Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415









Property Condition Report









Case Number: 011-532083

Full Address: 510 Navajo Circle

Alabaster, AL 35007

Inspection Date: December 2, 2007

Inspection Type: Property Condition Report

Inspector D Keough

NOTICE TO ALL PROSPECTIVE PURCHASERS: Pursuant to section 5.3.4 of HUD

RFP: R-OPC-22505, you are hereby notified that the contents of this inspection

report are for information only and do not imply any guarantee or warranty of

property conditions

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415





Table of Contents

Section Title Page

1 INSPECTION REQUIREMENTS



1.1. Exclusions of Inspection………………………………………………………………………….



1.2. Exclusions and Limitations……………………………………………………………………..



1.3. Well Exclusion……………………………………………………………………………………

2 REPORT SUMMARY…………………………………………………………………



3 DIRECTIONS TIPS TO PROPERTY………………………………………………..



4 PROPERTY INFORMATION………………………………………………………..



5 ADDITIONAL COMMENTS………………………………………………………….



6 STRUCTURAL COMPONENTS



6.1. General Structural Information……………………………………………………………………..



6.2. Structural Checkpoints………………………………………………………………………………



6.3. Structural Comments. ……………………………………………………………………………….







7 EXTERIOR OF STRUCTURE



7.1. General Exterior Information…………………………………………………………………………



7.2. Exterior Checkpoints…………………………………………………………………………………...



7.3. Exterior Comments…………………………………………………………………………………….



8 ROOFING



8.1. General Roof Information……………………………………………………………………………...



8.2. Roof Checkpoints………………………………………………………………………………………..



8.3. Roofing Comments………………………………………………………………………………………



9 PLUMBING



9.1. General Plumbing Information…………………………………………………………………………



9.2. Plumbing Checkpoints…………………………………………………………………………………..



9.3. Plumbing System Comments…………………………………………………………………………….

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415

10 ELECTRICAL

10.1. General Electrical Information……………………………………………………………………………



10.2. Electrical Checkpoints……………………………………………………………………………………...



10.3. Electrical System Comments……………………………………………………………………………….



11 HVAC (Heating Ventilation, Air Conditioning)

11.1. General HVAC Information……………………………………………………………………………



11.2. HVAC Checkpoints……………………………………………………………………………………..



11.3. HVAC Comments………………………………………………………………………………………..



12 INTERIOR

12.1. General Interior Information…………………………………………………………………………….



12.2. Interior Checkpoints………………………………………………………………………………………



12.3. Interior Comments………………………………………………………………………………………...



13 APPLIANCES

13.1. General Appliance Information………………………………………………………………………….



13.2. Appliance Checkpoints…………………………………………………………………………………...







13.3. Appliance Comments…………………………………………………………………………………….





14 HOA INFORMATION………………………………………………………………………………………..



15 CODE VIOLATIONS…………………………………………………………………………………………



16 PENDING LITIGATION……………………………………………………………………………………..



17 DEMO ORDERS………………………………………………………………………………………………



18 MOLD DISCLOSURE 5.3.8.5…SEE MOLDDISCLOSURE…………………………………………………



19 ENVIRONMENTAL ISSUES…………………………………………………………………………………



20 ENVIRONMENTAL COMPLIANCE RECORD, Attachment 18 in Handbook 4310.5…………………

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415





1 INSPECTION REQUIREMENTS

STRUCTURAL COMPONENTS including foundation, floors, walls, columns, ceilings, and roofs.



EXTERIOR OF STRUCTURE including wall claddings, entryway doors, decks, steps, eaves, driveways, windows,

patios, pools/spas, lawns, landscape, retaining walls, sheds/outbuildings, and fences.



ROOFING including roof coverings, roof drainage systems, flashing, skylights, and chimneys.



PLUMBING including interior water supply and distribution system, interior waste drains and vent system, hot

water system, fuel storage and distribution system, and sump pump.



ELECTRICAL including service entrance conductors, service equipment, main distribution panels, voltage ratings,

a representative number of installed ceiling fans, lighting fixtures, switches and receptacles, ground fault circuit

interrupters, and smoke detectors.



