EURODIN CATALOGUE SEPTEMBER 2005 1
Problem n°1: untimely trip
This is a trip of a switch that
happens without the fault presence:
it is very felt by the users
EXTERNAL CAUSES
Storms
Manoeuvre on the electric system
from the electric distributor
Manoeuvre on the electric load in a
nearby factory
INTERNAL CAUSES
Noises induced by electronic
devices
EURODIN CATALOGUE SEPTEMBER 2005 2
Consequence
Economical damages for perishable
goods
Loss of important service
Lack of safety
EURODIN CATALOGUE SEPTEMBER 2005 3
Restart
Automatic reset for 90 Range circuit breakers
Function: in case of untimely trip of the
circuit breaker close it automatically
Gewiss patent
Winner of Intel design 2003 prize
EURODIN CATALOGUE SEPTEMBER 2005 4
Restart
Automatic reset for 90 Range circuit breakers
For SD – MTC – MT – MDC max 2
poles supplied 230V phase - neutral
2 modules DIN device
Suitable for the installation in small
spaces
EURODIN CATALOGUE SEPTEMBER 2005 5
Restart
Automatic reset for 90 Range circuit breakers
Two versions
ReStart RD ReStart RM
Automatic reset for Automatic reset for
RCD type SD RCD type MDC
MCB type MTC and MT
EURODIN CATALOGUE SEPTEMBER 2005 6
Restart RD
Automatic reset for 90 Range circuit breakers
ReStart RD
Automatic reset for SD
Three dedicated codes already
wired with SD type A 30mA
Rated current 25A GW 90961
Rated current 40A GW 90962
Rated current 63A GW 90963
EURODIN CATALOGUE SEPTEMBER 2005 7
Restart RD
SD +
All the other versions of SD + RD are available
code letter
with this simple codes:
GW 90 XXX R
EURODIN CATALOGUE SEPTEMBER 2005 8
Restart RD
ReStart RD
Automatic reset for
RCCBs SD
Top safety
Preventive control of earth leakage
before closure and stop in case of fault
Segnalling of reset in progress
EURODIN CATALOGUE SEPTEMBER 2005 9
Restart RD
Supply
Sliding door
activation /
deactivation
Cables for
installation
Signalling led
control
EURODIN CATALOGUE SEPTEMBER 2005 10
Restart RD
RESTART OPERATING MODE
Automatic Manual
mode mode
WITH RCCB TRIPPED AUTOMATIC
FEATURES CAN’T BE ACTIVATED
EURODIN CATALOGUE SEPTEMBER 2005 11
Restart RD
RESTART OPERATING MODE
Regular working
Electrical system supplied
Led off
Preventive control of earth leakage after the tripping
Electrical system not supplied
Led is flashing
Restart stops because of a fault
Only manual reset
Led is red
EURODIN CATALOGUE SEPTEMBER 2005 12
Restart RM
Automatic reset for 90 Range circuit breakers
ReStart RM
Automatic reset for MTC and MT type
MCCB and for MDC type RCBO
Four dedicated codes already wired
with MDC type A 30mA
Rated current 10A 4,5 – 6 kA
Rated current 16A 4,5 – 6 kA
EURODIN CATALOGUE SEPTEMBER 2005 13
Restart RM
MDC +
All the other versions of MDC + RM are available code letter
with this simple codes:
GW 94 XXX R
EURODIN CATALOGUE SEPTEMBER 2005 14
Restart RM
Top safety
Preventive control of earth leakages
and stop in case of fault
Preventive control of short circuits
and stop in case of fault
Segnalling of reset in progress
EURODIN CATALOGUE SEPTEMBER 2005 15
Problem n°2: reliability of device
The RCD is a device extremely delicate. It uses a little differential
current to produce a mechanical force for the trip of the switch
It is very easy to compromise the proper running
Some causes of improper working order:
Dust
Humidity degree
Aggressive atmosphere
Sudden variation of room temperature
Vibration
Presence of electromagnetic field
For this reason the residual current devices are provided
with a button to make a periodic test
EURODIN CATALOGUE SEPTEMBER 2005 16
Test of residual current device
What is the function of test button?
