                     SOR /       S.No.                            DESCRIPTION                                 UNIT               QTY.
                    NON SOR


                    PART-A
                      NSOR         A      POINT WIRING
                                          Supply,Installation, Testing and commissioning of (Providing
                                          and fixing of all standard accessories) of light point, fan
                                          point, exhaust fan point, bell point, group control points,
                                          two way control points etc. using 16 gauge heavy duty MS
                                          BLACK enameled conduit with all conduit accessories like
                                          heavy duty junction boxes, conduit bends, MS 16 gauges pull
                                          boxes 100MM x 100 MM x 50MM or 150MM x200MM x
                                          50MM deep, with MS covers etc.

                                          The work scope is for concealed conduit system IN RCC
                                          ceiling / WALL and surface conduit system above false
                                          ceiling and therefore wall chiseling i.e. ziri cutting with
                                          mechanical cutter, laying of conduits on ceiling , installation
                                          of conduits in wall with metallic modular boxes,
                                          staples/saddles etc. is included in scope of contractor.

                                          Job includes repairing of holes with plaster 20mm thick
                                          painting in same colour to match with ceiling. All conduit
                                          accessories will be of threaded type & tools & consumable
                                          like hacksaw blades, threading dyes to be arranged by
                                          contractor.
                                          The switch / socket (contractor supplied) shall be of make as
                                          specified in list of approved make with metallic modular
                                          boxes shall be installed for concealed flush type
                                          arrangement. The earth wire PVC insulated 1.5 sq. mm
                                          copper 1.1 KV Grade is to be installed in conduit along with
                                          wires .The conduit shall be fixed on wall/slab at maximum
                                          450mm distance by GI saddles.

                                          The switch / socket (contractor supplied) shall be modular
                                          type of make as specified in list of approved make with
                                          metallic modular boxes shall be installed for executed as per
                                          drawing, specification to ensure good aesthetics, line &
                                          level.
                                          All materials like wire, conduit, switches, switchboard shall
                                          be supplied by contractor as per approved make. Above
                                          specification governs all work specified in items N.1 to N.4

                                  A.1     Supply, Installation, testing and commissioning of light             Nos.               200
                                          point, exhaust fan point , wall fan point with 1.5 sq. mm.
                                          multi strand fire resitant copper wire (for phase,neutral
                                          earth wire)1.1KV grade PVC insulated (including supply of all
                                          material like hardware , GI boxes , conduits
                                          accessories.Neutral & earthing can be looped up to 6 points
                                          on one circuit.
                                  A.2     Supply, Installation, Testing and commissioning of light
                                          points in group control system including 1.5 sq. mm copper
                                          flexible 1.1 KV grade insulated wire (for phase,neutral earth
                                          wire), switch, switch board, conduit and material.Neutral &
                                          earthing can be looped on points for one light point.

                                 A.2.1    2 Lights controlled by 6A switch.                                    Nos.               150
                                 A.2.2    3 Lights controlled by 16A switch.                                   Nos.                30
                                 A.2.3    4 Lights controlled by 16A switch.                                   Nos.                12
                                  A.3     Supply, Installation, Testing and commissioning of                   Nos.                 6
                                          Bell/Buzzer point including 3*1.5 sq. mm multi strand fire
                                          resitant copper 1.1 KV grade insulated, conduit, bell, buzzer
                                          and material.Including CPL buzzer board




                                                                                                                                                            1of 26
                                                                      dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                    Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                            DESCRIPTION                                  UNIT               QTY.
                    NON SOR

                                  A.4     Supply, Installation, Testing and commissioning of light
                                          points in two way control system including 2*1.5 sq. mm
                                          copper flexible 660 V/1.1 KV grade insulated wire, switch,
                                          switch board, conduit and material.
                                 A..4.1   2 Lights controlled by 2 nos 6A switch.                               Nos.               12

                                          SUB TOTAL

                      NSOR         B      CIRCUIT WIRING/MAINS WIRING
                                          Supply , Installation, Testing and commissioning of
                                          Circuit/Mains wiring from DB to switch board or outlet using
                                          16 gauge heavy duty MS BLACK enameled conduit with all
                                          conduit accessories like heavy duty junction boxes, conduit
                                          bends, MS 16 gauges pull boxes 100MM x100 MM x50MM to
                                          300MM x 450MM x50MM deep, with MS covers etc.

                                          The work scope is for concealed conduit system IN RCC
                                          ceiling / WALL and surface conduit system above false
                                          ceiling and therefore wall chiseling i.e. ziri cutting with
                                          mechanical cutter, laying of conduits during slab casting,
                                          installation of conduits in wall with GI staples/saddles etc. is
                                          included in scope of contractor. Job includes repairing of
                                          holes with plaster 20mm thick and painting in same colour
                                          to match with ceiling.

                                          All conduit accessories will be of threaded type & tools &
                                          consumable like hacksaw blades, threading dyes to be
                                          arranged by contractor.
                                          The switch / socket (contractor supplied) shall be of make as
                                          specified in schedule and list of approved make with metallic
                                          modular boxes shall be installed for concealed flush type
                                          arrangement.
                                          The earth wire PVC insulated 1.5/2.5 sq. mm copper 1.1 KV
                                          Grade is to be installed in conduit along with wires as per
                                          the drawing & specifications. The conduit shall be fixed on
                                          wall/slab at maximum 450mm distance by GI saddles.

                                          The work scope is including supply of all material like
                                          conduit , wire, pull boxes. Complete work has to be
                                          executed to ensure good aesthetics, line & level.
                                          All materials like wire, conduit, switches, switchboard shall
                                          be supplied by contractor. Above specification governs all
                                          work specified in items B.1 to B.12
                                  B.1     Supply & Installation of 16 gauge HGMS black enameled
                                          ERW grade conduit of approved make with accessories like
                                          heavy duty pull boxes with covers, GI saddles, bends, socket
                                          etc. in concealed/surface manner in wall, ceiling, floor etc.
                                          The work includes chiseling of wall i.e. ziri with mechanical
                                          cutter, saddling of conduits at maximum 400 mm distance
                                          etc.
                                 B.1.1    DIA 25mm conduit                                                      Mtr               3200
                                  B.2     Supply, Installation, Testing and commissioning of following
                                          size flexible copper wire 660 V/1.1 KV grade of approved
                                          make PVC insulated in existing MS conduits , pull boxes ,
                                          hardware etc.
                                  B2.1    2*2.5 sqmm(P&N)+1*1.5 sqmm (E) ( FOR UPS,LIGHTING                     Mtr               4200
                                          ,GEN POWER)
                                  B2.2    2*4 sq.mm(P&N)+1*2.5 sq.mm (E) ( for AC)                              Mtr                600
                                  B2.3    2*6 sq.mm(P&N)+1*2.5 sq.mm (E)                                        Mtr                100
                                  B2.4    4*4 sq.mm(P&N)+1*2.5 sq.mm (E)                                        Mtr                100
                                  B2.5    1*10 sq.mm(E)                                                         Mtr                100




                                                                                                                                                             2of 26
                                                                       dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                  Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                            DESCRIPTION                                UNIT               QTY.
                    NON SOR

                                  B.3     Supply, Installation, Testing and commissioning of 6A 5 pin
                                          switch and socket outlet on separate board (including supply
                                          of all material like MS box, switch, socket and hardware
                                          etc).The socket shall be suitable for international connectors
                                          and shall be approved from client before instllation.

                                 B.3.1    1 no. 6A switch and 1 no. 6A socket on separate board.              Nos.               50
                                 B.3.2    1 no. 16A switch and 3 noS. 6A socket on separate board( for        Nos.               55
                                          computer power) .
                                  B.4     Supply, Installation, Testing and commissioning of 6A               Nos.               30
                                          switch/socket outlet on switch board (including supply of all
                                          material like MS box, switch, socket and hardware
                                          etc).Including wiring between switch and socket.The socket
                                          shall be suitable for international connectors and shall be
                                          approved from client before instllation.

                                  B.5     Supply, Installation, Testing and commissioning of 16A single       Nos.               75
                                          phase switch and 16A 5 pin socket (including supply of all
                                          material like MS box, switch, socket and hardware etc).
                                          Including wiring between switch and socket.The socket shall
                                          be suitable for international connectors and shall be
                                          approved from client before instllation.

                                  B.6     Supply, Installation, Testing and commissioning of 20A              Nos.                9
                                          industrial socket, 20A pin top and 20A DP MCB with box and
                                          the box shall be concealed in wall. The box also shall be of
                                          respective make of MCB. Including wiring between switch
                                          and socket.
                                  B.7     Supply, Installation, Testing and commissioning of 32A              Nos.               12
                                          industrial socket5 Pin type(with neutral & earth), 32A pin top
                                          and 32A4P MCB with box and the box shall be concealed in
                                          wall. The box also shall be of respective make of MCB.
                                          Including wiring between switch and socket.

                                  B.8     Supply, Installation, Testing and commissioning of 63A              Nos.                6
                                          industrial socket 5 Pin type(with neutral & earth) , 63A pin
                                          top and 63A 4P MCB with box and the box shall be
                                          concealed in wall. The box also shall be of respective make
                                          of MCB. Including wiring between switch and socket.

                                  B.9     Supply, Installation, Testing and commissioning of floor box        Nos.               10
                                          of size 300mm(l)x300mm(w)x50mm(d) made out of 16G
                                          CRCA sheet with SS top cover complete with all accessories.

                                  B.10    Supply, Installation, Testing and commissioning of floor box        Nos.               10
                                          of size 450mm(l)x450mm(w)x50mm(d) made out of 16G
                                          CRCA sheet with SS top cover complete with all accessories.

