The Fitz-George Consultancy









Fire Risk Assessment for

Residential Care Homes









XX 200x







Page 1 of 31

Executive Summary





The main areas of concern that have become apparent as a result of this fire risk

assessment and that are in need of prompt attention are: -



1.



2.



3.



4.



5.



6.







These important points along with all other matters in need of action with respect to fire

safety will be explained in much greater detail within the report itself.









Page 2 of 31

Contents

1. Background .................................................................................................................................... 5



2. Fire Risk Assessment ..................................................................................................................... 6



2.1 Premises Overview .................................................................................................................. 6



2.2 Fire Hazards & Ignition Sources.............................................................................................. 7



2.2.1 Summary of Significant Findings ................................................................................... 10



2.3 People at Risk ........................................................................................................................ 10



2.4 Control Measures ................................................................................................................... 12



2.4.1 Detection and Warning ................................................................................................... 12



2.4.2 Fire Fighting.................................................................................................................... 14



2.4.3 Escape Routes and Evacuation Arrangements ................................................................ 16



2.4.4 Housekeeping .................................................................................................................. 19



2.4.5 Emergency Lighting........................................................................................................ 19



2.4.6 Signs and Notices ............................................................................................................ 21



2.5 Maintenance and Other Risks ................................................................................................ 22



2.6 Information Instruction and Training..................................................................................... 24



2.7 Records .................................................................................................................................. 25



2.8 Review ................................................................................................................................... 26



3. Action plan ................................................................................................................................... 27



Appendix A – Fire Compartmentation Review .............................................................................. 30







Note. The full manual on which this fire risk assessment is based and which gives clear

instructions on how to do it, can be downloaded free of charge at the following link: -



http://www.communities.gov.uk/publications/fire/firesafetyrisk5









Page 3 of 31

READ THIS FIRST



Note. Only an individual with a reasonable understanding of fire safety should do this fire

risk assessment. Those without any core fire safety knowledge should seek some form of

instruction on the principles of fire safety and fire risk assessment and many local fire

authorities run such courses for businesses at reasonable, or sometimes no expense.



The above fire safety instruction can and ideally should be done by homes‟ owners, to

ensure that the knowledge and expertise on fire safety is always available at the site.



If this is not desired or possible, competent and qualified providers such as The Fire

Protection Association run courses and produce specific literature on fire safety in care

homes and these details can be found at the following web site: - http://www.thefpa.co.uk/.



If professional help is required, a register of qualified assessors can be found on The

Institution of Fire Engineers web site at the following address: - http://www.ife.org.uk/frr/.



All completed fire risk assessments should be shown to your local fire authority on

completion to ensure that all appropriate areas have been covered and suitable measures

have been taken to protect clients, staff and the business.



Note that the completion of a suitable and sufficient fire risk assessment is not only a legal

obligation, but will in all probability be a mandatory duty in the insurer‟s terms and

conditions clauses of your current insurance policy.



Other Useful Websites



The Health and Safety Executive (HSE), the UK‟s main governmental organisation for

health and safety: - http://www.hse.gov.uk/index.htm



The Institution of Occupational Safety and Health (IOSH), the UK‟s leading safety

organisation for safety professionals: - http://www.iosh.co.uk/index.cfm?go=home.main









Page 4 of 31

1. Background

On the XX 2008, NAME undertook a full fire safety risk assessment at xx. The

establishment provides living, sleeping and eating facilities for up to XX service users. The

premises are owned by xx and managed and staffed by xx.



The purpose of this assessment was to identify significant fire hazards within the premises

and highlight any areas for immediate or long-term improvement. An action plan with

timescales is attached to assist in the prioritisation of any such actions (also see priority

ratings below). This assessment replicates the requirements made in the appropriate

Regulatory Reform Manual, „Fire Risk Assessment, residential care premises‟ issued by

HM Government.





The observations and any recommendations made are only pertinent to the conditions

found at the time of the assessment or review. Regular inspections and risk assessment

reviews are required to ensure that appropriate standards are maintained. Please note that

any checks made of compartment integrity under false ceiling areas or in roof voids, will be

specifically detailed in this assessment. If this has not been possible due to the ceiling or

roof voids‟ construction, a statement will be made in the report to this effect and inspection

of these areas may have to wait until substantial maintenance or repair works are next

carried out.



Wherever a recommendation has been made within this risk assessment, a priority rating

has been assigned which translates as: -





Priority Ratings

0 No action required



1 Urgent – Complete within 1 week of assessment date



2 Complete within 1 month of assessment date



3 Complete within 3 months of assessment date



4 Complete within 6 months of assessment date



5 Complete within 12 months of assessment date

RRO Care Home Online Version 1, July 2009.









