                                                                                                                               Units
                                                                                                                                               Capacity                                 Qualifying




                                                                                                                            (Y/N)
             Equipment Description                                                                                                                                        Efficiency                        Subtotal
                                                                  Select from Pull Down Menu                                                   of Equip.                               Efficiency (2)
                (Make/Model) (1)                                                                                                                                           Rating
Item
                                                             (Click on cell then arrow box on right)
  #

 1

 2

 3

 4

 5

 6

 7

 8

 9

10

11

12

13

14

15




Programmable Thermostats
                       Make                                                          Model                                                         Quantity                   Controlled Area ft2           Subtotal




(1)
      Manufacturer's specification sheet showing ARI EER, ARI SEER or ARI IPLV must accompany the final application.
(2)
      IPLV = Integrated Part Load Value, EER = Energy Efficiency Ratio, SEER = Seasonal Energy Efficiency Ratio
(3)
      Minimum Qualifying EER based on ASHRAE 90.1-2004 and equal to 12.5 - 0.213 x Capacity / 1000.
(4)
      Minimum Qualifying EER is 11.5. Minimum Qualifying SEER is 14 with additional incentive for exceeding SEER.


           Project Completion Date
                                                                                                                                                                          Cooling Total                 $0.00
Incentives cannot exceed 75% of incremental measure cost.


                                                                                            13




                   Visit aps.com/businessrebates for program information                                                                                                                                                   Prescriptive Appl: June 1-Nov 30, 2010
                  Specifications for Cooling Measures
Unitary Air-Conditioning and Air-Source Heat Pump Equipment
Measure: Install air conditioning units or heat pumps that meet or exceed the qualifying efficiency rating shown on the
incentive worksheet.
 Units can be split systems or single packaged units.
 All packaged and split system cooling equipment must meet Air-Conditioning and Refrigeration Institute (ARI)
    standards (210/240-2008 or 340/360-2007), be UL listed, and use a minimum ozone-depleting refrigerant (e.g., HCFC
    or HFC).
Evaporative coolers and water source heat pumps do not qualify as prescriptive measures, but may qualify under the
Custom Incentive Program.
 A manufacturer's specification sheet indicating the system efficiency must accompany the application.

Water- and Air-Cooled Chillers
Measure: Install water- or air-cooled chiller with Integrated Part Load Value (IPLV), expressed as kW/ton, less than or
equal to the qualifying efficiency shown on the incentive worksheet.
 Chiller efficiency rating must be based on ARI Standard 550/590-2003 for IPLV Standard Conditions and not based
   on full-load conditions.
 Chiller must meet ARI standards 550/590-2003, be UL listed, and use a minimum ozone-depleting refrigerant (e.g.,
   HCFC or HFC). The ARI net capacity value should be used to determine the chiller tons.
A manufacturer’s specification/performance sheet with the rated kW/Ton-IPLV or COP-IPLV must accompany the
application.

Incentive Calculations for Air Conditioners and Chillers
The incentive is determined by two components: an equipment incentive and an efficiency incentive, which are applied
per ton of cooling installed.
 Equipment that meets the minimum qualifying efficiency rating is eligible for an incentive.
 Equipment that exceeds the minimum qualifying efficiency for the equipment size category is eligible for an
    efficiency incentive (added on a prorated basis).
 Please contact the Solutions for Business team for assistance if only the IEER rating is available.

The incentive for air conditioners and heat pumps is calculated as follows:
   Tons X {Equipment Incentive/ton + [Efficiency Incentive/ton X (IPLV new – IPLV qualifying)]} or
   Tons X {Equipment Incentive/ton + [Efficiency Incentive/ton X (SEER new – SEER qualifying)]} or
   Tons X {Equipment Incentive/ton + [Efficiency Incentive/ton X (EER new – EER qualifying)]}
   corresponding to the appropriate qualifying efficiency rating.