HVAC (Heating Ventilation, Air Conditioning) including permanently installed heating system and its controls,

chimneys, heat distribution system, including fans, pumps, and ducts, and automatic safety controls.



Normal operating control of the central air conditioning system and the distribution system



Insulation vapor barriers, ventilation of attic and foundation, kitchen, bathroom and laundry venting systems, and the

operation of any readily accessible attic ventilation fan when temperature permits



INTERIOR including walls, ceilings, floors, steps, cabinets, doors, windows, etc



BUILT-IN KITCHEN APPLIANCES including the observation and operation of dishwasher, range, trash

compactor, garbage disposal, ventilation equipment, permanently installed oven and microwave oven.





1.1. Exclusions of Inspection



1.2. Exclusions and Limitations

This inspection is limited to visual observations of apparent conditions existing at the time of the inspection

only. This inspection is not intended to provide the purchaser with information regarding the advisability of

this purchase, the market value of the property, the compliance or non-compliance with codes, ordinances and statutes,

the suitability of this property for specialized use, the life expectancy of any component or system in the property, the

presence or absence of pests or insects, or cosmetic or underground items or items that are not permanently

installed. This inspection report does not address and is not intended to address the possible presence of any

danger from any potentially harmful substance and environmental hazards, including but not limited to radon

gas, lead paint, asbestos, urea formaldehyde (UFFI), toxic or chemical analysis, airborne hazards, polluted

water, or underground oil tanks.



This inspection was completed on a home that was serviced by the former lender. Systems that are being evaluated

may have been off and shutdown for an extended period of time thus requiring repairs that are not noted in this

inspection. This inspection may not reveal conditions that compromise a particular system. Systems that have been

off for extended periods of time will require service, repairs and or new components. This inspection is a condition

reports only not a home inspection or home warrantee. The general public visits these homes and conditions are

subject to change. Interested buyers are to use this report as a guide in viewing the property only.

All buyers should obtain a complete home inspection by a licensed home inspector prior to purchasing.



Signature: David Keough

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415

2 REPORT SUMMARY



This summary is provided to highlight those findings that we believe are for information, significant in nature or

which appear to be in immediate need of repair or a safety concern.



This inspection is visual only in areas that were accessible at the time of inspection. No dismantling of building

components or systems, no destructive testing, no engineering functions, and no code compliance inspections were

performed at the time of the inspection. The findings were as follows:





A Structural Components

 Structure was in marginal condition at time of inspection



 Water seepage into basement room in front



 Structural components should be tested/checked by licensed inspector prior to purchase



B Exterior of Structure

 Exterior was in marginal condition at time of inspection

 Pool deck damaged, undermining occurred

 Retaining wall damaged & leaning in rear

 Shed door hinge, floor & siding damaged. Roof shingle missing in large area on shed

 Fence missing or damaged at very rear & side of property

 Exterior components should be tested/checked by licensed inspector prior to purchase



C Roofing



 Roof was in satisfactory condition at time of inspection



 Roofing components should be tested/checked by licensed inspector prior to purchase



D Plumbing



 Plumbing system was pressure tested with compressor & in marginal condition at the time of

inspection



 Recommend Plumbing professional evaluate when water is turned on



 Toilets loose. Kitchen sink trap/drain pipe damaged



 Wells and septic systems, if present, are inspected only for presence of obvious visible defects.

The water quality and flow capacity of wells is not determined and the full operational

functionality of septic systems cannot be determined due to the unavailability of water and

extended non-use of the system



 This report reflects general conditions noted during time of inspection. Systems such as HVAC,

Plumbing and Electrical because of their nature and complexity are subject to deterioration or

breakdown over time that cannot be predicted



 Because of this, prospective buyers are strongly urged to obtain a full home inspection prior

to purchase

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415

E Electrical

 Electrical components were checked via generator & in marginal condition at the time of

inspection

 Living room, master & front middle bedroom ceiling fans did not turn on

 Wire in shed capped



 Recommend Electrical professional evaluate



 This report reflects general conditions noted during time of inspection. Systems such as HVAC,

Plumbing and Electrical because of their nature and complexity are subject to deterioration or

breakdown over time that cannot be predicted



 Because of this, prospective buyers are strongly urged to obtain a full home inspection prior

to purchase



F HVAC – Heating, Ventilation, Air Conditioning



 HVAC components were checked via generator & in marginal condition at the time of inspection



