Checklist to be Completed with Submission – Surface Mounted Fuse Combination Unit and Switch Disconnector



The following tables must be completed by the applicant and submitted during application.



A. Supporting Documents Required :



Compliance

Items Documents

(Yes/No)

1. Company code of ethics of the Supplier



2. Company organization chart, Form AR1 and/or Business Registration Certificate of the Supplier



3. Certified agency agreement or other Manufacture’s authorization document showing his authorization for the

Supplier to serve as his local agent



4. Letter from Manufacturer showing the Manufacturer’s name, plant address (must be accompanied by a location map

and street map and VCD or digital photos showing the outlook of the manufacturer’s plant), products being

produced, country/place of manufacture, name of contact person, telephone no., fax no. and email address etc. The

documents must be authenticated by appropriate authorities or trade commission of the exporting country.



5. Brochure/catalogue/shop drawings of the materials.



6. Test certificate or other certificates/reports as required showing the material’s compliance with the standard

specification (certificates shall be in English or Chinese or English/Chinese translation issued by certification bodies

or by approved independent translation agency).



7. Document showing the name of the accredited laboratory that conduct the tests.



8. Job references showing the projects (either public or private) which have used the materials (for detailed

requirement on local job reference, refer to table “C” of this Checklist).





May 2003 (Page 1 of 7)

B. Compliance of Specifications :



Clause No. Compliance

Description Manufacturer’s Offer

ELE (Yes/No)

3.2.1.010.3 Surface mounted switch-disconnector fuses, fuse-switch disconnectors and

switch-disconnectors shall be air-break, metalclad type and shall comply

with BSEN 60947-1 : 1992 and BSEN 60947-3 : 1992.



3.2.1.020.3 The switch-disconnector fuses or fuse-switch disconnectors shall be a

combination of a switch-disconnector and one or more fuses in a composite

unit.



3.2.1.030.3 a. Rated operational voltage: 380/220V(Min.)



b. Rated frequency: 50HZ



c. Rated insulation voltage: 415V



d. Rated impulse withstand voltage: 6kV (min.)



e. Conventional enclosed thermal current and rated operational

current/power for uninterrupted duty



f. Utilization category: AC22B and AC23B.



g. Rated short-time withstand current : At least twelve times the

maximum rated operational current for one second.



h. Rated short-time making capacity.







May 2003 (Page 2 of 7)

Clause No. Compliance

Description Manufacturer’s Offer

ELE (Yes/No)

i. Rated short-circuit current (for switch-disconnectors protected by fuses

to BSEN 60269-1:1994, BSEN 60269-2:1995 BS 88 : Part 2 :

Section 2.2 : 1988 and for switch-disconnector fuses / fuse-switch

disconnectors): 40kA



3.2.2.010.3 Switch-disconnector fuses, fuse-switch disconnectors and

switch-disconnectors shall be type-tested in accordance with clause 8.2 and

clause 8.3 of BSEN 60947-3 : 1992. For switch-disconnectors to be used

in circuits protected by fuses, test sequence III of clause 8.3.5 is not

required, but test sequence IV of clause 8.3.6 shall be performed to such

switch-disconnectors connected in series with BSEN 60269-1 : 1994,

BSEN 60269-2 : 1995 and BS 88 : Part 2 : Section 2.2 : 1988 fuse links of

the corresponding rated maximum current.



3.2.2.020.A The following test sequences of BSEN 60947-3 : 1992 shall be carried out

by an Independent Short Circuit Testing Organisation.



a. For fuse combination units – test sequences I & IV



b. For switch - disconnectors – test sequences I & III



3.2.2.030.3 For switching devices with electrolytically deposited silver contacts, the

temperature-rise requirement for the contact parts shall comply with the

limit as specified in Table II of BSEN 60947-1 : 1992.



3.2.2.040.3 Type-test for switch-disconnectors may be waived if they are converted

from type-tested switch-disconnector fuses/fuse-switch disconnectors by

replacing the fuse links with copper short links for a rated operational

May 2003 (Page 3 of 7)

Clause No. Compliance

Description Manufacturer’s Offer

ELE (Yes/No)

current not greater than the maximum rated operational current for the

original switch-disconnector fuses/fuse-switch disconnectors and are

installed in circuits protected by fuses to BSEN 60269-1 : 1994, BSEN

60269-2 : 1995 and BS 88 : Part 2 : Section 2.2 : 1988.