Page 5 of 31

2. Fire Risk Assessment

2.1 Premises Overview



This section provides information on the premises and its current use. Note. Technical

drawings of the premises may also accompany this fire risk assessment in order to understand its layout, size

and room locations. There may also be a document showing photographs taken at the site during the

assessment that pinpoints particular issues.

Name & address of

premises

Note. Does the site have a completion

certificate from the local authority Building

Inspector (new buildings)



Type of premises



Owned by



Managed by



Designated person

Premises used out of

Yes

normal office hours?

Type of structure



Number of lift shafts 0

Use Yes No

Offices ✓

Sleeping accommodation

Living / lounge areas

Internal smoking areas

Industrial kitchens

Use of premises

Kitchenettes

Manufacturing processes

Workshops

Hot work e.g. welding

Flammable substance storage

Other:

Total number of people x employees (shift workers and day staff)

A breakdown of the total number

x service users

of people employed and / or

staying at the premises Total



Monday - Friday Saturday - Sunday

Occupancy profile 0000 - 0400 0000 - 0400

0400 - 0800 0400 - 0800

Maximum number of persons in

the most highly occupied

0800 - 1200 0800 - 1200

compartment or area of the 1200 - 1600 1200 - 1600

premises at a given time 1600 - 2000 1600 - 2000

2000 - 2400 2000 - 2400



Page 6 of 31

2.2 Fire Hazards & Ignition Sources



The premises have been divided up into the following locations. Any fuel and ignition

sources are then identified within rooms or areas in order to gain an understanding of the

likelihood of a fire starting.



This section corresponds to „Identify fire hazards‟, in Step 1 of the RRO Manual with fuel

and ignition sources being categorised below. Oxygen sources as the manual states,

‘comprises of natural airflow through doors windows and other openings; or mechanical air

conditioning systems and air handling systems’ and these are mentioned where present.

Other sources of oxygen may include oxidising materials and oxygen cylinders, again as

per the RRO manual, and these will be identified in this section where and if found.



Note. Augment and delete the details below to mirror the configuration of your care home



GROUND FLOOR



Room / area Fuel source(s) Ignition source(s)

 All bedrooms  Clothing  Faulty electrical

 Bed linen equipment or wiring

 Furnishings  Unauthorised

 Curtains smoking

 Clients‟ personal  Arson

electrical equipment

 Wiring

 Main kitchen and kitchenettes in  Cooking oil  Faulty hobs, cookers

accommodation areas  Gas or fryers

 Foods  Faulty electrical

 Kitchen appliances equipment or wiring

 Wiring  Unauthorised smoking

 Reception office  Paper  Smoking materials

 Staff room/Handover room  Furnishings  Faulty electrical

 Visitors‟ room  Wall hangings (e.g. equipment or wiring

 Medical room curtains, leaflet  Unauthorised

 Entertainment/Activities room holders, pictures). smoking

 Laundry room  Clothing  Arson

 Lounges  TV, computers,

 Bathrooms washing machines

 WCs and other electrical

 Smoking room equipment

 Corridors  Flammable

 Main dining areas products in

 Hairdresser‟s room cleaners‟

cupboards, medical

 Other rooms

or hairdressers‟

rooms

 Wiring









Page 7 of 31

 Internal electrical distribution  Miscellaneous  Faulty electrical

cupboard and main exterior combustibles equipment or wiring

electrical incomer and distribution (wood, paper,  Faulty gas boilers

board rubbish etc.).  Arson

 Main gas incomer  Decorating  Fireworks (seasonal)

 Exterior garden sheds materials  Smoking

 Boiler Room (Internal or External)  Gas, oil, electricity  Sparking from tool or

 Small additional internal boiler  White spirit and/or object striking hard

 Garden area discarded cooking surface (if gas

 External store rooms oil present)

 Bin Areas including any skips  Gas, electricity

present  Garden refuse

including leaf

accumulations

 Garden sheds and

contents

 Substances given

off by faults in

battery rooms

 Wiring







FIRST FLOOR

Room / area Fuel source(s) Ignition source(s)

 All Bedrooms  Clothing  Faulty electrical

 Bed linen equipment or wiring

 Furnishings Unauthorised

 Curtains smoking

 Clients‟ personal  Arson

electrical equipment

 Wiring

 Bathrooms  Furniture  Faulty electrical

 WC‟s  Curtains equipment or wiring

 Lounges  TVs, computers,  Unauthorised

 Hairdresser‟s room other electrical smoking

 Kitchenettes equipment  Arson

 Storage cupboards  Flammable

 Corridors products





Note. Furniture and soft furnishings at this home are purchased on the basis that they are

of a suitable BS fire retardant standard.