                                  B.11    Supply, Installation, Testing and commissioning of push             Nos.                3
                                          button station for emergency power off in data centre and
                                          network monotoring centre.
                                  B.12    Supply, Installation, Testing and commissioning of Floor pop        Nos.               12
                                          up boxes complete with adaptor & metallic box & cover
                                          suitable for 3module . Cat no.6503 00 make Legrand


                                          SUB TOTAL


                       SOR                MCCB. Isolator, MCB (Tripping characteristics confirming to
                                   C      ISI-
                                          8828 and BS-3871 Part-I-II)
                                  13.2     Supplying and fixing of ISI marked of
                                          accepted standard of miniatur circuit
                                          breaker, suitable of 240/415 volts 50




                                                                                                                                                           3of 26
                                                                      dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                 Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                           DESCRIPTION                UNIT               QTY.
                    NON SOR

                                          cycle (7.5 to 10 KA value)
                                          A.C. supply but without encloseres.
                                   A      SINGLE POLE-
                                    II    6 Amp to 32 Amp Rating                             Each               69
                                   C      DOUBLE POLE
                                   III    For 40 Amp. Only                                   Each                8

                                   D      TRIPLE POLE
                                   II     6 to 32Amp                                         Each                2

                                    F     FOUR POLE
                                    II    6 to 32Amp                                         Each               12
                                   IV     52 to 63 Amp.                                      Each               1

                                  13.3    Supply of ISI marked and accepted
                                          standard isolator suitable for 240 / 415
                                          volts 50 HZ A.C. supply with KA calue
                                          rating from 7.5 to 10KA value of approved
                                          make confirming to IS specification
                                          without encloser etc.
                                   B      DOUBLE POLE
                                    I     Current Rating upto 40 Amp                         Each                6
                                   II     Current Rating upto 63 Amp                         Each                3
                                   D       FOUR POLE
                                    I     Current Rating upto 40 Amp                         Each                6
                                   II     Current Rating upto 63 Amp                         Each                4

                                  13.5     Supply and fixing of approved make
                                          accepted standard sheet steel encloser
                                          powder painted doubler door distribution
                                          board sleek consumer unit type inclusive
                                          of busbar, neutral bar, earth bar and the
                                          isolator of capacity as required etc.
                                          complete as per specification. (Exclusive
                                          of MCB). Including fixing on surface /
                                          racessed type with necessory material
                                          complete.
                                   A      SINGLE PHASE AND NEUTRAL D.B.
                                          ENCLOSER WITH 40AMP. ISOLATOR
                                   II     5 to 8 No. MCB with 40 Amp. Isolator               Each                5
                                   B      FOR THREE PHASE & NEUTRAL D.B.
                                          ENCLOSER WITH 40 TO 80 AMP,
                                          ISOLATOR
                                    I     Upto 4 No. MCB per pole                            Each                1
                                          Upto 7 TO 8 No. MCB Per Pole                       Each                4
                                   IV     For 9 to 12 No. MCB per pole                       Each                2
                                  13.6    Supply and fixing of approved makeplug
                                          socket D.B's (without SP MCB) S.P.N.
                                          sheet encloser inclusive of 2 pole and
                                          earth metal plug arid socket and space to
                                          incoporate S.P. MCB complete as per
                                          specificaiton.
                                   II     20 Amp                                             Each                8
                                  13.7     Supply and fixing of approved make plug
                                          socket D.B's (without SP MCB) T.P.N.
                                          sheet encloser inclusive of three pole and
                                          earth metal plug and socket and space to
                                          incorporate T.P. MCB complete as per
                                          specification.
                                   II     30 Amp                                             Each                8
                                          SUB TOTAL




                                                                                                                                          4of 26
                                                                     dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                            DESCRIPTION                              UNIT               QTY.
                    NON SOR

                       SOR         D      Under Ground Cables
                                   1      Supply of pvc insulated heavy duty power grade 2 core, 3
                                          core, 3.5 core, 4 core ISI marked with Alu. Stranded / solid
                                          (XLPE) conductor.
                                    F     ARMOURED 3.5 CORE (XLPE)
                                    I     25 sq.mm                                                         P.Mtr              350
                                    II    35 sq.mm                                                         P.Mtr              550
                                  III     50 sq.mm                                                         P.Mtr              100
                                  IV      70 sq.mm                                                         P.Mtr              100
                                   V      95 sq.mm                                                         P.Mtr              200
                                  VI      120 sq.mm                                                        P.Mtr              100
                                  VII     150 sq.mm                                                        P.Mtr              100
                                  VIII    185 sq.mm                                                        P.Mtr              1400
                                   X      300 sq.mm                                                        P.Mtr              1100
                                   H      ARMOURED 4 CORE (XLPE)
                                    I     6 sq.mm                                                          P.Mtr              100
                                    II    10 sq.mm                                                         P.Mtr              2300
                                   III    16 sq.mm                                                         P.Mtr               900
                                  IV      25 sq.mm                                                         P.Mtr               200

                       SOR         6      BRASS COMPRESSION GLAND
                                  6.1     Supply and fixing heavy duly cable gland for
                                          p.v.c insulated armoured cable with brass
                                          washer, rubber ring complete erected with
                                          cable and lead connection etc. as per
                                          specification.
                                 6.1.1    Gland size 22mm suitable for cable 2,3,3.5 &
                                          4 x upto 6 sq.mm                                                 Each                 8
                                 6.1.2    Gland size 25mm suitable for cable 2,3,3.5 /
                                          2,4 & 4 x upto 16 sq.mm                                          Each                140
                                 6.1.4    Gland size 32mm for 2/3,3.5 4x25 sq.mm or
                                          2/3, 3.5 x 35 sq.mm or 2/3 x 50 sq.mm                            Each                28
                                 6.1.5    Gland size 35mm 4 x 35 sq.mm 3.5, 4 x 50
                                          sq.mm, 3 x 70 sq.mm                                              Each                 4
                                 6.1.7    Gland size 45mm 3/3.5 x 120 sq.mm, 3.5 x 95
                                          sq.mm, 3 x 150 sq.mm                                             Each                2
                                 6.1.8    Gland size 50mm 3.5 x 150 sq.mm, 3 x 185                         Each                4
                                 6.1.9    Gland size 57mm 3 x 225 sq.mm, 3.5 x 185                         Each                46
                                 6.1.11   Gland size 70mm 3.5 x 300 sq.mm,                                 Each                26

                       SOR         7      Supplying and fixing ferrules (Alu. In line
                                          Connector) As per IS-specification suitable for
                                          following size of cable with Alu. Strd./ soild
                                          conductor evently cramped with high pressure
                                          tool including connection as required
                                          complete.
                                   7.1    For conductor size
                                  7.1.2   10 sq.mm                                                         Each                262
                                  7.1.3   16.00 sq.mm                                                      Each                 28
                                  7.1.4   25.00 sq.mm                                                      Each                 28
                                  7.1.5   35.00 sq.mm                                                      Each                 28
                                 7.1.6    50.00 sq.mm                                                      Each                12
                                 7.1.7    70.00 sq.mm                                                      Each                 6
                                 7.1.8    95.00 sq.mm                                                      Each                46
                                 7.1.10   150.00 sq.mm                                                     Each                48
                                 7.1.11   185.00 sq.mm                                                     Each                138
                                 7.1.14   300.00 sq.mm                                                     Each                108

                       SOR         8      LUGS:-
                                          Supplying and fixing cramping type copper /
                                          Alu. Lugs as per ISS specification suitable for
                                          following size of cable with Alu. / copper solid
                                          / strd. Conductor evently cramped with high
                                          pressure tool and connected to switch gear/
                                          bus/ MCCB/ MCB/ etc. as requried complete.




                                                                                                                                                         5of 26
                                                                       dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                     Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                            DESCRIPTION                   UNIT               QTY.
                    NON SOR

                                          For conductor size
                                  8.1     6 sq.mm to 16 sq.mm                                   Each                62
                                  8.2     25 sq.mm                                              Each                28
                                  8.3     35 sq.mm                                              Each                28
                                  8.4     50 sq.mm                                              Each                12
                                  8.5     70 sq.mm                                              Each                 6
                                  8.6     95 sq.mm                                              Each                46
                                  8.8     150 sq.mm                                             Each                 48
                                  8.9     185 sq.mm                                             Each                138
                                  8.12    300 sq.mm                                             Each                108
                       SOR          9     Supply and fixing pin terminal lugs as per ISS
                                          specification suitable for cable evently
                                          cramped with high pressured tool &
                                          connection to switch gear terminal.
                                  9.1     Upto 16 sq.mm conductor size                          Each                220
                       SOR        10      Supplying and installing G.I. Pipe for
                                          protection of under ground cable fixed onwall/
                                          support/ in trench/ fixed between two rigid
                                          existing support of wall/ beam for erection of
                                          ceiling fan/ down rod for stiff pendent for light
                                          luminaries/fan/protective for earthing,
                                          lightening conductor down strip/ over head
                                          service line/ for submercible or centrifugal
                                          pump for water supply with necessary iron
                                          clamp coupler, bend, tee, elbow, nuts and
                                          bolts etc. complete, in an approved manner as
                                          requried to complete excluding cost of
                                          excavation / dismentalling & other finished
                                          masonary item complete.
                                  10.1    For 'B' class pipe ISI marked (IS-1161-68)
                                 10.1.5   38.1mm                                                P.Mtr               50
                                 10.1.7   63.00mm                                               P.Mtr               60
                                 10.1.9   101.00mm                                              P.Mtr               75

                       SOR         11     Supply and laying in existing trench, ISI
                                          marked R.C.C. Hume pipe N.P. 2 as per IS -
                                          458-1988 WITH COLLER etc. complete at
                                          work site as per specification.
                                  11.2    100.00mm dia with std. Length of 2 mtr.               P.Mtr               100
                                  11.3    150.00mm dia with std. Length of 2 mtr.               P.Mtr               150
                                  11.4    200.00mm dia with std. Length of 2 mtr.               P.Mtr               100
                                  11.7    300.00mm dia with std. Length of 2 mtr.               P.Mtr               250

                       SOR         12     CABLE LAYING
                                  12.4    Laying of one number additional PVC
                                          insulated and pvc sheathed power cable of
                                          1.1 kv grade of the same trench in one tier
                                          horizontal formation including excavation.
                                          Sand cushioning. protective covering and
                                          refilling the pit etc. as                             P.Mtr               300
                                  12.5    Laying of one number additional PVC
                                          insulated and pvc sheathed power cable of
                                          1.1 kv grade ofsize exceeding 25 sq.mm but
                                          not exceeding 120 sq.mm. direct in ground in
                                          the same trench in one tier horizontal
                                          formation including excavation Sand
                                          cushioning, protective covering and refilling
                                          the pit etc. as required.                             P.Mtr               200
                                  12.6    Laying of one number additional PVC
                                          insulated and pvc sheathed power cable of
                                          1.1 kv grade of size exceeding 120 sq.mm but
                                          not exceeding 400 sq.mm direct in ground in
                                          the same trench in one tier horizontal
                                          formation including excavation Sand
                                          cushioning, prtective covering and refilling the




                                                                                                                                              6of 26
                                                                       dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                              Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                           DESCRIPTION                             UNIT               QTY.
                    NON SOR

                                        pit etc. as required.                                            P.Mtr               600
                                  12.7  Laying of one number PVC insulated and pvc
                                        sheathed power cable of 1.1 kv grade of size
                                        not exceeding 25 sq.mm in the existing RCC
                                        hume/ stone/ ware/ G.I. Pipe as required.                        P.Mtr               500
                                 12.8   Laying of one number PVC insulated and pvc
                                        sheathed power cable of 1.1 kv grade of size
                                        exceeding 25 sq.mm but not exceeding 400
                                        sq.mm in the existing RCC hume/ stone/ ware
                                        / G.I. Pipe as required.                                         P.Mtr               900
                                 12.9   Laying of one number pvc insulated and pvc
                                        sheathed power cable of 1.1 kv grade of size
                                        not exceeding 25 sq.mm in the existing
                                        masonary open duct as required.                                  P.Mtr              1700
                                 12.1   Laying of one number pvc insulated and pvc
                                        sheathed power cable of 1.1 kv grade of size
                                        exceeding 25 sq.mm but not exceeding 400
                                        sq.mm in the existing masonry open duct as.                      P.Mtr              1900
                                 12.22 Laying of cement concrete or approved type
                                        of cable cover/ flage stone over L.T. cover
                                        trench as per specification.                                     P.Mtr               40
                                 12.23 Supply and laying rigid PVC single socket and
                                        non-matelic pipe ISI marked (IS-4985-1968)
                                        for protection of under ground cable/ or for
                                        water pump delivery side, for water supply
                                        complete with necessary clamp coupler, bend
                                        tee, elbow, etc. in an approved manner
                                        excluding cost of excavation etc.
                                12.23.1 50.00 mm                                                         P.Mtr               20
                                12.23.3 101.00 mm                                                        P.Mtr               20

