Industrial Power Supply
This power supply is recommended for panel installations of Gatecraft
products, or where the included desktop power adapter does not meet your
requirements. Example instances where you may prefer this supply include:
• Panel/cabinet mount installations
• Where UL approval is required
• When DIN rail mounting is desired
• When more robust power supply is desired (fused, less AC line
noise, industrial power connections)
Features
• Universal AC input (85-264 VAC)
• DC compatible input (120 to 370 VDC)
• Short circuit/Over load/Over voltage/Over temperature protection
• DIN-Rail mountable
• Cooled by free air convection
• 100% full load burn-in test
• UL508
• Fix switching frequency at 100KHz
• LED indicator
• 95 × 36 × 108mm (3.74 × 1.42 × 4.25in)
Hardware
• Output
• 48W wattage
• 24VDC
• 2A rated current
• 0 to 2A current range
• 480mVp-p maximum ripple and noise
• 21.6 to 26.4V voltage adjustment range
• ±1% voltage tolerance/line regulation/load regulation
• Setup/Rise/Hold Time: 800ms, 60ms, 50ms/230VAC at full load
• Input
• (85 to 264VAC) and (120 to 370VDC) voltage range
• 47-63Hz frequency range
• 80% efficiency
• (1.5A/115VAC) and (0.75A/230VAC) AC curent
• (cold start: 30A/115VAC) and (60A/230VAC) maximum inrush current
• Protection
• Over load:
105 to 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault
condition is removed
• Over voltage:
27.6 to 32.4V
Shut down o/p voltage, re-power on to recover
• Over temperature:
135°C typically (U1) - Detect on heat sink of power transistor
Shut down o/p voltage, recovers automatically after temperature goes down
• Environment
• -10 to 50°C operating temperature (-20 to 85°C storage)
• 20 to 90% RH non-condensing working humidity (10-95% storage)
• Temperature coefficient: ±0.03% / °C (0 to 50°C)
• 10 to 500Hz, 2G 10min/1 cycle, period for 60min each along X, Y, Z axes vibration
• Regulations
• UL508, TUV EN60950 Approved
• EN55011, EN55022 (CISPR22) Class B
• EN61000-3-2,-3
• EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2)
Heavy industry level, criteria A
• 93 × 78 × 67mm (L × W × H)