EURODIN CATALOGUE                SEPTEMBER 2005    1
                            Problem n°1: untimely trip

   This is a trip of a switch that
   happens without the fault presence:
   it is very felt by the users

 EXTERNAL CAUSES
  Storms
  Manoeuvre on the electric system
   from the electric distributor
  Manoeuvre on the electric load in a
   nearby factory

 INTERNAL CAUSES
  Noises induced by electronic
   devices


EURODIN CATALOGUE                   SEPTEMBER 2005       2
                          Consequence



      Economical damages for perishable
       goods
      Loss of important service
      Lack of safety




EURODIN CATALOGUE        SEPTEMBER 2005    3
                                  Restart

  Automatic reset for 90 Range circuit breakers

                     Function: in case of untimely trip of the
                      circuit breaker close it automatically


                     Gewiss patent


                     Winner of Intel design 2003 prize




EURODIN CATALOGUE                     SEPTEMBER 2005              4
                                 Restart

  Automatic reset for 90 Range circuit breakers


                     For SD – MTC – MT – MDC max 2
                    poles supplied 230V phase - neutral


                     2 modules DIN device
                    Suitable for the installation in small
                    spaces




EURODIN CATALOGUE                    SEPTEMBER 2005          5
                                Restart

  Automatic reset for 90 Range circuit breakers

                        Two versions




  ReStart RD                      ReStart RM
  Automatic reset for             Automatic reset for

  RCD type SD                     RCD type MDC

                                  MCB type MTC and MT
EURODIN CATALOGUE                  SEPTEMBER 2005       6
                            Restart RD


  Automatic reset for 90 Range circuit breakers

 ReStart RD
 Automatic reset for SD
 Three dedicated codes already
 wired with SD type A 30mA
 Rated current 25A        GW 90961
 Rated current 40A        GW 90962
 Rated current 63A        GW 90963

EURODIN CATALOGUE              SEPTEMBER 2005     7
                                 Restart RD

                                                          SD         +
All the other versions of SD + RD are available
                                                         code      letter
with this simple codes:
                                                       GW 90 XXX     R




 EURODIN CATALOGUE                    SEPTEMBER 2005                 8
                             Restart RD

ReStart RD
Automatic reset for
RCCBs SD

                      Top safety

                       Preventive control of earth leakage
                       before closure and stop in case of fault
                       Segnalling of reset in progress




EURODIN CATALOGUE                 SEPTEMBER 2005              9
                        Restart RD

                      Supply


                    Sliding door
                    activation /
                    deactivation




                     Cables for
                    installation
                                              Signalling led
                      control
EURODIN CATALOGUE            SEPTEMBER 2005             10
                             Restart RD

                    RESTART OPERATING MODE




              Automatic                    Manual
                  mode                     mode




               WITH RCCB TRIPPED AUTOMATIC
               FEATURES CAN’T BE ACTIVATED


EURODIN CATALOGUE               SEPTEMBER 2005      11
                                  Restart RD

                    RESTART OPERATING MODE
                        Regular working
                        Electrical system supplied
                        Led off

                        Preventive control of earth leakage after the tripping
                        Electrical system not supplied
                        Led is flashing

                        Restart stops because of a fault
                        Only manual reset
                        Led is red


EURODIN CATALOGUE                         SEPTEMBER 2005                    12
                      Restart RM


Automatic reset for 90 Range circuit breakers

ReStart RM
Automatic reset for MTC and MT type
MCCB and for MDC type RCBO

Four dedicated codes already wired
with MDC type A 30mA
Rated current 10A     4,5 – 6 kA
Rated current 16A     4,5 – 6 kA

EURODIN CATALOGUE             SEPTEMBER 2005    13
                           Restart RM

                                                   MDC         +
All the other versions of MDC + RM are available   code      letter
with this simple codes:
                                                 GW 94 XXX     R




 EURODIN CATALOGUE                 SEPTEMBER 2005             14
                        Restart RM

                    Top safety
                     Preventive control of earth leakages
                      and stop in case of fault

                     Preventive control of short circuits
                      and stop in case of fault

                     Segnalling of reset in progress




EURODIN CATALOGUE                SEPTEMBER 2005              15
                         Problem n°2: reliability of device


  The RCD is a device extremely delicate. It uses a little differential
   current to produce a mechanical force for the trip of the switch
  It is very easy to compromise the proper running
  Some causes of improper working order:
      Dust
      Humidity degree
      Aggressive atmosphere
      Sudden variation of room temperature
      Vibration
      Presence of electromagnetic field

     For this reason the residual current devices are provided
     with a button to make a periodic test

EURODIN CATALOGUE                      SEPTEMBER 2005                16
                          Test of residual current device


   What is the function of test button?