                       SOR         13     ROUT MARKER
                                          Fixing rout marker with cement concrete 1:2:4
                                          (1 cement and 2 coarse sand 4 graded stone
                                          aggregate 20mm nomminal size) of size
                                          60cm. X60cm at the bottom and 50cm x 50cm
                                          at the top with a thickness of 10cm. Including
                                          inscription duly engraved as required.
                                                                                                         Each                70
                       SOR         14     Supplying rout marker with 10cm. x 10 cm.
                                          G.I. Plate 5mm thick with inscription thereon
                                          bolted/ welded to 35mm x 35mm x 6mm in
                                          ground as required.                                            Each                70
                                          SUB TOTAL


                      NSOR         E      CABLING WORK
                                  E.1     Supply and laying of cables in excavated trenches,
                                          concrete trenches, along walls, through hume pipes, cable
                                          trays etc with testing & commissioning. The cable shall be
                                          1.1 KV grade XLPE, copper armoured of approved make as
                                          per following sizes The scope includes supply & fixing of
                                          aluminium       cable tags(     at    every      6     Mts
                                          distance),clamps/saddles    for dressing of cable/cable
                                          route markers at every 7 Mtr. distance as              per
                                          drawings, specifications & instructions of consultant.

                                 E.1.1    4CX4 SQMM CU.AR XLPE CABLE                                      mtr               1000
                                 E.1.2    4CX2.5 SQMM CU.AR XLPE CABLE                                    mtr                80
                                 E.1.3    12CX2.5 SQMM CU.AR XLPE CABLE                                   mtr                150
                                 E.1.4    24CX2.5 SQMM CU.AR XLPE CABLE                                   mtr                150




                                                                                                                                                       7of 26
                                                                     dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                   Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                            DESCRIPTION                                 UNIT               QTY.
                    NON SOR

                                  E.2     Cable termination of armoured cables 1.1 KV grade
                                          including supply & installation of cable glands, cable lugs
                                          (copper or aluminium single compression type), heat
                                          shrinkable sleeves on long ends, crimping paste etc. The
                                          work includes testing & commissioning of cables,
                                          meggaring values & submitting reports of tests. (One set
                                          includes termination of all cores of one end only)

                                 E.2.1    4CX4 SQMM CU.AR XLPE CABLE                                           Set                54
                                 E.2.2    4CX2.5 SQMM CU.AR XLPE CABLE                                         Set                 6
                                 E.2.3    12CX2.5 SQMM CU.AR XLPE CABLE                                        Set                18
                                 E.2.4    24CX2.5 SQMM CU.AR XLPE CABLE                                        Set                 8

                                          SUB TOTAL

                      NSOR         F      CABLE TRAY
                                  F.1     Supply ,installation ,testing & commissioning of GI
                                          perforated cable tray 2mm thick without cover and all
                                          accessories like perforated tee , 90 degree horizontal bend
                                          ,elbow , horizontal tee,,supports,hangers etc. of following
                                          sizes
                                 F.1.1    900 mm (depth - 100mm)                                               Mtr                 50
                                 F.1.2    600 mm (depth - 100mm)                                               Mtr                120
                                 F.1.3    300 mm (depth -60mm)                                                 Mtr                100
                                 F.1.4    150 mm (depth -60mm)                                                 Mtr                100

                                          SUB TOTAL

                      NSOR         G      LT PANELS AND DB
                                  G.1     Supply,Installation , Testing & Commissioning of following
                                          panels .
                                 G.1.1    MAIN ELECTRICAL PANEL ( APFCR with harmonic reactor                  No                  1
                                          capacitor         ,      14%       detuned       reactors)
                                          AS PER DWG NO:- NVBA/NVB/KUSH/MEP/01
                                 G.1.2    DG AMF PANEL                                 AS PER DWG              No                  1
                                          NO:- NVBA/NVB/KUSH/MEP/02
                                 G.1.3    COMMON AREA MAIN PANEL                       AS PER DWG              No                  1
                                          NO:- NVBA/NVB/KUSH/COMMON AREA MAIN PANEL/08

                                 G.1.4    COMMON AREA LPDB                           AS PER DWG NO:-           No                  1
                                          NVBA/NVB/KUSH/GLPDB/COM/010
                                 G.1.5    COMMON AREA ACDB                            AS PER DWG NO:-          No                  1
                                          NVBA/NVB/KUSH/ACDB/COM/12
                                 G.1.6    ACDB      CANTEEN                           AS PER DWG NO:-          No                  1
                                          NVBA/NVB/KUSH/ACDB/CANT/13
                                 G.1.7    SECURITY GATE PANEL -                        AS PER DWG NO:-         No                  1
                                          NVBA/NVB/KUSH/SECU/PN/18
                                 G.1.8    Supply ,installation, testing & commissioning of sheet steel
                                          enclosed 3 phase & neutral 415V, 50 Hz. aluminium
                                          conductor bus duct including bends, transposition piece
                                          expansion joint, all flexible connections as per specifications
                                          and drawings with all accessories, supports and termination
                                          of bus duct to switchgear/transformer/DG SET.Cost for all
                                          supports required for mounting of bus duct with all bends ,
                                          hardware ets is included in running meter cost.

                                G.1.8.1    BUS DUCT 2500A (outdoor duty type)                                  Mtr                30
                                G.1.8.2   Supply , Installation testing and comissioning of flexible
                                          jointing box for end connection.
                                G.1.8.3   2500A                                                                 No                 2

                                          SUB TOTAL




                                                                                                                                                            8of 26
                                                                      dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                  Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                            DESCRIPTION                                UNIT               QTY.
                    NON SOR

                      NSOR         H      LT EARTHING
                                  H.1     Supply, Installation, Testing & commissioning of earthing
                                          stations using Chemical earth electrodes of Ashlok /
                                          Equivalent make with 80mm Dia ,3000mm Long GI pipe
                                          electrode complete with Back Filling ompound. The scope
                                          also includes excavation / Boring required for electrode up
                                          to 3000mm deep. In all type of soil and back filling including
                                          preparing brick masonry chamber 200 mm thick and 450 mm
                                          deep with 1:4 cement mortar with 1:3 plaster from inside
                                          the chamber 20 mm thick fixing of 300 mm* 300mm CI cover
                                          (cover shall be of medium duty with weight not less than 10
                                          Kg), funnel etc. as per IS 3043/1987 revised up to date.


                                 H.1.1    80MM dia , 3000MM long Electrode with necessary back                Nos.               40
                                          filling compound.

                                  H.2     Supply & laying of hot dipped GI/pure copper earthing strip
                                          to connect to the DBS,Poles and equipments in outdoor yard
                                          and also in indoor portion of substation.
                                 H.2.1    25*3 mm GI strip                                                    Mtr               350
                                 H.2.2    25*5 mm GI strip                                                    Mtr               100
                                 H.2.3    35*5 mm GI strip                                                    Mtr               300
                                 H.2.4    50*5 mm GI strip                                                    Mtr               150
                                 H.2.5    25*3 mm CU strip                                                    Mtr                75
                                 H.2.6    50*5 mm CU strip                                                    Mtr                80
                                 H.2.7    35*5 mm CU strip                                                    Mtr                60
                                 H.2.8    25*5 mm CU strip                                                    Mtr                30
                                 H.2.9    8G GI wire                                                          Mtr               1200

                                          SUB TOTAL

                      NSOR          I     LIGHTING FIXTURES AND FANS
                                             Supply, Installation , Testing & Commissioning          of
                                          following lighting fixture and fan. All fixtures should be
                                          complete with all accessories such as lamps, starters , low
                                          loss copper chokes, PF improvement capacitors etc. As
                                          per following details the model no. given in BOQ is for one
                                          particular make . The fixture,fan shall be supplied and
                                          installed of given make or equivalent type from list of
                                          approved make as per instructions of Architects / EIC . The
                                          above specification governs all work specified in item I.1 to
                                          I.23

                                   I.1    Mirror optic fitting suitable for 2X36W CFL lamps complete          Nos                160
                                          with all accessories and lamp & electronic ballast. MAKE
                                          WIPRO WVP 56236 SGW
                                   I.2     Mirror optic fitting suitable for 2X36W FTL lamps complete         Nos                10
                                          with all accessories and lamp& electronic ballast.MAKE
                                          WIPRO WVF-40236 SGW
                                   I.3    Industrial channel suitable for 1X36W FTL tube light                Nos                30
                                          complete with all accessories and lamp.MAKE - WIPRO
                                          WCF 12136 SGW (stair case & other area)
                                   I.4    Industrial channel suitable for 2X36W FTL tube light                Nos                25
                                          complete with all accessories and lamp.MAKE - WIPRO
                                          WCF 12236 SGW (store area)
                                   I.5    Down light fitting suitable for 2x18W CFL lamp complete             Nos                250
                                          with all accessories and lamp MAKE - WIPRO WCP 32218
                                          SGW
                                   I.6    Down light fitting suitable for 1x18W CFL lamp complete             Nos                40
                                          with all accessories and lamp MAKE - WIPRO WCP 32118
                                          SGW for emergency lights.