The incentive for chillers is calculated as follows:
   Tons X {Equipment Incentive/ton + [Efficiency Incentive/ton X (kW/ton qualifying – kW/ton new)]}

Packaged Terminal Air Conditioner and Heat Pumps (PTAC/PTHP)
Measure: Install PTAC or PTHP units with efficiency ratings based on ASHRAE 90.1-2004 and equal to or greater than
the qualifying efficiency shown on the incentive worksheet (12.5 – (0.213 x cap/1000) EER).
 All EER values must be rated at 95o F outdoor dry bulb temperature.

Outside Air Economizers
Measure: Install outside air economizers on existing AC or Heat Pump units or with purchase of new units.
 Economizers must be capable of automatically modulating between 5-95%.

Programmable Thermostats
Measure: Install programmable thermostat.
 Thermostat must be capable of maintaining two separate programs (to address changing occupancy and comfort
   needs) and up to four temperature settings for each program.
A manufacturer's specification sheet must accompany the application.



                                                             14




     Visit aps.com/businessrebates for program information                                                                Prescriptive Appl: June 1-Nov 30, 2010
                   HVAC Testing and Repair Incentive Worksheet
                                                                                                        Per Unit                                     Per Ton
                                                                                                       Incentive                                    Incentive

 Advanced Diagnostic Tune Up                                                                               $240.00

 HVAC Testing and Repair - Duct Test and Repair                                                            $225.00                                     $15.00

 HVAC Testing and Repair - Economizer                                                                          $75.00


                                                                                                                               Select from Pull Down Menu
                                                                                                                                   (Click on cell, then
                                                                                                                              arrow box on right, select yes)




                                                                          Number of Units




                                                                                                                              Diagnostic Tune
                                                                                                           (Minimum 4 tons)
                                                                                            Unit Tonnage




                                                                                                                                                             Economizer
                                                                                                                                                and Repair
                                                                                                                                 Advanced



                                                                                                                                                 Duct Test
            Equipment ID                  Equipment Description




                                                                                                                                    Up
        (Enter multiple IDs for         One Model Number Per Line                                                                                                         Total Incentive
         identical equipment)                 (Make/Model)
Item
  #
 1

 2

 3

 4

 5

 6

 7

 8

 9

 10

 11

 12

 13

 14

 15

 16

 17

 18

 19

 20

 21

 22

 23

 24

 25



       Project Completion Date
                                                                                        HVAC Testing and Repair Total                                                         $0.00


