Low Voltage Automatic

Capacitor Banks









Automatic Power Factor

Correction For Low Voltage

Systems: 240VAC - 600VAC /

75KVAR - 1000kVAR



NEPSI

Northeast Power Systems, Inc. LV-ACB™ Product Literature

May, 1999

LV-ACB™ - Low Voltage Automatic

Capacitor Banks

Low Voltage Automatic Capacitor Banks for Improving

Power Factor, Reducing Transformer Loads and Power Specification

Factor Penalties

NEPSI’s low voltage automatic capacitor banks are designed to

NEPSI’s low voltage automatic capacitor banks are designed for endure the harsh electrical and environmental conditions that are

industrial and commercial power systems requiring a single point typically found in industrial process facilities.

source of power factor correction at the low voltage level.

Enclosure

Product Benefits NEPSI’s automatic capacitor banks are housed in NEMA 3R

enclosure and is suitably supported, constructed, and assembled

to meet the strength and rigidity necessary to meet the

• Automatically controlled power factor regulation. requirements given in ANSI/IEEE C37 and UL Standards. All

• System wide correction with a single piece of equipment. fastening hardware inside and out is stainless steel. To maximize

• Low installation cost. corrosion resistance, the outside of the enclosure is coated with

an ANSI 61 light gray enamel finish.

The front of the enclosure is equipped with a hinged door for

Product Features easy access. The doors are mounted on stainless steel hinges and

are held shut with 3-point latching handles. The handles are

stainless steel and are lockable.

• System is designed with Aerovox 3-terminal ICS capacitors

and are rated for conversion to a harmonic filter. Capacitor supports and enclosure base consists of welded C4

• Compact modular design with provisions for future structural steel channel. Four removable lifting eyes are

expansion in the field. provided.

• Programmable digital power factor controller with control

up to 15 steps.

• Standard reactive power ratings from 150 kvar to 1000 kvar Capacitors

at 480 and 600 volts (75 kvar to 300 kvar at 240 volts).

Higher ratings available upon request. The capacitor bank consists of UL Listed, low loss, three

• Indoor/Outdoor Design as standard bushing, industrial rated, metallized electrode, self-healing

• Automatic C/K Calibration capacitors with integral discharge resistors mounted in a single

• UL Listed as Industrial Control Panel (508A) steel tank. The capacitors are finished with a UL listed ANSI #61

• Multi-Ratio Split-Core Current Transformer Supplied as light-gray finish and meet or exceed the latest applicable ANSI

standard. and IEEE standards.

• Short lead times.

The capacitors have a proven 20-year (continuous duty) life

expectancy. The capacitor’s steel case is welded and

hermetically sealed with an internal pressure interrupter, virtually

Application eliminating the possibility of case rupture.



NEPSI’s low voltage automatic capacitor banks are designed for The capacitors are designed for harmonic filter bank duty and

low voltage systems requiring automatic power factor correction, can be utilized in a harmonic filter bank retrofit, if required.

reduced system capacity, and improved voltage regulation. The Discharge Resistors: Each capacitor cell incorporates internal

simple modular design allows for future expansion as plant loads discharge resistors designed to reduce the capacitor voltage to 50

increase. The capacitors and system topology is designed for volts or less within one minute after removal from the circuit.

direct conversion into harmonic filters, if the need should ever

arise. Installation and startup is simple and free of common Environmental Parameters: Capacitors are designed to operate

problems. between

-40°C and +46°C (-40°F to +115°F).









NEPSI

Northeast Power Systems, Inc. LV-ACB™ Product Literature Page 2

Contactors

Each step of the LV-ACB™ is switched with a NEMA rated 600

Protection

Volt contactor that is UL listed for capacitor switching. The

NEPSI’s capacitor banks are equipped with overload and short

contacts, coils, and auxiliary contacts can be changed without

circuit protection. Protection features are as follows:

disturbing other components within the bank.