To chek the good mechanical and
electrical working of residual current
device
The test button is necessary to
maintain the efficiency and reliability
of the residual current device in time
EURODIN CATALOGUE SEPTEMBER 2005 17
Reliability of residual current
Also a IEC document shows how the periodic use
of the test button increases the reliability of
residual current devices
Source: document SC23E IEC
Without periodic test
With periodic test
EURODIN CATALOGUE SEPTEMBER 2005 18
Restart with Autotest
Automatic resetting device with self testing RCD
ReStart with Autotest
ReStart RD Autotest
RCD with automatic reset
and periodic self testing
One piece versions
(already complete with 25A e 40A
type A residual current circuit breaker)
EURODIN CATALOGUE SEPTEMBER 2005 19
Restart with Autotest
GW 90901 (25 A) - GW 90902 (40 A)
Size: 5 modules
Functions:
like Restart RD automatic resetting
only after insulation to earth check
weekly self test without
interruption of power supply
residual current protection always
active
EURODIN CATALOGUE SEPTEMBER 2005 20
Restart with Autotest
Signallings
Left Led
System test in progress
System fault
Device anomaly
Synchronization button
Right Led
System powered
System not powered
Auxiliary contact for
remote signalling
EURODIN CATALOGUE SEPTEMBER 2005 21
Applications of Restart
HOME - BLOCKS OF FLATS FRIDGE
(stair lights, entry phones, gate automation)
EURODIN CATALOGUE SEPTEMBER 2005 22
Applications of Restart
AQUARIUM AUTOMATIC SPRINKLER
(for garden irrigation)
EURODIN CATALOGUE SEPTEMBER 2005 23
Applications of Restart
ALARM
(antitheft)
FAX
PERSONAL
COMPUTER
EURODIN CATALOGUE SEPTEMBER 2005 24
ReStart 4P
ReStart 4P Range
EURODIN CATALOGUE SEPTEMBER 2005 25
ReStart 4P
RD - Add-on Restart Restart with
for RCCBs 4P Autotest 4P
+
EURODIN CATALOGUE SEPTEMBER 2005 26
ReStart RD 4P
Safe reclosure of the RCCB after an unwanted
tripping
Continuosly checking of the installation in
case of earth leakage
Compactness: 3 mod. only
1 CO alarm switch integrated
Fittable to RCCBs up to 100A
EURODIN CATALOGUE SEPTEMBER 2005 27
ReStart RD 4P
segédérintkező betáplálás
Áram -
védőkapcsoló
Led-es visszajelzés:
Csúsztatható előlap
a Restart be- és
kikapcsolásához
Hálózat ellenőrző
kábel
EURODIN CATALOGUE SEPTEMBER 2005 28
ReStart RD 4P
RCCB RD PRO 4P
Auxiliaries
4 modules 3 modules
In: 25A ÷ 100A
EURODIN CATALOGUE SEPTEMBER 2005 29
ReStart RD 4P
How to wire ReStart?
Power supply
Supply cable
Load Test cable
EURODIN CATALOGUE SEPTEMBER 2005 30
ReStart RD 4P
How does Restart work? 2) Untimely tripping
R
S
T
N
RC RESTART RESTART
PRO 4P PRO 4P
RG
RE RE
1) Fault to earth
RE: installation earth resistance
RC: transfo earth resistance
RG: fault resistance
EURODIN CATALOGUE SEPTEMBER 2005 31
ReStart RD 4P
Main Electrical features
Distribution system: TT-TN
Nominal voltage Vn: 400 a.c. [V]
Nominal frequency: 50 [Hz]
Power dissipation: 1,2 [W]
Reclosing power: 30 [W]
EURODIN CATALOGUE SEPTEMBER 2005 32
ReStart RD 4P
Main Mechanical features
Mechanical operations
(number of resets): 10000
Maximum operation
frequency: 30 [man/h]
Closing control: AUTOMATIC
Closing time: <10 [s]
Protection degree: IP20
EURODIN CATALOGUE SEPTEMBER 2005 33
ReStart RD 4P
Local and remote signals
Sliding cover to
activate/disconnect Auxiliary
Restart contact
Sliding window
position
Isolation control
status
EURODIN CATALOGUE SEPTEMBER 2005 34
ReStart RD 4P
Led signals working status:
Measurement of the
insulating in progress
0,5s 0,5s 0,5s 0,5s t
Fault to earth
5s 5s 5s t (stand-by condition)
Restart blocked
t
EURODIN CATALOGUE SEPTEMBER 2005 35
ReStart RD 4P
Auxiliary contact features
Type: change - over
0,4(a.c.)/1,5(d.c.