                                                                     15




             Visit aps.com/businessrebates for program information                                                                                                                          Prescriptive Appl: June 1-Nov 30, 2010
   Specifications for HVAC Testing and Repair Measures
HVAC TESTING and REPAIR                                                 Economizer Repair
Measure: Performed on (4 ton and up) existing (DX) packaged or          If economizer does not open or close under simulated cold or hot outdoor
split systems. There are three separate incentive categories listed     temperatures, a repair must be completed.
below. Special training is required to participate in the Advanced              A second APS HVAC Testing & Repair sticker (in addition to the one
Diagnostic Tune-up and Duct Test & Repair measure. The                           applied in Category #1) must be applied to the equipment after service
following sections summarize the basic incentive requirements.                   is complete and the appropriate month/year holes must be punched
Detailed program requirements are found in the, HVAC Test and                    out.
Repair Technical Specification measure. (See Table 1 and Table 2)               See HVAC Testing & Repair Technical Specifications Guidebook for
                                                                                 complete service procedures.
Advanced Diagnostic Tune-up
Advanced Diagnostic Tune-up consists of an air conditioning             Duct Test & Repair
equipment performance test-in with specialized program approved         The Duct Testing & Repair measure uses diagnostic equipment to measure and
specialized test equipment, tune-up with repairs and a test-out.        repair duct leakage. The first step is to perform “Duct Leakage Test In” to
Refrigerant charge and air flow verification, belt replacement, air     determine total leakage. If system leakage is greater than 60 CFM per ton, seal
filters change, condenser coil cleaning with a non-acidic chemical,     ducts until leakage is below 60 CFM per ton or until leakage is reduced by 20%
evaporator coil cleaning (as needed), cleaning condensate drain         of total fan flow. Measure duct leakage (Test Out) after sealing or repairing duct
lines, electrical connections checked and tightened, economizer         system using same test procedure as the initial test. This verifies that the
functional testing, and any repairs needed to bring the system back     required leakage reduction was achieved.
to the manufacturer’s specifications.                                             Contractor must be Building Performance Institute (BPI) Certified.
          Only one rebate per system will qualify during a 5-year                Only ducts located in the “un-conditioned” space qualify for the
           time period from the original date of the tune-up.                      incentive.
          Outdoor temperature must be 55°F or higher for systems                 See HVAC Testing & Repair Technical Specifications Guidebook for
           with R410A refrigerant and 60°F or higher for systems                   complete service procedures.
           with R22 refrigerant during the tune-up and repair           PARTICIPATION & TRAINING REQUIREMENTS
           procedure. The indoor return air plenum temperature must
                                                                        To participate in the HVAC Testing & Repair program, contractors must be a
           be 70°F or higher at the end of the test cycle.
                                                                        Solutions for Business program Trade Ally.
          Test economizers for proper operation.
          See HVAC Testing & Repair Technical Specifications           Technician Training
           Guidebook for complete service procedures.                   Air Conditioning Contractors of America of Arizona (ACCA-AZ) has created
                                                                        the Professional Air Conditioning (PAC) program to qualify and recognize your
The Advanced Diagnostic Tune-up and Duct Test &                         company as one of the best in the field. Technicians become certified after
Repair measures require specialized program training in                 completing all required PAC classes.
order to participate.                                                            Initial training requirement. 10% of all company technicians must
                                                                             be certified through the Professional Air Conditioning program.
                                                                                 Annual training requirement. Each technician already certified
                                                                             through the PAC program must complete 12 NATE Continuing Education
                                                                             Units (CEU’s) and one course from the ACCA-AZ (PAC) program.
    Table 1. Advanced Diagnostic Tune-Up Criteria
                     System Type                                                              Criteria

              For Fixed Orifice Systems                     +/- 5°F of Target Superheat        &    +3°F/-5°F of Target Temp Split
                                                            (See Technical Guidebook)
                For Systems with TXV                        +/- 3°F of Target Sub cooling & +3°F/-5°F of Target Temp Split
                                                            (See Technical Guidebook)
                                                            Air flow >325 CFM <450 CFM per ton or
                             All                            +3°F/-5°F of Target Temp Split between supply and return air
                                                            (See Technical Guidebook)
    Table 2. Documentation Requirements (provide where applicable for each system)
    Equipment Sizing Calculations (for Quality Installation only)
    System Size (tons)
    Nameplate SEER or EER or age (if available)
    Nameplate Refrigerant Quantity
    Target and actual superheat or subcool temps from all tests
    Amount of refrigerant added or removed
    Target and actual for supply/return temperature differentials from all tests
    Air flow CFM from all tests
    Duct leakage CFM from all tests
    Economizer position at simulated outside hot and cold temperatures

                                                                         16




        Visit aps.com/businessrebates for program information                                                                                                Prescriptive Appl: June 1-Nov 30, 2010
 New Construction HVAC Quality Installation Incentive Worksheet
                                                                                                                                  Incentive
                                                          Number of
                                                                      Total Tons     Total Cost         Incentive Cap            75% of cost
                                                            Units
                                                                                                                               (not to exceed cap)

                                                                                                         $180 per unit
Quality Installation - Phase I
                                                                                                        $225 per unit +
Quality Installation - Phase II - Duct Seal                                                                $15/ton
  Quality Installation – New Construction                               Quality Installation – Retrofit
  Quality Installation is split into two phases. Phase I includes       Quality Installation is split into two phases. Phase I includes
  sizing, testing, and repair activities. Phase II involves sealing     sizing, testing, and repair activities. Phase II involves sealing
  ducts based on the Phase I test results. The incentive                ducts based on the Phase I test results. The incentive
  requirements are summarized as follows.                               requirements are summarized as follows.

