REMOTE CONTROLLED HYDRAULIC CONTROL VALVE
Document Sample


REMOTE CONTROLLED HYDRAULIC CONTROL VALVE – RC
Description:
Dorot “RC” model valve is a hydraulic control valve operated by line pressure or
pneumatic pressure (if desired). It is used for opening / closing process in
applications from which electric source, control device, control pressure etc. is far
away.
Features:
It is closed as fully sealed without causing surge thanks to its flexible
diaphragm.
It performs easy and fast controlling function even in high pressure lines
thanks to 3-way hydraulic relay mounted on valve.
It may be used in different applications by adding different pilot valves on main
valve body.
Installation:
Make sure that valve is on a level with the pipeline while mounting it.
Mount valve in direction of arrow indicated on it.
While connecting valve on pipeline, place gasket between valve flange and
pipe flange to ensure sealing and tighten the bolts as crosswise.
Determine diameter of hydraulic pressure pipe which ensures operating
control of valve according to distance from other energy sources or consult our
technical department.
It is recommended that insulation valves (butterfly or gate valves etc.), air relief
valve and strainer valves will be used in line-mounting of valve (see sample
montage illustration).
Adjustment:
Open ball valve indicated with “b1”.
Select set point by means of 3-way selector valve indicated with “a” on valve.
Valve is open in “Open” position and closed in “Close” position.
Bring 3-way selector valve indicated with “a” into “auto” position and connect
hydraulic pipe to “auto” port.
Maintenance:
Check finger filter on valve upstream according to water quality.
Drain water within actuator and pilot valves of valves not used in winter.
TROUBLESHOOTING
FAILURE CAUSES CORRECTING/REPAIR
Line pressure may be low. Check upstream pressure and
ensure required upstream
3-way selector valve may be pressure.
Valve not closed. Check selector valve. Bring valve
opening into “Open” position.
3-way selector valve may be Check 3-way valve and clean it.
clogged.
Diaphragm may be punctured. Check diaphragm and replace with
the new one if it is punctured.
Foreign substances may exist Check diaphragm seat and
Valve not in diaphragm seat. remove foreign substances if any.
closing
3-way selector valve may be Check selector valve. Bring valve
closed. into “Close” position.
3-way selector valve may be Check 3-way valve and clean it.
clogged..