SIMATIC Workstation - DOC - DOC

Document Sample
SIMATIC Workstation - DOC - DOC Powered By Docstoc
					                     SIMATIC Workstation
                   System Recovery Procedure

                                   Project Data
Date:                           13 Nov 2011
Project Number:                 0000-0000
Project Name:                   SIMATIC Project
Project Manager:                Reuben Allott
Client:                         Client Company
Client Representative:          Client Representatives




                                     Allottware CC
                                   Reg No: 2004/028046/23
                     P.O. Box 12611, Vorna Valley, 1686, South Africa

                                 Tel: +27 82 809 3262
                                Fax: +27 11 315 1464
                             Email: reuben@allottware.co.za
                              Web: www.allottware.co.za

                                   Managing Members:
                                     Reuben Allott
System Recovery Procedure                                                SIMATIC Workstation



      CONTENTS

      1     INTRODUCTION ....................................................................................................................................... 4
          1.1         OVERVIEW ........................................................................................................................................... 4
          1.2         SOFTWARE REQUIREMENTS.................................................................................................................. 4
          1.3         HARDWARE REQUIREMENTS ................................................................................................................ 4
      2     INSTALLATION CHECKLIST ............................................................................................................... 5
          2.1         AUTHORIZATIONS ................................................................................................................................ 5
          2.2         HARDWARE INSTALLATION .................................................................................................................. 5
          2.3         SOFTWARE INSTALLATION ................................................................................................................... 5
          2.4         PROJECT INSTALLATION ....................................................................................................................... 5
          2.5         SYSTEM STARTUP................................................................................................................................. 5
      3     RECOVER ORIGINAL AUTHORIZATIONS ....................................................................................... 6
      4     HARDWARE INSTALLATION ............................................................................................................... 7
          4.1         STANDARD EQUIPMENT........................................................................................................................ 7
          4.2         SIMATIC CP-1613 .............................................................................................................................. 7
      5     OPERATING SYSTEM INSTALLATION .............................................................................................. 8
          5.1         OPERATING SYSTEM............................................................................................................................. 8
          5.2         ADDITIONAL WINDOWS COMPONENTS ................................................................................................ 8
          5.3         VIDEO, NETWORK & SOUND DRIVERS ................................................................................................. 9
          5.4         INTERNET EXPLORER V6 + SP2............................................................................................................ 9
          5.5         OPERATING SYSTEM SERVICE PACK .................................................................................................... 9
          5.6         WINDOWS 2000 SP4 HOTFIX KB828748 ............................................................................................. 9
          5.7         CREATE USERS ................................................................................................................................... 10
      6     SIMATIC SOFTWARE INSTALLATION ............................................................................................ 11
          6.1         SIMATIC NET V6.1 + SP1 ............................................................................................................... 11
          6.2         CP-1613 AS TCP/IP CARD ................................................................................................................. 12
          6.3         NETWORK CONFIGURATION ............................................................................................................... 13
             6.3.1      Computer Name ............................................................................................................................ 13
             6.3.2      Network Connections ................................................................................................................... 14
             6.3.3      Office LAN ................................................................................................................................... 15
             6.3.4      PLC Network ................................................................................................................................ 15
          6.4         PG/PC INTERFACE ............................................................................................................................. 16
             6.4.1      TCP/IP via CP-1613 ..................................................................................................................... 16
             6.4.2      Industrial Ethernet via CP-1613.................................................................................................... 17
             6.4.3      TCP/IP via Standard Ethernet Card .............................................................................................. 17
          6.5         MICROSOFT SQL SERVER 2000 + SP3 ............................................................................................... 18
          6.6         STEP7 PROFESSIONAL......................................................................................................................... 19
          6.7         WINCC V6.0 + SP2 ............................................................................................................................ 20
          6.8         WINCC DATA MONITOR V6.0 + SP1 + HOTFIX2 ............................................................................... 22
          6.9         WINCC V6.0 + SP2 + HOTFIX3 .......................................................................................................... 23
          6.10        TRANSFER AUTHORIZATIONS ............................................................................................................. 24
      7     PROJECT INSTALLATION .................................................................................................................. 25
          7.1         CREATE PROJECT FOLDER .................................................................................................................. 25
          7.2         RETRIEVE PROJECT ............................................................................................................................ 25
          7.3         OPEN THE WINCC PROJECT ............................................................................................................... 25
          7.4         SET COMPUTER PROPERTIES .............................................................................................................. 26
             7.4.1      Computer Name ............................................................................................................................ 26
             7.4.2      Limiting Runtime .......................................................................................................................... 26
          7.5         SET TCP/IP SYSTEM PARAMETER ...................................................................................................... 27
      APPENDIX A: SIMATIC AUTHORIZATIONS ............................................................................................ 28