  Phase I                                                               Phase I
  1.    System Sizing: Must use Air Conditioning Contractors            1.   System Sizing: Must use Air Conditioning Contractors
        Association (ACCA) standard calculations and provide                 Association (ACCA) standard calculations and provide
        documentation                                                        documentation
          Manual N for load estimation                                        Manual N for load estimation
          Manual CS for system selection                                      Manual CS for system selection
          Manual Q for duct sizing                                     2.   Refrigerant Charge and Air Flow (RCAF)
  2.    Refrigerant Charge and Air Flow (RCAF)                                 Perform RCAF Testing (See QI Installation Standards
          Perform RCAF Testing (See HVAC Test and Repair                          Supplement for measurement procedures and target
              Technical Specification Manual)                                      flow tables)
          Correct refrigerant charge and/or air flow to meet                  Correct refrigerant charge and/or air flow to meet
              criteria in Table 2                                                  criteria in Table 2
  3.    Duct Leakage Testing (See HVAC Test and Repair                  Phase II
        Technical Specification Manual)                                 If leakage is >60 CFM per ton perform Phase II Duct Sealing.
  Phase II                                                              1. Seal ducts until leakage is below 60 CFM per ton or until
  If leakage is >25 CFM per ton perform Phase II Duct Sealing.               leakage is reduced by 20% of total fan flow. Leakage of up
  1. Seal ducts until leakage is below 25 CFM per ton. Leakage               to 60 CFM per ton is allowed for major renovation projects
       of up to 60 CFM per ton is allowed for major renovation               where the ducts were not replaced. (See QI Installation
       projects where the ducts were not replaced. (See HVAC Test            Standards Supplement for Approved sealing materials and
       and Repair Technical Specification Manual.).                          procedures).
  2. Measure duct leakage after sealing to verify that required         2. Measure duct leakage after sealing to verify that required
       leakage targets were met.                                             leakage targets were met.
                                                                        3. Incentive is only for duct leakage and repairs can only be
   Table 1. RCAF Criteria                                                    performed on ductwork located in non-conditioned space

       System Type                         Criteria
                                                                         Table 2. Documentation Requirements
                           +/- 5°F of Target Superheat                       Provide the following information for each system
    For Fixed Orifice
                           +3°F/-5°F of Target Temp Split
        Systems                                                          Equipment Sizing Calculations
                           (See Technical Guidebook)
                                                                         System Size (tons)
                           +/- 3°F of Target Sub cooling                 Nameplate IPLV or EER
   For Systems with
                           +3°F/-5°F of Target Temp Split                Nameplate Refrigerant Quantity
         TXV
                           (See Technical Guidebook)                     Target and actual superheat or subcool temps from all tests
                                                                         Amount of refrigerant added or removed
                           Air flow 325-450 CFM per ton
                           or                                            Target and actual for supply/return temperature differentials
            All            +3°F/-5°F of Target Temp Split                from all tests
                           between supply and return air                 Air flow CFM from all tests
                           (See Technical Guidebook)                     Duct leakage CFM from all tests


         Project Completion Date
                                                                                HVAC Testing and Repair Total                        $0.00


                                                                       17




           Visit aps.com/businessrebates for program information                                                                                     Prescriptive Appl: June 1-Nov 30, 2010
                                                   Building Envelope Worksheet
                                                               Incentive Center of Glass
                                                                                                       Area of Glass   Incentive
                          New Glazing                           Amount      U-Factor         SHGC
                                                                                                         Sq. Feet       Subtotal
                                                               per Sq. Ft. Btu/hr-ft2-°F
                           Description                                       Max 0.32       Max 0.40
                                                                    $0.50
                                                                    $0.50
                                                                    $0.50
                                                                    $0.50
                                                                    $0.50
                                                                    $0.50
                                                                    $0.50
                                                                    $0.50
                                                                    $0.50
                                                                    $0.50
                                                                    $0.50
                                                                    $0.50
                                                                    $0.50
                                                                    $0.50