   To chek the good mechanical and
   electrical working of residual current
   device

   The test button is necessary to
   maintain the efficiency and reliability
   of the residual current device in time




EURODIN CATALOGUE                       SEPTEMBER 2005      17
                            Reliability of residual current

            Also a IEC document shows how the periodic use
               of the test button increases the reliability of
                         residual current devices
                                             Source: document SC23E IEC


    Without periodic test




    With periodic test




EURODIN CATALOGUE                      SEPTEMBER 2005               18
                            Restart with Autotest

   Automatic resetting device with self testing RCD
                ReStart with Autotest

ReStart RD Autotest
RCD with automatic reset
and periodic self testing


One piece versions
(already complete with 25A e 40A
type A residual current circuit breaker)




EURODIN CATALOGUE                      SEPTEMBER 2005   19
                             Restart with Autotest

                    GW 90901 (25 A) - GW 90902 (40 A)

                          Size: 5 modules
                          Functions:
                               like Restart RD automatic resetting
                                only after insulation to earth check
                               weekly self test without
                                interruption of power supply
                               residual current protection always
                                active


EURODIN CATALOGUE                        SEPTEMBER 2005           20
                    Restart with Autotest

Signallings
                                Left Led
                                   System test in progress

                                    System fault

                                    Device anomaly

                               Synchronization button

                               Right Led
                                   System powered
                                   System not powered

                               Auxiliary contact for
                               remote signalling
EURODIN CATALOGUE           SEPTEMBER 2005                   21
                                     Applications of Restart




      HOME - BLOCKS OF FLATS                                    FRIDGE
    (stair lights, entry phones, gate automation)




EURODIN CATALOGUE                                   SEPTEMBER 2005       22
                    Applications of Restart




         AQUARIUM                AUTOMATIC SPRINKLER
                                       (for garden irrigation)




EURODIN CATALOGUE            SEPTEMBER 2005                      23
                     Applications of Restart


                    ALARM
                    (antitheft)




                     FAX




                     PERSONAL
                     COMPUTER



EURODIN CATALOGUE                 SEPTEMBER 2005   24
                    ReStart 4P




                ReStart 4P Range
EURODIN CATALOGUE         SEPTEMBER 2005   25
                        ReStart 4P

 RD - Add-on Restart                 Restart with
 for RCCBs 4P                        Autotest 4P




                    +


EURODIN CATALOGUE             SEPTEMBER 2005        26
                    ReStart RD 4P
   Safe reclosure of the RCCB after an unwanted
    tripping
   Continuosly checking of the installation in
    case of earth leakage
   Compactness: 3 mod. only
   1 CO alarm switch integrated
   Fittable to RCCBs up to 100A




EURODIN CATALOGUE             SEPTEMBER 2005       27
                       ReStart RD 4P
  segédérintkező                                   betáplálás

Áram -
   védőkapcsoló

                                          Led-es visszajelzés:



 Csúsztatható előlap
 a Restart be- és
 kikapcsolásához
                                                Hálózat ellenőrző
                                                   kábel
 EURODIN CATALOGUE             SEPTEMBER 2005                       28
                           ReStart RD 4P


                           RCCB                      RD PRO 4P




                                                                 Auxiliaries



               4 modules     3 modules

    In: 25A ÷ 100A


EURODIN CATALOGUE                        SEPTEMBER 2005                    29
                 ReStart RD 4P
   How to wire ReStart?
           Power supply

                                       Supply cable




                    Load               Test cable
EURODIN CATALOGUE          SEPTEMBER 2005             30
               ReStart RD 4P
   How does Restart work? 2) Untimely tripping
                       R

                       S
                       T

                       N



             RC                 RESTART                                   RESTART
                                PRO 4P                                    PRO 4P




