									                       SECTION 08 44 13 GLAZED ALUMINUM CURTAIN WALL

                 Series 5600 2-Sided or 4-Sided Structural Glazed Curtain Wall System

PART 1 GENERAL

1.01    Work Included

   A. Furnish and install architectural aluminum curtain wall complete with related components as
      shown on drawings and specified in this section.
                                            ®
   B. Curtain Wall System shall be EFCO Series 5600 2-Sided or 4-Sided Structural Glazed. Other
      manufacturers requesting approval to bid their product as an equal must submit the following
      information fifteen days prior to close of bidding.
      1. A proposal drawing showing full size details of all curtain wall components including all
           anchors and building attachments.
      2. Test reports documenting compliance with requirements of Section 1.05.
   C. Glass
      1. Reference Section 08 81 00 for Glass and Glazing.
   D. Single Source Requirement
      1. All products listed in Section 1.02 shall be by the same manufacturer.

List work and materials related to this section but specified in other sections. EFCO recommends
that one manufacturer furnish all applicable Division 8 products to ensure consistent product
quality and compatibility.

1.02    Related Work

   A.   Section 08 32 13 – Sliding Aluminum – Framed Glass Doors
   B.   Section 08 41 13 – Aluminum – Framed Entrances and Storefronts
   C.   Section 08 44 33 – Sloped Glazing Assemblies
   D.   Section 08 51 13 – Aluminum Windows
   E.   Section 10 71 13 – Exterior Sun Control Devices

1.03    Items Furnished but Not Installed

1.04    Items Installed but Not Furnished

1.05    Laboratory Testing and Performance Requirements

   A. Test Units
      1. Air, water, and structural test unit size shall be a minimum of two (2) stories high and three (3)
         lites wide.
      2. Thermal test unit sizes shall be 80" (2032 mm) wide x 80" (2032 mm) high with one (1)
         intermediate vertical mullion and two (2) lites of glass.
   B. Test Procedures and Performance
      1. Air Infiltration Test
         a. Test unit in accordance with ASTM E 283 at a static air pressure difference of 6.24 psf
              (300 Pa).
         b. Air infiltration shall not exceed .06 cfm/FSF (.31 l/s•m²) of unit.
      2. Water Resistance Test
         a. Test unit in accordance with ASTM E 331.
         b. The test for static water penetration (ASTM E 331) shall be conducted at an air pressure
              difference of 15.0 psf (720 Pa). There shall be no water leakage as defined by AAMA
              501.1, paragraph 5.5.
     The specification must establish a minimum air pressure difference at which no water
     leakage will occur. AAMA recommends an air pressure difference equal to 20% of the
     positive design wind pressure with a minimum of 6.24 psf (300 Pa) and a maximum of
     15.0 psf (720 Pa).

 3. Uniform Load Deflection Test
    a. Test in accordance with ASTM E 330.
    b. Deflection under design load shall not exceed L/175 for spans less than 162" (4114 mm).
    c. Deflection under design load shall not exceed L/240 +1/4” (6 mm) for spans greater than
        162" (4114 mm).
 4. Uniform Load Structural Test
    a. Test in accordance with ASTM E 330 at a pressure 1.5 times the design wind pressure in
        1.05.4.B.3.b.
    b. At conclusion of the test there shall be no glass breakage, permanent damage to
        fasteners, curtain wall parts, or any other damage that would cause the curtain wall to be
        defective.
 5. Dynamic Water Resistance Test
    a. Test unit in accordance with AAMA 501.
    b. There shall be no water leakage at a dynamic test pressure of 15.0 psf (720 Pa).
 6. Condensation Resistance Test (CRF)
    a. Test unit in accordance with AAMA 1503.1.
    b. Condensation Resistance Factor (CRF) shall not be less than 67 (frame) and 65 (glass)
        when glazed with 1" (25 mm) insulated – 1/4" (6 mm) clear low emissivity, 1/2" (12 mm)
        air, 1/4" (6 mm) clear glass.
 7. Thermal Transmittance Test (Conductive U-Value)
    a. Test in accordance with AAMA 1503.1.
    b. Conductive thermal transmittance (U-Value) shall not be more than 0.53 BTU/hr•ft²•ºF
        (3.00 W/m²•K) when glazed with 1" (25 mm) insulated – 1/4" (6 mm) clear low emissivity,
        1/2" (12 mm) air, 1/4" (6 mm) clear glass.
 8. Thermal Transmittance Test (Conductive U-Value)
    a. Test in accordance with NFRC-102.
    c. Conductive thermal transmittance (U-Value) shall not be more than 0.49 BTU/hr•ft²•ºF
        (2.66 W/m²•K) when glazed with 1" (25 mm) insulated – 1/4" (6 mm) clear low emissivity,
        1/2" (12 mm) air, 1/4" (6 mm) clear glass.


