ASTTAC TANK INSTALLATION AND MODIFICATION SUBCOMMITTEE



SHOP ERECTED STORAGE TANK RESEARCH



TASK FL REG MD REG



GENERAL NOTES









SITING REQUIREMENTS









DESIGN REQUIREMENTS









RELOCATION REQUIREMENTS









REPAIR AND MODIFICATION

TASK FL REG MD REG



CORROSION PROTECTION









ANCILLARY REQUREMENTS Emergency venting per NFPA 30

Tanks with connections below liquid level shall

have valves adjacent to the tank

High level gauge, alarm, or pump cut-off req'd









RELEASE PREVENTION AND LEAK DET. Tanks to have dikes with 10-4 cm/sec perm.

No flapper-type valves









CLOSURE

TASK MN REG NH REG



GENERAL NOTES Regulated by properties- type A (gasoline)

type B (Diesel) and type C ( asphalt)









SITING REQUIREMENTS









DESIGN REQUIREMENTS Ul142, API 620 and 650, UL 2085, PEI/RP 200-96

API 2165 and 2610

All new tanks to sit on impermeable liner or double

bottom with leak detection and cathodic protection

interstitial monitoring req'd

Tanks to be tightness tested per API 650 or

Saf-C 6009.1 for other than field erected



RELOCATION REQUIREMENTS Tested sound by tracer, vacuum, pressure or Tank to be thoroughly inspected and certified

hydro test structurally sound by PE or API 653 inspector

Leak detection req'd -visual, vapor or interstitial

monitoring





REPAIR AND MODIFICATION Tank must be protected from external corrosion Tank to be inspected for corrosion, abnormal

thinning, holes, and structural integrity

Overfill protection req'd

TASK MN REG NH REG



GENERAL NOTES

CORROSION PROTECTION Cathodic protection req'd unless on concrete, Bottoms protected by sacrificial or impressed

internally lined, double walled or double bottomed current cp per API 651 or NACE RP-0285-85

Shop built tanks and lines in contact with soil to Be designed and installed Cert Corrosion expert

dielectrically protected with a coating or PE

Designed by NACE expert-tested after 6 mos Sacrif inspected after 6 mos and every 3years

and every 3 years- impressed current every 60 days Imp Current checked monthly

Tank to be painted



ANCILLARY REQUREMENTS Substance transfer safeguards req'd ( spill boxes, Piping to be above ground with check valves and

remote fill boxes, containment areas) operating valve located as close to tank as possible

Lines cathodically protected if in contact with soil Steel pipe SCH 40 or greater

and not double walled Gauge and separate HLA req'd

Overfill protection req'd









RELEASE PREVENTION AND LEAK DET. 100% capacity plus displaced vol of tanks in dike Dike secondary containment determined by product

10% additional if exposed to rain

Secondary containment req'd

Permeability varies by type of product





CLOSURE

TASK NJ REG NY REG



GENERAL NOTES Fill Ports are colored coded based on product









SITING REQUIREMENTS









DESIGN REQUIREMENTS Tanks to have secondary containment, impermeable Tank to have impermeable barrier with leak

base, pipes to have remotely activated or readily monitoring system

accessible valves to prevent release. Ul 142 and 58, API 650 and 620, CAN4-S601-M84

Regular intergretity testing or static head CAN4-S630-M84, ASTM D4097-88, ASTM D3299-88

product testing CP must be used if tank rests on ground

Emmissions per NSPS, RACT and NESHAP Tanks must be painted

standards Tanks must be tested per API 650



RELOCATION REQUIREMENTS If tank is certified sound it may be reused









REPAIR AND MODIFICATION Impermeable barrier if repair exceeds 50% of All welds must be tightness tested

replacement cost

TASK NJ REG NY REG



GENERAL NOTES

CORROSION PROTECTION CP req'd for all tanks resting on ground

All exposed exterior surfaces of tanks, piping or

ancillary equip must be corrosion resistant

materials, coated or cathodically protected









ANCILLARY REQUREMENTS Valves to be close to tank to prevent product from Automatic shutoff valves

exiting sec cont. Level gauges req'd

Pipes cannot pass thru sec cont walls check valves for pump fed tanks

Overfill detection devices req'd valves req'd on piping below product level

high level alarm and way to immediately stop Spill protection req'd at pumps and valves

flow of product Piping greater than 2" dia shall have welded flanges

no threaded fittings where threads are exposed

to flowing product

on ground and underground piping to have sec cont



RELEASE PREVENTION AND LEAK DET. Secondary containment of dike req'd after secondary containment req'd