        High Performance Windows and Glass Doors
        Measure: New windows and glass door can utilize any combination of glazing, coating, internal film, and gas filling that
        meets the specified U-factor and Solar Heat Gain Coefficient.
         U-factor must be 0.32 Btu/hr-ft2-oF or less.
         U-factor is at center of glass.
         Solar Heat Gain Coefficient (SHGC) must be 0.40 or less.
         Films or coatings only added to existing glazing do not qualify.
         Incentive is paid on a per square foot basis.




                          Project Completion Date
                                                                                           Building Envelope Total      $0.00
Incentives cannot exceed 75% of incremental measure cost.


                                                                             18




            Visit aps.com/businessrebates for program information                                                                  Prescriptive Appl: June 1-Nov 30, 2010
                                   Refrigeration Incentive Worksheet
   Refrigeration Measures
                        Measure                                        Incentive Unit                   Quantity   Incentive/Unit   Subtotal

   Strip Curtains on Walk-Ins                                       Per Linear Foot                                    $5.00
                                                                      (door width)
   Night Covers                                                     Per Linear Foot                                   $10.00

   Reach-in Cooler Controls                                        Reach-in Cooler                                    $100.00

   Anti-Sweat Heater Controls
                                                                                           Number        Case
                                                                    Type                                           Incentive per
                      Make/Model                                                             of         Length
                                                             (Click cell and select)                                LF of Case
                                                                                           Sensors       (LF)
                                                                                                                      $12.00
                                                                                                                      $12.00
                                                                                                                      $12.00

   High-Efficiency Ice Makers (1)

                                                             Air or Water                        Size              Incentive per
                      Make/Model                               Cooled                      ≥ 101 lbs    Quantity
                                                             (Click cell and select)       per 24 hrs
                                                                                                                     Ice Maker

                                                                                                                     $300.00
                                                                                                                     $300.00
                                                                                                                     $300.00

   High-Efficiency Refrigerators or Freezers (1)

                                                            Type & Number of Doors                                 Incentive per
                      Make/Model                                                                        Quantity
                                                                       (Click cell and select)                         Unit

                                                                                                                      $75.00
                                                                                                                      $75.00
                                                                                                                      $75.00

   High-Efficiency Evaporator Fan Motors

                                                           PSC, EC Motor                                           Incentive per
                      Make/Model                                                          Motor HP      Quantity
                                                             (Click cell and select)                                   Unit
                                                                                                                      $10.00
                                                                                                                      $10.00
                                                                                                                      $10.00

   Vending Machine Controls
                                                                                                                   Incentive per
                      Make/Model                                              Unit                      Quantity
                                                                                                                        Unit
   Beverage Machine Controls                                      Vending Machine                                     $100.00
   Snack Machine Controls                                         Vending Machine                                      $50.00
   (1)
         Manufacturer's specification sheet must accompany the final application.

            Project Completion Date
                                                                                                           Refrigeration Total      $0.00
Incentives cannot exceed 75% of incremental measure cost.


                                                                                   19




               Visit aps.com/businessrebates for program information                                                                           Prescriptive Appl: June 1-Nov 30, 2010
        Specifications for Refrigeration Measures
Strip Curtains on Walk-ins
Measure: Install new strip curtains or clear plastic swinging doors on doorways of walk-in boxes and refrigerated
warehouses.
 Not available for display cases or for replacing existing strip curtains.
Incentive is based on linear foot of door width.

Night Covers
Measure: Install a cover on open vertical or horizontal refrigerated case to decrease cooling load.
 Recommend: Install films with small, perforated holes to decrease moisture buildup.
 Recommend: Use proper compressor capacity modulation mechanisms (such as VSDs or an unloader).
The incentive amount is based on the length of the case.