 HVAC system turned on during test



 Duct in basement causing stains on ceiling



 Recommend routine maintenance



 Recommend HVAC professional evaluate



 This report reflects general conditions noted during time of inspection. Systems such as HVAC,

Plumbing and Electrical because of their nature and complexity are subject to deterioration or

breakdown over time that cannot be predicted



 Because of this, prospective buyers are strongly urged to obtain a full home inspection prior

to purchase



G Interior

 Interior was in marginal condition & in need of repairs at time of inspection

 One drawer in kitchen not aligned properly

 Basement room ceiling tiles stained and sagging

 Countertop worn and older

 Closet doors missing in bedrooms

 Front side bedroom door missing

 Carpet stained in various areas

 Garage wall has some damage with mold

 Master bedroom window pane replaced with plexiglass

 Interior components should be tested/checked by licensed inspector prior to purchase

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415

H Appliances



 Appliances were checked via generator



 Range Hood and Dishwasher turned on during test



 Appliances should be tested/checked by licensed inspector prior to purchase









3 DIRECTIONS TIPS TO PROPERTY



4: I-65 N



5: Take the US-31 exit- EXIT 238- toward ALABASTER. 0.2 miles Map



6: Turn LEFT onto US-31 N / AL-3 N / MONTGOMERY HWY.1.2 miles Map



7: Turn LEFT onto 2ND PL NW. <0.1 milesMap



8: Turn LEFT onto 1ST ST NW. <0.1 milesMap



9: Turn RIGHT onto 1ST AVE W / CR-44. 1.2 miles Map



10:Turn RIGHT onto NAVAJO TRL. 0.1 miles Map



11:Turn RIGHT onto NAVAJO CIR. <0.1 milesMap

End at 510 Navajo Cir

12: Map

Alabaster, AL 35007-5802, US

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415

4 PROPERTY INFORMATION



Address: 510 Navajo Circle Access to Property: Yes

City/County: Alabaster

Status of Utilities: Electric OFF

Water: OFF

Gas: OFF

State: AL Approx Structure Age: 1977

Zip Code: 35007 Approx Square Footage: 1350

Occupied: Vacant Number of Baths: 2









5 ADDITIONAL COMMENTS:



Power Company: Alabama Power Meter Number: Meter missing

Water Company: City Meter Number: 16047040

Gas Company: Alagasco Meter Number: 3435798

HOA Transferable Warranties: Unknown

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415



6 STRUCTURAL COMPONENTS

This portion of the inspection covers general structural component checkpoints of the subject property such as

Foundation, floors, walls, columns, ceilings, basement, etc.



6.1. General Structural Information

Access Method: Walk in basement



Foundation Type: Block



Basement Type: Finished



6.2. Structural Checkpoints



Checkpoints Rating * Comments





Basement Floor S

Beam Supports S

Ceilings S

Cracks S

Crawlspace Door NA

Floor S

Footing Drain NV

Ground Grade M Water seepage into basement room in front

Insulation NV

Joists S

Sill Plate S

Structural M Water seepage into basement from in front

Sub-Flooring S

Walls S

Wood-Ground Distance S



* Ratings: S=Satisfactory U=Unsatisfactory M=Marginal MG=Missing NA=Not Applicable NV=Not Visible

6.3. Structural Comments

Structure was in marginal condition & in need of repairs at time of inspection

Water seepage in basement room front wall

Structural components should be tested/checked by licensed inspector prior to purchase

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415

7 EXTERIOR OF STRUCTURE

This portion of the inspection covers general exterior checkpoints of the subject proprety structure such as wall

claddings, entryway doors, decks, steps, eaves, driveways, windows, patios, pools/spas, lawns, landscape, retaining

walls, sheds/outbuildings, fences, ect.