Qualify. Delete the above statement and this advisory if you cannot comply with its

condition. By having furnishings that are not fire retardant, you risk the chance of a fire

that does occur spreading more quickly.









Page 8 of 31

Other Areas



Room / area Fuel source(s) Ignition source(s)





 Pitched roof voids  Wooden beams  Electrical motor or

 Flat roofs and joists wiring fault

 Lift shafts and rooms  Roof surface  Defective kitchen

 Under ceiling voids (false ceilings) coverings, e.g. tar extraction system

paper and wooden  Defective lightening

clapperboard protection

facings  Unauthorised

 Items stored in roof smoking

voids without

authorisation, e.g.

paper, cardboard

 Lubricants and oils

used for lift

machinery

maintenance

 Wiring

 Electrical

equipment

 Lift décor and facia







Substantial quantities of oxidising materials, oxygen cylinders or any

other hazardous material found at the site?

Room / area Fuel source(s) Ignition source(s)









Some abbreviations used in this document: -



„The Fire Safety Order‟ – The regulatory Reform (Fire Safety) Order 2205



„RRO Manual‟ – The appropriate guidance manual for this type of premises



„Approved Document B‟ – The building Regulations 2000 covering Fire Safety



„BS‟ - British Standards‟ technical guidance documents







Page 9 of 31

2.2.1 Summary of Significant Findings



 Smoking materials (accidental fire

started by elderly client)

 Boilers and heaters

Main ignition sources  Electrical appliances and wiring (if

Based on use of premises and occupancy profile faulty)

 Cooking processes, e.g. hobs and

cookers (if cooking equipment faulty)

 Arson

 Sleeping accommodation

High risk area(s)  Smoking room

Based on use of premises, occupancy profile and  Kitchens

findings during assessment  Boiler room

 Main electrical and gas incomers





SECTION RECOMMENDATIONS

Ref Recommendation(s) Priority









2.3 People at Risk



The following people have been identified as regular users of the premises and as such are

likely to be at risk in the event of a fire occurring.



This section corresponds to Step 2 of Figure 1 in the RRO Manual, „Identify people at

risk‟. (copy and paste the ✓ symbol into the appropriate yes/no column)



Type of people Yes No Comments



Employees ✓



Agency staff



Visitors / guests







Page 10 of 31

Cleaning staff



Contractors



Anyone with hearing impairment



Anyone with visual impairment



Service user - older people

Service users „higher risk

considerations‟.

What is the population type at this

establishment? If it is simply older clientele

with conditions normally associated with old

age, then the risk level will be that

associated with an average residential care

home. However, if there are a large

number of wheelchair or dementia sufferers

at the site, then the site‟s risk level will be

higher, which will adversely affect such

things as evacuation times and travel

distances. Is there a higher than normal

chance of an arson incident occurring at the

site due to the age and nature of its

clientele? If either of these factors or others

not mentioned here are present, then due

consideration will have to be made of this in

appropriate areas of the risk assessment.

Are users with poor mobility

accommodated on the ground

floor?

Service user - children



Service user - mental health



Service user - learning difficulty



Service user - physical disability



Others, e.g. security staff



Trespassers





SECTION RECOMMENDATIONS

Ref Recommendations Priority









Step 3 of Table 1 in the RRO Manual







Page 11 of 31

Sections 2.4 through 2.5 below, covers Step 3 of Figure 1 in the RRO manual requiring the

controller of the workplace to „Evaluate, remove, reduce, and protect from risk‟. It

includes appropriate evaluation of the risks of a fire occurring, the risks to people from fire,

action needed to remove or reduce fire hazards and action needed to remove or reduce the

risks to people.



2.4 Control Measures

2.4.1 Detection and Warning



All premises must have fire detection and warning systems fitted and there are few if any

exceptions to this. The system should incorporate fire detection devices, a control panel,

audible and / or visual alarms and manually operated break-glass boxes as a means of

ensuring the early detection of fire and safe and prompt escape of a site‟s inhabitants. The

majority of detectors at care homes should be smoke type, the principle being that these

give the quickest detection and alarm activation time in the event of any fire starting. Heat

detectors should be used in areas where smoke detectors would result in false alarms. An

L1, detection system throughout premises should be used at care homes to give the

quickest possible alert of a fire condition. The following system exists within this particular

premises: -





System model







Control panel location(s)





System maintained by

System Category, e.g. L1

Note. For reference BS5839-1 stipulation‟s state

that in an L1 system all areas need to be covered

save for the following: -



f) In a Category L1 or P1 system, automatic fire

detectors should be installed in all rooms and

areas of the building, but the following rooms or

areas need not be protected if they are of low fire

risk (see 3.31):

— toilets, shower rooms and bathrooms;

NOTE 7 In some public buildings, such as hospitals and

shopping centres, toilets might not be of low fire risk, owing to

the potential for arson.