                  Glass Types                         Center of Glass                   EFCO
                                                                                      S-5600 CW
                                                    U-Value        SHGC                U-Value
 1” IG: ¼” CLEAR ANNEALED                             0.47         0.70           0.64 BTU/hr•ft²•ºF
        ½” AIR SPACE                                                                (3.63 W/m²•K)
        ¼” CLEAR ANNEALED
 1” IG: ¼” BRONZE ANNEALED                            0.47         0.50           0.64 BTU/hr•ft²•ºF
        ½” AIR SPACE                                                                (3.63 W/m²•K)
        ¼” CLEAR ANNEALED
 1” IG: ¼” GRAY ANNEALED                              0.47         0.47           0.64 BTU/hr•ft²•ºF
        ½” AIR SPACE                                                                (3.63 W/m²•K)
        ¼” CLEAR ANNEALED
 1” IG: ¼” CLEAR ANNEALED LOW EMISSIVITY              0.29         0.38           0.49 BTU/hr•ft²•ºF
        ½” AIR SPACE                                                                (2.78 W/m²•K)
        ¼” CLEAR ANNEALED
 1” IG: ¼” CLEAR ANNEALED LOW EMISSIVITY              0.24         0.37           0.45 BTU/hr•ft²•ºF
        ½” ARGON                                                                    (2.55 W/m²•K)
        ¼” CLEAR ANNEALED
 1” IG: ¼” CLEAR ANNEALED                             0.21         0.48           0.43 BTU/hr•ft²•ºF
        ½” TC88 HEAT MIRROR & ARGON                                                 (2.44 W/m²•K)
        ¼” CLEAR ANNEALED

*U-Values are based on a nominal size of 80" (2032 mm) x 80" (2032 mm) with two lights of glass using AAMA 507-03
 and NFRC-102.
      9. Seismic Performance
          a. Test unit in accordance to AAMA 501.4 system to meet design displacement of 0.010 x
              the greater adjacent story height and ultimate displacement of 1.5 x the design
              displacement.
      10. Sound Transmission Loss
          a. Test unit in accordance with ASTM E 90-02.
          b. Sound Transmission Class (STC) shall not be less than 29.
   C. Project Wind Loads

            Architect to specify design wind pressure, both positive and negative required by the
            governing building code, as calculated from ASCE 7, or as determined by boundary
            layer wind tunnel testing. Use 20.0 psf (960 Pa) as a minimum. Stress on structural
            silicone should not exceed 20.0 psi.

       1.   The system shall be designed to withstand the following loads normal to the plane of the
            wall:
            a. Positive pressure of     psf (    Pa) at non-corner zones.
            b. Negative pressure of     psf (    Pa) at non-corner zones.
            c. Negative pressure of     psf (    Pa) at corner zones.

Note to specifier: select either paragraph “D” or “E” based on applicability to project.