                           RG

                                 RE                                       RE

   1) Fault to earth
                                      RE: installation earth resistance

                                      RC: transfo earth resistance

                                      RG: fault resistance
EURODIN CATALOGUE                       SEPTEMBER 2005                              31
                     ReStart RD 4P
   Main Electrical features
   Distribution system:               TT-TN
   Nominal voltage Vn:               400 a.c.    [V]
   Nominal frequency:                  50       [Hz]
   Power dissipation:                  1,2      [W]
   Reclosing power:                    30       [W]




EURODIN CATALOGUE            SEPTEMBER 2005            32
                    ReStart RD 4P

  Main Mechanical features
   Mechanical operations
   (number of resets):               10000
   Maximum operation
   frequency:                        30      [man/h]
   Closing control:              AUTOMATIC
   Closing time:                     <10       [s]
   Protection degree:               IP20




EURODIN CATALOGUE           SEPTEMBER 2005           33
                      ReStart RD 4P
   Local and remote signals
Sliding cover to
activate/disconnect                               Auxiliary
Restart                                           contact




                                               Sliding window
                                               position
                                               Isolation control
                                               status

 EURODIN CATALOGUE            SEPTEMBER 2005                  34
                              ReStart RD 4P

   Led signals working status:

                                                      Measurement of the
                                                      insulating in progress
            0,5s    0,5s   0,5s   0,5s            t



                                                       Fault to earth
              5s            5s           5s       t    (stand-by condition)


                                                       Restart blocked
                                                  t



EURODIN CATALOGUE                             SEPTEMBER 2005                   35
                    ReStart RD 4P

   Auxiliary contact features
   Type:                         change - over
                                0,4(a.c.)/1,5(d.c.
   Maximum current:                     )           [A]
   Operating voltage:           230 a.c./ 30 d.c.   [V]
   Insulating voltage:                 600           [V]
   Maximum terminal capacity:          2,5      1CO[mm2]




EURODIN CATALOGUE               SEPTEMBER 2005         36
                       ReStart RD 4P

   Auxiliary contact behaviour
                                                     RCCB   Aux
   Switchover       in case of:
    Sliding cover opened,
       circuit breaker on (after 10s)

    Low insulation of the
       installation (stand-by condition)

    After 3 consecutive reset
       (block condition, red led)

EURODIN CATALOGUE                   SEPTEMBER 2005                37
                    ReStart Autotest 4P


 RCCB with monthly selftest
  function
 No black-out during the self test
  procedure
 Complete test of the RCCB
  (tripping relay and main contacts)
 Restart function included



EURODIN CATALOGUE              SEPTEMBER 2005   38
                    ReStart Autotest 4P


   Fast Autotest of RCCB (<3s)
   Alarm switch included
   In: 25-40-63 A
   IΔn: 30-300 mA
   Type A[IR] 3kA 8/20s
   Compactness: 7 mod.



EURODIN CATALOGUE              SEPTEMBER 2005   39
                      ReStart Autotest 4P

 Change over switch               MONOBLOC: no cables to wire !



                                                  Signalling LED

RCCB                                              Left LED:

                                                    RCCBs fault

                                                    working status


Sliding cover to                                  Right LED
activate/disconnect
Autotest                                              device ON


EURODIN CATALOGUE                SEPTEMBER 2005                    40
                    ReStart Autotest 4P

 Autotest without blackout:
     The bypass circuit is got by parallel contacts fixed on the
     same shaft of the main contacts
                                                   Line

                                  M


                               Electronic device
                                                          Change
                                                          over
                                                          contact

EURODIN CATALOGUE                     SEPTEMBER 2005                41
                    ReStart Autotest 4P

   Bypass contact

    Main circuit: ON
    Bypass circuit: OFF

           LINE


                            M


           LOAD
EURODIN CATALOGUE               SEPTEMBER 2005   42
                    ReStart Autotest 4P



    Main circuit: ON
    Bypass circuit: ON

           LINE


                            M


           LOAD
EURODIN CATALOGUE               SEPTEMBER 2005   43
                    ReStart Autotest 4P