— stairway lobbies" and toilet lobbies;

— small cupboards (typically, less than 1 m 2);

NOTE 8 A riser in which there is a fire resisting floor and

ceiling may be treated as a cupboard.



Note. An L1 system is the usual model fitted at care

homes and this is in line with the recommendations

made in BS5819-1, Section 2, sub-section 8.1.2

which states the following: -



An L1 system might be appropriate in buildings in





Page 12 of 31

which there is a significant number of occupants

at special risk in the event of fire (e.g. hospitals

and certain residential care premises), or in

which, throughout the building, structural fire

precautions are not of as high a standard as

normally specified for buildings of that type.









Is this acceptable for the risks present?



Smoke ✓

Type(s) of automatic fire detection Heat

Flame

Audible siren/bells

Visual strobe / flashing light

Type(s) of automatic fire warning

Vibrating pad

Pager (allows for delayed alarm)

Water sprinkler

Type(s) of automatic fire fighting CO2 suppression

Foam suppression

Do main kitchens have appropriate fire

detection and damper systems within

their extract systems and are extract

*Heavy-duty cooker installations in main kitchens may have flame

fans interlocked with the main detection detection and smoke detection within ducting runs. They may/will

system and turn off in the event of a fire also have fire damper capability inherent in their construction.

alert? * (Erase if not applicable or format black if it is)





Are any fire alarm zones within the site

greater than 2000m2 and if so, does the

site have an addressable fire panel?



Note. If the site has only a simple single zones fire

2

panel then no single zone should exceed 2000m as

per BS5839-1: -

13.2.3 Additional recommendations

applicable to detection zones that contain

non-addressable automatic fire detectors

The following recommendations are applicable.

a) The floor area of a single zone should not

exceed 2000 m2.

b) The search distance (the distance that has to be

travelled by anyone responding to a fire alarm signal after

entry to the zone in order for the location of the fire to be

determined visually, see 3.50) should not exceed 60 m.



Are there any large voids in pitched

roofs or are there flat roof ceiling voids

over 800mm and if so has detection

been fitted within them?







Page 13 of 31

Does the alarm system have a back-up

battery?



Is there an audible alarm in the boiler

room?



Can the alarm be heard clearly in all

parts of the site?

e.g. 65dBA or 5dBA above persistent

background noise levels, 75dBA at the

bedheads (45dBA throughout high

dependant premises permissible).



All manual call points within 45m

distance?

Note. The requirement for call points at 25m

intervals is in all probability not feasible at care

homes, as though the majority of persons at these

sites are of limited mobility, their mental state is

such that they are unlikely to fulfil the following

criteria in BS5839-1, that; ‘it can reasonably be

anticipated that one of these occupants will be the

appropriate person to first operate the fire alarm

system in the event of fire’.



Date of last weekly system (bell) test?

Has it been done within the last 7 days?



Is a different call point used (in rotation)

for the test?



Date of last service (must be within last

six months as per BS5839-1)



Records up to date





SECTION RECOMMENDATIONS

Ref Recommendations Priority







2.4.2 Fire Fighting

All premises must have appropriate first aid fire fighting equipment provided for use in a fire

emergency. This can be used if, for example, an exit is blocked due to fire and escape

needs to be made via it, or if a fire starts that is small enough to be tackled and put out by

trained staff as long as it is safe for them to do so and before it can get larger. Equipment

should be provided at strategic points around the building (usually by fire exits or in high

risk areas e.g. kitchens or boiler rooms) and should be safe to use and suitable for the type

of fire it is to be used on (e.g. Class „A‟ for organic/paper type fires). It must also be

properly maintained to appropriate BS standards. Note that a recent article in Fire



Page 14 of 31

Engineering stated that 80% of fires are put out using first aid fire-fighting equipment; its

proper provision is therefore a prudent (and legal) measure at your site. Premises with

sprinkler systems must ensure that to avoid any sprinkler systems‟ failures, the appropriate

testing regimes per BS standards are carried out. The following equipment exists within

these particular premises:



 Water

 Carbon dioxide

 Dry powder

 Foam

Types of equipment

 Class F

 Hose Reels

 Fire blankets

 Sprinklers



Location(s)