   D. Anti-Terrorism Force Protection Requirements – DoD Unified Facilities Criteria
      1. Design to meet the requirements of UFC 4-010-01 DoD MINIMUM ANTITERRORISM
          STANDARDS FOR BUILDINGS, 8 October 2003, including change 1, 22 January 2007.
      1. Design of framing and connections shall be based on the following design criteria:
          a. Standoff Distance of ( ) ft
          b. Applicable Explosive Weight of: [Type I], [Type II] (Select one)
          c. Level of Protection of: [Low], [Very Low] (Select one)
      2. Window manufacturer shall provide, with their bid/quote, a “Blast Narrative” describing which
          design method of the UFC 4-010-01 was utilized to show product compliance to the
          performance specification in F.2.a., b. and c. above.
   E. Anti-Terrorism Force Protection Requirements – GSA-ISC Design Criteria
      1. Design of framing and connections shall be based on inelastic dynamic analysis utilizing the
          following design criteria:
          a. Peak reflective pressure ( ) psi at an impulse of ( ) psi-msec.
      2. GSA glass performance level (based on Wingard 5.5.1) shall be [1], [2], [3a], [3b], [4], [5]
          (Select one)
      3. End rotations of framing members supporting laminated glass shall not exceed ( ) degrees.
      4. Ductility of framing members supporting laminated glass shall not exceed ( ).
      5. Maximum deflection of framing members supporting laminated glass shall not exceed L/ ( ).
      6. Window manufacturer shall provide, with their bid/quote, a sample calculation using non-
          linear dynamic analysis methods demonstrating product compliance to the performance
          specifications for a typical member for the project.
      7. Window manufacturer shall provide, with their bid/quote, a “Blast Narrative” to accompany the
          dynamic calculations in section G.6. “Blast Narrative” shall define design methods and
          philosophy used by the manufacturer to show product compliance to the performance
          specifications in Section G above.

1.06   Field Testing and Performance Requirements

Optional at discretion of specifier.

   A. Test Units
      1. Air, water, and structural test unit size shall be a representative sample of typical construction
         and shall have no outstanding punch list or other visible defects. If no test area and/or location
         have been identified, the persons doing the test shall select an area. This area shall be
                                                                                               2
           selected to provide representative performance data, usually a minimum of 100 ft . The area
           to be tested shall include perimeter caulking, typical splices, frame intersections, and, if
           applicable, at least 2 entire vision lites and 2 entire spandrel lites containing an intermediate
           horizontal member. All operable components within the test area shall be isolated and exempt
           from the test procedure.

           Architect should insert an exact description of the area(s) to be field tested. Failure to
           do so can dramatically affect the cost of testing. The recommended procedure for
           identification of the test area is to reference an architectural elevation/plan drawing
           that clearly shows the intent of the area to be field tested.

   B. Test Procedures and Performance
      1. Air Infiltration Test
         a. Test unit in accordance with AAMA 503-03 for field testing. The unit test shall be
              conducted at a minimum uniform static test pressure differential of at least 1.57 psf
              (75 Pa), but at a pressure differential not to exceed 6.24 psf (300 Pa).
         b. The maximum allowable rates of air leakage for field testing shall not exceed 1.5 times
              the project specification rate or .09 cfm/SF (.45 l/s•m²), whichever is greater.

           The specifier may require project specific air leakage; however, this must be stipulated
           in Section 1.06.B.1 of this specification.

       2. Water Resistance Test
          a. Test unit in accordance with AAMA 503-03.
          b. The field water penetration resistance tests shall be conducted at a static test pressure of
             two-thirds of the specified project water penetration test pressure, but not less than
             6.24 psf (300 Pa).

           The specifier may increase the field water test pressure to the value specified for the
           project; however, this must be stipulated in Section 1.06.B.2 of this specification. In the
           event that the project does not have a specified water penetration test pressure, the
           value will be equal to 20% of the positive design wind load times 0.67.

1.07   Quality Assurance

   A. Provide test reports from AAMA accredited laboratories certifying the performance as specified in
      1.05.
   B. Test reports shall be accompanied by the curtain wall manufacturer’s letter of certification stating
      that the tested curtain wall meets or exceeds the referenced criteria for the appropriate curtain
      wall type.

1.08   References

1.09   Submittals

   Insert quantity of shop drawings required.

   A. Contractor shall submit ( ) copies of all shop drawings to the architect for his approval.
      Drawings shall show scale elevations and sections. Full size sections shall be shown only when
      needed for clarity. Drawings shall show construction of all parts of the work, including metal and
      glass thickness, methods of joining, details of all field connections and anchorage, fastening and
      sealing methods, metal finishes, and all pertinent information. Relationship to other work should
      be clearly indicated. No work shall be fabricated until shop drawings for that work have been
      finally approved for fabrication.
   B. Contractor shall submit finish samples, test reports, and warranties.
      1. Samples of materials as may be requested without cost to owner, i.e., metal, glass, fasteners,
           anchors, frame sections, mullion section, corner section, etc.
1.10   Warranties

   A. Total Curtain Wall System
      1. The responsible contractor shall assume full responsibility and warrant for one year the
          satisfactory performance of the total curtain wall installation. This includes the glass (including
          insulated units), glazing, anchorage and setting system, sealing, flashing, etc. as it relates to
          air, water, and structural adequacy and the specifications and approved shop drawings.
      2. Any deficiencies due to such elements not meeting the specifications shall be corrected by
          the responsible contractor at their expense during the warranty period.
   B. Material and Workmanship
      1. Per AAMA standard 601, provide written guarantee against defects in material and
          workmanship.