3.2.3.010.3 Switch-disconnector fuses, fuse-switch disconnectors and

switch-disconnectors shall be triple or single pole with detachable fully

rated front accessible neutral link.



3.2.3.020.A For fuse combination units with current ratings above 100A, the switching

devices shall make and break on both the incoming supply side and the

outgoing load side.



3.2.3.030.A For fuse combination units with current ratings of 100A and below, fuse

bases and carriers shall be provided for housing the fuse links if the

switching device are not making and breaking on both the incoming supply

side and the outgoing load side.



3.2.3.040.3 The current carrying parts shall be made of hard drawn, high conductivity

copper to BS 1432 : 1987 or BS 1433 : 1970.



3.2.3.050.3 The enclosure shall be made of sheet steel of thickness not less than 1.6

mm for current ratings above 32A and not less than 1.2 mm for 32A and

below, complete with stoved epoxy powder paint, or equal and Approved

finish of a gloss light colour.



3.2.3.060.3 The front cover of switching devices shall be hinged or of an equal and

Approved construction, to enable easy access to the interior for

May 2003 (Page 4 of 7)

Clause No. Compliance

Description Manufacturer’s Offer

ELE (Yes/No)

replacement of fuse links. Gland plates shall be provided for top and

bottom cable entry for switching devices of current ratings above 32A.



3.2.3.070.3 a. Under normal service conditions, the enclosure shall be of totally

enclosed type with a degree of protection against ingress of foreign

solid bodies and liquids of at least IP41 as per BSEN 60529 : 1992 for

the top surface and IP31 for the other surfaces of the enclosures. With

the front hinged door open and in replacing fuse links, the degree of

protection to the live parts shall be at least IP2X;



b. The switching devices shall be suitable for installation under

environmental condition of pollution degree 3 unless otherwise

specified.



3.2.3.080.3 a. Terminal connections shall be by means of screws so to ensure that the

necessary contact pressure is maintained;



b. The terminal enclosure shall have sufficient space for accommodating

cable lugs for the largest cables which the switching device is designed

to receive, and also for proper cable termination with cable bending

radius in accordance with the COP of the Electricity (Wiring)

Regulations, otherwise proper extension cable terminals and/or cable

boxes shall be provided. The palm width of the cable lugs shall

comply with BS 91 : 1973 Table 2.



3.2.3.090.3 For switch-disconnector fuses or fuse-switch disconnectors, the fuse

holders shall be capable of accepting any fuse links of physical dimension



May 2003 (Page 5 of 7)

Clause No. Compliance

Description Manufacturer’s Offer

ELE (Yes/No)

complying with the minimum and maximum limits of the respective fuse

reference tabulated in the Specification for Fuses.



3.2.3.100.3 An external accessible earthing terminal shall be provided at the side panel

of the enclosure.



3.2.4.010.3 The switching devices shall be independent manual operated and shall have

mechanical interlock to prevent access to the interior except when the

switching devices are in the “OFF” position, and to prevent the contacts

from being switched to close when the door is open.



3.2.4.020.3 The latter interlock shall be able to be defeated by trained personnel for

maintenance when necessary.



3.2.4.030.3 A facility shall be provided for padlocking the switching devices in the

“OFF” position.









May 2003 (Page 6 of 7)

C. Particulars of Local Job Reference :



Compliance

Items Documents

(Yes/No)

1. Local job reference:



2. Details of local job recommended for site visit and inspection by HA (at least one): -



a. Project name:



b. Client/Consultant:



c. Contractor:



d. Scope of work:



e. Completion date:









May 2003 (Page 7 of 7)



Related docs
Other docs by Kerala g
union-budget-2012-13-highlights
Views: 29  |  Downloads: 0
notification M.Tech_05-03-09
Views: 22  |  Downloads: 0
India_Customs Regulation 1
Views: 25  |  Downloads: 0
CE Notification 39-2011-12.9.2011
Views: 21  |  Downloads: 0
STATISTICS
Views: 36  |  Downloads: 0
A Hero (R.K. Narayan)
Views: 49  |  Downloads: 6
RRBPatna-Info-HN
Views: 69  |  Downloads: 0
RRB-Notice-Para
Views: 73  |  Downloads: 0
By registering with docstoc.com you agree to our
privacy policy

You are almost ready to download!

You are almost ready to download!