Rev: 1, 18 Nov 2005                                                    Doc no: 0000-0000-SRP-1                                                                    0000-0000
Status: As-Built                                                             Page 2 of 36                                                                    SIMATIC Project
System Recovery Procedure                                                SIMATIC Workstation



         WINCC V6.0 .................................................................................................................................................... 28
         STEP 7 PROFESSIONAL V5.3 ............................................................................................................................. 29
      APPENDIX B: WINCC AUTOSTART ............................................................................................................ 30
      APPENDIX C: RESTRICTING THE WINCC RUN-TIME.......................................................................... 31
      APPENDIX D: AUTOMATIC LOGON FOR WINDOWS............................................................................ 32
      APPENDIX E: WINDOWS STARUP COUNTER ......................................................................................... 33
      APPENDIX F: DISABLING USB FLASH DISK AUTO-START ................................................................. 34
      APPENDIX G: WINDOWS 2000 / XP FOREGROUND LOCK TIMEOUT ............................................... 36




Rev: 1, 18 Nov 2005                                                    Doc no: 0000-0000-SRP-1                                                                   0000-0000
Status: As-Built                                                             Page 3 of 36                                                                   SIMATIC Project
System Recovery Procedure                   SIMATIC Workstation




      1     INTRODUCTION
      1.1     Overview

      This document lists the steps required to install a new computer workstation to be used for
      the project.

      The Service Technician should know a little about Siemens hardware or software. A general
      working knowledge of installing hardware and software and working with files, folders,
      networking and user access on the Windows platform is essential.


      1.2     Software Requirements

      The following software is required. Other versions have not been tested and may not work
      together correctly:

      Required Software                              Version (Revision Level)
      Windows XP Professional                        5.1.2600 Service Pack 2 Build 2600
      Windows 2000 Professional                      5.00.2195 Service Pack 4
      MS Internet Explorer                           V6 + SP2
      MS Internet Information Services               IIS 5.1
      WinCC                                          V6.0 + SP2 + Hotfix 3 (V6.0.2.3)
      Web Navigator/Data Monitor Server              V6.0 + SP1 + Hotfix 2 (V6.0.1.2)
      Web Navigator/Data Monitor Client              V6.0 + SP1 (V6.0.1.0)
      SIMATIC NET PC Software                        V6.1 + SP1 (V6.1.1.0)

      NOTE: Please don’t try to install Windows XP and Windows 2000 at the same time. You
      may cause a rip in the space-time continuum.


      1.3     Hardware Requirements

      The following minimum hardware is recommended in the PC:

      Required Hardware      Description
         SIMATIC CP-1613     Siemens Ethernet Communications Processor (PCI adapter)
               Or            Any 100mbps Ethernet card may be used in the PC, however the CP-1613
           100mbps NIC       has an onboard processor and yields much greater data throughput.
      Motherboard            Intel Pentium 4 3.0 GHz
      RAM                    1 GB
      HDD                    Entry Level
      Sound                  Entry Level
      Video                  1024 x 768 x True Color
      Monitor                17” Panel
      NIC                    100mbps Ethernet Card (additional to the PLC network card)




Rev: 1, 18 Nov 2005                        Doc no: 0000-0000-SRP-1                             0000-0000
Status: As-Built                                 Page 4 of 36                             SIMATIC Project
System Recovery Procedure                    SIMATIC Workstation




      2     INSTALLATION CHECKLIST
      2.1    Authorizations
             Recover Original Authorizations

      2.2    Hardware Installation
             PC, Keyboard, Monitor, Mouse
             Video Card, Sound Card
             NIC #1 – “Office LAN”
             NIC #2 – “PLC Network”

      2.3    Software Installation
             Operating System (Windows 2000 or XP)
             Additional Windows Components (IIS and Message Queuing)
             Video, Network & Sound Card Drivers
             Internet Explorer V6 + SP2
             Operating System Service Pack
             Windows 2000 SP4 Hotfix KB828748
             Create “WinCC” User
             SIMATIC Net V6.1 + SP1
             Configure Networking
             Configure PG/PC Interface
             Microsoft SQL Server 2000 + SP3
             Step7 Professional V5.3
             WinCC V6.0 + SP2
             WinCC Data Monitor V6.0 + SP1
             WinCC V6.0 + SP2 + Hotfix 3
             Transfer Authorizations

      2.4    Project Installation
             Create Project Folder
             Create Project Share
             Retrieve Project
             Set Computer Properties
             Set TCP/IP System Parameter
             Configure the Web Server

      2.5    System Startup
             Configure WinCC Autosart
             Configure Windows Auto-logon




Rev: 1, 18 Nov 2005                         Doc no: 0000-0000-SRP-1          0000-0000
Status: As-Built                                  Page 5 of 36          SIMATIC Project
System Recovery Procedure                    SIMATIC Workstation




      3     RECOVER ORIGINAL AUTHORIZATIONS

      Do not forget to remove all your SIMATIC authorizations from the original WinCC
      workstation before formatting or disposing of the hard disk!