    Main circuit: OFF
    Bypass circuit: ON

           LINE


                            M


           LOAD
EURODIN CATALOGUE               SEPTEMBER 2005   44
                    ReStart Autotest 4P



    Main circuit: ON
    Bypass circuit: ON

           LINE


                            M


           LOAD
EURODIN CATALOGUE               SEPTEMBER 2005   45
                    ReStart Autotest 4P



    Main circuit: ON
    Bypass circuit: OFF

           LINE


                            M


           LOAD
EURODIN CATALOGUE               SEPTEMBER 2005   46
                    ReStart Autotest 4P

   Electrical features
   Reference Standards:                EN 61008-1
   Distribution system:                  TT-TN
   Rated current In:                   25 - 40 - 63   [A]
   Nominal voltage Vn:                  400 a.c.      [V]
   Nominal differential tripping
   current:                              30 - 300     [mA]
   Type:                                  A[IR]
   Nominal frequency:                       50        [Hz]

EURODIN CATALOGUE                  SEPTEMBER 2005            47
                           ReStart Autotest 4P

   Power supply connection:              Only from top
                    From top


            OK
                                      NO




                                         From bottom




EURODIN CATALOGUE                     SEPTEMBER 2005     48
                    ReStart Autotest 4P
  Local and remote signals
                          Auxiliary
                          contact




                          Manual
                          Autotest
                          button
                          Sliding window
                          position
                          Isolation control and Autotest
                          status

EURODIN CATALOGUE                SEPTEMBER 2005            49
                    ReStart Autotest 4P

   Auxiliary contact features
   Type:                        change - over
   Maximum current:           0,4(a.c.)/1,5 (d.c.)     [A]
   Operating voltage:          230 a.c./ 30 d.c.       [V]
   Insulating voltage:               600               [V]
   Maximum terminal
   capacity:                            2,5     1CO   [mm2]




EURODIN CATALOGUE              SEPTEMBER 2005                50
                    ReStart Autotest 4P

                                         Bypass      RCCB   Aux
   Switchover in case of:
    Sliding cover opened,
       circuit breaker on (after 10s)

    Low insulation of the
       installation (standby)

    Malfunctioning (yellow led)

    After 3 consecutive reset
       (block condition, red led)
EURODIN CATALOGUE                   SEPTEMBER 2005                51
               ReStart 4P & Autotest 4P

                              ReStart 4P      Autotest 4P




               Insulation           10kΩ (30mA)
                  control           2kΩ (300mA)
              Continuous
                  control                         
            Automatic self-
                    test                           
                Auxiliary
EURODIN CATALOGUE               0,4A
                                  SEPTEMBER 2005   0,4A     52
                  contact
                    ReStart 4P & Autotest 4P

  2 international patents
  concerning:
   Reset mechanism (ReStart)
   Bypass mechanism (Autotest)




EURODIN CATALOGUE                SEPTEMBER 2005   53
                    ReStart 4P & Autotest 4P

  Rohs compliant
  Free of:
   Lead
   Mercury
   Cadmium
   Hexavalent Chromium
   PBB
   PBDE



EURODIN CATALOGUE                SEPTEMBER 2005   54
                          ReStart 4P & Autotest 4P

   Applications


                                                                      Nurseries,
Refineries,                                                           schools,
petrochemical Industry,                                               universities,
paper mills                                                           officies




                                                Harbours and docks,
                                                camp sites,
                                                holiday village
 Swimming pools

EURODIN CATALOGUE                      SEPTEMBER 2005                           55
                    Köszönjük!




EURODIN CATALOGUE        SEPTEMBER 2005   56

						
Related docs
Other docs by 22zklI
CALIBRATION
Views: 38  |  Downloads: 1
Calendar - Download as Excel
Views: 2  |  Downloads: 0
One Day Campaign
Views: 0  |  Downloads: 0
University of Arkansas - Download Now DOC
Views: 7  |  Downloads: 0
COMISS�O
Views: 16  |  Downloads: 0
Planning Committee 10th June 2002
Views: 4  |  Downloads: 0
Marblehead P.S. BSEA # 07-4615
Views: 14  |  Downloads: 0
English-Persian SMT
Views: 18  |  Downloads: 0
struggling reader vocab fac Guide
Views: 1  |  Downloads: 0