HVAC Retrofits



Sustainability Best Practices for HVAC Retrofits



Cal Poly State University, San Luis Obispo



Presented to the UC/CSU/CCC Sustainability Conference



June 22, 2009



Presented by

Dennis K. Elliot, PE, CEM

Sustainability Manager

HVAC Retrofits

Cal Poly San Luis Obispo

Founded 1901



Wide variety of HVAC equipment

and systems

Began conversions to DDC control

in 1984

Many older buildings are still

constant volume and have DDC

control at the air handler, but not at

the zone level.

Buildings built since 1990 are VAV

and have full DDC control down to

the zone level.

DDC retrofits expensive, typically

$1500 per point.

HVAC Retrofits

Four technology demonstration

projects implemented for the 2008

Sustainability Conference



Partners:

Cal Poly

CIEE/PIER

Federspiel Controls

Architectural Energy Corp

Melink Corporation

CulinAire Systems

UC/CSU/CCC Partnership Program

HVAC Retrofits

Constant Volume to VAV Retrofits



Problem:

Need cost effective solution for

VAV retrofits of constant volume

systems.

Must integrate into campus

Siemens DDC System.

Must preserve occupant comfort

and minimum ventilation rates.

Must minimize hazardous material

abatement costs.



Solution:

DART – Discharge Air Regulation

Technique

Federspiel Advanced Control

System – Wireless VAV

HVAC Retrofits

What is DART and how does it work?

DART - Discharge Air Regulation Technique



Monitors all zone temperatures and compares them to an allowable

range, i.e. CSU Executive Order 987 – 68 degrees heating, 78 degrees

cooling.

If all zones are within the range, fan runs at minimum speed.

If zones are outside the range, fan speed is ramped up to provide

adequate heating or cooling. Select 2nd or 3rd worst zone for control,

rather than worst zone.

When at low fan speeds, minimum OSA damper position is reset to

provide adequate fresh air ventilation rates as per ASHRAE 62.1.

Requires VFD’s on supply and return fans.

Uses existing building zone temperature controls.

HVAC Retrofits

Federspiel Advanced Control

System Components:



Supervisory controller

(microcomputer with integral web

server)

Wireless hub/gateway

Wireless temperature sensors

Wireless output modules for

connection to VFD’s or building

DDC system

HVAC Retrofits

Wireless mesh network:



All devices are surface mounted

Minimal electrical work required

No penetrations of structures or work in

plenums/crawl spaces – avoids haz mat

abatement!

Network is self healing, has N+1

redundancy, and uses frequency hopping

technology to maximize battery life –

expected to be 4 to 8 years.

Operates in 900 MHz band – will not

interfere with WiFi



Integration/Interoperability

Many open protocol options for

integration with existing DDC systems.

HVAC Retrofits

Cal Poly demonstration projects

Implemented in three buildings:



Collegeof Science and Math

Double duct CAV, heating only





Education Building

Double duct CAV, heating only





Health Center

Single duct CAV, heating and

cooling, terminal reheat

HVAC Retrofits

Total Fan Power, Post-retrofit, Fall, Sample Daily Profiles



Daily Fan Demand Profile:Education Building





Results: 10





9





8





Reduced fan energy by 52-72% 7





6







Reduced heating energy by 24-31%









kW

5





4





3



No hot/cold complaints 2





1





No air quality complaints 0

0:00 2:00 4:00 6:00 Cal 8:00 DART - COSAM System Fan Power

Poly 10:00 12:00 14:00 16:00 18:00 20:00 22:00 0:00

Pre-Retrofit and Summer- Post-Retrofit

Time of Day (10/27 11/1/08)









Cost approximately $60K (less than Fan Energy Before/After:

Total SF1 RF1



16



half the cost of full DDC) 14







12



Energy savings $15K/yr

10

kW









8



Payback 3 years after incentives

6







4







2







0

7/6/08 7/13/08 7/20/08 7/27/08 8/3/08 8/10/08 8/17/08

HVAC Retrofits

Lessons Learned:



Beforeinstalling VFD’s, replace motors with NEMA

Premium Efficiency, inverter duty rated motors.



Check grounding system in older buildings before

installing VFD’s.



Consider options for integration with your DDC

system, or can be installed as a standalone system.



O&M staff during installation, start up and

Involve

commissioning to make use of training opportunity.



about 80% of the energy savings of full

Achieves

DDC VAV controls, for half the cost.

HVAC Retrofits

Kitchen Hood Demand Ventilation



Central Campus Dining Facility



Problem:

Kitchen hoods run full speed from 6 am to

midnight – 3 fans, 9 hp total

Cooking activities are intermittent

Fan energy and conditioned air are wasted





Solution:

Kitchen Hood Demand Ventilation Controls

Slow fans down when no cooking is taking

place, ramp up to full speed only when

needed

HVAC Retrofits

Melink Intelli-Hood Control System



VFD’s installed on hood exhaust fans

Temperature sensors installed in each

exhaust duct to detect heat

Optical light beam across hood opening

detects steam or smoke

If exhaust temperatures rise, fan speed

is increased

If smoke or steam is detected, fans

ramp up to 100% speed

If no cooking is taking place, fans slow

down to 50% speed

HVAC Retrofits

Kitchen Hood Demand Ventilation



Results:

Reduced fan energy by 54%

Reduced heating energy by 34%

Cost $52,700 (included replacement of 3 exhaust fans)

Energy savings $9,600/yr

4 yr payback after incentives



EF1

250









200









150

W-hrs









100









50









0

10/20/08 10/27/08 11/03/08 11/10/08 11/17/08

EF2

250 Date

HVAC Retrofits

Kitchen Hood Demand Ventilation



Lessons Learned



Must involve and train kitchen staff to understand usage and

monitor operation.



Be sure to properly interface controls with existing fire suppression

system.



Melink control system is stand-alone, but consider remote

monitoring from campus DDC system.

HVAC Retrofits

Contacts:



Dennis Elliot, Sustainability Manager, Cal Poly, SLO - delliot@calpoly.edu



PIER Program – http://www.energy.ca.gov/research/index.html



Federspiel Controls - http://www.federspielcontrols.com



Melink - http://www.melinkcorp.com



CulinAire Systems - http://www.culinairesystems.com



Architectural Energy Corporation - http://www.archenergy.com


Related docs
Other docs by HC111212212526
March 2008 Grand Champion
Views: 0  |  Downloads: 0
Le v�ritable amour c' est...
Views: 1  |  Downloads: 0
Etre �l�ve en �ducation prioritaire
Views: 0  |  Downloads: 0
CIMARRON GOWAN COMMUNITY ASSOCIATION
Views: 14  |  Downloads: 0
PowerPoint Presentation
Views: 1  |  Downloads: 0
Anf�bios
Views: 0  |  Downloads: 0
Sheet1
Views: 10  |  Downloads: 0
Centennial School District
Views: 4  |  Downloads: 0
CERTIFICATED
Views: 6  |  Downloads: 0
ASMC flyer
Views: 1  |  Downloads: 0
By registering with docstoc.com you agree to our
privacy policy

You are almost ready to download!

You are almost ready to download!