      Optional: include Anodic finish in material and workmanship warranty.
      2. Warranty period shall be for 3 years from the date of final shipment.
   C. Glass
      1. Provide written warranty for insulated glass units, that they will be free from obstruction of
         vision as a result of dust or film formation on the internal glass surfaces caused by failure of
         the hermetic seal due to defects in material and workmanship.
      2. Warranty period shall be for 10 (ten) years.
   D. Organic finish
      1. Provide organic finish and warranty based on AAMA standard 2603.

           OR

       1. Provide organic finish and warranty based on AAMA standard 2604.

           OR

       1. Provide organic finish and warranty based on AAMA standard 2605

PART 2 PRODUCTS

2.01   Materials

   A. Aluminum
      1. Extruded aluminum shall be 6063-T6 alloy and temper.
   B. Glass
      1. Insulated glass shall be 1" (25 mm) consisting of ( ) exterior, (        ) air spacer, and
          ( ) interior.

                OR

      1. Glass shall be 1/4" (6 mm) monolithic.
   C. Dissimilar Metals
      1. All dissimilar metals must be properly insulated to prevent galvanic action.
   D. Fasteners
      1. All exposed fasteners shall be aluminum, stainless steel, or zinc plated steel.
   E. Anchors
      1. Perimeter and floor line anchors shall be aluminum or steel. All steel anchors shall be properly
          insulated from the aluminum.
   F. Thermal Barrier
      1. The thermal barrier shall be extruded PVC used as an applied thermal isolator.

      Optional at discretion of specifier.
   G. Sustainable Design
      1. The materials specified in this section are intended to have applicable credits toward LEED®
         certification. Provide documentation in accordance with USGBC’s LEED for New Construction
           and Major Renovation (insert one) version 2.2 or version 3 (2009), verifying that the
           components, processes or assemblies specified herein conform to the following
           requirements.
   Select the credits required for the specified level of certification being sought. Modify the
   criterion as needed to coincide with other LEED® standards.
           a) EA Credit 1: Optimize Energy Performance
                   i. Provide area weighted overall U-Factor in accordance with section 1.05
                   ii. Provide area weighted center of glass or overall SHGC in accordance with
                        section 1.05
           b) EA Credit 2: On site renewable energy
                   i. Provide coordination for glazing of photovoltaic panels or other energy generating
                        glazing.
           c) MR Credit 1.1 and 1.2: Building Reuse
                   i. Provide windows and accessories which allow easy retrofit and minimal
                        demolition into existing building conditions.
           d) MR Credit 4.1 and 4.2: Recycled Content.
                   i. Provide aluminum framing with overall recycled content values of minimum 60%.
                        All secondary aluminum must comply with alloy and temper requirements outlined
                        in section 2.01. A.1.
                   ii. Overall recycled content must contain the following levels of post and pre
                        consumer recycled content.
                        a) Post consumer content no less than 5%
                        b) Pre consumer content no less than 50%
                   iii. Submit documentation outlining recycled content percentages (post and pre
                        consumer content separately) and the weight of aluminum in proportion to the
                        overall assembly weight.