7.1. General Exterior Information



Exterior Siding Type: Brick/Vinyl

Approx Lot size: Odd size lot, under half acre

Temperature: 70°

Wall Structure: Wood

Weather Conditions: Overcast

7.2. Exterior Checkpoints



Checkpoints Rating* Comments



Balconies S

Carports NA

Debris S

Decks S

Driveway M Very steep

Eaves S

Entry Locks S

Exterior Doors S

Fencing/Gates M

Fence missing or damaged at very rear & side of

property

Garage Door S

Garage Door Opener NA

Landscape S

Lawn Care S

Leaf Removal M

Patio S

Pool/Spa U Pool deck damaged, undermining occurred

Porches S

Railings S

Retaining Walls U Retaining wall damaged & leaning in rear

Sheds/Outbuildings U Shed door hinge, floor & siding damaged. Roof

shingle missing in large area

Sidewalks NA

Siding Conditions S

Snow Removal S

Steps S

Storm/Screen Doors S

Storm/Screen Windows S

Windows S

* Ratings: S=Satisfactory U=Unsatisfactory M=Marginal MG=Missing NA=Not Applicable NV=Not Visible

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415

7.3. Exterior Comments

Exterior was in marginal conditon & in need of the above repairs at time of inspection

Pool deck damaged, undermining occurred

Retaining wall damaged & leaning in rear

Shed door hinge, floor & siding damaged. Roof shingle missing in large area

Fence missing or damaged at very rear & side of property

Exterior components should be tested/checked by licensed inspector prior to purchase

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415

8 ROOFING

This portion of the inspection covers general exterior roofing component checkpoints of the subject proprety such as

roof coverings (shingles, flashing, skylights, chimneys, etc.), structural elements of the roof (trusses, rafters, ceiling

foists, etc.), roof drainage systems, etc.



8.1. General Roof Information

Attic Type: Scuttle Hole Hatch

Gutter Type: Plastic

Method to Observe Attic In Attic

Method Used to Observe Roof: On Roof

Number of Layers: 1

Roof Type: Gable

Roofing Material: Dimensional shingle





8.2. Roof Checkpoints



Checkpoints Rating* Comments





Shingle Condition S

Flashing/Joints S

Soffits/Fascias S

Skylights NA

Vent Pipes S

Chimney NA

Gutters S

Downspouts S

Attic Ventilation S

Attic Water NV

Attic Insulations S

Structural Condition S

Sheathing Condition S

Truss S

Roof Exhaust Fan(s) S Turbines



* Ratings: S=Satisfactory U=Unsatisfactory M=Marginal MG=Missing NA=Not Applicable NV=Not Visible

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415

8.3. Roofing Comments

Roof components were in satisfactory condition at time of inspection

Roofing components should be tested/checked by licensed inspector prior to purchase

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415

9. PLUMBING

This portion of the inspection covers general plumbing checkpoints of the subject proprety such as interior water

supply and distribution system, interior waste drains and vent system, hot water system, fuel storage and

distribution system, and sump pump.



9.1. General Plumbing Information



Waste Piping: PVC/Cast iron

Water Heater Capacity: 40 Gallons

Water Heater Manufacturer: Craftmaster

Water Heater Model Number: GIF4634T3NV

Water Piping: Copper

Water Supply: City





9.2.Plumbing Checkpoints



Checkpoints Rating* Comments



Bar Sink NA

Bath Fixtures M Toilets loose

Connections M Toilets loose. Kitchen sink trap/drain pipe damaged

Hot Tub/Spa NA

Interior Vent S

Kitchen Sink M Trap drain pipe damaged, needs replaced

Laundry Tub NA

Main Shut off S

Pressure Relief Valve M Extension pipe cut

Pressure Tank S

Septic Location/Condition NV

Septic System NV

Sewer Drainage NV

Shower Pan NV

Sprinkler System NV

Storage Tanks NA

Vent System S

Water Filter NA

Water Heaters NA

Water Meter

Water Softener NA

Water Supply CITY

Well NA

Well Location NA

Well Pump/Sump Pump NA

* Ratings: S=Satisfactory U=Unsatisfactory M=Marginal MG=Missing NA=Not Applicable NV=Not Visible

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415

9.3. Plumbing System Comments

Plumbing system was pressure tested with compressor.

