Acheson & Glover

Tel: 028 8778 4208







To complete the clause, select the appropriate wording from below.



D41 CRIB WALLS/ GABIONS/ DRYSTACK MASONRY



310 DRYSTACK INTERLOCKING MASONRY



Designed to be constructed without mortar or pins to create retaining walls up to 1200mm

high where there are no slopes above or below the wall and no surcharge. Anchor

Diamond® can be used for taller walls with the inclusion of geosynthetic reinforcement.

The blocks incorporate a rear lip which automatically provides a uniform setback and

perfect alignment, thus speeding installation. The system is flexible enough to shift and

expand with ground movements around the blocks. Acheson & Glover can also provide a

design and specification service.

The blocks available are:

Anchor Diamond® Dimensions: 435mm wide x 150mm high x 300mm deep.

Weight: Approx 29kg.

Face coverage: Approx. 15.3 units/m²

Batter: 10.6°

Compressive strength: 24 N/mm²

Bond: Stretcher

Finish: Textured.

Anchor Diamond® Cap Dimensions: 450mm wide x 75mm high x 250mm deep

Weight: Approx 16.5kg.

Anchor Diamond® Corner Dimensions: 200mm wide x 150mm high x 300mm deep

Weight: Approx 14.5kg.

Colour: Consult with Acheson & Glover for availability of colours and to obtain

samples. Basalt / Bracken / Brindle – for multi colours Cotswold Buff / Cathedral – for

solid colours

Special Shapes: The units can be laid to internal or external radius:

Outside curve minimum radius 900mm to back of block on top course

Inside curve minimum radius 2700mm to back of block on base course

Block Manufacturer: Acheson & Glover, 64 Old Moy Road, Dungannon, Co.Tyrone,

BT71 6PU. Tel: 028 8778 4208. Fax: 028 8778 4805.

Email: sales@acheson-glover.com Web: www.acheson-glover.com





Also at the following:

Southern Ireland - Unit 4, Howth Junction Business Park, Kilbarrack, Dublin 5.

Tel: 00353 1 832 5699. Fax: 00353 1 832 5734.

Great Britain – 4 Marlin Office Village, 1250 Chester Road, Castle Vale,

Birmingham. B35 7AZ Tel: 0121 747 0202 Fax: 0121 747 2913

Email: gbsales@acheson-glover.com Web: www.acheson-glover.com





Substrate: Compacted trench base deep enough to bury one course of units with 150mm

of compacted base comprising 20mm gravel with fines or selected hardcore 20mm to

dust – for walls up to 1200mm high. Walls greater than 1200mm - consult Acheson &

Glover’s technical department.

Features: Consult with Acheson & Glover for recommendations and details.

Geogrid reinforcement: Not required for walls under 1200mm. As clause 330 – for

walls more than 1200mm high, as specified by Acheson & Glover’s technical

department.

Backfill: Consult with Acheson & Glover for recommendations and details.

Design parameters: Consult with Acheson & Glover for recommendations and details.

Assembly/ Installation: As clause 320.



320 LAYING DRYSTACK INTERLOCKING MASONRY



The specification below is designed for use with walls up to 1200mm high with no slopes

above or below the wall and no surcharge loads. For walls greater than 1200mm consult

with Acheson & Glover’s technical department.



Installation: To specified line, level and batter, with vertical joints aligned and all voids

filled.

First course: Commence wall construction at the lowest elevation. Ensure the

foundation material is level in all directions. Lay the base course of blocks ensuring all

units are in full contact with the base material and that the vertical edge to each unit is in

full contact with the edge of the preceding unit. Base course blocks should be aligned

longitudinally and levelled front to back, side to side and relative to adjacent units.

Subsequent courses: Clean any debris from the top of the blocks. Construct the second

course of the wall by ‘centering’ a unit directly above the vertical joints of the course

below. Pull top block forward until back locating lip is in contact with block below.



Place drainage pipe behind the block facing units in accordance with the project design

drawings. Backfill with 2-20mm free drainage gravel 300mm behind the wall, in 150mm

layers. Fill in the voids.



As required by the project design drawings, connect geosynthetic reinforcement to the

units at the appropriate wall elevations. Geosynthetic reinforcement should be of the type

specified by designers and must be installed in the correct orientation. It must be laid flat

and covered by at least 150mm of backfill prior to operating vehicles over it. Repeat

subsequent unit installation instructions to the finished height of the wall.

Backfill: To top of each course as work proceeds and compact in layers not exceeding

150mm deep. Sweep debris from top of each course before laying next course.





330 GEOGRID REINFORCEMENT



Geogrid reinforcement is not required on walls up to 1200mm high with no slopes above

or below the wall and no surcharge present. For walls over 1200mm a reinforced soil

backfill is required using geosynthetic reinforcement. Acheson & Glover can also

provide a design and specification service and it is recommended that they are consulted

early in the design process.


Related docs
Other docs by HC11111004228
Paxton
Views: 3  |  Downloads: 0
ismail_ozturk
Views: 1  |  Downloads: 0
2005 EB 4
Views: 1  |  Downloads: 0
SearchProcessTraining
Views: 0  |  Downloads: 0
102
Views: 0  |  Downloads: 0
Gerodontologia06 07
Views: 2  |  Downloads: 0
jbptunikompp gdl alisyamsdu 23033 1 bahanaj m
Views: 24  |  Downloads: 0
Organization 20List 202 20 202009
Views: 3  |  Downloads: 0
edinvest
Views: 0  |  Downloads: 0
report07
Views: 0  |  Downloads: 0
By registering with docstoc.com you agree to our
privacy policy

You are almost ready to download!

You are almost ready to download!