Portable Fire Fighting Equipment

maintained by: -



Date of last service (annual as per

BS5306-3: 2003)

Records up to date



Date of last sprinkler system service (if

present). A service must have been

done within the last year as per BS

Standards, BS9251: 2005. Areas that

need not be covered by sprinklers

include: -

5.2.3 Extent of sprinkler protection

Sprinkler protection should be provided in all parts

of the dwelling, with the permitted exception

of: bathrooms with a floor area of less than 5 m2;

cupboards and pantries with a floor area of less

than 2 m2 and where the least dimension does not

exceed 1 m and the walls and ceilings are covered

with non-combustible or limited-combustible

materials; non communicating, attached buildings

such as garages, boiler houses, etc.; crawl spaces.

NOTE 1 “Non communicating” means separated from the

protected premises by a 30 min fire resisting construction in

accordance with BS 476 or equivalent European Standard.

NOTE 2 Certain authorities may require 60 min fire resisting

construction.

NOTE 3 Lift shafts are not excluded from protection.



Source: Fire Sprinkler Association









Page 15 of 31

Sprinkler System maintained by: -







Records up to date





SECTION RECOMMENDATIONS

Ref Recommendations Priority









2.4.3 Escape Routes and Evacuation Arrangements



All premises must have escape routes and emergency exits that allow persons to quickly

evacuate during a fire emergency either to a place of safety outside and in the open air, or

to reach a place of safety within the site, such as a fire-resisting compartment or refuge

area. This needs to be able to be done within a short period of time, e.g. 2.5 minutes,

depending on the site‟s layout and population. This is particularly important where a PHE

or Progressive Horizontal Evacuation system is in use. Escape routes should be protected

from fire for a designated amount of time (at least 30‟), and there should be enough exits

provided to enable the safe escape of the site‟s entire population at any time. All

emergency exits should be fee from obstruction and be able to be used without the use of a

key.



Adequate evacuation procedures should also be in place, which ensure the prompt and

orderly evacuation of persons within the site to appropriate safe areas.



The table below gives information about the numbers and physical state of fire exits and

escape routes at the site and details about the site‟s evacuation systems and procedures:







Main access to building









Page 16 of 31

Alternative means of escape





Travel distances acceptable?

Is compartmentation acceptable for the

layout and size of the premises? Has the

risk level been assessed using available

data to determine what a suitable

„protected area‟s size (see pages 67-69 &

76 of RRO) is?

Is structural integrity of

compartmentation acceptable, e.g. are

there any holes/breaches in

compartment walls, any missing

sections? Are all materials, e.g. glass

on windows or walls within escape

routes, of a correct robustness/fire

resistance throughout compartments‟

borders? Note. See Appendix „A‟ for

compartmentation verification check sheet.

Is the protection of escape routes

acceptable, e.g. doors, windows, door

co-ordinators, magnetic locks, self-

closers, smoke seals?



Have fire-resisting doorsets been

extended under false ceilings to

structural ceiling height?



Do bulkheads within pitched roofs have

fire-resisting doorsets directly below

them to prevent fire spread within a

compartment?

Are lift shafts compartmented or within

a protected enclosure and is there an

appropriate 0.1m2 vent at the top of each

lift well to allow smoke to escape?

Wall and ceiling coverings of escape

routes acceptable, e.g. Class „0‟?

Are all escape routes free from

obstructions?

Evacuation Arrangements and

Procedures in Case of Fire

Number of daytime staff on duty?









Page 17 of 31

Number of night time staff on duty?



Is there a written fire evacuation

procedure that covers daytime and night

time fire evacuation procedures and is it

reviewed and if necessary updated at

regular intervals (see also Instruction,

Section 2.6)?



Is the current staffing level considered

adequate enough to ensure the safe and

prompt evacuation of service users to a

place of safety within a reasonable time

(2.5 minutes to next protected area as per pages 69

& 70 or RRO)? Consider numbers and mobility of

service users. Note. Progressive horizontal

evacuation of elderly service users or those with

reasoning difficulties is considered the primary

procedure used for evacuation of this type of site by

the fire authority, with evacuation to the outside

considered only if this method is deemed to be

unsafe due to the fire’s size or the way in which it is

spreading.

Are there any employees or service

users who need assistance to evacuate

from the building? e.g. wheelchair

users



If yes, does each one have a written

Personal Emergency Evacuation Plan?



Is there a signing in / out system for

visitors and contractors?

Are contractors and other visitors, e.g.

Social Care or Health Visitors, briefed

on fire evacuation procedures when

they arrive at the site?

Note. These persons should evacuate on

a single stage basis as opposed to the PHE

system used for clients.