System was in marginal condition & in need of the above repairs at time of inspection

Toilets loose. Kitchen sink trap/drain pipe damaged



Recommend Plumbing professional evaluate when water is turned on

Wells and septic systems, if present, are inspected only for presence of obvious visible defects. The water

quality and flow capacity of wells is not determined and the full operational functionality of septic systems

cannot be determined due to the unavailability of water and extended non-use of the system



This report reflects general conditions noted during time of inspection. Systems such as HVAC, Plumbing

and Electrical because of their nature and complexity are subject to deterioration or breakdown over time

that cannot be predicted



Because of this, prospective buyers are strongly urged to obtain a full home inspection prior to

purchase

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415

10. ELECTRICAL

This portion of the inspection covers general plumbing checkpoints of the subject proprety such as service entrance

conductors, service equipment, main distribution panels, voltage ratings, a representative number of installed

ceiling fans, lighting fixtures, switches and receptacles, ground fault circuit interrupters, smoke detectors, ect.



10.1. General Electrical Information

Additional Space Available: No

Box Location: Garage Utility Room

Capacity: 60 amps

Conductor Type: Aluminum

General Wiring: Romex

Number of Disconnects: 20

Panel Manufacturer: ITE

Panel Type: Breakers

Wiring: Copper



10.2. Electrical Checkpoints



Checkpoints Rating* Comments

Appliance Wiring S

Bath GFCI NA Recommend adding

Breaker Condition S

Exterior GFCI NA Recommend adding

Exterior Wiring M Wire in shed cut/capped

Ground Bonding NA

HVAC Wiring S

Interior Wiring S

Kitchen GFCI NA Recommend adding

Lighting Fixtures U Living room, master & front middle bedroom

ceiling fans did not turn on

Panel Box S

Receptacle Location S

Service Attach S

Service Meter MG

Sub Panel Box NA







* Ratings: S=Satisfactory U=Unsatisfactory M=Marginal MG=Missing NA=Not Applicable NV=Not Visible

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415

10.3. Electrical System Comments

Electrical system was checked via generator.

System was in marginal condition & in need of the above repairs at time of inspection

Recommend GFCI Protection in house

Recommend Electrical professional evaluate

Living room, master & front middle bedroom ceiling fans did not turn on

Wire in shed capped

This report reflects general conditions noted during time of inspection. Systems such as HVAC,

Plumbing and Electrical because of their nature and complexity are subject to deterioration or

breakdown over time that cannot be predicted



Because of this, prospective buyers are strongly urged to obtain a full home inspection prior

to purchase

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415

11 HVAC (Heating Ventilation, Air Conditioning)

This portion of the inspection covers general HVAC checkpoints of the subject proprety such as permanently installed heating

system and its controls, chimneys, heat distribution system, including fans, pumps, and ducts, and automatic safety controls.

Normal operating control of the central air conditioning system and the distribution system, etc. Insulation vapor barriers,

ventilation of attic and foundation, kitchen, bathroom and laundry venting systems, and the operation of any readily

accessible attic ventilation fan when temperature permits ect.

11.1. General HVAC Information

Inside Unit Brand: Rheem

Inside Unit Model Number: RGOG07EAUEA

Inside Unit Type: Gas Furnace/Air Handler

Outside Unit Brand: Rheem

Outside Unit Model Number: RAKA 037JAZ

Outside Unit Type: Electric

11.2. HVAC Checkpoints

Checkpoints Rating* Comments

Air Conditioning S

Boiler NA

Coil NV

Coil Fins NV

Condensation Pipe S

Controls S

Draft Device S

Duct Work M Duct in basement causing stains on ceiling

Electric Heat NA

Evaporator NV

Fans NV

Filters M Change

Fireplace NA

Flu Pipes S

Furnace NA Visually in fair condition. Unable to test with no gas

Gas Lines M Recommend evaluation when gas is turned on

Heat Exchanger NV

Heat Pump NA

Inside Fan Motor NV

Oil Tank NA

Oil Tank Vent NA

Refrigerant Line S

Supply Returns S

Temperature Drop Test S

Thermostat S

Vapor Barrier NV

Ventilation S



* Ratings: S=Satisfactory U=Unsatisfactory M=Marginal MG=Missing NA=Not Applicable NV=Not Visible

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415



11.3. HVAC Comments

HVAC system was checked via generator & in marginal condition at time of inspection

Duct in basement causing staining on ceiling tiles

HVAC system turned on during test

Recommend routine maintenance

Recommend HVAC professional evaluate when gas is turned on

This report reflects general conditions noted during time of inspection. Systems such as HVAC,

Plumbing and Electrical because of their nature and complexity are subject to deterioration or

breakdown over time that cannot be predicted



Because of this, prospective buyers are strongly urged to obtain a full home inspection prior

to purchase

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415

12 INTERIOR

The interior portion of the inspection covers checkpoints involving the interior walls, ceilings, floors, steps,

cabinets, doors, and windows.