Maximum current: ) [A]
Operating voltage: 230 a.c./ 30 d.c. [V]
Insulating voltage: 600 [V]
Maximum terminal capacity: 2,5 1CO[mm2]
EURODIN CATALOGUE SEPTEMBER 2005 36
ReStart RD 4P
Auxiliary contact behaviour
RCCB Aux
Switchover in case of:
Sliding cover opened,
circuit breaker on (after 10s)
Low insulation of the
installation (stand-by condition)
After 3 consecutive reset
(block condition, red led)
EURODIN CATALOGUE SEPTEMBER 2005 37
ReStart Autotest 4P
RCCB with monthly selftest
function
No black-out during the self test
procedure
Complete test of the RCCB
(tripping relay and main contacts)
Restart function included
EURODIN CATALOGUE SEPTEMBER 2005 38
ReStart Autotest 4P
Fast Autotest of RCCB (<3s)
Alarm switch included
In: 25-40-63 A
IΔn: 30-300 mA
Type A[IR] 3kA 8/20s
Compactness: 7 mod.
EURODIN CATALOGUE SEPTEMBER 2005 39
ReStart Autotest 4P
Change over switch MONOBLOC: no cables to wire !
Signalling LED
RCCB Left LED:
RCCBs fault
working status
Sliding cover to Right LED
activate/disconnect
Autotest device ON
EURODIN CATALOGUE SEPTEMBER 2005 40
ReStart Autotest 4P
Autotest without blackout:
The bypass circuit is got by parallel contacts fixed on the
same shaft of the main contacts
Line
M
Electronic device
Change
over
contact
EURODIN CATALOGUE SEPTEMBER 2005 41
ReStart Autotest 4P
Bypass contact
Main circuit: ON
Bypass circuit: OFF
LINE
M
LOAD
EURODIN CATALOGUE SEPTEMBER 2005 42
ReStart Autotest 4P
Main circuit: ON
Bypass circuit: ON
LINE
M
LOAD
EURODIN CATALOGUE SEPTEMBER 2005 43
ReStart Autotest 4P
Main circuit: OFF
Bypass circuit: ON
LINE
M
LOAD
EURODIN CATALOGUE SEPTEMBER 2005 44
ReStart Autotest 4P
Main circuit: ON
Bypass circuit: ON
LINE
M
LOAD
EURODIN CATALOGUE SEPTEMBER 2005 45
ReStart Autotest 4P
Main circuit: ON
Bypass circuit: OFF
LINE
M
LOAD
EURODIN CATALOGUE SEPTEMBER 2005 46
ReStart Autotest 4P
Electrical features
Reference Standards: EN 61008-1
Distribution system: TT-TN
Rated current In: 25 - 40 - 63 [A]
Nominal voltage Vn: 400 a.c. [V]
Nominal differential tripping
current: 30 - 300 [mA]
Type: A[IR]
Nominal frequency: 50 [Hz]
EURODIN CATALOGUE SEPTEMBER 2005 47
ReStart Autotest 4P
Power supply connection: Only from top
From top
OK
NO
From bottom
EURODIN CATALOGUE SEPTEMBER 2005 48
ReStart Autotest 4P
Local and remote signals
Auxiliary
contact
Manual
Autotest
button
Sliding window
position
Isolation control and Autotest
status
EURODIN CATALOGUE SEPTEMBER 2005 49
ReStart Autotest 4P
Auxiliary contact features
Type: change - over
Maximum current: 0,4(a.c.)/1,5 (d.c.) [A]
Operating voltage: 230 a.c./ 30 d.c. [V]
Insulating voltage: 600 [V]
Maximum terminal
capacity: 2,5 1CO [mm2]
EURODIN CATALOGUE SEPTEMBER 2005 50
ReStart Autotest 4P
Bypass RCCB Aux
Switchover in case of:
Sliding cover opened,
circuit breaker on (after 10s)
Low insulation of the
installation (standby)
Malfunctioning (yellow led)
After 3 consecutive reset
(block condition, red led)
EURODIN CATALOGUE SEPTEMBER 2005 51
ReStart 4P & Autotest 4P
ReStart 4P Autotest 4P
Insulation 10kΩ (30mA)
control 2kΩ (300mA)
Continuous
control
Automatic self-
test
Auxiliary
EURODIN CATALOGUE 0,4A
SEPTEMBER 2005 0,4A 52
contact
ReStart 4P & Autotest 4P
2 international patents
concerning:
Reset mechanism (ReStart)
Bypass mechanism (Autotest)
EURODIN CATALOGUE SEPTEMBER 2005 53
ReStart 4P & Autotest 4P
Rohs compliant
Free of:
Lead
Mercury
Cadmium
Hexavalent Chromium
PBB
PBDE
EURODIN CATALOGUE SEPTEMBER 2005 54
ReStart 4P & Autotest 4P
Applications
Nurseries,
Refineries, schools,
petrochemical Industry, universities,
paper mills officies
Harbours and docks,
camp sites,
holiday village
Swimming pools
EURODIN CATALOGUE SEPTEMBER 2005 55
Köszönjük!
EURODIN CATALOGUE SEPTEMBER 2005 56