Embed
Email

circuit

Document Sample

Shared by: cuiliqing
Categories
Tags
Stats
views:
25
posted:
11/1/2011
language:
English
pages:
8
ELECTRICAL AND MECHANICAL WORKS

CABLE SIZING CALCULATION FOR LVB



Supply voltage 220 V

Fault Level 24 MVA

Voltage drop limit 1.5 %



Cable Type Description British Standard

A 4/C XLPE/SWA/LSOH BS5467 BS6724

B 3/C XLPE/SWA/LSOH BS5467 BS6724

C 2/C XLPE/SWA/LSOH BS5467 BS6724

D 1/C XLPE/SWA/LSOH BS5467 REMARK

E 4/C FR/SWA/LSOH BS6387 Cat.C.W.Z.

F 3/C FR/SWA/LSOH BS6387 Cat.C.W.Z. V Volt drop higher than limit.

G 2/C FR/SWA/LSOH BS6387 Cat.C.W.Z. A Cable rating lower than protective device rating.

H 1/C FR/SWA/LSOH BS6387 Cat.C.W.Z. T Cable type not suitable.

I 1/C LSHF BS5467 BS7211 E1 Earth fault relay is needed to trip the protective device for 5s disconnection

J 1/C FR/LSHF BS6387 Cat.C.W.Z. E2 Earth fault relay is needed to trip the protective device for 0.4s disconnection

K 4/C XLPE/SWA/LSHF with moulded outlets K Let-through energy of protective device will damage cable

L 2/C XLPE/SWA/LSHF with moulded outlets KK Let-through energy of protective device will damage protective conductor

M 1/C PVC BS6004 S Touch voltage for 5s disconnection > 50V









CIRCUITRY CABLE PROTECTIVE DEVICE EARTHING Remark

of Protective









Rating of BS 88 back-up









Max. Prospective fault for

Calculated Cable Rating









Max. earth fault loop





Max. earth fault loop







loop

RCD of 30mA in









Calculated Voltage Drop

Device (A) (MCB /









Type ( Cable / Armour /









5s









Touch voltage for 5s

0.4s







impedance at fault (ohm)

disconnecton time (ohm)





disconnecton time (ohm)

sensitivity is employed

No.of Cable per phase









MCCB / BS88 Fuse)

Connected Load (A)









Length of Cable (m)









Type ( B / 3 / Fuse )









for









disconnection (V)

for

downstream (kA)

Cable size (mm²)









fault

No.of Phase









Cable Type









Size (mm²)









impedance





impedance

fuse (A)

Rating









Tape )









Earth

(%)

(A)

Cable No. From To



A01 LVB-3-1 eg 1 25.00 1. C 50. 1. 100. 32. 3 N/A N/A Armour N/A 190 1.14 3 1.528 0.688 0.357 42

A02 LVB-3-1 eg 2 25. 3. A 10. 1. 50 32. 3 N/A N/A Armour N/A 65 1.31 2 1.528 0.688 0.381 34

A18 LVB-3-1 eg 3 25.00 1. C 100. 1. 100. 32. Fuse N/A N/A Cable 6 296 0.59 5 1.760 0.688 0.422 49

A19 LVB-3-1 eg 4 25. 3. A 10. 1. 50 32. Fuse N/A N/A Cable 4 65 1.31 2 1.760 0.688 0.439 37

A03 LVB-3-1 eg 5 230. 3. A 240. 4. 450 250. 3 N/A N/A Tape 50x6 1,824 1.43 13 0.196 0.088 0.060 50



A05 LVB-3-1 SB-3-801 62.24 3. E 120. 1. 52 250. 3 N/A N/A Tape 50x6 295 0.31 17 0.196 0.088 0.020 6

A06 LVB-3-1 ISO-3-801 15.15 1. C 16. 1. 52 63. 3 N/A N/A Tape 50x6 96 1.04 2 0.776 0.349 0.101 1

A07 LVB-3-1 MCC-1-5 293.32 3. E 300. 1. 89 400. 3 N/A N/A Tape 50x6 525 1.27 16 0.122 0.055 0.022 16

A08 LVB-3-1 Capacitor bank 227.27 3. A 240. 1. 24 400. 3 N/A N/A Tape 50x6 456 0.30 28 0.122 0.055 0.009 4