      Please refer to Appendix A for instructions on transferring authorizations.

      If the original workstation has “crashed” and will not start up, you can try installing the hard
      disk into another computer as a slave. From there you can extract the licences as usual.

      If the hard disk has failed and cannot be accessed in this manner, a data recovery specialist
      may still be able to recover the data.

      If all else fails, you will have to use the Emergency 14-day licenses included on your original
      Siemens authorization disks and contact Siemens for replacement licenses.




Rev: 1, 18 Nov 2005                         Doc no: 0000-0000-SRP-1                               0000-0000
Status: As-Built                                  Page 6 of 36                               SIMATIC Project
System Recovery Procedure                   SIMATIC Workstation




      4     HARDWARE INSTALLATION
      4.1     Standard Equipment

      Make sure all the usual computer hardware is installed, such as video card, sound card, HDD,
      mouse, keyboard monitor etc.

      Make sure there are TWO network adapters installed:

           NIC #1 – Network interface card for the “Office LAN”
           NIC #2 – Network interface card for the “PLC Network” (or CP-1613 card)

      The PLC network is separate from the Office LAN for performance reasons; hence two
      adapter cards are required.


      4.2     SIMATIC CP-1613

      This document describes installing the CP-1613 at this initial point. This is to save opening
      up the computer twice.

      The official documentation from Siemens instructs you to only install the card AFTER you
      have installed the SIMATIC Net drivers for the card. This prevents Windows prompting you
      for device drivers after start-up when it detects the plug-and-play CP-1613 card. When you
      start up windows simply ignore the driver installation prompts launched automatically by
      windows (click “Cancel” or “Close”). They will stop popping up once you have installed the
      SIMATIC Net drivers.

      Alternately, do not install the CP-1613 hardware at this point. When you are prompted to
      restart the computer after installing the SIMATIC Net drivers (later on in the procedure) shut
      down the computer and install the CP-1613 hardware before restarting again.




Rev: 1, 18 Nov 2005                        Doc no: 0000-0000-SRP-1                              0000-0000
Status: As-Built                                 Page 7 of 36                              SIMATIC Project
System Recovery Procedure                     SIMATIC Workstation




      5     OPERATING SYSTEM INSTALLATION
      5.1     Operating System

      Install Windows 2000 Professional or Windows XP Professional.

      It is very important that you perform a “clean” installation – do not try to upgrade or
      overwrite an already existing operating system.

      Format the destination partition with the NTFS file system during the installation. NTFS is
      more efficient than FAT and supports better security features.


      5.2     Additional Windows Components

      Select these additional Windows Components during installation:

           Internet Information Services (IIS)
           Message Queuing Services

      WinCC and WinCC Data Monitor will not install without them.

      You can install these components after installing the operating system from the Control
      Panel. Open “Add/Remove Programs” and select the components from the “Add/Remove
      Windows Components” button:




Rev: 1, 18 Nov 2005                          Doc no: 0000-0000-SRP-1                          0000-0000
Status: As-Built                                   Page 8 of 36                          SIMATIC Project
System Recovery Procedure                     SIMATIC Workstation




      5.3     Video, Network & Sound Drivers

      Install the drivers for the “Office LAN” network interface card (NIC), the Video adapter and
      the Sound Card installed in the PC. If you are using a standard network interface card for the
      “PLC Network” and not a CP-1613 card, then install the drivers for that card also.

      Select screen size: 1024 x 768 x True Color


      5.4     Internet Explorer V6 + SP2

      Install the latest version of Internet Explorer. This is possibly already included in the
      Windows Service Pack. Otherwise the CD is supplied with the WinCC software pack.


      5.5     Operating System Service Pack

      Install the latest Service Pack for Windows – Windows 2000 SP4 (or later) or Windows XP
      SP2 (or later).


      5.6     Windows 2000 SP4 Hotfix KB828748

      If you have installed Windows 2000 Service Pack 4 you will need to install this hotfix. The
      hotfix is found on the MS Tools CD included with WinCC V6.0. It is also included on the
      project backup CD in “<CDROM>\Windows 2000 KB828748”.

      If it is not installed you will receive the following error during the installation of WinCC:




Rev: 1, 18 Nov 2005                          Doc no: 0000-0000-SRP-1                                0000-0000
Status: As-Built                                   Page 9 of 36                                SIMATIC Project
System Recovery Procedure                 SIMATIC Workstation




      5.7     Create Users

      Create a local user called “wincc” with password “wincc”. Add this user to the
      Administrators group.