Reach-in Cooler Controls
Measure: Install controls with passive infrared occupancy sensor to turn off fluorescent lights and other refrigerated
systems when the surrounding area is unoccupied for 15 minutes or longer.
 Presumes refrigerated unit contains only non-perishable bottled and canned beverages.
 Control logic should power up the machine at 2-hour intervals to maintain product temperature.

Anti-Sweat Heater Controls
Measure: Install device that senses the relative humidity in the air outside of the display case and reduces or turns off the
glass door (if applicable) and frame anti-sweat heaters at low-humidity conditions.
 Technologies that can turn off anti-sweat heaters based on sensing condensation (on the inner glass pane) also qualify.
The incentive amount is based on the horizontal length of the case.

High-Efficiency Icemakers
Measure: Install air-cooled or water-cooled icemaker with minimum capacity of 101 lbs of ice per 24-hour period.
 The minimum efficiency required is per the Federal Energy Management Program guidelines at:
   www1.eere.energy.gov/femp/procurement/eep_ice_makers.html
A manufacturer's specification sheet must accompany the application.

High-Efficiency Reach-in Refrigerators and Freezers
Measure: Replace standard supermarket reach-in refrigerated cases with; or install, ENERGY STAR®-rated high-
efficiency cases, which are designed with components such as electronically commutated motor (ECM) evaporators and
condenser fan motors, hot gas anti-sweat heaters, or high-efficiency compressors.
 Eligible equipment includes one-door, two-door, and three-door refrigerators and freezers.
      All one-door units have a capacity of ≤30 cubic feet; two-door units are ≤60 cubic feet; and three-door units are
        ≤90 cubic feet.
A manufacturer's specification sheet must accompany the application.

Evaporative Fan Motor
Measure: Replace standard-efficiency shaded-pole evaporator fan motor in refrigerated display cases or fan coil in walk-
ins with electronically commutated motor (ECM) or permanent split-capacitor (PSC) motor.

Vending Machine Controls: Beverage and Snack
Measure: Install controls with a passive infrared occupancy sensor to turn off fluorescent lights and other vending
machine systems when the surrounding area is unoccupied for 15 minutes or longer.
 Presumes refrigerated vending machine contains only non-perishable bottled and canned beverages.
 For the beverage machine, the control logic should power up the machine at 2-hour intervals to maintain product
   temperature.


                                                                20




        Visit aps.com/businessrebates for program information                                                                   Prescriptive Appl: June 1-Nov 30, 2010
                                               Motors Incentive Worksheet
  Premium-Efficiency Motors - Minimum Qualifying Efficiencies
         Horse                      3600 RPM                                              1800 RPM                                   1200 RPM
                                                                                                                                                           Incentive/HP
         Power                  Open         Closed                                  Open        Closed                           Open    Closed
            1                   77.0%         77.0%                                  85.5%        85.5%                           82.5%    82.5%                $10.00
           1.5                  84.0%         84.0%                                  86.5%        86.5%                           86.5%    87.5%                $7.00
            2                   85.5%         85.5%                                  86.5%        86.5%                           87.5%    88.5%                $6.00
            3                   85.5%         86.5%                                  89.5%        89.5%                           88.5%    89.5%                $6.00
            5                   86.5%         88.5%                                  89.5%        89.5%                           89.5%    89.5%                $6.00
           7.5                  88.5%         89.5%                                  91.0%        91.7%                           90.2%    91.0%                $5.00
           10                   89.5%         90.2%                                  91.7%        91.7%                           91.7%    91.0%                $4.00
           15                   90.2%         91.0%                                  93.0%        92.4%                           91.7%    91.7%                $3.00
           20                   91.0%         91.0%                                  93.0%        93.0%                           92.4%    91.7%                $2.50
           25                   91.7%         91.7%                                  93.6%        93.6%                           93.0%    93.0%                $2.50
           30                   91.7%         91.7%                                  94.1%        93.6%                           93.6%    93.0%                $2.50
           40                   92.4%         92.4%                                  94.1%        94.1%                           94.1%    94.1%                $2.50
           50                   93.0%         93.0%                                  94.5%        94.5%                           94.1%    94.1%                $2.25
           60                   93.6%         93.6%                                  95.0%        95.0%                           94.5%    94.5%                $2.00
           75                   93.6%         93.6%                                  95.0%        95.4%                           94.5%    94.5%                $1.75
           100                  93.6%         94.1%                                  95.4%        95.4%                           95.0%    95.0%                $1.50
           125                  94.1%         95.0%                                  95.4%        95.4%                           95.0%    95.0%                $1.50
           150                  94.1%         95.0%                                  95.8%        95.8%                           95.4%    95.8%                $1.50
          ≥ 200                 95.0%         95.4%                                  95.8%        96.2%                           95.4%    95.8%                $1.50
 For motors less than 1 HP, use values for 1 HP.
           Motor Description                                 Motor
                                                                          3600 RPM