A09 LVB-3-1 LVB-3-2 889.39 3. E 400. 2. 36 1,000. 3 N/A N/A Tape 50x6 1,216 0.71 30 0.049 0.022 0.008 16

A10 LVB-3-1 Capacitor bank 303.03 3. A 400. 1. 24 500. 3 N/A N/A Tape 50x6 608 0.32 28 0.122 0.055 0.008 4

A11 LVB-3-1 MCC-1-6 291.12 3. E 300. 1. 81 400. 3 N/A N/A Tape 50x6 525 1.14 17 0.122 0.055 0.020 14

A12 LVB-3-1 SB-2-602 48.08 3. E 240. 1. 72 400. 3 N/A N/A Tape 50x6 456 0.19 18 0.122 0.055 0.020 13

A13 LVB-3-1 ATS of UPS-1-01 166.67 3. E 150. 1. 83 250. 3 N/A N/A Tape 50x6 339 1.09 14 0.196 0.088 0.028 9

A15 LVB-3-1 DBP-1-222 22.73 3. A 70. 1. 81 160. 3 N/A N/A Tape 50x6 210 0.29 9 0.306 0.138 0.044 6

A14 LVB-3-1 SB-2-502 13.39 3. E 120. 1. 145 250. 3 N/A N/A Tape 50x6 295 0.19 8 0.196 0.088 0.052 16







REMARK

1 Grouping factor 0.87 is based on assumption of 5 groups cable spaced with one diameter.

2 Ambient temperature is assumed to be 40 deg.C.

3 Volt-drop limit to be 1.5 %. ( volt-drop limit for final circuit is 2.5% )

4 50 x 6 mm bare copper tape is used as protective conductor between main switchboards and panel boards.

Cable armour or separate conductor is used as protective conductor for final or sub-final circuits.



CONCLUSION

1 Those cables with V in remark are undersized regarding the limit in voltage drop.

2 Those cables with A in remark are undersized as they are not protected by the protective device.

3 For those circuits with E1 in remark, either the earth fault loop impedance should be decreased or earth fault relay should be provided.

4 For those circuits with S in remark, either the CPC impedance should be decreased or earth fault relay should be provided.









3d112809-10ed-4344-8762-3212619336d2.xls LVB-3-1 - Page 1 Print Date : 11/1/2011

Cable Insulation Material Thermosetting



resistive

correction

factor from

cable resistive

cross- operating correction

sectional temp. to factor from k value for k value for

PVC 2 area 20C 20C to fault cable armour

Rubber 85 8 1 0.78 1.6 143 46

Thermosetting 14 300 0.78 1.6 143 46









Part of Table 43A



PVC 70 Rubber 85 Thermosetting



Correctio Correction k value

cross- Max. Correction n factor Max. Correction factor for Max. Correction Correction k value k value

sectional conductor temp limiting final factor from from 70C k value for k value for conductor limiting final factor from from 85C k value steel conductor limiting final factor from factor from for for

area (C) temp (C) 20C to fault to 20C cable steel armour temp (C) temp (C) 85C to fault to 20C for cable armour temp (C) temp (C) 90C to fault 90C to 20C cable armour

1 70 160 1.38 0.83 115 51 85 220 1.53 0.79 134 51 90 250 1.6 0.78 143 46

300 70 140 1.34 0.83 103 51 85 220 1.53 0.79 134 51 90 250 1.6 0.78 143 46









Type 1/C LSOH, 1/C PVC ( BS 7211 & BS 7889 ) M/C XLPE/SWA/LSOH ( BS 6387 C,W & Z )

Conduit/Trunking

Installation Method Perforated cable tray / free air

Voltage drop (mV/A/m)









Voltage drop (mV/A/m)









Voltage drop (mV/A/m)









Voltage drop (mV/A/m)

Conductor Impedance









Conductor Impedance









Conductor Impedance









Conductor Impedance

Cross-sectional area of

Armour impedance at









Armour impedance at

per phase at 20C









per phase at 20C









per phase at 20C









per phase at 20C

steel armour (mm2)

1 Phase 2/C (A)









3 Phase 4/C (A)









1 Phase 2/C (A)









3 Phase 4/C (A)

20C (ohms/km)









20C (ohms/km)

Cross-sectional









(ohms/km)









(ohms/km)









(ohms/km)









(ohms/km)