                                                            Open Computer Management from the
                                                            Desktop from the My Computer context
                                                            menu.




                                                            In Local Users and Groups, add a new user
                                                            named “WinCC” with the password “wincc”.

                                                            Select “User cannot change password” and
                                                            “Password never expires”.

                                                            Click “Create” and “Close” to create the
                                                            user.




                                                            Open the properties for the new WinCC
                                                            user and add “Administrators” to the user’s
                                                            group membership.




      Log out and only log in as “wincc” from now on.




Rev: 1, 18 Nov 2005                     Doc no: 0000-0000-SRP-1                                    0000-0000
Status: As-Built                             Page 10 of 36                                    SIMATIC Project
System Recovery Procedure                   SIMATIC Workstation




      6     SIMATIC SOFTWARE INSTALLATION
      6.1     SIMATIC NET V6.1 + SP1

      Install the SIMATIC NET V6.1 + SP1 software, or the version that came with your
      communications card:




      If you have not yet installed the CP-1613 card hardware, select “No” and manually shutdown
      the computer. Install the CP-1613 in a free PCI slot (you can try installing it in a used PCI
      slot, but you will probably damage it and again cause that space-time continuum thing).

      Restart the computer, or the remainder of the installation process may seem to take a long
      time (Don’t you hate these obvious instructions? At least you’re not reading something badly
      translated from Chinese, like “Upon completion of the PCI installation successful, pass begin,
      collect 200 dollars, and proceed once again through the cables with the flow of electricity”).



Rev: 1, 18 Nov 2005                        Doc no: 0000-0000-SRP-1                              0000-0000
Status: As-Built                                Page 11 of 36                              SIMATIC Project
System Recovery Procedure                                 SIMATIC Workstation




      6.2     CP-1613 as TCP/IP Card

      To use the CP-1613 as a standard TCP/IP card, you must install the NDIS drivers from the
      SIMATIC Net CD. Open the “Add/Remove Hardware” applet from the Control Panel:




                              Click “Next”                                           Select “Add/Troubleshoot a device”




                        Select “Add a new device”                                               Select “No”




                        Select “Network adapters”                                            Click “Have Disk”




       Select the CP-1613 NDIS drivers from the SIMATIC Net CD that
                                                                          Click “Next” to install the SIMATIC CP-1613 NDIS drivers
                       came with your CD-1613 card




Rev: 1, 18 Nov 2005                                      Doc no: 0000-0000-SRP-1                                               0000-0000
Status: As-Built                                              Page 12 of 36                                               SIMATIC Project
System Recovery Procedure                  SIMATIC Workstation




      6.3     Network Configuration

      6.3.1 Computer Name

      Set the computer name to “WINCC”:




                                                       Open Computer Properties from the Desktop
                                                       from the My Computer context menu.




                                                       Click “Properties”




                                                       Enter the Computer    Name   “WinCC”   and
                                                       Workgroup “SIMATIC”




      You will be asked to reboot the computer after making this change (you’re not even half-way
      yet, so don’t start getting upset now).




Rev: 1, 18 Nov 2005                       Doc no: 0000-0000-SRP-1                             0000-0000
Status: As-Built                               Page 13 of 36                             SIMATIC Project
System Recovery Procedure                 SIMATIC Workstation




      6.3.2 Network Connections

      At this stage you should see two networks in the “Network and Dial-Up Connections” in the
      Control Panel:




      Rename the connections to “Office LAN” and “PLC Network”:




Rev: 1, 18 Nov 2005                      Doc no: 0000-0000-SRP-1                            0000-0000
Status: As-Built                              Page 14 of 36                            SIMATIC Project
System Recovery Procedure                 SIMATIC Workstation




      6.3.3 Office LAN

      The following TCP/IP setting must be selected for the Office LAN (DHPC):




                                        Select “Obtain an IP address automatically” and “Obtain
                                        DNS server address automatically”. This is Microsoft
                                        DummySpeek for “Use DHCP”. And don’t get me started on
                                        that stupid little paper clip Office Assistant.




      6.3.4 PLC Network

      The following TCP/IP setting must be selected for the PLC Network (XX.XX.XX.XX with
      subnet mask 255.255.255.0):




                                        Enter this address:
                                        IP Address:        XX.XX.XX.XX
                                        Subnet mask:       255.255.255.0




Rev: 1, 18 Nov 2005                      Doc no: 0000-0000-SRP-1                            0000-0000
Status: As-Built                              Page 15 of 36                            SIMATIC Project
System Recovery Procedure                   SIMATIC Workstation




      6.4     PG/PC Interface

      You can configure the CP-1613 card for Industrial Ethernet or for TCP/IP.