substantial reconstruction or replacement of tank 1x 10-6 cm/sec

(50% of tank replacement value) need normal vents, emergency vents







CLOSURE

TASK PA REG VA REG



GENERAL NOTES Certified company, installer and inspector reqd for

tank handling activities









SITING REQUIREMENTS









DESIGN REQUIREMENTS Cert tank company, installer to oversee work UL, API or STI

Cert inspector to sign off Strength tested

Test for tightness RPB req'd under or in tank

Sec containment liner req'd under tank









RELOCATION REQUIREMENTS Same as new Same as new









REPAIR AND MODIFICATION Cert tank company, installer to oversee work Reconstructed or bottom replacements to follow new

Cert inspector to sign off tank requirements

Work and testing per industry standards

Sec containment to be provided when bottom

replaced

TASK PA REG VA REG



GENERAL NOTES

CORROSION PROTECTION Metallic tank in contact with ground to be evaluated Corrosion Professional to det whether cp is needed

by corrosion expert when in contact with ground

Paint exposed surfaces

Linings to extend 18" up shell









ANCILLARY REQUREMENTS Emerg vents for overpressurization and excessive Safefill and shutdown devices req'd

vacuum. Normal vents for breathing cp for underground piping

Operating valve adjacent to tank









RELEASE PREVENTION AND LEAK DET. Level gauge, high level alarm req'd rpb req'd

Sec containment 1x 10-6 req'd

Area under bottom monitored by visual, mechanical

or electronic leak detection





CLOSURE

ASTTAC TANK INSTALLATION AND MODIFICATION SUBCOMMITTEE



FIELD ERECTED STORAGE TANK RESEARCH



TASK FL REG MD REG



GENERAL NOTES

was installed (grandfathering for pre 1998 and

pre 1991)









SITING REQUIREMENTS









DESIGN REQUIREMENTS Shop per UL 142, API 620, API 12B,F&P

STI F911-93, STI F921, ASME B96.1, UL 2085



Field Erected per ASME B96.1, API 620, 650,

12B or 12D







RELOCATION REQUIREMENTS Same requirements as new tank









REPAIR AND MODIFICATION Repairs made after tank is isolated from system

All repairs tightness tested before return to service

TASK FL REG MD REG



CORROSION PROTECTION Cathodic Protection Systems must be inspected

and tested w/in 6 mos and every year

Instlled per API 651and NACE RP-0193-93









ANCILLARY REQUREMENTS Spill containment req'd at outlets Emergency venting per NFPA 30

Per NFPA 30 Tanks with connections below liquid level shall

have valves adjacent to the tank

High level gauge, alarm, or pump cut-off req'd









RELEASE PREVENTION AND LEAK DET. Secondary containment by 2000 Tanks to have dikes with 10-4 cm/sec perm.

110% dike containment capacity No flapper-type valves









CLOSURE

TASK MN REG NH REG



GENERAL NOTES Regulated by properties- type A (gasoline)

type B (Diesel) and type C ( asphalt)









SITING REQUIREMENTS









DESIGN REQUIREMENTS Ul142, API 620 and 650, UL 2085, PEI/RP 200-96

API 2165 and 2610

All new tanks to sit on impermeable liner or double

bottom with leak detection and cathodic protection

interstitial monitoring req'd

Tanks to be tightness tested per API 650 or

Saf-C 6009.1 for other than field erected



RELOCATION REQUIREMENTS Tested sound by tracer, vacuum, pressure or Tank to be thoroughly inspected and certified

hydro test structurally sound by PE or API 653 inspector

Leak detection req'd -visual, vapor or interstitial

monitoring





REPAIR AND MODIFICATION Tank must be protected from external corrosion Tank to be inspected for corrosion, abnormal

thinning, holes, and structural integrity

Overfill protection req'd

TASK MN REG NH REG



GENERAL NOTES

CORROSION PROTECTION Cathodic protection req'd unless on concrete, Bottoms protected by sacrificial or impressed

internally lined, double walled or double bottomed current cp per API 651 or NACE RP-0285-85

Shop built tanks and lines in contact with soil to Be designed and installed Cert Corrosion expert

dielectrically protected with a coating or PE

Designed by NACE expert-tested after 6 mos Sacrif inspected after 6 mos and every 3years

and every 3 years- impressed current every 60 days Imp Current checked monthly

Tank to be painted



ANCILLARY REQUREMENTS Substance transfer safeguards req'd ( spill boxes, Piping to be above ground with check valves and

remote fill boxes, containment areas) operating valve located as close to tank as possible