Fusing: Each stage is protected from overloads (resulting from

Power Factor resonance) and faults by 600 volt 200,000 AIC (amps

Controller interrupting current), UL rated, bus mounted fuses. Fuses are

located on the line side of the capacitors and contactors.

The LV-ACB™ is controlled by a digital power controller with Blown Fuse Lights: Each fuse is equipped with a blown fuse

the following features: light that indicates a fuse operation. Lights are mounted on the

outside of the enclosure.

• Automatic self adjustment to any capacitor step value

• Digital indication of power factor, preset parameters and

specified installation data Warranty

• No-Volt release feature to immediately disconnect all

capacitors in the event of a power failure. • 12 system warranty

• Plug-in terminal connection

• Automatic elimination of defective capacitor steps, and their

indication (i.e. Welded contacts, failed capacitor, etc.)

• Visual display of target power factor alarm

• Visual display of harmonic overload alarm







Optional Accessories

Main Disconnecting Devices: (MC___) or (FD___) NEPSI’s Out of KVAR Alarm: (KA or KL) An out of kvar alarm can be

automatic capacitor banks may be equipped with either a main provide to give visual and/or audible indication of not having the

disconnect, main fusible disconnect, or a molded case circuit capability to meet the target power factor.

breaker that is externally operated through a rotary handle.

Ammeter: (A) A three-phase ammeter can be provided to show

the operating current of each filter bank stage.

On/Off/Auto Switches: (H) On/Off/Auto Switches may be

added to NEPSI’s standard automatic banks to provide complete Voltmeters: (V) A three-phase voltmeter can be provided to

individual control of each capacitor bank stage. show the system voltage.

Dust Proofing: (D) Can be provided where location require Keyed Interlock System: (KK) A keyed interlock system can be

filtering over louvers. provided that will prevent access into the capacitor bank until the

bank has been shut down by an upstream disconnecting device.

Cooling Fan: (CF) A cooling fan can be provided that increases

the cooling when installed in places where accessive heat may

cause problems. Not recommended if ambient temperature does

not exceed 90oF.





240 Volt Automatic Capacitor Bank

Selection Chart

BANK RATED SHIPPING

RATING STEP X MODEL CURRENT WEIGHT

(KVAR) KVAR NUMBER (AMPS) (POUNDS)



75 3 X 25 75LVA240F2B 181 800

100 4 X 25 100LVA240F2B 241 870

125 5 X 25 125LVA240F2B 301 940

150 6 X 25 150LVA240F2B 361 1005

200 8 X 25 200LVA240F2B 482 1140

250 10 X 25 250LVA240F2B 602 1275

300 6 X 50 300LVA240F2B 723 1410

Consult the factory or your sales representative for capacitor bank kvar ratings greater than

those or different than those shown in the table above.





NEPSI

Northeast Power Systems, Inc. LV-ACB™ Product Literature Page 3

480 & 600 Volt Automatic Capacitor Bank

Selection Chart

BANK RATED RATED SHIPPING

RATING STEP X 480 VOLT CURRENT 600 VOLT CURRENT WEIGHT

(KVAR) KVAR MODEL NUMBER (AMPS) MODEL NUMBER (AMPS) (POUNDS)