                                                                              Open “Set PG/PC
                                                                              Interface” from the
                                                                              Control Panel:




      6.4.1 TCP/IP via CP-1613

      Select “CP1613(RFC1006)” for the WinCC and S7ONLINE Access Points:




      You must configure the IP address from the “Properties” button. Note that this address must
      be different to the TCP/IP address assigned to the same card in the Control Panel in “Network
      and Dial-Up Connections”. Set this address to XX.XX.XX.YY with subnet mask
      255.255.255.0.




Rev: 1, 18 Nov 2005                        Doc no: 0000-0000-SRP-1                             0000-0000
Status: As-Built                                Page 16 of 36                             SIMATIC Project
System Recovery Procedure                  SIMATIC Workstation




      6.4.2 Industrial Ethernet via CP-1613

      If you are only using Industrial Ethernet (no TCP/IP) then select the “CP1613(ISO)” Access
      Point instead.


      6.4.3 TCP/IP via Standard Ethernet Card

      If you do not have a CP-1613 you must use the TCP/IP protocol as follows:




                                                         Select the “TCP/IP” option with the network
                                                         card that is connected to the “PLC Network”.

                                                         Here the ethernet card is a “Via Networking
                                                         Velocity”. Yours may be something else, such as
                                                         3COM, Intel, Planet, Genius etc.




                                                         If you do not see your network card, click the
                                                         “Select” button and install the TCP/IP option.




Rev: 1, 18 Nov 2005                       Doc no: 0000-0000-SRP-1                                   0000-0000
Status: As-Built                               Page 17 of 36                                   SIMATIC Project
System Recovery Procedure                SIMATIC Workstation




      6.5     Microsoft SQL Server 2000 + SP3

      Install Microsoft SQL Server 2000 + SP3. You must install the version supplied with the
      WinCC software pack.




                                                     Click “Next” to begin installation. You may have
                                                     to reboot the computer after installation.




Rev: 1, 18 Nov 2005                     Doc no: 0000-0000-SRP-1                                  0000-0000
Status: As-Built                             Page 18 of 36                                  SIMATIC Project
System Recovery Procedure                 SIMATIC Workstation




      6.6     Step7 Professional

      If you plan to use Step7 then install it BEFORE WinCC. You must have Step7 and WinCC to
      make changes to the project. If you are only setting up a runtime system, then you do not
      require Step7.




                                                      Click “Next” to begin installation. You may,
                                                      surprisingly, have to reboot the computer after
                                                      installation.




Rev: 1, 18 Nov 2005                      Doc no: 0000-0000-SRP-1                                 0000-0000
Status: As-Built                              Page 19 of 36                                 SIMATIC Project
System Recovery Procedure                           SIMATIC Workstation




      6.7     WinCC V6.0 + SP2

      Install WinCC V6.0. Select the following options during installation:

      Options:
       Basic Process Control

      If you are setting up an integrated engineering system (Step7 & WinCC) then select the
      following additional components:

      Communications:
       SIMATIC Device Drivers
       Object Manager
       AS-OS Engineering
       STEP7 Symbol Server

      Proceed as follows:




                 Click on “Install SIMATIC WinCC”                                   Click “Next”




         Enter your name and the serial number from your
                                                                          Select “User-Defined Installation”
         yellow authorization disk that came with WinCC




Rev: 1, 18 Nov 2005                             Doc no: 0000-0000-SRP-1                                         0000-0000
Status: As-Built                                     Page 20 of 36                                         SIMATIC Project
System Recovery Procedure                             SIMATIC Workstation




                                                                        Select “Server” and “Basic Process Control”
         Select everything in the “Communication” options
                                                                                          options




                      Install authorizations later                             Yep, you guessed it – reboot!




Rev: 1, 18 Nov 2005                                  Doc no: 0000-0000-SRP-1                                        0000-0000
Status: As-Built                                          Page 21 of 36                                        SIMATIC Project
System Recovery Procedure                             SIMATIC Workstation




      6.8     WinCC Data Monitor V6.0 + SP1 + Hotfix2

      Install the WinCC Data Monitor server.




                      Select “Install Software”                                Select “Dat@Monitor Server”




                                                                     Enter your name and the serial number from your
                             Click “Next”                            yellow authorization disk that came with WinCC
                                                                                      Dat@Monitor




                      Install authorizations later                                       Reboot!




Rev: 1, 18 Nov 2005                                  Doc no: 0000-0000-SRP-1                                      0000-0000
Status: As-Built                                          Page 22 of 36                                      SIMATIC Project
System Recovery Procedure                          SIMATIC Workstation




      6.9     WinCC V6.0 + SP2 + Hotfix3

      This Hotfix for WinCC is included on the WinCC Data Monitor CD.




                      Select “Install Software”                             Select “WinC V6.0 SP2 Hotfix 3”




                            Click “Next”                                               Reboot!