                                                                                                                                                           9of 26
                                                                      dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                 Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                           DESCRIPTION                                UNIT               QTY.
                    NON SOR

                                   I.7    Spot light fitting suitable for 1x50W Diachronic halogen lamp      Nos                75
                                          complete with all accessories ,electronic transformer and
                                          lamps. MAKE - WIPRO WCQ 22150 SGW

                                   I.8    Recess mounted metal halide downlighter suitable for               Nos                 5
                                          1x150Wcomplete with all accessories ,electronic transformer
                                          and lamps. MAKE - WIPRO WCG 50150
                                   I.9    Down light fitting suitablefor 2x11W CFL lamp complete with        Nos                10
                                          all accessories and lamp MAKE - CROMPTON COC-211( FOR
                                          TOILETS)
                                  I.10    Surface Down light fitting suitablefor 2x18W CFL lamp              Nos                12
                                          complete with all accessories and lamp MAKE - WIPRO
                                          WVP 41218 ( FOR PORCH)
                                  I.11    Wall light fitting suitable for 1x18W CFL lamp complete with       Nos                 5
                                          all accessories and lamp MAKE - CROMPTON CWU18

                                  I.12    Celling fan 1400 mm sweep complete with down rod , up              Nos                 2
                                          and down canopy etc complete in all respect with step fan
                                          type modular electronic regulator .Make Crompton High
                                          Speed
                                  I.13    Wall fan 300mm sweep complete with all accessories .Make           Nos                 1
                                          Crompton WM TROPICANA
                                  I.14    Fresh Air Exhaust fan with louvers 200 mm sweep complete           Nos                12
                                          with all accessories .Make KHAITAN FRESH AIR DELUX

                                  I.15    Industrial Heavy duty Exhaust fan 300 mm sweep complete            Nos                 6
                                          with all accessories .Make KHAITAN / Crompton

                                  I.16    Post Top decorative light fitting suitable for 1x150W metal        Nos                12
                                          halide lamp complete with all accessories and lamp. -
                                          PHILIPS-Sonara HPS360 1 x CDM-TT 150/Wipro
                                  I.17    Bollard light fitting suitable for 1x18W CFLlamp complete          Nos                21
                                          with all accessories and lamp. - PHILIPS-Sonara HPS360 1 x
                                          PL-C-18 / Wipro
                                  I.18    Flood light fitting suitable for 2x250W metal halide lamp          Nos                 8
                                          complete with all accessories and lamp. - PHILIPS-RVP301/ 2
                                          x SON-T 250 / Wipro
                                  I.19    Wall mounted decorative light fitting suitable for 1x70W           Nos                16
                                          metal halide lamp complete with all accessories and lamp. -
                                          PHILIPS-Ophelia DCP731/ CDM-T 70W / Wipro

                                  I.20    BUSH light fitting suitable for 1x50W,12v Halogen lamp             Nos                12
                                          complete with all accessories and lamp. - PHILIPS- DGP 65 I /
                                          Wipro
                                  I.21    LED Strip light fitting(1mtr. Length) suitable for 3Watt LED       Mtr.               10
                                          lamp,24v complete with all accessories and lamp. - WIPRO-
                                          LS10-003-XXX-WW-05 / Philips.
                                  I.22    LED UP/DOWN Lighter suitable for 6x1Watt LED lamp,230v             Nos                 6
                                          complete      with     all   accessories    and     lamp.   -
                                          WIPRO-LW17-006-045-RD/ GR/BL /AM/WH /WW/- / Philips.

                                  I.23    Street Light fitting suitable for1x150 Watt metal hallide          Nos                 6
                                          lamp,230v complete with ballast, all accessories and lamp. -
                                          Philips- Modena SGP 682 / Wipro.




                                          SUB TOTAL




                                                                                                                                                         10of 26
                                                                     dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                 Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                           DESCRIPTION                                UNIT               QTY.
                    NON SOR

                      NSOR          J     TELEPHONE WIRING
                                   J.1    Supply & Installation of 16 gauge HGMS black enameled
                                          ERW grade conduit of approved make with accessories like
                                          heavy duty pull boxes with covers, GI saddles, bends, socket
                                          etc. in concealed/surface manner in wall, ceiling, floor etc.
                                          The work includes chiseling of wall i.e. ziri with mechanical
                                          cutter, saddling of conduits at maximum 400 mm distance
                                          etc.
                                  J.1.1   DIA 25mm conduit                                                   Mtr               1000
                                   J.2    Supply,Installation, Testing & commissioning of 0.5 mm size        Mtr               2500
                                          tinned copper conductor , 2 pair PVC insulated telephone
                                          wire of approve make in existing MS conduits.

                                   J.3    Supply,Installation, Testing & commissioning of crone type
                                          tag block for termination of telephone cables/conduits in MS
                                          sheet steel enclosures as per drawing and specifications.

                                  J.3.1   Tag block 5 pair.                                                  Nos.                1
                                  J.3.2   Tag block 10 pair.                                                 Nos.                2
                                  J.3.3   Tag block 20 pair.                                                 Nos.                2
                                  J.3.4   Tag block 50 pair.                                                 Nos.                2
                                  J.3.5   Tag block 200 pair.                                                Nos.                1
                                   J.4    Supply,Installation, Testing & commissioning of 0.5 mm size
                                          copper tinned conductor armoured PVC cable of following
                                          sizes
                                  J.4.1   5 pair.                                                            Mtr                60
                                  J.4.2   10 pair.                                                           Mtr                150
                                  J.4.3   20 pair.                                                           Mtr                150
                                  J.4.4   50 pair.                                                           Mtr                 60
                                  J.4.5   200 pair.                                                          Mtr                150
                                   J.5    Supply,Installation, Testing & commissioning of 0.5 mm size
                                          copper tinned conductor unarmoured PVC cable of
                                          following sizes
                                  J.5.1   50 pair.                                                           Mtr                60
                                  J.5.2   20 pair.                                                           Mtr                10
                                   J.6    Supply,Installation, Testing & commissioning of Telephone          Nos.               55
                                          outlet box with top plate

                                          SUB TOTAL

                      NSOR         K       COMPUTER CABLING
                                  K.1     Supply & Installation of 16 gauge HGMS black enameled
                                          ERW grade conduit of approved make with accessories like
                                          heavy duty pull boxes with covers, GI saddles, bends, socket
                                          etc. in concealed/surface manner in wall, ceiling, floor etc.
                                          The work includes chiseling of wall i.e. ziri with mechanical
                                          cutter, saddling of conduits at maximum 400 mm distance
                                          etc.
                                 K.1.1    DIA 25mm conduit                                                   Mtr               1200
                                  K.2      Supply , installation,testing and commissioning of enhanced       Mtr               2640
                                          CAT E6 LAN cable in preveiously laid conduits .Data cable
                                          installation shall be carried out by approved vendor & final
                                          certification shall be required.

                                  K.3     Supply , installation,testing and commissioning of RJ 45           Nos                55
                                          connector type computer socket outlet with RJ 45 connector
                                          of approved make .The sockets installation shall be carried
                                          out by approved vendor & final certification shall be
                                          required.

                                          SUB TOTAL




                                                                                                                                                         11of 26
                                                                     dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                 Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                           DESCRIPTION                                UNIT               QTY.
                    NON SOR

                      NSOR         L       TV CABLING
                                  L.1     Supply & Installation of 16 gauge HGMS black enameled
                                          ERW grade conduit of approved make with accessories like
                                          heavy duty pull boxes with covers, GI saddles, bends, socket
                                          etc. in concealed/surface manner in wall, ceiling, floor etc.
                                          The work includes chiseling of wall i.e. ziri with mechanical
                                          cutter, saddling of conduits at maximum 400 mm distance
                                          etc.
                                 L.1.1    DIA 25mm conduit                                                   Mtr                100
                                  L.2     Supply,Installation, Testing & commissioning of TV outlet          Nos.                2
                                          box with top plate
                                  L.3     Supply,Installation, Testing & commissioning of coaxial TV
                                          cable
                                  L.4     RG 11                                                              Mtr                70
                                  L.5     RG 6                                                               Mtr                100
                                  L.6     Supply,Installation, Testing & commissioning of TV tap off         Nos.                2
                                          boxex and TV splitter boxes.
                                          SUB TOTAL

                      NSOR        M       SPEAKER WIRING
                                  M.1     Supply & Installation of 16 gauge HGMS black enameled
                                          ERW grade conduit of approved make with accessories like
                                          heavy duty pull boxes with covers, GI saddles, bends, socket
                                          etc. in concealed/surface manner in wall, ceiling, floor etc.
                                          The work includes chiseling of wall i.e. ziri with mechanical
                                          cutter, saddling of conduits at maximum 400 mm distance
                                          etc.
                                 M.1.1    DIA 25mm conduit                                                   Mtr                700
                                 M.2      Supply & laying of twin twisted 1.5 sqmm cu flexible wire          Mtr.              1200
                                          1.1 kv grade pvc insulated.
                                  M.3     Supply, Installation, Testing and commissioning of 2 pin           No.
                                                                                                                                10
                                          Audio socket
                                  M.4     Supply, Installation, Testing and commissioning of 6w ceiling
                                          ring speakers with line matching transformer suitable for 4
                                                                                                             No.                70
                                          ohm impedence. dia 200mm LBD 0606/10. MAKE
                                          PHILIPS/BOSCH
                                  M.5     Supply, Installation, Testing and commissioning of 6w
                                          wall/coloumn speakers with line matching transformer               No.                12
                                          suitable for 4 ohm impedence. MAKE PHILIPS/BOSCH
                                  M.6     Supply, Installation, Testing and commissioning of public          No.                 1
                                          address audio conference system with CD player /recorder/
                                          and double channel (L/R) output suitable for 4 ohm
                                          impedence.The system shall be with 1 No. power amplifier
                                          400W+400W and 1 no.table top microphone unit. MAKE -
                                          PHILIPS/BOSCH
                                  M.7     Supply, Installation, Testing and commissioning of                 No.                 4
                                          distribution box for PA distribution made out of 16 SWG
                                          CRCA sheet with double door lockable arrangement having
                                          connectors (15 NOS) suitable for 4 sqmm/2.5sqmm wire
                                          with facity for cable termination of 4cx10 sqmm ALAR.
                                          Required at each floor for PA wire termination

                                  M.8     Supply, Installation, Testing and commissioning of Audio           No.                 1
                                          Conference System with CD player /recorder/ and double
                                          channel (L/R) output suitable for 4 ohm impedence.The
                                          system shall be with 1 No. power amplifier 150Watt and 1
                                          no.table top microphone unit, 1no. Chairman unit, 12no.
                                          delegate unit with goosenecks, 1no. Secretary unit. MAKE -
                                          PHILIPS/BOSCH




                                                                                                                                                         12of 26
                                                                     dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                     Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                             DESCRIPTION                                  UNIT               QTY.
                    NON SOR

                                  M.9     Supply, Installation, Testing and commissioning of Audio               No.                 1
                                          Conference System with CD player /recorder/ and double
                                          channel (L/R) output suitable for 4 ohm impedence.The
                                          system shall be with 1 No. power amplifier 150Watt and 1
                                          no.table top microphone unit, 1no. Chairman unit, 8 no.
                                          delegate unit with goosenecks, 1no. Secretary unit. MAKE -
                                          PHILIPS/BOSCH


                                          SUB TOTAL

                      NSOR         N      FIRE ALARM SYSTEM
                                  N.1     Supply,      Installation,Testing  &     Commisioning      of          Nos                 1
                                          Microprocessor based DOUBLE LOOP configuration panel ,
                                          fully networkable with each loop capable of taking (125X2)
                                          devices, 8 line x 40 character alpha-numeric liquid crystal
                                          display .The panel shall be soft addressable type . The panel
                                          shall be able to give pin point location of all fire/fault
                                          conditions. Further, the panel must be able to automatically
                                          switch off respective control switches when ever any alarm
                                          is triggered.