Are visitors chaperoned throughout

their visit?

Are external routes to the assembly

point acceptable and do they lead to a

place of safety?

Fire assembly point location(s)

acceptable, e.g. sufficiently far enough

away and in a safe place to prevent

harm to persons from smoke, radiated

heat, fire or any traffic in the area?





Page 18 of 31

SECTION RECOMMENDATIONS

Ref Recommendations Priority









2.4.4 Housekeeping



Good housekeeping is an essential part of effective fire safety management and ensures

that unwanted fire load does not build up at a site and that emergency escape routes and

exits are kept clear at all times. The following table describes the standard of

housekeeping found at this site:



Are housekeeping standards

acceptable?





SECTION RECOMMENDATIONS

Ref Recommendations Priority









2.4.5 Emergency Lighting



All „means of escape‟ must be adequately lit to ensure the safe escape of persons from a

place of danger to a place of safety during a fire or other emergency, especially where

there is no natural light available such as in internal rooms or corridors or during the hours

of darkness.



There should be suitable levels of lighting available during an emergency that illuminate an



Page 19 of 31

area to an adequate degree, e.g. BS 5266 Pt 7: 1999 (EN1838) calls for a minimum of 1 lux

anywhere on the centre line of the escape route for normal risks and this should be

measured as being present at the site if there is any doubt that this level is not being

achieved. Note that there does not have to be an individual light for each item in the list

below, the caveat being that the appropriate level of lighting is achieved in the area using

the luminaries present. Installations kite marked EN60598-2-22 are currently compliant.

The following guidance is given in the appropriate RRO manual as to where emergency

lighting should be located: -



An escape lighting system provided for escape purposes would normally cover the following:



• Each exit door (within 2m); • Escape routes; • Intersections of corridors;



• Outside each final exit and on external escape routes; • Emergency escape signs;



• Stairways so that each flight receives adequate light; • Changes in floor level;



• Windowless rooms and toilet accommodation exceeding 8m2;



• Firefighting equipment; • Fire alarm call points; • Boiler room



• Equipment that would need to be shutdown in an emergency; • First Aid points



• Lifts; and • Halls or other areas greater than 60m2.



It is not necessary to provide individual lights (luminaires) for each item above, but there should be a sufficient overall

level of light to allow them to be visible and usable.







It is essential therefore that areas, particularly escape routes and emergency exit doors

(both internally and externally) contain a suitable number of emergency lighting units to

ensure the safe escape of occupants should the site‟s main lighting system fail.



Please note that emergency lighting systems must be fully maintained to appropriate British

Standards and inspected at regular intervals according to criteria laid out in these

standards.



A guidance document on emergency lighting systems‟ design can be found at the following

link: - http://www.menvier.co.uk/dg_emersystem.html



The following emergency lighting configuration exists within these particular premises: -







Type of system

e.g. maintained, non-maintained,

generator, mixed.





Location(s)









Page 20 of 31

Equipment maintained by





Are emergency lighting units located at

all „higher risk‟ areas?

Date of last service (must be within last

6 months)?

Records up to date?





SECTION RECOMMENDATIONS

Ref Recommendations Priority









2.4.6 Signs and Notices



All safety signs should be easy to see and understand. Signs must be of a pictograph type

and be of a colour specific to their use and meaning e.g. red for prohibitory signs such as

no smoking, green for safe conditions such as a direction of escape in a fire emergency. It

is permissible to provide supplementary information in words or by using additional

pictographs such as arrows, but safety messages consisting of words only are no longer

allowed. The following table comments on the state and adequacy of fire safety signage at

this site:





Do all of the fire safety signs and

notices comply with the Health and

Safety (Signs and Signals) Regulations

1996 and other applicable guidance

documents e.g. BS 5499, the FPA Guide

to Fire Safety Signs?



Are there adequate fire exit signs?



Are “site specific fire action” notices

displayed?



Are there adequate “fire action” notices

(site specific and general)?





Page 21 of 31

SECTION RECOMMENDATIONS

Ref Recommendations Priority









2.5 Maintenance and Other Risks



This section is used to highlight maintenance procedures at the site. It is also used to

identify any „other risks‟ (including special ones) that have not been covered within specific

sections of this fire risk assessment or are considered, due to their high-risk nature, to be

worth reiterating in this section for the sake of clarity and to ensure action is considered.



Are there any acetylene or gas cylinders

at the site (e.g. LPG type)?

Are there any oxygen or other types of

medical gas cylinders at the site?



