					                                                                                        SINGLE-PHASE
                                                                                      WATTHOUR METER
                                                                                                                                     CMAx

Single-phase watthour meters of CMAx type are induction meters meant for electric energy
measuring on single-phase 2 wire or 3 wire networks.
Single-phase watthour meters comply with the technical requirements provided by EN 60521,
CEI IEC 62053-11 standards. The meters has been granted EEC-Pattern Approval Certificate
by NMI the Netherlands.                                                                            • active energy
                                                                                                   • class 2 according to EN 60521
  TECHNICAL CHARACTERISTICS:                                                                       • base current Ib 2.5 ; 5 ... 50 A
Electrical characteristics:                                                                        • max. current 600%Ib (max. 100A)
- Reference voltage*, Ur:                  100, 110, 120, 127, 220, 230, 240 V                     • extended limits for the operating
- Basic current*, Ib:                      2.5; 5; 10; 15; 20; 25; 30; 40; 50 A
- Maximum current:                         200, 300, 400, 500, 600 %Ib (max. 100 A)
                                                                                                     temperature, long operating life
- Reference frequency, fr:                 50, 60 Hz
- Voltage circuit power loss:              max. 1.6 W / 6 VA
- Current circuit power loss:              max. 0.5 VA
* Other customized values

Accuracy and influences characteristics:
- Class index:                             2
- Starting current:                        0.5 %Ib
- Running with no load:                    (80-110) %Ur
- Mean temperature coefficient for (-20...55) oC:
            • cos j = 1                    max. 0.10 % / oC
            • cos j = 0.5 lagging          max. 0.15 % / oC

Climatic characteristics:
- Operating temperature range:             (-40...70)°C
- Storage and transport temperature:       (-50...80)°C
                         o
- Relative humidity at 20 C:               max. 95%
Mechanical characteristics:
- Rotor weight:                            max. 25 g
- Basic torque:                            min. 4•10-4 Nm
- Basic speed:                             min. 11, max. 22 rot/min.
- Weight of meter:                         (1.2...1.9) kg
- Protection according to                  IP 51 or, optionally IP 53
  IEC 60529:
The meter is manufactured of high quality materials with the implementation of advanced
technologies. A good anti-corrosive protection is ensured to the whole product.
Case
The base is manufactured of steel plate or bakelite. Allows the meter fastening on the panel in
three points.
The cover is manufactured of aluminium plate, glass, polycarbonate or bakelite. The meter
tightening is provided by a ring made of rubber located between the meter cover and the
meter base.
The rotor consists of a high purity aluminium disc die-casted with aluminum alloy on a
stainless steel shaft. The disc has a mark, which helps to count the revolutions of the disc for
testing or calibration purposes. The meter can be provided with reversal - preventing device.
Bearings
The upper bearing is of rotor guiding shaft type. The shaft is manufactured of stainless steel.
The lower bearing is of double sapphire type or with magnetic suspension, ensuring a long
operating life.
The terminal block is manufactured of bakelite. The terminals enable the connection of
cables having diameters up to 5 mm (45 A), and 8 mm (100 A).
The terminal cover is manufactured of steel plate, polycarbonate or bakelite. It shall be
assembled on the terminal block by means of two sealing screws. The wiring diagram is
provided inside the cover.
The frame is made of AlSi alloy by die casting of high mechanical strength and long time
dimensional stability.
The driving element is of tangential type, two electromagnets being fixed to die-cast frame.
The voltage coil is covered by a PVC shrinkable plastic tube. The current coil is of synthetic
resin insulated wire on a plastic body, high insulation against the current core being thus
ensured.
 The braking element is made up of a permanent magnet with one magnetic part,
 manufactured of an AlNiCo alloy which ensures high stability to the magnetic field for a long
 time. The magnet is provided with a device for compensating errors due to ambient                IDENTIFICATION MODE:
 temperature variations. The braking element is provided with pins for the meter adjustment at
 rated load. The braking element can also be provided with only two magnetic parts.             CMA x x x x
                                                                                                    1 2 3 4
 The register is provided with aluminium or plastic drums mounted on an aluminium frame.
 The figures are easily readable, being white on a black field. The register options are either               register type:
 normal or unidirectional.                                                                                 B1 bidirectional (normal); plastic drums
 The adjustment devices are easily accessible from the meter front. They do not present                    B2 bidirectional (normal); metal drums
 alterations during handling and transportation. The adjustment ranges fall within the limits              U1 unidirectional; plastic drums
 allowed by EN 60521, CE IEC 62053-11.                                                                     U2 unidirectional; metal drums
                                                                                                                                                   braking element type:
 Typical performance curves                                                                                                                      1 with one magnetic part
 Error curves as function of load variation                                                                                                      2 with two magnetic parts
          2                                                                                                                                     terminal cover type:
          1                                                                                                                                  M1 metallic; steel
                                                                                                                                             I1 insulating; polycarbonate
 D [%]