                                                                                      1800 RPM


                                                                                                 1200 RPM




                                                                                                                             Enter Actual
                                                                                                                    Closed




                                                                                                                                          Req'd     Incentive
                                                                                                             Open




       (Make/Model) Enter X under                   Qty      Size                                                                                                   Subtotal
                                                                                                                              Motor Eff. Motor Eff.   $/HP
                speed and type                               (HP)




  Variable-Speed Drives (1)                                                                                                                   Motors Total           $0.00
 Incentive per horsepower (all sizes)                             $60

                  VSD Description (Make / Model)                                                 Quantity           VSD Size (HP)         Incentive Amount          Subtotal




 (1)
       VSDs required by ASHRAE 90.1-2004 are not eligible for New Construction incentives.                                                         VSD Total         $0.00
              Project Completion Date
                                                                                                                                        Motors & VSD Total           $0.00
Incentives cannot exceed 75% of incremental measure cost.


                                                                                                            21




                  Visit aps.com/businessrebates for program information                                                                                                        Prescriptive Appl: June 1-Nov 30, 2010
                   Specifications for Motor Measures
Motor Measures
Measure: Install three-phase induction motors of open drip-proof (open) and totally enclosed fan-cooled (closed)
classifications.
 Recommend: Consider matching water or air flows (GPM, CFM) of the existing pump or fan when installing energy
    efficient motors that inherently have higher speeds (less slip), which may increase energy savings.

Incentives are based on the motor's Nominal Full Load Efficiencies that meet or exceed the efficiency standards on the
Motors Incentive Worksheet (NEMA Premium).
A manufacturer's specification sheet showing equipment type, equipment size, model number, and efficiency rating must
accompany the application.
                                                                        Limited Time Offer!
                                                                          $60/hp for VSDs.
Retrofit                                                                  Available through
                                                                              11/30/10.
Variable-Speed Drives
Measure: Install VSD on existing motor to reduce energy use.
 Must permanently remove or disable any throttling devices such as inlet vanes, bypass dampers, and throttling valves.
 VSDs replacing existing VSDs are not eligible for incentives.
 VSDs purchased for “Soft Start” only applications are not eligible for incentives.
 A 3% impedance choke is recommended to handle any power factor corrections that may occur. VSDs are sensitive to
   overvoltage.


New Construction
Variable-Speed Drives
Measure: Install VSD on motors to reduce energy use.
 Must not install any throttling devices such as inlet vanes, bypass dampers, and throttling valves.
 VSDs required by ASHRAE 90.1-2004 are not eligible for incentives
        Example: Variable Air Volume (VAV) with motors 15 hp or greater
        Example: HVAC pump on variable flow system with motor greater than 50 hp.
 VSDs purchased for “Soft Start” only applications are not eligible for incentives.
 A 3% impedance choke is recommended to handle any power factor corrections that may occur. VSDs are sensitive to