Information re the safe use of oxygen

cylinders can be found at the following

HSE link: -



http://www.hse.gov.uk/pubns/hse8.pdf



Is there a permit to work system in use

at the site and are staff aware of how it

works?

Has appropriate equipment been PAT

tested?

Does the site have lightening protection

and has this been tested?

Note. This system is subject to annual testing and

inspection as detailed and laid down in BS6651.

Has the electrical system been tested in

the last 5 years?



Does the site have gas-fuelled systems

and are they maintained?

Has the main kitchen‟s cooker

extraction vent for fat fryer etc been

deep cleaned in the last 3, 6 or 12

months?





Page 22 of 31

The link below may help staff to calculate the

appropriate cleaning schedules for the site: -



http://www.indepthhygiene.co.uk/1TR19SECTIO

N7.htm





Are the dryers in the laundry room/s lint

traps cleaned/vacuumed weekly?



Are ashtrays emptied into metal-lipped

bins at the end of the day?



Are there any garden sheds or other

structures located close to the main

buildings? If so, is there a chance that

due to their proximity to the site, a fire

within them may spread into the main

building via windows (radiation), via

overhanging roofs (flat or pitched) or by

any other means (e.g. burning brands)?



SECTION RECOMMENDATIONS



Ref Recommendations Priority









Step 4 of the RRO – record, plan, inform, instruct and train, and Step 5, Review



Sections 2.6 through 2.8 below, covers Steps 4 and 5 of Figure 1 in the RRO manual

requiring the controller of the workplace to



Step 4:



 Record significant findings and action taken



 Prepare an emergency plan



 Inform and instruct relevant people; co-operate and co-ordinate with others



 Evaluate, remove, reduce, and protect from risk‟



 Provide training



Step 5



Page 23 of 31

 Keep assessment under review



 Revise where necessary



2.6 Information Instructions and Training



A vital component of effective fire safety management is the provision of adequate

information, instruction and training re fire emergencies to all employees. For example, the

procedures for escaping, contacting the fire service, assisting others in the event of a fire

emergency and dealing with contingencies (e.g. defective sprinkler or detection systems)

must be communicated to all appropriate staff. The current state of these arrangements

and systems at this site, are detailed in the table below:







Is there an established fire emergency

plan as per Section 7.2 of the RRO?



Is the plan written down and available?



If yes, is it appropriate?

Is there appropriate cooperation and

coordination re fire emergency and

evacuation procedures, with any other

undertaking that may be on the site, e.g.

day centres, special needs, mobility for

the elderly organisations?

Are employees familiar with the

evacuation plan?

Try asking someone if they know what to do

Are evacuation drills conducted and

have they so far meet with the standards

outlined and required in Section 2.4.3 of

this document (verify records confirm

drills and optimum 2.5 minute

evacuation time)?



Records up to date?



Have all staff been given suitable

information, instruction and training to

satisfy the requirements for service

users‟ evacuation contained in Section

2.4.3 of this document?



Have fire wardens been nominated?









Page 24 of 31

Is there an adequate number?



Have the nominated fire wardens been

given enhanced training (e.g. able to

supervise other, „all‟ staff as per above)

to satisfy the requirements for service

users‟ evacuation contained in Section

2.4.3 of this document?

Have all employees been given a basic

level of fire safety awareness training in

other fire safety matters such as use of

extinguishers, raising the alarm,

identification of fire hazards, procedure

for reporting hazards etc.?







SECTION RECOMMENDATIONS

Ref Recommendations Priority









2.7 Records



Suitable, sufficient and up-to-date records are required to show that the site‟s fire safety

systems, their maintenance, and appropriate fire safety training and procedures for

personnel have been checked, are being maintained and that they work correctly. A site

fire logbook should be kept and any fire-related incidents, events, drills and maintenance

checks etc. are to be recorded in this. The following documents and records were seen at

these premises (Note. a comment is also made in this section if records documents were

not found to be present):



Type of record Yes No Comments

Fire register

Personal emergency egress plans

(PEEP)







Page 25 of 31

Monthly fire safety inspections



Employee fire safety induction



Employee training records

Are fire records kept for at least

three years for insurance

purposes?



SECTION RECOMMENDATIONS

Ref Recommendations Priority









2.8 Review



This risk assessment should be reviewed:



 Following any structural or material changes to the premises;

 Following a change in the nature of work practices or processes;

 Following changes in staff levels or disposition;

 Following a sizeable change in the type of clients being accommodated at this site, e.g.

the site moves from a moderate number of immobile and mentally adept clients to a

large number of wheelchair and/or dementia sufferers.

 Following a near miss or actual fire;

 In any case it is recommended at intervals not exceeding 12 months.