   NOTE: Glass components are a large portion of total assembly weight and do not contribute to
   the recycled content value.
           e) MR Credit MR 5.1 and 5.2: Regional Materials (only for projects located within 500 miles
              of Monett Missouri)
                  i. Provide assemblies that are manufactured as well as use materials that are
                  harvested, recovered or extracted from within 500 miles of the job site.
           f) EQ Credit 2: Increased ventilation
                  i. Provide operable vents with occupant-enabled hardware.
                  ii. Provide operable vent quantity and sizes as shown on project drawings.
           g) EQ Credit 4.1 and 4.2: Low-Emitting Materials (adhesives, sealants / paints and coatings)
                  i. Verify that the as shipped product does not require any on site application of
                      adhesives, sealants, paints or coatings other than perimeter or installation
                      sealants.
                  ii. All interior “on site” applied primers, structural glazing adhesives, metal to metal
                      sealants and cosmetic seals must meet applicable South Coast Air Quality
                      Management District (SCAQMD) Rule #1168 VOC limits.
           h) EQ Credit 6.1: Controllability of Systems - Lighting
                  i. Provide windows with internal occupant controlled blinds.
           i) EQ Credit 6.2: Controllability of Systems - Thermal Comfort
                  i. Provide operable vents with occupant-enabled hardware.
                  ii. Provide operable vent quantity and sizes as shown on project drawings.
           j) EQ Credit 8.1 and 8.2: Daylight and Views
                  i. Provide Glass with visual light transmittance (VT) as outlined in section 2.01 E.
                  ii. Provide operable vent quantity and sizes as shown on project drawings.

2.02   Fabrication

   A. General
      1. All aluminum vertical and horizontal main frame extrusions shall have a minimum wall
          thickness of .093" (2.3 mm) to .125" (3 mm).
   B. Frame
      1. Frame components shall be mechanically fastened by means of extruded aluminum shear
          blocks attached to vertical mullions.
      2. Curtain wall system is able to accommodate separate interior and exterior finishes and colors.
   C. Glazing
      1. The 2-sided structural glazed curtain wall shall include a dense silicone spacer and silicone
          sealant at the structural joint, and can be captured horizontally by means of an exterior
          aluminum pressure plate and cover.
      2. The horizontals are dry glazed using an interior and exterior dense EPDM preset gasket.
   D. Finish

       See separate finish specification for more details.

       1. Anodic
          a. Finish all exposed areas of aluminum curtain wall and components with electrolytically
             deposited color in accordance with Aluminum Association Designation AA-( ). Exterior
             color shall be ( ) and interior color shall be ( ).

        Available colors are clear, champagne, light bronze, medium bronze, dark bronze, and
        black.

               AA Description            Description          Arch. Class     AAMA Guide Spec.
              AA-M10-C22-A41            Clear Anodized             I              611-98
              AA-M10-C22-A44            Color Anodized             I              611-98

               OR

       1. Organic
          a. Finish all exposed areas of aluminum curtain wall and components with (          ). Exterior
             color shall be ( ) and interior color shall be ( ).
                                                                    ™
           High performance 70% PVDF fluoropolymer Ultrapon and 50% PVDF fluoropolymer
                    ™
           Ultraflur finishes are available in standard colors. Reference the EFCO color
           brochure for assistance in color and resin selection. Custom colors are available upon
           request.

               AA Description                   Description                   AAMA Guide Spec.
                                                                ™
              AA-M12-C42-R1X                 70% PVDF Ultrapon                    2605-98
                                                                ™
              AA-M12-C42-R1X                 50% PVDF Ultraflur                   2604-98

PART 3 EXECUTION

3.01   Inspection

   A. Job Conditions
      1. All openings shall be prepared by others to the proper size and shall be plumb, level, and in
          the proper location and alignment as shown on the architect's drawings.

       Optional at discretion of specifier

       2. Provide for manufacturer representation to conduct pre-installation site meeting.
3.02        Installation

    A. Use only skilled tradesmen with work done in accordance with approved shop drawings and
       established specifications, and erect all curtain wall components to all building bench marks and
       column center lines.
    B. Plumb and align curtain wall faces in a single plane for each wall plane, and erect curtain wall
       materials square and true. Adequately anchor to maintain positions permanently when subjected
       to normal thermal movement, building movement, and specified wind loads.
    C. Adjust windows in curtain wall for proper operation after installation.
    D. Furnish and apply sealants to provide a weather tight installation at all joints and intersections and
       at opening perimeters. Wipe off excess material, leave all exposed surfaces and joints clean and
       smooth.

3.03        Anchorage

    A. Adequately anchor to maintain positions permanently when subjected to normal thermal
       movement, specified building movement, and specified wind loads.

3.04        Protection and Cleaning

    A. The general contractor shall protect the aluminum materials and finish against damage from
       construction activities and harmful substances. The general contractor shall remove any
       protective coatings as directed by the architect and shall clean the aluminum surfaces as
       recommended for the type of finish applied.