Rev: 1, 18 Nov 2005                               Doc no: 0000-0000-SRP-1                                          0000-0000
Status: As-Built                                       Page 23 of 36                                          SIMATIC Project
System Recovery Procedure                        SIMATIC Workstation




      6.10 Transfer Authorizations

      You must transfer all required authorizations to the WinCC machine. Please refer to
      Appendix A for instructions on how to do this.

      The following Authorizations are required by the system:

      Required Authorization                             Order Number
      SIK/SIMATIC WINCC-V6 RC64K
      SIK/SIMATIC WinCC Server
      SIK/SIMATIC WinCC DataMonitor Server
      SIK/SIMATIC WinCC-V6 Dat@M.3 Clients
      SIK/SIMATIC NET Industrial Ethernet-S7
      Step 7 Professional 2004 V5.3 (Optional)




Rev: 1, 18 Nov 2005                          Doc no: 0000-0000-SRP-1                  0000-0000
Status: As-Built                                  Page 24 of 36                  SIMATIC Project
System Recovery Procedure                    SIMATIC Workstation




      7     PROJECT INSTALLATION
      7.1     Create Project Folder

      Create a folder called “C:\Projects” and share it as “Projects”.


      7.2     Retrieve Project

      The project backup is in a Step7 archive. Use Step7 to retrieve the archive into the Project
      folder, or simply unzip the project with WinZip or Windows XP. The Step7 project should
      then be located in “C:\Projects\XXX”.


      7.3     Open the WinCC Project

      You open the WinCC project with the WinCC Explorer:

      Start > SIMATIC > WinCC > WinCC Control Centre 6.0

      From the File > Open menu select the WinCC project file:

      C:\Projects\XXX\wincproj\XXX\XXX.mcp



                                 You may get a message that the “configured server is not available”.
                                 Select “Start server locally” to use the local machine as server and
                                 proceed to the next section to set the computer name.




Rev: 1, 18 Nov 2005                        Doc no: 0000-0000-SRP-1                               0000-0000
Status: As-Built                                Page 25 of 36                               SIMATIC Project
System Recovery Procedure                   SIMATIC Workstation




      7.4     Set Computer Properties

      7.4.1 Computer Name

      If the computer name is not the same as the one configured in the project you will need to
      change it.

      Open the properties dialog for the WinCC server from the Computers list and set the
      computer name to “WINCC” from the computer properties dialog:




      You must close and reopen the project after changing the computer name.


      7.4.2 Limiting Runtime

      To restrict users from accessing the operating system and running other applications, refer to
      Appendix C “Restricting the WinCC Runtime”.




Rev: 1, 18 Nov 2005                        Doc no: 0000-0000-SRP-1                              0000-0000
Status: As-Built                                Page 26 of 36                              SIMATIC Project
System Recovery Procedure                 SIMATIC Workstation




      7.5     Set TCP/IP System Parameter

      Make sure WinCC is using the correct access point for TCP/IP or Ethernet communications.
      Open the “System Parameter” dialog for the SIMATIC S7 Protocol Suite:




      Make sure the logical device name is “S7ONLINE”, or the network adapter used for the PLC
      Network. The example on the right is using the CP1613 card.

      You must close and reopen WinCC after changing this parameter.




Rev: 1, 18 Nov 2005                      Doc no: 0000-0000-SRP-1                           0000-0000
Status: As-Built                              Page 27 of 36                           SIMATIC Project
System Recovery Procedure                   SIMATIC Workstation




      APPENDIX A: SIMATIC AUTHORIZATIONS
      WinCC V6.0

      For WinCC to operate correctly, the workstation must be installed with all required WinCC
      authorizations. These authorizations are stored on specially manufactured 3.5” diskettes that
      cannot be copied. These diskettes are shipped with the WinCC software packs that were
      supplied with the project.

      The Siemens program “AuthorsW” is used to transfer authorizations from these diskettes
      onto the hard drives of the WinCC workstations (Server and Clients). It is usually started
      from:

      Start > SIMATIC > AuthorsW > AuthorsW

      In the event of hardware failure of a WinCC workstation, the authorizations must be
      transferred back to the 3.5” diskettes. Once the backup machine has been put in place, and the
      computer name changed to reflect the correct WinCC workstation name, the authorizations
      can be transferred onto the backup machine.

      Should the hard disk fail, and authorizations cannot be retrieved from the WinCC
      workstation, then the emergency authorization is to be used. Each WinCC authorization is
      also shipped with a 14-day emergency authorization. These are to be used while Siemens
      replaces the original.

      Use the “AuthorsW” program to drag-
      and-drop licences from the authorization
      disks onto the local hard drive on which
      you installed WinCC.