Lines cathodically protected if in contact with soil Steel pipe SCH 40 or greater

and not double walled Gauge and separate HLA req'd

Overfill protection req'd









RELEASE PREVENTION AND LEAK DET. 100% capacity plus displaced vol of tanks in dike Dike secondary containment determined by product

10% additional if exposed to rain

Secondary containment req'd

Permeability varies by type of product





CLOSURE

TASK NJ REG NY REG



GENERAL NOTES Fill Ports are colored coded based on product









SITING REQUIREMENTS









DESIGN REQUIREMENTS Tanks to have secondary containment, impermeable Tank to have impermeable barrier with leak

base, pipes to have remotely activated or readily monitoring system

accessible valves to prevent release. Ul 142 and 58, API 650 and 620, CAN4-S601-M84

Regular intergretity testing or static head CAN4-S630-M84, ASTM D4097-88, ASTM D3299-88

product testing CP must be used if tank rests on ground

Emmissions per NSPS, RACT and NESHAP Tanks must be painted

standards Tanks must be tested per API 650



RELOCATION REQUIREMENTS If tank is certified sound it may be reused









REPAIR AND MODIFICATION Impermeable barrier if repair exceeds 50% of All welds must be tightness tested

replacement cost

TASK NJ REG NY REG



GENERAL NOTES

CORROSION PROTECTION CP req'd for all tanks resting on ground

All exposed exterior surfaces of tanks, piping or

ancillary equip must be corrosion resistant

materials, coated or cathodically protected









ANCILLARY REQUREMENTS Valves to be close to tank to prevent product from Automatic shutoff valves

exiting sec cont. Level gauges req'd

Pipes cannot pass thru sec cont walls check valves for pump fed tanks

Overfill detection devices req'd valves req'd on piping below product level

high level alarm and way to immediately stop Spill protection req'd at pumps and valves

flow of product Piping greater than 2" dia shall have welded flanges

no threaded fittings where threads are exposed

to flowing product

on ground and underground piping to have sec cont



RELEASE PREVENTION AND LEAK DET. Secondary containment of dike req'd after secondary containment req'd

substantial reconstruction or replacement of tank 1x 10-6 cm/sec

(50% of tank replacement value) need normal vents, emergency vents







CLOSURE

TASK PA REG VA REG



GENERAL NOTES Certified company, installer and inspector reqd for

tank handling activities









SITING REQUIREMENTS









DESIGN REQUIREMENTS Cert tank company, installer to oversee work UL, API or STI

Cert inspector to sign off Strength tested

Test for tightness RPB req'd under or in tank

Sec containment liner req'd under tank









RELOCATION REQUIREMENTS Same as new Same as new









REPAIR AND MODIFICATION Cert tank company, installer to oversee work Reconstructed or bottom replacements to follow new

Cert inspector to sign off tank requirements

Work and testing per industry standards

Sec containment to be provided when bottom

replaced

TASK PA REG VA REG



GENERAL NOTES

CORROSION PROTECTION Metallic tank in contact with ground to be evaluated Corrosion Professional to det whether cp is needed

by corrosion expert when in contact with ground

Paint exposed surfaces

Linings to extend 18" up shell









ANCILLARY REQUREMENTS Emerg vents for overpressurization and excessive Safefill and shutdown devices req'd

vacuum. Normal vents for breathing cp for underground piping

Operating valve adjacent to tank









RELEASE PREVENTION AND LEAK DET. Level gauge, high level alarm req'd rpb req'd

Sec containment 1x 10-6 req'd

Area under bottom monitored by visual, mechanical

or electronic leak detection





CLOSURE


Related docs
Other docs by HC111110054529
W5_readme
Views: 0  |  Downloads: 0
20100510 20UPST 20Contractor 20List
Views: 1  |  Downloads: 0
HirschArticle
Views: 1  |  Downloads: 0
National 20Driver 20Registry 20Checks
Views: 0  |  Downloads: 0
livros04_2010
Views: 28  |  Downloads: 0
listagemvolks
Views: 310  |  Downloads: 0
Specialties
Views: 2  |  Downloads: 0
Index1936 1960
Views: 0  |  Downloads: 0
nwp ris
Views: 0  |  Downloads: 0
By registering with docstoc.com you agree to our
privacy policy

You are almost ready to download!

You are almost ready to download!