Area/mm2









K2 S 2









K2 S 2









K2 S 2

k









k









k

1 17 46 18.1 143 20449 15 40 18.1 143 20449 0 0 0 0 0 0 0 0 0 0

1.5 22 31 12.1 143 46010.25 19 27 12.1 143 46010 29 31 12.053+.104i 10.2 143 46010 15 25 27 12.053+.104i 8.8

2.5 30 19 7.41 143 127806.25 26 16 7.41 143 127806 39 19 7.381+.101i 8.8 143 127806 17 33 16 7.381+.101i 7.7

4 40 12 4.61 143 327184 35 10 4.61 143 327184 52 12 4.592+0.099i 7.9 143 327184 21 44 10 4.592+0.099i 6.8

6 51 7.9 3.08 143 736164 45 6.8 3.08 143 736164 66 7.9 3.068+.094i 7 143 736164 24 56 6.8 3.068+.094i 4.3

10 71 4.7 1.83 143 2044900 63 4 1.83 143 2E+06 90 4.7 1.823+.093i 6 143 2E+06 41 78 4 1.823+.093i 3.7

16 95 2.9 1.15 143 5234944 85 2.5 1.15 143 5E+06 115 2.9 1.145+.088i 3.7 143 5E+06 42 99 2.5 1.145+.088i 3.1

25 126 1.9 0.727 143 12780625 111 1.65 0.727 143 1E+07 152 1.9 .723+.082i 3.7 143 1E+07 43 131 1.65 .723+.082i 2.3

35 156 1.35 0.524 143 25050025 138 1.15 0.524 143 3E+07 188 1.35 .522+.077i 2.6 143 3E+07 62 162 1.15 .522+.077i 2

50 189 1.05 .379+.092i 143 51122500 168 0.9 .379+.092i 143 5E+07 228 1 .386+.076i 2.3+.3i 143 5E+07 70 197 0.87 .386+.076i 1.8+.3i

70 240 0.75 .263+.088i 143 100200100 214 0.65 .263+.088i 143 1E+08 291 0.69 .267+.075i 2+.3i 143 1E+08 80 251 0.6 .267+.075i 1.2+.3i

95 290 0.58 .191+.086i 143 184552225 259 0.5 .191+.086i 143 2E+08 354 0.52 .193+.074i 1.4+.3i 143 2E+08 114 304 0.45 .193+.074i 1.1+.3i

120 336 0.48 .151+.084i 143 294465600 299 0.42 .151+.084i 143 3E+08 410 0.42 .153+.072i 1.3+.3i 143 3E+08 126 353 0.37 .153+.072i 0.76+.3i

150 375 0.43 .124+.083i 143 460102500 328 0.37 .124+.083i 143 5E+08 472 0.35 .125+.073i 1.2+.3i 143 5E+08 139 406 0.3 .125+.073i 0.68+.3i

185 426 0.37 .0995+.083i 143 699867025 370 0.32 .0995+.083i 143 7E+08 539 0.29 0.1+.073i 0.82+.3i 143 7E+08 196 463 0.26 0.1+.073i 0.61+.3i

240 500 0.33 .0764+.082i 143 1177862400 433 0.29 .0764+.082i 143 1E+09 636 0.24 .0773+.072i 0.73+.3i 143 1E+09 218 546 0.21 .0773+.072i 0.54+.3i

300 573 0.31 .062+.081i 143 1840410000 493 0.27 .062+.081i 143 2E+09 732 0.21 .0626+.072i 0.67+.3i 143 2E+09 239 628 0.185 .0626+.072i 0.49+.3i

400 915 0.2 .05+.08i 143 3271840000 840 0.16 .05+.08i 143 3E+09 847 0.195 .005+.071i 0.59+.3i 143 3E+09 279 728 0.17 .005+.071i 0.35+.3i

500 1044 0.185 .0414+.079i 143 5112250000 973 0.16 .0414+.079i 143 5E+09

630 1191 0.175 .0342+.077i 143 8116208100 1115 0.16 .0342+.077i 143 8E+09

800 1358 0.17 1275 0.155

1000 1520 0.165 1436 0.155







3d112809-10ed-4344-8762-3212619336d2.xls AC Cable - Page 2 Print Date : 11/1/2011

2.5(Ring) 60 9.5 52 8

on tray not in trunking on tray not in trunking



Table 4E1A Table 4E1B Table 4E1A Table 4E1B Table 4E4A Table 4E4B Draka Draka Table 4E4A Table 4E4B Draka Draka