150 3 X 50 150LVA480F2B 181 150LVA600F2B 145 825

200 4 X 50 200LVA480F2B 241 200LVA600F2B 193 900

250 5 X 50 250LVA480F2B 301 250LVA600F2B 241 975

300 3 X 100 300LVA480F2B100 361 300LVA600F2B100 289 1050

300 6 X 50 300LVA480F2B 361 300LVA600F2B 289 1100

350 7 X 50 350LVA480F2B 421 350LVA600F2B 337 1125

400 4 X 100 400LVA480F2B100 482 400LVA480F2B100 385 1200

400 8 X 50 400LVA480F2B 482 400LVA600F2B 385 1250

450 9 X 50 450LVA480F2B 542 450LVA600F2B 433 1275

500 5 X 100 500LVA480F2B100 602 500LVA600F2B100 482 1350

500 10 X 50 500LVA480F2B 602 500LVA600F2B 482 1350

550 11 X 50 550LVA480F2B 662 550LVA600F2B 530 1425

600 6 X 100 600LVA480F2B100 723 600LVA600F2B100 578 1500

600 12 X 50 600LVA480F2B 723 600LVA600F2B 578 1550

650 13 X 50 650LVA480F2B 783 650LVA600F2B 626 1575

700 7 X 100 700LVA480F2B100 843 700LVA600F2B100 674 1650

700 14 X 50 700LVA480F2B 843 700LVA600F2B 674 1700

750 15 X 50 750LVA480F2B 903 750LVA600F2B 723 1725

800 8 X 100 800LVA480F2B100 963 800LVA600F2B100 771 1800

800 16 X 50 800LVA480F2B 963 800LVA600F2B 771 1835

850 17 X 50 850LVA480F2B 1020 850LVA600F2B 819 1855

900 9 X 100 900LVA480F2B100 1080 900LVA600F2B100 867 1875

900 18 X 50 900LVA480F2B 1080 900LVA600F2B 867 1910

950 19 X 50 950LVA480F2B 1140 950LVA600F2B 914 1950

1000 10 X 1000 1000LVA480F2B100 1200 1000LVA600F2B100 963 1975

Consult the factory or your sales representative for capacitor bank kvar ratings greater than those or different than those shown in

the table above.

FRONT SIDE









ENCLOSURE

DIMENSION: 90"H x 33"Wx33"D

FINISH: ANSI 61 GRAY

NEMA-1,3R CONSTRUCTION









NEPSI

Northeast Power Systems, Inc. LV-ACB™ Product Literature Page 4

Automatic Capacitor Bank Accessories

Accessory

DESCRIPTION Code



ADDITIONAL CURRENT TRANSFORMER CT

MOLDED CASE/INSULATED CASE

CIRCUIT BREAKERS

250 AMP MC250

400 AMP MC400

600 AMP MC600

800 AMP MC800

1000 AMP MC1000

1200 AMP MC1200

1600 AMP MC1600

2000 AMP MC2000

FUSED DISCONNECT SWITCH

200 AMP FD200

400 AMP FD400

600 AMP FD600

800 AMP FD800

ON/OFF/AUTO SWITCHES H

OUT OF KVAR LIGHT KL

OUT OF KVAR ALARM KA

AMMETER A

VOLTMETER V

DUST PROOFING D

COOLING FAN CF

HF REACTOR RETROFIT (ADD 6” TO RR

WIDTH DIMENSION)

KEY INTERLOCK KK



Three-line diagram of typical low voltage automatic capacitor bank. Capacitors, transient inrush reactors, control power transformer,

contactors, 3 phase fusing, current transformer placement and incoming breaker are shown.









Northeast Power Systems, Inc.

66 Carey Road

Queensbury, New York 12804



Phone: 518-792-4776

Fax: 518-792-5767



Email: sales@nepsi.com

Webpage: www.nepsi.com









NEPSI

Northeast Power Systems, Inc. LV-ACB™ Product Literature Page 5

NEPSI

Northeast Power Systems, Inc. LV-ACB™ Product Literature Page 6



Related docs
Other docs by dandanhuanghua...
Human2
Views: 0  |  Downloads: 0
COH Application
Views: 0  |  Downloads: 0
1 INTRODUCTION
Views: 0  |  Downloads: 0
labour_supply
Views: 1  |  Downloads: 0
Chpt15HW
Views: 0  |  Downloads: 0
membership-fees-2008
Views: 0  |  Downloads: 0
Treatnet ASI Workshop 3 Slides 010107
Views: 0  |  Downloads: 0
By registering with docstoc.com you agree to our
privacy policy

You are almost ready to download!

You are almost ready to download!