                                          The panel shall have in built rectifier, Loop cards,provision
                                          for internal printer(if required), L C D unit to indicate
                                          Fire/Fault Signal with address and analog output, built in
                                          printer to log all fire or fault events complete in all respects,
                                          integral SMF lead acid batteries with sealed cells of 24 V
                                          capable of running for a minimum of 8 hours with integral
                                          battery charger complete as required and as per
                                          specification. (Approved Make: Esser/Honeywell/Siemens
                                          /Notifier)
                                  N.2     Supply, Installation,Testing & Commisioning of Analogue                Nos.               225
                                          Addressable Intelligent Optical Smoke Detector with
                                          decentralised intelligence , soft addressable type, with
                                          inbuilt fault isolator complete with base as required.
                                          (Approved Make: Esser/Honeywell/Siemens /Notifier)

                                  N.3     Supply, Installation,Testing & Commisioning of Analogue                Nos.                3
                                          Addressable Intelligent Heat Detector with fixed & rate of
                                          rise temperature function with decentralise intelligence ,
                                          soft addressable type, with inbuilt fault isolator complete
                                          with     base      as     required.    (Approved     Make:
                                          Esser/Honeywell/Siemens /Notifier) ( for pantry)

                                  N.4     Supply, Installation,Testing & Commisioning of Addressable             Nos.               15
                                          Manual Call Point soft addressable type with in built fault
                                          isolator complete as required. (Approved Make:
                                          Esser/Honeywell/Siemens /Notifier) (location near each floor
                                          stair case)
                                  N.5     Supply, Installation,Testing & Commisioning of Analogue                Set                 3
                                          Addressable Intelligent loop powered sounder,flasher &
                                          speaker. (Approved Make: Esser/Honeywell/Siemens
                                          /Notifier) (location near each floor stair case)

                                  N.6     Supply, Installation,Testing & Commisioning of Analogue                NOS                12
                                          Addressable Intelligent approved make exit glow signs with
                                          lamp 24V DC operated for route indications as required
                                          for installation of sensor.

                                  N.7     Supply, Installation,Testing & Commisioning of Analogue                Nos.                1
                                          Addressable Intelligent loop powered sounder. (Approved
                                          Make: Esser/Honeywell/Siemens /Notifier)




                                                                                                                                                             13of 26
                                                                       dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                   Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                            DESCRIPTION                                 UNIT               QTY.
                    NON SOR

                                  N.8     Supply , installation, testing and commissioning of approved        MTR                2200
                                          make 1.1KV grade PVC insulated and shethed shielded
                                          3cx2.5 sqmm copper armoured FRLS cable .


                                          SUB TOTAL

                      NSOR         O      CCTV SYSTEM
                                          Indoor and Outdoor Cameras
                                  O.1     Supply, installation, testing and commissioning of indoor           Each                25
                                          colour fixed type dome camera 2.1mm/4mm/6mm focal
                                          length lens capable to 1.0 lux sensitivity, 480 TV lines as per
                                          tender specifications.
                                  O.2     Supply, installation, testing and commissioning of Digital          Each                 2
                                          Video Recorder to record above camera signals as per
                                          following specifications.
                                 O.2.1    The System shall have capability to handle 2 no. video inputs

                                 O.2.2    The basic configuration of the DVR shall be
                                 O.2.3    Camera inputs - -- nos
                                 O.2.4    External monitor : 01 composit CCTV monitor
                                 O.2.5    Display : Real Image
                                 O.2.6    Recording Speed (Min) : PAL 200 Frame/Sec
                                 O.2.7    Image compression method : MPEG-4 or better
                                 O.2.8    External Alarm Input - -- Channels
                                 O.2.9    Relay Control Output : -- output
                                 O.2.10   Remote transmission : On LAN or WAN
                                 O.2.11   Image verify water mark
                                 O.2.12   Surveillance method : Motion detection,sensor
                                 O.2.13   PAN/TILT : RS -422 / Other data
                                 O.2.14   Compliance to UL listed
                                  O.3     The system programming shall be password protected and
                                          shall have different levels of passwords for virusprotection
                                          must be provided in DVR using operating system like
                                          Windows , Unix ,Linux etc
                                  O.4     All camera and the integrated CCTV system equipment shall
                                          be designed for continuous operation.
                                  O.5     The DVR shall have built in DVD writer . The system should
                                          be non PC based and should allow connectivity of external
                                          hard disc arrays through SCSI ports. The DVR should have
                                          hard disc of 320 GB (min) internal built in with a capacity to
                                          expend up to 2 TB.
                                  O.6      Supply, Installation, testing and commissioning of switcher        Each                 2
                                          & mixer for cctv system as per specifications and consisting
                                          of 16 camera inputs and 1 no. monitor output with
                                          programmable sequencial switcher / split screen viewing .
                                          Video motion detector auxillary inputs and outputs with
                                          keyboard operation for on site programming.

                                  O.7     Supply, installation, testing and commissioning of 19" Flat         Each                 2
                                          Screen VGA Color Monitor
                                  O.8     Supply, installation, testing and commissioning of wall              Set                 2
                                          mounted cabinet with drawer shelves and wiring channels to
                                          accommodate CCTV system equipment and accessories as
                                          mentioned in the BOQ above and including all connections
                                          and terminations as required fabricated from minimum 2
                                          mm thick CRCA sheet including power coating after surface
                                          treatment complete as required.




                                                                                                                                                           14of 26
                                                                      dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                 Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                           DESCRIPTION                                UNIT               QTY.
                    NON SOR

                                  O.9     Supply, Installation, Testing and commissioning of                 No.                 2
                                          distribution box for CCTV distribution made out of 16 SWG
                                          CRCA sheet with double door lockable arrangement having
                                          connectors (16 NOS) suitable for 4 sqmm/2.5sqmm wire
                                          with facity for cable termination of 4cx10 sqmm ALAR.
                                          Required at each floor for CCTV wire termination ( 2 on each
                                          floor mall area , 2 on each parking floor)

                                 O.10     Supply, installation, testing and commissioning of Coaxial
                                          Cable of the following types including Video Signal
                                          Amplifiers and drawing through conduits, cable transmission
                                          media shall be copper.
                                 O.11     Supply, installation, testing and commissioning of RG 11           RM                 900
                                          Coaxial cable including all necessary BNC connector.
                                          (Cameras to DVR & DVR to Monitor)-Armoured
                                 O.12     Supply, installation, testing and commissioning of Power           RM                 900
                                          cable of 2 x 1.5 sq. mm. FRLS shielded copper conductor
                                          cable. (Power to Cameras).
                                 O.13     Supply & Installation of 16 gauge HGMS black enameled
                                          ERW grade conduit of approved make with accessories like
                                          heavy duty pull boxes with covers, GI saddles, bends, socket
                                          etc. in concealed/surface manner in wall, ceiling, floor etc.
                                          The work includes chiseling of wall i.e. ziri with mechanical
                                          cutter, saddling of conduits at maximum 400 mm distance
                                          etc.
                                 O.13.1   25 mm dia                                                          RM                 600

                                 O.14     Supply,Installation,Testing and commissioning of 2 KVA UPS
                                          suitable for 2 hours back up complete with Ni-Cadmium
                                          maintenance free batteries duly charged complete with
                                          connecting lead as required for 10 hour back up for all
                                          controls and equipment operating mechanism of VCBs ,
                                          indications , protection devices and alarm.Other details are
                                          as per Technical Specifications Of this tender. Make-Rocket
                                          / Exide (SMF type). -1 no.

                                          Make:- Emerson /APC                                                No.                 1
                                          SUB TOTAL

                      NSOR         P      SENSOR
                                  P.1     Supply & Installation of 16 gauge HGMS black enameled              mtr                700
                                          ERW grade conduit of approved make with accessories like
                                          heavy duty pull boxes with covers, GI saddles, bends, socket
                                          etc. in concealed/surface manner in wall, ceiling, floor etc.
                                          The work includes chiseling of wall i.e. ziri with mechanical
                                          cutter, saddling of conduits at maximum 400 mm distance
                                          etc.
                                  P.2     Supply,Installation Testing and commissioning of Proximity         No.                10
                                          card Sensor RF 10/RF 20 suitable for Surface mounting
                                          having possibility of computer connectivity .Make - Toshi

                                  P.3     Supply,Installation Testing and commissioning of thin              No.                45
                                          Proximity card standard .Make - Toshi
                                  P.4     Supply,Installation     Testing and   commissioning of             No.                 3
                                          electromagnetic lock .Make - Toshi
                                  P.5     communication device                                               No.                 1
                                  P.6     Supply installation, testing and Commissioning of                  mtr                600
                                          8 CORE X 0.5 mm size tinned copper conductor flexible, PVC
                                          insulated access control cable in existing 25 mm MS
                                          conduits laid as per item X.1

                                          SUB TOTAL




                                                                                                                                                         15of 26
                                                                     dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                    Internal Electrification for Network Monitoring Center.




                     SOR /         S.No.                           DESCRIPTION                                 UNIT               QTY.
                    NON SOR

                      NSOR            Q    INVERTER
                                     Q.1   Supply installation ,testing & commissioning of 3000VA ,1HR          nos.                1
                                           back up inverter with 12 volt Invagreen Exide or Farukawa
                                           make battery . The inverter is to be installed on every floor &
                                           connection shall be made with lighting DB for floor
                                           emergency lighting . Inverter shall be make
                                           MICROTECH/LUMINIOUS/EXIDE
                    ESTIMATE FOR ELECTRICAL WORKS OF NETWORK MONITORING CENTRE AT
                       PART-B
                     SOR /         S.No.                           DESCRIPTION                                 UNIT               QTY.
                    NON SOR


                               R           HT LINE EXTENSION WORK
                                           Following items are to be executed for external HT Line
                                           erected along the road from the point of tapping as agreed
                                           by MPEB up to the premises of project for bringing two sets
                                           of feeders from different locations ; The scope of work under
                                           this item may increase or decrease as per MPEB's approval
                                           for point of supply.The contractor has to arrange all
                                           necessary approvals from various departmnets related to
                                           this work and no separate charges shall be payble.
                               R.1         Supply erection and installation ,testing & commissioning of         nos.               40
                                           HT rail pole (52 kg/mtr) with single length of 13mtr
                                           alongwith crossarm made from ISMC100 channel , guard
                                           wires supports made from ismc 100 channel with overhang
                                           up to1.2 times , including all clamps and hardware ,
                                           including all clamps and hardware.
                                           The work includes digging of pit of required size & for
                                           grouting of 20% length of pole undergroung ,supply & filling
                                           with 1:3:6 cement concrete of 0.6 mtr dia up to ground ,
                                           muffing of 0.5 mtr from ground to level of 0.2 mtr . The work
                                           also include supply and intallation of earthing coil of 150
                                           turns made from 8 guage wire , anticlimbing device &
                                           danger board on each pole.The poles are to be panted with
                                           one coat of red oxide primer and two coats of Aluminium
                                           paint of berger/bombay paints makr . complite work shall be
                                           cassied out as per instruction of E/C consultant , weight of
                                           pole shall be 52 kg/mtr.
                               R.2         Supply installation ,testing & commissioning of pin & disc
                                           insulators as per followingdetails incluiding all supply &
                                           installation     of    hardware,clamps      for   conductors
                                           ,bindingmaterial,support fabrication ect. As per approved
                                           make
                               R.2.1       33kv pin insulators                                                  nos                120
                               R.2.2       33kv disc insulators                                                 nos                54
                               R.3         Supply installation ,testing & commissioning, of following
                                           including required digging of atleast 2.5 mtr depth pit of
                                           required size and concreating as per drawing, direction and
                                           specification
                               R.3.1       rail pole strut supports with all hardware & clamps                  nos.                8
                               R.3.2       stay set complete with all hardware & clamps,                        nos.                8
                               R.4         Supply installation,stringing, testing & commissioning of            mtr               6300
                                           AAAC conductor (DOG) of approved make, 100 SQMM
                                           aluminium equiv. conductor .