SECTION RECOMMENDATIONS

Ref Recommendations Priority









Page 26 of 31

3. Action plan



Priority Ratings

0 No action required



1 Urgent – Complete within 1 week of assessment date



2 Complete within 1 month of assessment date



3 Complete within 3 months of assessment date



4 Complete within 6 months of assessment date



5 Complete within 12 months of assessment date



Recommendation

Reference No. Recommendation Priority To be Actioned by Date Completed









Page 27 of 31

Recommendation

Reference No. Recommendation Priority To be Actioned by Date Completed









Page 28 of 31

Recommendation

Reference No. Recommendation Priority To be Actioned by Date Completed









Page 29 of 31

Appendix A – Fire Compartmentation Review



Compartmentation Verification Check Sheet (2.4.3)



Compartment‟s Compartment‟s Number of Compartments‟ integrity

Location length in Rooms*** satisfactory, Yes? No? If

metres* no, state why. **









* Measure and verify travel distances within compartments to ensure they are within RRO

limits. Obtain compartment integrity information from any available area e.g. voids, lift

shafts, service ducts.



** Any defective compartments are to be reported to the site‟s Fire/Health and Safety

responsible/competent person as soon as possible so that remedial action can be taken.



*** Includes all bedrooms, lounges, dining rooms, miscellaneous rooms, WC‟s, sluice

rooms etc., but not small cupboards.



**** Estimated or not measured, as I could not use a laser-measuring device in close

proximity to guests or staff for safety reasons.



Compartment integrity is achieved when there are no holes or gaps in fire resisting walls

and doors and when fire resisting walls or doors dividing compartments, continue up from

these features and through any void (e.g. a ceiling void above a door set or room/corridor

wall) up to the building‟s fire-resisting roof bulkhead (one storey building), or floor of the

compartment above (multi-storey building). See Section 4.1, General Principles, paragraph

headed „fire resisting construction for further advice.



END OF REPORT



Page 30 of 31

Disclaimer



This document is provided for the use of persons wishing to carry out a fire risk assessment

of care homes and in accordance with the stipulations and caveats in the READ THIS

FIRST statement at the beginning of this document. It is provided free of charge and can

be duplicated an unlimited number of times.



The object of providing this document is to promote awareness of fire hazards in residential

care homes and to encourage best practice with respect to fire safety procedures. The

author hopes that by providing the document in this way that both residents, their families

and staff member‟s lives will be saved and injures avoided.



All information published in this document has been gathered from sources, which are

believed to be reliable but the reader and the user should not assume that the information

is official or final. Paul Fitz-George and the Fitz-George Consultancy do not assume

responsibility for errors or incorrect or unqualified use of any or all of the information used

and the information is subject to change without notice. The reader/user must therefore

keep up-to-date with the concepts used via the various web links e.g. the IFE, FPA, IOSH,

HSE that are given in the document to ensure that the latest criteria are applied to the fire

risk assessment‟s questions.



Certain programs, projects and links listed here are not operated by nor are they the

responsibility of the Fitz-George Equine Consultancy. Links from these pages to external

Web sites are provided as a service to readers/users and do not constitute an endorsement

by Fitz-George Equine Consultancy, save for the ones to the IFE, FPA, IOSH and HSE.





Note. Don‟t forget to update the indexe‟s page numbers once you have completed the risk

assessment. This will ensure that the correct page number is shown in the index and

enable you to quickly go to the page number by just clicking on it in the electronic version of

the document. The sequence to do this is: -



 Right click on the index table anywhere



 Select the „update field‟ option



 Select „update page numbers only‟



 Click on „OK‟



Your new page numbers will then be shown on both the index and take you to the right

location when you click on them



Any Comments



Comment (and any constructive criticism of course) on this form‟s content, is welcomed via

the contact form on the Fitz-George Consulting web site.







Page 31 of 31


Related docs
Other docs by HC111111154527
Dumbwaiter_Specs_for_Architects
Views: 1  |  Downloads: 0
2004_FBC_IBC
Views: 2  |  Downloads: 0
ref1jgr
Views: 1  |  Downloads: 0
Reserach 20manual 20RCSBPR 20team
Views: 2  |  Downloads: 0
CooperLCA
Views: 0  |  Downloads: 0
exhibitorlist20110801 e
Views: 1  |  Downloads: 0
tehnodom_garden
Views: 12  |  Downloads: 0
Life_exp_infant_mort
Views: 0  |  Downloads: 0
Embezzlement_101
Views: 0  |  Downloads: 0
By registering with docstoc.com you agree to our
privacy policy

You are almost ready to download!

You are almost ready to download!