3d112809-10ed-4344-8762-3212619336d2.xls AC Cable - Page 3 Print Date : 11/1/2011

K2 S 2

k









0 0

143 46010

143 127806

143 327184

143 736164

143 2E+06

143 5E+06

143 1E+07

143 3E+07

143 5E+07

143 1E+08

143 2E+08

143 3E+08

143 5E+08

143 7E+08

143 1E+09

143 2E+09

143 3E+09









3d112809-10ed-4344-8762-3212619336d2.xls AC Cable - Page 4 Print Date : 11/1/2011

3d112809-10ed-4344-8762-3212619336d2.xls AC Cable - Page 5 Print Date : 11/1/2011

Size of

conduit/trunking/tape Impedance ohm/km

(mm) at 20C



16 4.75i

20 3.125i

25 2.125i

35 1.375i

50x38 2.13i

38x50 2.13i

50x50 1.77i

75x50 1.26i

50x75 1.26i

75x75 0.98i

100x50 1.1i

50x100 1.1i

100x75 0.88i

75x100 0.88i

100x100 0.63i

150x50 0.76i

50x150 0.76i

150x75 0.63i

75x150 0.63i

150x100 0.46i

100x150 0.46i

150x150 0.37i

3x25 0.2404

25x3 0.2404

6x25 0.1202

25x6 0.1202

6x50 0.0601

50x6 0.0601







Remark: heavy gauge conduit and trunking are considered.

Reactance of conduit and trunking is much greater than resistance. Hence, the temperature rise due to fault has an insignificant effect on impedance.









3d112809-10ed-4344-8762-3212619336d2.xls Earthing - Page 6 Print Date : 11/1/2011

Rating of back-up Breaking capacity of fault

Current For Disconnection (A) fuse (A) current device (kA)

Fuses (BS 88) MCB (BS 3871) 5 4.5

Rating Current for disconnection (A) Type B Type 3 160 4.5

(A) 0.1 s 0.2 s 0.4 s 5s <0.01s (let through energy A sec) <0.1s (let through energy A2sec) 5s (Max)

2

<0.1s (let through energy A2sec) 5s (Max) 200 23

5 25 20 50 9000 22.5 400 23

6 36 31 27 17 52 60 30 24 60 27 630 40

10 60 51 45 31 140 290 50 40 100 26000 45

15 N/A N/A N/A N/A N/A N/A 75 60 150 26000 67.5

16 120 95 85 55 250 570 80 64 160 72 COP table 9(2)

20 175 150 130 79 360 1100 100 80 200 30000 90

25 220 180 160 100 430 1850 125 100 250 112.5

30 150 120 300 37000 135

32 320 260 220 125 620 3400 160 128 320 144

40 400 340 280 170 810 8500 200 160 400 70000 180

50 540 450 380 220 900 13500 250 200 500 225

63 710 590 500 280 1300 24000 315 252 630 70000 283.5

80 1100 890 740 400 1500 40000 400 320 800 360

100 1400 1150 980 550 2000 60000 500 400 1000 450

125 1800 1500 1300 690 2500 85000 1250 562.5

160 2400 2000 1700 900 3500 160000 1600 720

200 3000 2500 2200 1200 4000 255000 2000 900

250 1467 6100 550000 2500 1125

315 2200

400 2444 10000 1900000 4000 1800

630 18000 5300000 6300 2835

1000 10000 4500









3d112809-10ed-4344-8762-3212619336d2.xls Trip - Page 7 Print Date : 11/1/2011

Revision Date Remarks



A 17/11/03 First Issue



Related docs
Other docs by cuiliqing
7 Recipes from Joe A.
Views: 2  |  Downloads: 0
Re-installingXPMode
Views: 3  |  Downloads: 0
telefonica_en
Views: 4  |  Downloads: 0
3220 Chap 6 demos
Views: 2  |  Downloads: 0
chap history.docx
Views: 3  |  Downloads: 0
Subcontractor Bid Form - The Fountains
Views: 1  |  Downloads: 0
English
Views: 1  |  Downloads: 0
DESIGNER'S SCHEDULE USE
Views: 1  |  Downloads: 0
Security Service Providers
Views: 45  |  Downloads: 0
By registering with docstoc.com you agree to our
privacy policy

You are almost ready to download!

You are almost ready to download!