                                           SUB TOTAL

                               S           HT INSTALLATION




                                                                                                                                                            16of 26
                                                                       dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                    Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                            DESCRIPTION                                  UNIT               QTY.
                    NON SOR

                               S.1        Supply, installation, testing and commissioning of single             SET                 2
                                          piece non-linear resistor type lightning arrestor suitable for 3
                                          wire, 33 KV O/H line, rated. Voltage of 10 KV (rms) with a
                                          nominal discharge current rating of 10 KA (station class) and
                                          complete with galvanised clamping arrangement G.I. bolts,
                                          nuts, washers etc. as required (to be provided on all phases).
                                          (1 set contains 3 pieces)

                               S.2        Supply,Installation, Testing, Commissioning of 400A,33KV, 3           SET                 2
                                          Phase approve make AB switch with GI 40 mm dia B class
                                          operating rod & handle with pad locking arrangements.

                               S.3        Supply,Installation, Testing, Commissioning of 33 KV, 400A            SET                 2
                                          approved make dropout fuse mounts complete with 5A DO
                                          fuses, fuse holders etc.
                               S.4        Supply,Installation, Testing, Commissioning of Operating rod          No.                 2
                                          of DO fuse.
                               S.5        Supply, installation, testing and commissioning of Two pole           SET                 2
                                          structure (approved make) fabricated from using `H`-
                                          BEAM(37.1 KG/MTR)-13 MTR.LONG to accommodate the
                                          equipments as mentioned above with one coat of red oxide
                                          primer and two coats of aluminum paint complete in all
                                          respect. The work has to be executed as per dwg. &
                                          specifications and directions of consultant. `H`-BEAM(37.1
                                          KG/MTR)-13 MTR.LONG 2 NOS. 2. ISMC 100 4.5 MTR. LONG
                                          – 9 NOS.
                               S.6        Supply, installation, testing and commissioning of Two pole           Set                 2
                                          structure fabricated (approved make) from using `H`-
                                          BEAM(37.1 KG/MTR)-13 MTR.LONG to accommodate the
                                          CT/PT unit 11 KV and meter box with one coat of red oxide
                                          primer and two coats of aluminum paint complete in all
                                          respect. The work has to be executed as per dwg. &
                                          specifications and directions of consultant. The work also
                                          includes providing help in installation of CT/PT AND
                                          METERING           UNIT        of     electricity     board.
                                          1. `H`-BEAM (37.1 KG/MTR)-13 MTR.LONG-2NO. 2. ISMC 100
                                          4.5 MTR. LONG – 4 NOS. 3. MS EQUAL ANGLE 35*35*5
                                          mm.– 8M 4.MS FLAT 50 * 5 mm – 8 MTR.

                               S.7        Providing interlocking between 33KV GOD & transformer                 JOB                 2
                                          MCCB complete using 4C*2.5 sq. mm. copper armoured
                                          cable approved make maximum length 20 mtr. With limit
                                          switches approved make.
                               S.8        Supply,Installation, Testing, Commissioning of 33 KV                  Nos.               12
                                          approved make pin insulators with hardware.
                               S.9        Supply,Installation, Testing, Commissioning of 33 KV                  Set                24
                                          approved make disk insulator with hardware (3 disk
                                          insulator = 1 set)
                               S.10       Supply,Installation, stringing, Testing, Commissioning of             Mtr.               300
                                          AAAC conductor (DOG) of approved make 100 SQMM
                                          aluminium equiv. conductor & providing PIN type/ EYE type
                                          heavy duty aluminum lugs at all termination ends as per
                                          requirements. All material and labour for termination and
                                          binding also to be considered in scope of work.

                               S.11       Supply , Installation, Testing & commissioning of 1600 KVA            No.                 2
                                          Dry type with OFTC( +5% to -12.5% in steps of 2.5%)
                                          33KV/0.415 KV, 3 phase, 50 Hz. Copper wound transformer
                                          with vector group DYN-11 mounted in the indoor substation
                                          yard. The electrical contractor shall execute all work of
                                          interconnection of transformer with D.O. fuse on two pole
                                          structure etc. Make- Voltamp / Crompton /AREVA




                                                                                                                                                            17of 26
                                                                       dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                   Internal Electrification for Network Monitoring Center.




                     SOR /         S.No.                           DESCRIPTION                                UNIT               QTY.
                    NON SOR

                               S.12        Supply , Installation, Testing & commissioning of 1600 KVA          No.                 2
                                           AC servo controlled Automatic voltage stabilizer , suitable
                                           for unbalance load condition , Oil cooled ( to be supplied
                                           with first filling of oil) , construction for outdoor use in a
                                           maximum ambient temp of 45 degree cent , with IP 55/65
                                           protection .       INPUT VOLTAGE – 340-480 V, 3 PHASE &
                                           NEUTRAL , 50 HZ , 4 WIRE AC OUTPUT VOLTAGE - 415V +/-
                                           1.0% , 3 PHASE & NEUTRAL, 50 HZ CAPACITY – 1600 KVA , 3
                                           PHASE
                                           Make- Jindal / AE



                                           SUB TOTAL

                    NSOR       T           HT BREAKER PANEL
                               T.1         Design, manufacture, supply, installation, testing and              No.                 1
                                           commissioning of Panel set 33KV, 1250A, 26.3KA,800 MVA
                                           indoor type metal clad floor mounted vermin proof
                                           horizontal drawout fully interlocked vertical isolation
                                           SF6circuit breaker panel board fabricated out of minimum
                                           2mm thick CRCA sheet as per specifications. The panel shall
                                           be complete with all accessories / fitting / wiring like
                                           insulated copper Busbar, cable termination boxes suitable
                                           for 3C x 240 Sqmm XLPE armoured aluminium cable for
                                           incoming and outgoing feeder, foundation bolts etc.
                                           complete as required and as specified below :-

                               T.1.1       Incoming:
                               -           TWO No. 33KV 1250 Amps. ,26.3KA 800 MVA           electrically
                                           operated draw out type SF6circuit breaker complete with
                                           trip free spring charged closing mechanism, necessary
                                           auxiliary relays, control switches, emergency hand trip
                                           devices and mechanical ON / OFF indicator etc with
                                           following metering and protection(for each unit):.

                               -           PF Meter - 1nos
                               -           digital frequency meter - 1nos
                               -             digital type ammeter with 3 no. cast raisin CTs for metering
                                           (75/50/5-5A, CL- 1, 15VA) with ASS and 2 Amp SP MCB - 1
                                           sets
                               -             voltmeter (0-40KV) with VSS - 1 sets
                               -             kW meter - 1 nos
                               -             kWh meter with RS-485 Port - 1nos
                               -            Phase indication lamps with 2Amp SP MCB for protection
                                           (Red, Yellow and Blue) - 3 no.
                               -            Red/ Green indicating lamp for close and open position - 2
                                           no
                               -            amber indicating lamp for auto trip - 1 No.
                               -            clear indicating lamp for trip circuit healthy - 1nos
                               -            blue indicating lamp for spring charged-1nos
                               -            strip heater to prevent absorption of moisture -1nos
                               -            2Nos. O/C and 1No E/F (CDG-11 or equivalent) relay with 1
                                           Nos. CTs 75/50 /5-5A, CL 5P10, 15VA - 1 sets
                               -           Master Trip Relay - 1nos
                               -           Trip circuit supervision relay - 1nos
                               -            33KV/1.712/110/1.712. 200VA burden P.T -1nos
                               -           12 windows annunciation system for annunciation of
                                           transformer / electrical protection faults - 1 sets

                               T.1.2       Busbar :

                               -           1250 Amp. Color coded heat shrinkable PVC sleeved TP
                                           copper busbar of 26.3KA fault rating.




                                                                                                                                                           18of 26
                                                                       dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                   Internal Electrification for Network Monitoring Center.




                     SOR /          S.No.                          DESCRIPTION                                UNIT               QTY.
                    NON SOR

                               T.1.3        Outgoing :

                               -            Two No . outgoing feeder equipped with the following:-


                               a)           One (1) No. 33KV 1250 Amp 26.3KA electrically operated
                                            draw out type SF6 circuit breaker.
                               b)           One (1) No. trip free spring charged closing mechanism
                                            complete with necessary auxiliary relays, control switches,
                                            emergency hand trip device and mechanical ON / OFF
                                            indicator.
                               c)           One (1) No. digital type Ammeter with CTs 10/5-5A CL-1,
                                            15VA with ASS.
                               d)           One (1) Set of IDMTL over current and earth fault with
                                            instantaneous high set o/c and E/F relay similar to CDG -61
                                            or equivalent with 3 Nos. CTs 10/5-5A, CL-5 P10, 15VA.

                               e)           Auxiliary switch/relay, master trip, anti pumping relay and
                                            other control relays etc. as per requirements.
                                            transformer diffrential relay with primary and secondary cts.


                               T1.4         Bus coupler

                               -            One No . outgoing feeder equipped with the following:-


                               a)           One (1) No. 33KV 1250 Amp 26.3KA electrically operated
                                            draw out type SF6 circuit breaker.
                               b)           One (1) No. trip free spring charged closing mechanism
                                            complete with necessary auxiliary relays, control switches,
                                            emergency hand trip device and mechanical ON / OFF
                                            indicator.
                               c)           One (1) No. digital type Ammeter with CTs 10/5-5A CL-1,
                                            15VA with ASS.
                               d)           One (1) Set of IDMTL over current and earth fault with
                                            instantaneous high set o/c and E/F relay similar to CDG -61
                                            or equivalent with 3 Nos. CTs 10/5-5A, CL-5 P10, 15VA.

                               e)           Auxiliary switch/relay, master trip, anti pumping relay and
                                            other control relays etc. as per requirements.
                                            transformer diffrential relay with primary and secondary cts.

                                            Make- ABB /Schneider

                               T1.5         Battery

                                            Design, manufacture, assembly, supply erection, testing &
                                            commissioning of 150 AH, capacity 24 V DC Ni-Cadmium
                                            maintenance free batteries duly charged complete with
                                            connecting lead as required for 10 hour back up for all
                                            controls and equipment operating mechanism of VCBs ,
                                            indications , protection devices and alarm.Other details are
                                            as per Technical Specifications Of this tender. Make-Rocket
                                            / Exide (SMF type).