      Possible licences are listed on the
      authorization disk, but only the licences
      with a 1 in the “Counter” field are valid
      licences that can be moved onto the hard
      drive.

      WARNING!
      Once a licence has been moved onto the hard drive, it is no longer on the authorization
      disk. This is very important to remember - if the workstation ever needs to be re-installed
      then you must run the authorization program again to move any licences from the hard drive
      back onto the authorization disk. If you do not do this, then you will lose the authorization.

      NOTE:
      The AuthorsW program can be used to transfer licences across the network. This is useful if
      the target workstation has a “risky” floppy drive, in order to avoid damaging the original
      authorization disk by placing it in a faulty or dirty disk drive.



Rev: 1, 18 Nov 2005                        Doc no: 0000-0000-SRP-1                              0000-0000
Status: As-Built                                Page 28 of 36                              SIMATIC Project
System Recovery Procedure                SIMATIC Workstation




      Step 7 Professional V5.3

      Step 7 V5.3 onwards uses the new authorization program “Automation License Manager”.
      This program is very similar to the “AuthorsW” program with previous versions and other
      products, but it supports the newer SIMATIC authorizations. It is usually started from:

      Start > SIMATIC > License Management > Automation License Manager




      NOTE:
      The “Automation License Manager” can handle the previous authorizations, but the
      “AuthorsW” application cannot handle the newer authorizations.




Rev: 1, 18 Nov 2005                     Doc no: 0000-0000-SRP-1                           0000-0000
Status: As-Built                             Page 29 of 36                           SIMATIC Project
System Recovery Procedure                  SIMATIC Workstation




      APPENDIX B: WINCC AUTOSTART

      WinCC can be configured to “Auto-Start” a WinCC project. Use the AutoStart program that
      is installed with WinCC 6.0 to select the WinCC project to Auto-Start. It is usually started
      from:

      Start > SIMATIC > WinCC > AutoStart




      This program configures WinCC to automatically launch the selected project into Run-Time
      mode whenever the current user logs in to the Windows system.

      Configuring an automatic login to Windows can further enhance this automatic program
      launch. Appendix D describes how to do this.




Rev: 1, 18 Nov 2005                       Doc no: 0000-0000-SRP-1                             0000-0000
Status: As-Built                               Page 30 of 36                             SIMATIC Project
System Recovery Procedure                  SIMATIC Workstation




      APPENDIX C: RESTRICTING THE WINCC RUN-TIME

      WinCC can be configured such that the CTRL+ALT+DEL, ALT+TAB, CTRL-ESC and
      ALT-ESC shortcuts are not available during run-time of the WinCC project. This prevents
      the user from accessing the start menu or the task manager, disabling the user from running
      other programs or from logging out of Windows.

      Open the properties for the computer from the computer list in the WinCC Explorer program.
      Go to the “Parameters” page and check the options to disable the system shortcut keys.




      Got to the “Graphics Runtime” page and check these options to make the WinCC runtime
      operate in a full-screen window:




Rev: 1, 18 Nov 2005                       Doc no: 0000-0000-SRP-1                             0000-0000
Status: As-Built                               Page 31 of 36                             SIMATIC Project
System Recovery Procedure                    SIMATIC Workstation




      APPENDIX D: AUTOMATIC LOGON FOR WINDOWS

      Windows can be configured to automatically log on when the system is booted up. The
      operator does not have to type in a user name and a password to enter Windows.

      To do this, select “Run” from the Start Menu, and type in “regedit”. This will run the
      Windows NT Registry Editor.

      Open this registry key:

      HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\Windows NT\CurrentVersion\Winlogon

      Add in these three highlighted string values:




Rev: 1, 18 Nov 2005                         Doc no: 0000-0000-SRP-1                      0000-0000
Status: As-Built                                 Page 32 of 36                      SIMATIC Project
System Recovery Procedure                   SIMATIC Workstation




      APPENDIX E: WINDOWS STARUP COUNTER

      When Windows boots up, there is a default 30-second timer that waits for the user to select
      the required boot mode. The default mode is selected at the end of the timer. This timer can
      be reduced using the “System” Control Panel applet:




                                        Open the properties dialog for My Computer from the Desktop




                                        Open the “Advanced” page.

                                        Click on the “Settings” button in “Startup and Recovery”.




                                        Reduce the System startup counters from 30 seconds to 3
                                        seconds, or to 0 to select the operating system immediately.




Rev: 1, 18 Nov 2005                       Doc no: 0000-0000-SRP-1                                   0000-0000
Status: As-Built                               Page 33 of 36                                   SIMATIC Project
System Recovery Procedure                          SIMATIC Workstation




      APPENDIX F: DISABLING USB FLASH DISK AUTO-START

      Usually Windows XP/2000 will automatically open Windows Explorer as soon as you
      connect a USB flash disk to the system, giving access to the operating system. You can
      disable this via the registry:

      Open the Registry via Start > Run > "Regedit", and search for the code
      "NoDriveTypeAutoRun" in:

      HKEY_CURRENT_USER\ Software\ Microsoft\ Windows\CurrentVersion\ Policies\Explorer.