12.1. General Interior Information



There are no general information points in this section.





12.2. Interior Checkpoints



Checkpoints Rating * Comments



Cabinets M One drawer in kitchen not aligned

Ceilings M Basement room ceiling tiles stained/sagging

Closets M Doors missing in bedrooms

Countertops M Worn, older

Debris

Detectors M Recommend installing new detectors throughout

house

Door Hardware S

Doors M Front side bedroom door missing. Front bedroom

closet door nad one master bi-fold closet door missing

Dryer Vent S

Floors M Carpet stained in various areas

Mold M Garage

Railings S

Stairwells S

Steps S

Walls M Garage wall has some damage w/mold. Basement

front wall water damaged

Windows M Master bedroom window pane replaced w/plexiglass







* Ratings: S=Satisfactory U=Unsatisfactory M=Marginal MG=Missing NA=Not Applicable NV=Not Visible







12.3. Interior Comments

Interior was in marginal condition and in need of above mentioned repairs at time of inspection

Cabinet drawer in kitchen not aligned

Basement room ceiling tiles stained/sagging

Closet doors missing in bedrooms

Front bedroom door missing

Carpet stained in various areas

Garage wall has some damage with mold. Basement front wall water damaged.

Master bedroom window pane replaced with plexiglass

Interior components should be tested/checked by licensed inspector prior to purchase

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415

13 APPLIANCES

The kitchen appliance portion of the inspection covers checkpoints involving the observation and operation of

the refrigerator, dishwasher, range, trash compactor, garbage disposal, ventilation equipment, microwave and any

other permanently installed appliances.



13.1. General Appliance Information



There are no general information points in this section.





13.2. Appliance Checkpoints



Checkpoints Rating * Comments/Operating Condition



Dishwasher M Turned on. Unable to run full cycle with no water

Disposal NA

Dryer MG

Microwave NA

Oven MG

Range Hood S

Range/Stove MG

Refrigerator MG

Washer MG

Other



* Ratings: S=Satisfactory U=Unsatisfactory M=Marginal MG=Missing NA=Not Applicable NV=Not Visible







13.3. Appliance Comments

Appliances were checked via generator

Range hood and dishwasher turned on during test

Appliances should be tested/checked by licensed inspector prior to purchase

Hooks Van Holm, Inc. Case # 011-532083

1021 Noble St. Ste 212

Anniston, AL 36201

256-241-1415



14 HOA INFORMATION: No Known HOA







15 CODE VIOLATIONS: None posted









16 PENDING LITIGATION: None posted









17 DEMO ORDERS: None posted









18 MOLD DISCLOSURE: Garage wall

5.3.8.5

See Mold Disclosure







19 ENVIRONMENTAL ISSUES: None posted



19.1. Environmental Compliance Record, Attachement 18 in Handbook 4310.5

19.2.


Related docs
Other docs by HC11121112939
True-False, Why
Views: 1  |  Downloads: 0
Chapter 5
Views: 0  |  Downloads: 0
GRIEP
Views: 0  |  Downloads: 0
Textbook Analysis
Views: 4  |  Downloads: 0
APPENDIX D
Views: 2  |  Downloads: 0
Natural vs. Man Made
Views: 0  |  Downloads: 0
PROBLEMATIQUE
Views: 3  |  Downloads: 0
Agenda
Views: 0  |  Downloads: 0
MATERIAL DATA SAFETY SHEET
Views: 0  |  Downloads: 0
City of Worcester
Views: 0  |  Downloads: 0
By registering with docstoc.com you agree to our
privacy policy

You are almost ready to download!

You are almost ready to download!