                               T1.6         Battery Charger




                                                                                                                                                           19of 26
                                                                       dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                    Internal Electrification for Network Monitoring Center.




                     SOR /         S.No.                           DESCRIPTION                                 UNIT               QTY.
                    NON SOR

                                           Design, manufacture, assembly, supply, erection, testing &
                                           commissioning of suitable float cum boost battery charger
                                           and necessary distribution board with 6 Nos. 16A outgoing
                                           feeders,   instrument     panel,   Amp,     Volts   meter,
                                           interconnections etc. power supply 230 V, 1 phase, 50 Hz ±
                                           10%. Charger trouble annunciation shall be provided
                                           through potential free contacts.             Make:- Chabi
                                           /Hertz/BCH

                                           UPS
                                           Supply,Installation,Testing and commissioning of 1 KVA UPS -
                                           1 no.
                                           Make:- Emerson /APC


                                           SUB TOTAL

                    NSOR       U           HT CABLING WORK
                               U.1         Supply and laying of cables in excavated trenches,
                                           concrete trenches, through hume pipes, cable trays etc with
                                           testing & commissioning. The cable shall be 33 KV
                                           grade, aluminium armoured of approved make as per
                                           following sizes. The scope includes supply & fixing of
                                           aluminium      cable tags(      at    every      6     Mts
                                           distance),clamps/saddles    for dressing of cable/cable
                                           route markers at every 7 Mtr. distance as               per
                                           drawings, specifications & instructions of client.

                               U.1.1       33KV 3CX240 sqmm HT XLPE cable ( do fuse to ht pn i/c) ( 1           mtr                90
                                           WORKING + 1 STAND BY)
                               U.1.2       Cable termination of armoured cables 33 KV grade as
                                           per following
                               U.2         Supply,Installation, Testing & commissioning of Cable                Set                 4
                                           jointing of 33 KV grade XLPE insulated armoured cable
                                           3cx240 sqmm with suitable cable termination using
                                           RAYCHEM/Birla 3M/MECP KITS including all accessories i.e.
                                           Sockets, lugs, gland etc as required but without cable box
                                           suitable for outdoor installation           with water proof
                                           trifurcating box.
                               U.3           Supply, Installation, Testing & commissioning of Cable             Set                 8
                                           jointing of 33 KV grade XLPE insulated armoured cable
                                           3cx240 sqmm with suitable cable termination using
                                           RAYCHEM/Birla 3M/MECP KITS including all accessories i.e.
                                           Sockets, lugs, gland etc as required but without cable box for
                                           indoor installation.


                                           SUB TOTAL

                               V           LIASIONING WORK
                               V.1         Complete liasioning work with State Electricity board ,              Job                 1
                                           including preparation , submission and approval of
                                           drawings/Papers as per rules of Electricity board , electrical
                                           inspector follow up and getting the approval for installation ,
                                           sanction of power and connection and charging .Complete
                                           work to be arranged in a manner so as to get the power
                                           before final commissioning of project.




                                                                                                                                                            20of 26
                                                                       dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                       Internal Electrification for Network Monitoring Center.




                     SOR /         S.No.                            DESCRIPTION                                   UNIT               QTY.
                    NON SOR

                               V.2         Complete liasioning work with Electrical Inspector including            Job                 1
                                           preparation , submission and approval of drawings/Papers
                                           as per rules of Electricity board , electrical inspector follow
                                           up and getting the approval for installation , sanction of
                                           power and connection and charging .Complete work to be
                                           arranged in a manner so as to get the power before final
                                           commissioning of project. Total No. Of Transformers -
                                           1600KVA x 2 Nos
                               V.3         Preparation of final drawing of DG set / room layout based              Job                 1
                                           on drawings given by consultant and getting approval from
                                           State Electricity Board , office of Chief Electrical Inspector to
                                           run DG set. Complete permission , approval including site
                                           visits of officials has to be arranged by contractor and
                                           liasioning charges , expenses for above work shall be
                                           included .Final permission without any pending work remark
                                           shall be submitted to Employer .Calibration of meters /CT’s
                                           from electricity board is also included in above scope.
                                           Complete work to be arranged in a manner so as to get the
                                           power before final commissioning of project.                Total
                                           No. Of DG SETS 315 KVAX1NO



                                           SUB TOTAL

                    NSOR       W           SAFETY EQUIPMENTS
                               W.1         Supply & Laying of 25/12 mm thick & 1 mtr. Wide checkered
                                           rubber mat for outdoor HT panel board, Main panel,
                                           Generator etc.Mat shall be ISI mark conforming to IS 5424-
                                           1969 complete as required.
                               W.1.1       25 mm thickness                                                         Mtr.               15
                               W.1.2       12 mm thickness                                                         Mtr.               20
                               W.2         Supply & fixing shock treatment charts in Hindi & English               Set                5
                                           language in HT & LT rooms of sub station with wooden
                                           frame and glass cover.
                               W.3         Supply, Filling and Fixing of following type of approve make
                                           fire extinguishers in electrical room.
                               W.3.1       CO2 type fire extinguisher , Capacity 5 Kg. (conforming to IS-          Nos.                4
                                           2878).
                               W.3.2       Dry powder type , Capacity 5 Kg. (conforming to IS:2171                 Nos.                4
                                           with cylinder fully charged).
                               W.4         Supplying and installing at approved location approved                  Nos.                3
                                           make 4 nos. fire buckets of 24 gauge galvanized steel,
                                           painted white inside and red outside and black on the
                                           bottom, inscribed with letters ”FIRE” in black and gold
                                           including stand fabricated out of sheet metal (16 gauge)
                                           shade, platform and associated civil works, painting etc as
                                           approved by fire authority.
                               W.5         Supply of 33 KV hand gloves                                             Pair                1
                               W.6         Providing first aid box as per IS:2217.                                 Set                 2
                               W.7         Providing & fixing HT danger notice plate 200 mm x 150 mm               Nos.                1
                                           made of mild steel atleast 2mm thick & vitreous enameled
                                           white on both sides and with inscription in signal red colour
                                           with skull & bone on front side as required.

                               W.8         Discharge Rod                                                           Nos.                2
                                           SUB TOTAL

                    NSOR       X           STREET LIGHTING
                               X.1         Supply & Installation of decorative light MS swaged poles
                                           suitable for installation of street / garden light fixtures as per
                                           drawing and specification. The arm/mast shall be welded to
                                           top of the pole.




                                                                                                                                                               21of 26
                                                                         dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                     Internal Electrification for Network Monitoring Center.




                     SOR /         S.No.                           DESCRIPTION                                  UNIT               QTY.
                    NON SOR

                                           Complete pole shall be painted with one coat of anti
                                           corrosive primer and two coats of synthetic enamel paint.
                                           Two earth wire 8 SWG hot dipped GI shall be connected
                                           from earthing ring to earthing clamp and earthing clamp to
                                           MS box. 3 core * 2.5 sq. mtr flexible copper cable of
                                           FINOLEX/CCI make to be installed from control gear to light
                                           fixture.
                                           Complete erection work including excavation, civil work
                                           concreting (1:3:6) etc. shall be carried out as per drawing
                                           and specifications. Supply and Installation of cable, sleeves
                                           (pipes), coving for aesthetics etc. to be completed as per
                                           detail and instruction of engineer in charge. All material shall
                                           be supplied will cover guarantee for one year . Above
                                           specification governs all work specified in items P.1 to P.2

                               X.1.1       Decorative pole 3.5 mts. Long (60 Kg weight).                         Nos.               6
                               X.1.2       Street Light pole 9.0 mts. Long (150 Kg weight).                      Nos.               6
                               X.2         Supply,Installation, Testing and commissioning of weather             Nos.               12
                                           proof pole mounting control gear box with 5A English
                                           electric make HRC fuse, 2A approve make make MCB,
                                           approved make 4 way * 30A lock type connector strip, gland
                                           plate to accommodate up to 3 cables of 4C * 10 sq. mm. ‘AL’
                                           armoured, Nipple for wire etc. & earth stud.The control gear
                                           shall be hinged door type and to have key lock system with
                                           rubber gasketing. Mounting clamp arrangement shall be
                                           provided as per dwg. & specifications.



                                           SUB TOTAL

                    NSOR       Y           FABRICATION WORK
                               Y.1         Supply & Installation of MS structures fabricated from                 Kg               6500
                                           TATA/SAIL make equal angles/channels/beams for fencing of
                                           DG ROOM/H.T. yard. The job includes supply of all materials
                                           consumable /machines /tools & tackles required to
                                           complete work.
                               Y.2         Supply & installation of GI chain linked fencing made from 8          Mtr.               15
                                           gauge GI wire with each chain block are of approx. 100mm *
                                           100 mm. (Width of fencing is 1800 mm)



                                           SUB TOTAL

                    NSOR       Z           DG SET
                               Z.1         Design, manufacture, assembly, testing at works, supply,
                                           erection & testing at site as per specifications complete in all
                                           respect of Silent DG Sets of KVA rating as specified below :




                                                                                                                                                             22of 26
                                                                        dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                     Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                             DESCRIPTION                                  UNIT               QTY.
                    NON SOR

                                           415 Volts, 3 phase, 50 Hz, 1500 RPM AC alternator coupled
                                           with Water cooled Diesel Engine complete with all
                                           accessories, like self starting device, fly wheel coupling with
                                           guard V belts cooling system, instrument panel comprising of
                                           switch with key, battery charging device, safety control for
                                           lub oil pressure and high cooling water temperature with
                                           tripping PLC 3100/2100 etc. The alternator insulation shall
                                           be class 'H' with temperature rise limited to Class 'F' value
                                           suitable to with stand tropical conditions and shall generally
                                           comply with BS 5000 and IS 4722. The over load capacity
                                           shall not be less than 110% of rated capacity for 1 hour in
                                           every 12 hours. 24 Volt 360 AH sealed maintenance free
                                           chargeable lead acid battery set complete with suitable
                                           trickle/boost chargers & battery leads. Neutral CT of suitable
                                           ratio & Class PS accuracy with terminal box for Alternator
                                           REF protection for all DG sets to be provided. (DG controlled
                                           by AMF panel .)


                                           The DG set shall be mounted on a suitable designed
                                           fabricated rigid common base frame with antivibration pads
                                           to provide not less than 99% vibration isolation. First filling
                                           of lube of lube oil & HSD shall be included in DG Sets cost.
                                           The DG Set shall include all standard accessories, fittings,
                                           silencer, flexible bellow, and instruments manuals etc.
                                           complete as per specifications.


                                           The design of DG Sets shall conform to the requirement of
                                           CPCB.