          0
                                                                                                                                             I2 insulating; bakelite
         -1
         -2                                                                                                                                  case type:
               10 20 50    100       150    200            300                       400               500              600             M1   metallic; steel plate base, aluminium cover
                                                                                                                                        M2   metallic; steel plate base, polycarbonate cover
                                                          In [%]
                                                                                                                                        M3   metallic; steel plate base, bakelite cover
                                    Error curves as function of voltage variation                                                       M4   metallic; steel plate base, glass cover
                          10% Ib                                                                    100% Ib                             I1   insulating; bakelite base, polycarbonate cover
          2                                                                     2                                                       I2   insulating; bakelite base, bakelite cover
          1                                                                     1
                                                                                                                                   single-phase watthour meter
D [%]




                                                                   D [%]




          0                                                                     0
          -1                                                                    -1
          -2                                                                    -2
               90          100                110                                    90                100              110

                          Ur [%]                                                                     Ur [%]

                                    Error curves as function of frequency variation
                          10% Ib                                                                       100% Ib
                                                                                 2                                                                                             l
          2                                                                                                                                      h
                                                                                                                                                                                   5.4
          1                                                                      1
                                                                   D [%]
D [%]




          0                                                                      0
          -1                                                                    -1
          -2                                                                    -2
               95          100              105                                      95                100              105




                                                                                                                                                              a/




                                                                                                                                                                                               c
                          fr [%]                                                                    fr [%]




                                                                                                                                                                   /a
                                                                                                                                                          L
                                   power factor 1                                         power factor =0.5 lagging
                                                                                                                                                                                         5.4


        OVERALL AND MOUNTING DIMENSIONS:
 The overall and mounting dimensions depend upon the type of the base, cover,
 terminals block and terminals block cover, as shown below:
                                                                                                                                                                              b


         Meter type                Imax [A]         Overall dimensions [mm]                                    Mounting dimensions [mm]

                                                      L                     l                   h              a/a*            b             c
                                                     214                   124                114              146/-          94           173
                                     £ 45            214                   139                114              146/-          94           173
          CMA M1                                     181                   139                114              115/-          92           151
                                                     217                   139                114              160/-          104          186
                                     > 45
                                                     190                   139                114              160/-          104          186
                                     £ 45            214                   149                114              146/-          94           173
          CMA M2
          CMA M3                                     217                   149                114              160/-          104          186
                                     > 45
                                                     190                   149                114              160/-          104          186
                                                     214                   146                119              146/-           94          173
                                     £ 45
                                                     214                   124                119              146/-           94          173
          CMA M4
                                                     217                   146                119              160/-          104           86
                                     > 45
                                                     190                   146                119              160/-          104           86
                                                     228                   149                124             170/148         86,5         180
                                                     221                   149                124              -/148          86,5         173       *   The meters having a/a dimensions are
                                     £ 45
                                                     201                   149                124             144/115          92          153           provided with two mounting points:
                                                    **211                  149                124              -/134          104          166           - a/ the mounting point visible from the
          CMA I1                                                                                                                                               front;
          CMA I2                                     228                   149                124             170/148         86,5         190
                                                     221                   149                124              -/153          86,5         183           - /a hidden mounting point.
                                     > 45            201                   149                124             144/115          92          163       ** For meters with dimensions complying
                                                    **211                  149                124              -/134          104          166           with BS 7856.
                                                     170                   149                124             144/115          92          163       *** For meters with dimensions complying
                                                                                                                                                         with NBR 8379.
          CMA I1                     100            ***181                 138                116             153/132         72,5         178
BASIC CONNECTION DIAGRAMS




1        3              4   6           1             3         4      6




      P-P-N-N*                                  P-N-N-P




1       3           4           6   1             3         4          6




        P1-P1-P2-P2

                                            three wire - P1-P1-P2-P2

    * P - phase
      N - neutral




                                                                                  S.C. AEM S.A. Timisoara
                                                                                   Calea Buziasului nr. 26
                                                                                      300693, Timisoara
                                                                           Tel: 0256-222200; Fax: 0256-490928
                                                                                    E-mail: sales@aem.ro
                                                                                 Internet: http://www.aem.ro
                                                                             Quality management system
                                                                             ISO 9001 certified by KEMA
                                                                                                                v.09.2007

				