      The value in this code specifies the devices for which the Autostart function is to apply.

      The drives are coded in bits:

       Bit       Value      Meaning
         0          1       Disables Autostart for unknown drive types
         1          2       -
         2          4       Disables Autostart for removable data media (e.g. floppy disk drive)
         3          8       Disables Autostart for fixed data media
         4         16       Disables Autostart for network drives
         5         32       Disables Autostart for CD-ROM
         6         64       Disables Autostart for RAM-DISK
         7        128       Reserved and always set Value (hex) Value (dec) Meaning
                            Table 1: Bit assignment of the "NoDriveTypeAutoRun" byte

      The relevant bits of this byte enable or disable the Autostart function of each type of drive. A
      value of 0 in the bit concerned means that the Autostart function is enabled. The default value
      is hexadecimal 95 (decimal this corresponds to 149, that is 1+4+16+128 = 149). Thus it is
      also possible for floppy disk drives, for example, to switch on the Autostart function.




Rev: 1, 18 Nov 2005                               Doc no: 0000-0000-SRP-1                               0000-0000
Status: As-Built                                       Page 34 of 36                               SIMATIC Project
System Recovery Procedure                             SIMATIC Workstation




      Value      Value
                              Meaning
      (Dec)      (Hex)
        95            149     For CDs Autorun.inf is executed automatically
        B5            181     For CDs and hard disk Autorun.inf is executed with a doubleclick
        00             00     For all drives (also floppy disk) Autorun.inf is executed with a double-click
        FF            255     Autorun.inf is no longer executed at all
        FD            253     The Autostart function is switched off for all drives
                            Table 2: Sample assignments of the "NoDriveTypeAutoRun" byte

      If you also wish to suppress the "Info Balloon", then insert the code "EnableBalloonTips"
      into the following path:

      HKEY_CURRENT_USER\Software\Microsoft\Windows\CurrentVersion\Explorer\Advanced\

      Assign this code the data type DWORD and set the value to "0".




Rev: 1, 18 Nov 2005                                 Doc no: 0000-0000-SRP-1                                        0000-0000
Status: As-Built                                         Page 35 of 36                                        SIMATIC Project
System Recovery Procedure                         SIMATIC Workstation




      APPENDIX G: WINDOWS 2000 / XP FOREGROUND LOCK TIMEOUT

      You may have a script similar to this that prevents opening multiple instances of the same
      application window. If you have locked out all the ALT+TAB type key combinations, then
      application windows can get lost behind WinCC. Over time you can clog the system up with
      many lost windows:
      // For Calculator:        raRunProgram("calc.exe", "SciCalc", NULL);
      // For Windows Explorer: raRunProgram("Explorer.exe", "ExploreWClass", NULL);
      HWND raRunProgram(char *CommandLine, char *WinClassName, char *WinTitle)
      {
               HWND Handle;
               // First look for application window
               Handle = FindWindow(WinClassName, WinTitle);
               // If app is already running, then bring window to the foreground
               if (Handle != NULL) {
                        printf("Bring Application to foreground (%s).\r\n", CommandLine);
                        SetForegroundWindow(Handle);
                        if (IsZoomed(Handle))
                                 ShowWindow(Handle, SW_MAXIMIZE);
                        else
                                 ShowWindow(Handle, SW_RESTORE);
               } else {
                        printf("ProgramExecute(%s) = %d\r\n",CommandLine,ProgramExecute(CommandLine));
                        Handle = FindWindow(WinClassName, WinTitle);
               }
               return Handle;
      }


      This was fine until Windows 2000/XP. When a background task is activated, Windows may
      prevent it from moving to the foreground, and flashes the icon instead (so it is still lost behind
      WinCC). This behavior is designed to keep background tasks from stealing focus.

      You can control this behavior by editing the registry:

           1. Use Regedt32 to navigate to HKEY_CURRENT_USER\Control Panel\Desktop.
           2. Edit or Add Value name ForegroundLockTimeout, a REG_DWORD data type.
              Set the data value to 0 to disable this behavior. The default is 200000 milliseconds. If
              the time since the last user input exceeds the data value, the window is automatically
              brought to the foreground.
           3. Edit or Add Value name ForegroundFlashCount, a REG_DWORD data type. Set
              the data value to the number of flashes. The default is 3.




Rev: 1, 18 Nov 2005                              Doc no: 0000-0000-SRP-1                                      0000-0000
Status: As-Built                                      Page 36 of 36                                      SIMATIC Project

				