                                         a) 315 KVA (with acoustic enclosure for Light & gen power,              Set                 1
                                            Airconditioning , Utilities )

                               Z.2         EXHAUST SYSTEM :
                               Z.2.1       Silencer:
                                           Supply, installation, testing & commissioning of residential
                                           type silencers as per CPCB norms with 75mm glass/minral
                                           wool insulation complete with wire chicken mesh and 24
                                           guage Aluminium cladding from engine upto silencers,
                                           supporting arrangement suitable for the following DG Set
                                           complete as required.

                               Z.2.1.1     Set of silencer for each 315 KVA DG Set                               No                  1
                               Z.3         Exhaust Piping :
                                           Design, manufacture, supply, erection, testing &
                                           commissioning of 4.85 mm thick exhaust piping conforming
                                           to IS:3589 with expansion joints, bends, support thermal
                                           insulation with 75mm thick glasswool /mineral wool, wire
                                           chicken mesh over insulation and 24 gauge aluminium sheet
                                           cladding over the exhaust pipes from silencer to
                                           atmosphere.
                               Z.3.1       400 mm dia                                                            RM                 30
                               Note :      The sizes are indicative only and the Contractor should
                                           furnish calculation for exhaust piping size for approval by the
                                           Consultant. The system should meet the performance of the
                                           engine without exceeding the back pressure limit prescribed
                                           by engine supplier. Indicative exhaust pipe layout drawing is
                                           enclosed for reference. In case the selected size as per
                                           calculation of back pressure does not fall in the size specified
                                           above, the rate of pipe of size so selected shall also be
                                           indicated.

                               Z.4         M.S. Structural Support :




                                                                                                                                                             23of 26
                                                                        dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                        Internal Electrification for Network Monitoring Center.




                     SOR /           S.No.                            DESCRIPTION                                  UNIT               QTY.
                    NON SOR

                               Z.4.1         Chimney with with structure as per Pollution Control Act up            Kg.              10000
                                             to 30 Mtr. Height including all support & structure , civil
                                             work , foundation for self supported chimney. Self
                                             supporting structure suitable for approx. 30 meter exhaust
                                             pipe above the ground level. This self supporting structure
                                             shall be complete with Aviation light with battery & battery
                                             charger and earthing for lightning arrestor, including Guy
                                             wire supports. This structure shall be designed for a wind
                                             velocity prevailing at site. Including welding, cutting, 2 layers
                                             of anti-coating primer with 2 layers of silver paint etc.
                                             complete as required. The item given indicative and
                                             minimum to be provided. The bidder shall workout & furnish
                                             the detail for approval in their proposal.


                               Z.5           FUEL DAY OIL TANK :
                               Z.5.1         Supply, fabrication, installation, testing & commissioning of          Set                 1
                                             M.S. day oil tank of 990 litres capacity fabricated out of min.
                                             5mm thick M.S. sheet installed on steel frame or masonry
                                             pedestal with all associated accessories, filters, valves &
                                             fittings including level controller complete as required, float
                                             switch with contacts for remote interlock should be
                                             provided. The tank shall be suitably treated with oil resistant
                                             paint/anticorrosive treatment on inside & outside surface
                                             respectively. The contact of level controlled shall be wired
                                             up terminal block.

                               Z.6           Fuel Oil Piping :
                                             Supply, installation, testing and commissioning of schedule-
                                             B class MS piping conforming to IS-1239 for fuel piping
                                             complete with all necessary fittings and valves between day
                                             oil storage tanks and DG sets/priming motor including
                                             jointing of pipes, painting with 2 coats of red oxide and two
                                             coats of enamel paint.

                               Z.6.1         25 mm dia                                                              RM                 20
                               Z.6.2         50 mm dia (for branch)                                                 RM                 60

                               Z.7           Oil Hand Pump :
                               Z.7.1         Supply & installation of hand pump for pumping out fuel                No.                 1
                                             from barrels to the day oil tank with flexible hose pipe of 5
                                             mtr length.
                               Z.8           Supply,installation testing and commissioning of fuel meters           Nos.                1
                                             for incoming line to tank with pipe size up to 25mm having
                                             digital disply and communication port.This shall be supplied
                                             along with power supply unit.



                                             SUB TOTAL

                    NSOR       AB            LIGHTENING CONDUCTOR
                               AB.1          Supply & installation of Early Streamer Emission Lightening            Nos.                1
                                             Conductor Air Terminal (ESELC) to protect the Builidngs and
                                             other structures from direct Lighting Strikes which inlcudes :-
                                             Make : Ingesco (Spain) OR Equivalent.To be installed on shed
                                             top.
                               I)            ESE air terminal, Make :- Indelec, France Model No.
                                             Prevectron S6.60 or equivalent.
                               ii)           5 Meter GI mast with base plate & baseplate foundation
                                             bolts.
                               iii)          Guying Kit sets.
                               AB.2          Supply of earth pit materials for maintenance free earth pits          Nos.                1
                                             which includes
                               I)            ISOGEL earth enhancing compound (20 Kg) ( 6 nos)




                                                                                                                                                                24of 26
                                                                          dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                              Internal Electrification for Network Monitoring Center.




                     SOR /        S.No.                                    DESCRIPTION                                     UNIT             QTY.
                    NON SOR

                               ii)            Chem Rod 2.5" dia, 8 fts Long ( 6 nos)
                               iii)           High Grade Plastic Earth pit covers.( 6 nos)
                               iv)            Earth Test Link with 2" dia 1.5 mtr. PVC pipe for strip
                                              isolation from ground level.( 6 nos)
                               AB.3           Supply,installation,testing & commissioning of 70 Sq.mm                      RM                100
                                              PVC insulated stranded flexible copper cable through 2"dia 4
                                              mm wall thickness FRP tube with saddles and fxing.

                               AB.4           Supply of 6 Digit 7 segment LCD transient Lighting Counter in                No.                1
                                              weathor proof enclosure.
                               AB.5           Aviation Light with all accessories and mounting                             No.                1
                                              arrangement including wiring complete as required.
                      ESTIMATE FOR ELECTRICAL WORKS OF NETWORK MONITORING CENTRE AT
                    PART-C
                     SOR /            S.No.                          Description of Items                                  Unit              Qty
                    NON SOR

                       1               2                                     3                                              5                 4
                    NON SOR            2      Design, supply, installing, testing and commissioning of 10
                                              Passenger (680 Kg) (Gearless type) capacities Lift of
                                              JOHNSON or OTIS make, serving Ground plus two upper
                                              floors including Emergency drive unit for automatically
                                              rescuing trapped passenger from inside the Lift incase of
                                              power supply failure by bringing the Lift to the nearest
                                              landing as per following specification:

                                              Load/Speed: 10 persons (680Kgs)/1.25m per second
                                              Drive: Micro Processor based VVVF
                                              Number of Floor: 3 (Ground + 2 upper floor)
                                              Position of Machinery: Directly above the lift well (Gearless)

                                              Type or design of lift car: Stainless steel-Hairline finish
                                              Lift car inside size: 1300x1350 (mm wide* mm depth)
                                              Car ceiling/ Car floor: Sleek (Circular lights)/ SS Hairline
                                              finish-Pvc
                                              Fittings in car: Sleek circular lights (Fbs 085) & Regular
                                              (circular), Fan 1no.
                                              Car Entrance Protection: Power operated centre opening
                                              sliding door of Stainless steel with hairline finish

                                              Landing Entrance Protection: Door frame of stainless steel
                                              with hairline finish & Central opening sliding door of stainless
                                              steel with hairline finish
                                              Clear opening of Doors: 800x2000 (mm wide x mm height)

                                              Type of control system: Micro processor based simplex
                                              selective , collective control with/without attendant
                                              Operating Electric Power: AC 400/440 Volts, 3 phase, 50
                                              cycle
                                               including all required steel, civil and electrical materials e.g.
                                              machine beams, buffer support channels, fascia plates,
                                              landing sills, pit ladder etc. as required for installation of lift
                                              in the existing lift well and machine room. Scaffolding,
                                              damages in walls, floor, ceiling etc. for fixing accessories,
                                              foundation bolts, load hook etc., hoist way wiring and other
                                              associated wirings including fire mans switch and all
                                              required labour complete in all respect. (The quoted rate
                                              should include all taxes and duties as applicable and free
                                              comprehensive maintenance (including spares) of lifts for a
                                              period of Two year from the accepted date of completion of
                                              the contract.)
                                                                                                                    Each                      1
                                       B      GOODS LIFT




                                                                                                                                                                      25of 26
                                                                              dated 22 july 2011
Kushwah and Kushwah Architecture Planning Interior Design                                                          Internal Electrification for Network Monitoring Center.




                     SOR /       S.No.                                 DESCRIPTION                                     UNIT             QTY.
                    NON SOR

                    NON SOR        3      Design, supply, installing, testing and commissioning of
                                          GOODS LIFT capacities 1500kgs, Lift of JOHNSON or OTIS
                                          make, serving Ground plus two upper floors with the
                                          provision of car door opening at 1st and second floor
                                          opposite side of ground floor opening, including Emergency
                                          drive unit for automatically rescuing from inside the Lift
                                          incase of power supply failure by bringing the Lift to the
                                          nearest landing as per following specification:

                                          Load/Speed: 1500Kgs/0.50m per second
                                          Drive: Micro Processor based VVVF
                                          Number of Floor: 3 (Ground + 2 upper floor)
                                          Position of Machinery: Directly above the lift well (Gearless)

                                          Number & Position of car entrance: 2 (Two) On opposite
                                          side
                                          Type or design of lift car: Stainless steel-Hairline finish
                                          Lift car inside size: 1850x1780 (mm wide* mm depth)
                                          Car ceiling/ Car floor: Zig-Zag-SS Hairline finish-Pvc
                                          Fittings in car: Sleek circular lights (Fbs 085) & Regular
                                          (circular), Fan 1no.
                                          Car Entrance Protection: Power operated centre opening
                                          sliding door of Stainless steel with hairline finish

                                          Landing Entrance Protection: Door frame of stainless steel
                                          with hairline finish & Central opening sliding door of stainless
                                          steel with hairline finish
                                          Clear opening of Doors: 1000x2000 (mm wide x mm height)

                                          Type of control system: Micro processor based simplex
                                          selective , collective control with/without attendant
                                          Operating Electric Power: AC 400/440 Volts, 3 phase, 50
                                          cycle
                                           including all required steel, civil and electrical materials e.g.
                                          machine beams, buffer support channels, fascia plates,
                                          landing sills, pit ladder etc. as required for installation of lift
                                          in the existing lift well and machine room. Scaffolding,
                                          damages in walls, floor, ceiling etc. for fixing accessories,
                                          foundation bolts, load hook etc., hoist way wiring and other
                                          associated wirings including fire mans switch and all
                                          required labour complete in all respect. (The quoted rate
                                          should include all taxes and duties as applicable and free
                                          comprehensive maintenance (including spares) of lifts for a
                                          period of Two year from the accepted date of completion of
                                          the contract.)
                                                                                                                Each                      1